KAZAN: MODEL SPECIFICATIONS 1. TECHNICAL DATA 2 2. PRE-INSTALLATION 3 3. INSTALLATION 6 4. OPERATION TESTING 11. Keep for future use

Similar documents
NELSON: MODEL SPECIFICATIONS 1. TECHNICAL DATA 2. PRE-INSTALLATION 3. INSTALLATION 4. OPERATION 5. TESTING. Keep for future use

tipi: model specifications 1. Technical Data 2 2. PRE-Installation 3 4. Operation 9 Keep for future use

ARGOS: MODEL SPECIFICATIONS 1. TECHNICAL DATA 2. PRE-INSTALLATION 3. INSTALLATION 4. OPERATION 5. TESTING. Keep for future use

PHAROS: MODEL SPECIFICATIONS 1. TECHNICAL DATA 2. PRE-INSTALLATION 3. INSTALLATION 4. OPERATION 5. TESTING. Keep for future use

EMOTION: MODEL SPECIFICATIONS 1. TECHNICAL DATA 2 2. PRE-INSTALLATION 3 3. INSTALLATION 5 4. OPERATION 9 5. TESTING 10. Keep for future use

SKANTHERM SHAKER: INSTALLATION AND USER MANUAL 1. TECHNICAL DATA 2 2. PRE-INSTALLATION 3 3. INSTALLATION 5 4. OPERATION 9 5.

Skantherm shaker: Installation and User Manual. 1. Technical Data PRE-Installation Installation Operation 9. Keep for future use

PAxFocus. 1. Technical Data PRE-Installation Operation 13. Keep for future use. Oblica 200 Argyle St Fitzroy VIC

ErgoFocus: Installation and User Manual. 1. Technical Data PRE-Installation Operation 11. Keep for future use

SI T T FST

Model: 31ST-ACC-AU. Model: 31M-ACC-AU

SI T T FSS/FSTT Open Fire

Nouveau BBQ Single Flue

Model: WS18-AU. Model: WS22-AU

150MM FREE STANDING WOOD FIRE FLUE KIT MKIII INSTALLATION INSTRUCTIONS

150MM FREE STANDING WOOD FIRE FLUE KIT MKIII INSTALLATION INSTRUCTIONS

150MM FREE STANDING WOOD FIRE FLUE KIT MKIII INSTALLATION INSTRUCTIONS

Regency Bellerive & Berwick Zero Clearance Box and Flue Kit Part No Assembly Instructions

Inspire Your Creativity With Diversity From Eureka Woodheating

Inspire Your Creativity With Diversity From Eureka Woodheating

the heart of a warm home

170MM 360MM Specifications

MASPORT I5000 INSERT FIRE, AUSTRALIAN MODEL

INSTALLATION SPECIFICATION SHEET These instructions must be used in conjunction with the 'General Installation Instructions' for Masport wood fires.

FIREPLACE INSERT ENCLOSURE INSTALLATION INSTRUCTIONS

Traditional Open Fire

These installation instructions cover the installation and operation of Jetmaster Inset and Freestanding Barbecues

Installation Instructions

P36-10 / P36E-10 Gas Fireplace. 11 W.C. (2.74 kpa) 10 W.C. (2.49 kpa) 6.4 W.C. (1.59 kpa) 22,000 BTU/h (6.44 kw) 28,500 BTU/h (8.

CHIMNEYS AND FIREPLACES

P36 / P36E Gas Fireplace. 11 W.C. (2.74 kpa) 10 W.C. (2.49 kpa) 6.4 W.C. (1.59 kpa) 22,000 BTU/h (6.44 kw) 28,500 BTU/h (8.35 kw)

CHIMNEYS AND FIREPLACES

SPECIFICATION & INSTALLATION GUIDE FOR MASPORT LE4000 PROVINCIAL BUILT-IN FIRE, NEW ZEALAND MODEL

Regency Horizon HZ30E Gas Fireplace

Ecoteck Amalfi Freestanding. Wood Pellet Burning Heater

Gas Fireplaces. P36D-10 Gas Fireplace. Unit Dimensions With Vignette Faceplate. *** Important: Framing height requires consideration of the hearth

How to choose the best furnace?

B36XTCE Gas Fireplace

Outer Skin Kit & Flue: IB600, IB850, IB1100 Installation Manual

Gas Fireplaces. B41XTE-10 Gas Fireplace. Framing Dimensions: Unit Dimensions: Non-Combustible 1012mm Requirements: V Opening for gas connection

Installation instruction

Caution: FOR YOUR SAFETY

WOOD FIRE INSTALLATION GUIDE

Fireplaces and Chimneys

B41XTCE Gas Fireplace

Summit Stone. Summit Stone. Summit Stone Corner Outdoor Fireplace. Installation Guidelines. Summit Stone. Corner Outdoor Fireplace

P36 - P36D Zero Clearance Direct Vent Gas Fireplace. 12 W.C. (3.00 kpa) 11 W.C. (2.74 kpa) 2.9 W.C. (0.72 kpa) 15,000 BTU/h (3.

Sorrento Stone Surrounds

Wood & Pellet ECONOMIZER BIOMASS PRODUCTS

GEORGIAN. Traditional. Fireplace Design Collection WOOD BURNING FIREPLACES

Gas Fireplaces. P33-10/P33E-10 Gas Fireplace P33 DIMENSIONS WITH VIGNETTE FACEPLATE CLEARANCES WITH VIGNETTE FACEPLATE

WOOD FIRE INSTALLATION GUIDE

WD5 (Timber Cavity) Installation Guide Operating Instructions Warranty

GENERAL MECHANICAL SYSTEM REQUIREMENTS

Gas Fireplaces. P33 Zero Clearance Direct Vent Gas Fireplace. *** Important: Framing height requires consideration of the hearth

Wood Designer Series Woodburning Fireplaces

Wood & Pellet ECONOMIZER STOVES & INSERTS

GENERAL MECHANICAL SYSTEM REQUIREMENTS

+61 (0) /1 Simmons Street Ballina NSW 2478, Australia

RECOMMENDED STANDARDS for the INSTALLATION of WOODBURNING STOVES

ENGLISH INSTALLATION INSTRUCTION MANUAL. N550 Bakers Oven. CERTIFIED for USA & CANADA SAFETY TESTED to UL & ULC-S

Kemlan Coupe Series of Double Sided Wood Heaters

MODEL. These instructions must be used in conjunction with the 'General Installation Instructions' for MASPORT wood fires.

DIVISION: SPECIALTIES SECTION: MANUFACTURED FIREPLACES REPORT HOLDER: MASONRY FIREPLACE INDUSTRIES, LLC

STEP-BY-STEP PLANS FOR CONSTRUCTING A 250 STICK ROCKET BARN (RBN 3.0) (see RBR plans for furnace and metal component construction)

TC54. for architects & designers. Dimensions Clearances Venting

Builder's Manual for Ortal Fireplaces

GD Specifications

Dunbrik A1 Concrete Flue Liners

DIVISION: SPECIALTIES SECTION: MANUFACTURED FIREPLACES REPORT HOLDER: FIRE ROCK PRODUCTS LLC

PORTRAIT WARNING HOT GLASS WILL CAUSE BURNS. DO NOT TOUCH GLASS UNTIL COOLED. NEVER ALLOW CHILDREN TO TOUCH GLASS. 569 Ledge Front

Rediflow Concrete Gas Flue System

RULE RESIDENTIAL WOOD COMBUSTION (Adopted October 25, 2001; Recodified August 22, 2002) RULE 207 CONTENTS RULE 207

Summit Stone. Summit Stone. Summit Stone. Standard Outdoor Fireplace Installation Guidelines. Summit Stone Standard Outdoor Fireplace

YOUR SPACE. Buildings for your lifestyle

MASPORT I3000 DRY BUILT-IN FIRE MASPORT I3000 WET BUILT-IN FIRE INSTALLATION INSTRUCTIONS

Installation GUIde Please read these instructions before proceeding

Fireplace. Opening. Old. Opening up an old fireplace is like striking gold in your very own home.

Interior FRT Wood. References of Previous Model Building Codes

INSTALLATION INSTRUCTIONS

The great Aussie shed deserves great Australian insulation

Chimney and Fireplace Inspection Report

Guidance on U Values from Domestic Heating Design Guide

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade)

KEMLAN OUTDOOR FLUELESS PATIO FIRE

Wood Burning. Innovative Hearth Solutions

Bituminous Roofing Underlay & Valley Guard

RESPONSIBILITY OF THE BUILDER/OWNER

Customer Specification

Masonry Firebox. Models MM33, MM39, MM44, MM49 and MM63

Enviro EF2 Classic. Wood Pellet Fire FPI CB and FS CB. Classic Wood Pellet Burning Heater Insert and Free Standing Models Installation Specifications

This wood burning fireplace complies with UL127 standard as a FACTORY BUILT APPLIANCE.

Architect & Builder s Guide. ORTAL Heating Systems Ltd.

EXCELPrime 18 Clearance Stove Pipe INSTALLATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION SPECIFICATION SHEET

wall underlay Product BRANZ APPRAISAL No. 695 (2010) Scope Thermakraft Industries (NZ) Ltd PO Box Botany Manukau 2163 Auckland

Decking Buying Guide for Customers

RECONSTRUCTION AND REPLACEMENT OF EARTHQUAKE DAMAGED MASONRY CHIMNEYS

Incinerator Systems NFPA 82 Inspection Form

Signage Code. H101.2 Signs exempt from permits. The following signs are exempt from the requirements to obtain a permit before erection:

Transcription:

KAZAN: MODEL SPECIFICATIONS 1. TECHNICAL DATA 2 2. PRE-INSTALLATION 3 3. INSTALLATION 6 4. OPERATION 10 5. TESTING 11 Keep for future use

1. TECHNICAL DATA WEIGHT AND DIMENSIONS: Dimensions Firebox W642 x H801 x D362mm Firebox weight 162kg Flue kit Standard 6 DETERMINED UNDER TEST CONDITIONS: Nominal thermal output 8kW Efficiency (Australian Test) 60% Emissions (Australian Test) 1.3 g/kg 8 Flue 801 652 PAGE 2

2. PRE-INSTALLATION Congratulations on your purchase of the Kazan. This appliance should be installed and checked by a qualified professional. Ensure you have read the operation guidelines thoroughly prior to first use. For any questions or concerns please contact Oblica on 03 9416 0400. The installation process is outlined below: Determine position of firebox and flue carefully observing the clearances described within this section Install the external flue Install the internal flue and engage the firebox Ensure the floor has adequate protection CAUTION: Using components or parts other than those provided by the manufacturer or modifying the specification of components may result in inferior or unsafe operation. If such action is necessary, consult the manufacturer in the first instance. WARNING: The appliance and flue-system must be installed in accordance with AS/NZS 2918 and the relevant building code or codes. Any modification of the appliance that has not been approved in writing by the testing authority will be in breach of the approval granted for compliance with AS/NZS 4013. Once the flue has been installed and approved by a professional installer, the flue must not be modified in any way. PAGE 3

2. PRE-INSTALLATION (CONTINUED) MINIMUM CLEARANCE INTERNAL 2.1 Clearance from non-combustible surfaces (eg masonry) 100mm minimum clearance is required from fully non-combustible surfaces. Non 100 100 Non 2.3 Clearance from combustible surfaces (eg timber joist & concrete) Clearances may be reduced with the application of heat shielding to walls in accordance to the Australian Building Code. For information on heat shielding please contact our office on 03 9416 0400 or email info@oblica.com.au. Configuration 1 Parallel installation 750 2.2 Clearance from glass 350mm minimum clearance is required from normal non-combustible glass. 600mm Glass (frameless or aluminium frame) 200mm 200mm Glass (frameless or aluminium frame) Configuration 2 Corner installation 600mm 600mm IMPORTANT: Frames must also be considered. Timber window frames must be treated as combustible surfaces (see 2.3). Aluminium frames can be treated as non-combustible surfaces (see 2.2). PAGE 4

2. PRE-INSTALLATION (CONTINUED) MINIMUM CLEARANCE INTERNAL 2.3 Clearance from combustible surfaces (eg timber joist & concrete) Skamotec 225 sheet (2000mm x 1200mm) must be of 25mm thick and installed directly on combustible wall. The sheet must be fixed with the 2000mm length fixed centrally behind the appliance and must extend to a height of 1200mm above the hearth. Configuration 3 With Skamotec 225 25mm thick 2000mm 250 600mm PAGE 5

3. INSTALLATION 3.1 Installing flue kit Ensure flue is installed as per Australian standards (see the following diagrams below). Cowl (Chinaman Hat) 8 Outer Case 10 Outer Case RUBBER DEKTITE FLASHING 6 Active Flue 8 Outer Case 10 Outer Case CEILING RING 8 Outer decorative casing 6 Active Flue Crimped end up on dec outer case 8 Outer decorative casing NOTE: The active flue must go around the fireplace outlet on the outside. FIREBOX PAGE 6

3. INSTALLATION (CONTINUED) 3.2 Installing the external flue Ensure the triple skin flue is installed as per Australian standards (see diagrams below). PITCHED ROOF INSTALLATION The top of the flue must be 400mm higher than the highest point of the roof. Alternatively, there must be a minimum distance of 3 meters from any higher section of roof. > 40 cm > 40 cm > 3 m > 40 cm FLAT ROOF INSTALLATION (LESS THAN 5 PITCH) The top of the flue must be 900mm above the roofline. Alternatively, there must be a minimum distance of 3 meters from any higher section of roof. > 900 cm > 900 cm > 3 m > 900 cm PAGE 7

3. INSTALLATION (CONTINUED) 3.3 Protecting the floor Non-combustible finishes can be applied to the floor protector (tiles, steel sheet, light concrete, etc). If the combustible floor is installed on concrete, you can replace the combustible material with noncombustible material laid directly onto the concrete. A minimum of 1560mm deep x 1140mm wide x 18mm thick floor protector (Belis Board) should be used under and in front of the Kazan fireplace. The floor protector should extend 600mm in front of the appliance. The thermal conductivity of the floor protector is 0.1m 2 k/w for 9mm thick sheet. FLOOR PROTECTOR LAID ON TIMBER FLOOR FLOOR PROTECTOR LAID ON JOIST floor (eg. timber) Insulative board (18mm) + non combustible finish floor (eg. timber) Insulative board (18mm) + non combustible finish Joist Joist PAGE 8

3. INSTALLATION (CONTINUED) FLOOR PROTECTOR LAID ON CONCRETE floor (eg. timber) Non combustible finish (eg.tiles) Concrete TOP VIEW 244mm 244mm 1560mm Floor protector 600mm floor (eg: Timber) 1140mm PAGE 9

4. OPERATION 4.1 What you should burn Untreated, air dried hardwood Split logs with a humidity content of less than 20% 4.2 Do not burn Trash Painted plastic Coated or preservative treated wood Waste or black coal Inflammable liquids Fire gels Moist wood with a residual humidity content of more than 20% (this may cause soothing of the chimney). IMPORTANT: Misuse may lead to unhealthy and environmentally harmful emissions and will void any warranty or guarantee. The maximum load capacity for the Kazan is 5kg of wood. Burning only seasoned hardwood helps to protect the environment and lower emissions. For details of a wood supplier in your area please call our office on 03 9416 0400 or email info@oblica.com.au. WARNING: Do not use flammable liquids or aerosols to start or rekindle the fire. Do not use flammable liquids or aerosols in the vicinity of the fireplace when operating. Do not store fuel within prescribed installation clearance distances. The use of some types of preservative-treated woods as a fuel can be hazardous. PAGE 10

5. TESTING TEST REPORT NO ASFT17008 TESTING LABORATORY: MANUFACTURER: MODEL: Australian Solid Fuel Testing Invicta Kazan fireplace WORK REQUESTED: Assessment of appliance to AS/NZS 4012:2014 for determination of Power Output and Efficiency and AS/NZS 4013:2014 for Flue Gas Emission using hardwood fuel. ISSUE DATE: 25/01/2017 INVESTIGATING OFFICER: RESULTS: CONCLUSION: Steve Marland The appliance particulate emission factor established in testing is 1.3g/kg of dry wood, within the maximum specification of 2.5g/kg of dry wood, and have a 60% efficiency. This appliance does comply with the requirements of AS/NZS 4013:2014 for the configuration tested. PAGE 11