An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors

Similar documents
Variable Speed Solutions. Outstanding performance for residential applications

Variable Speed Solutions Outstanding Performance For Heat Pump Applications

Using Simulation Model to Reduce System Design Time and Cost

Heating Performance with a Volume Ratio on 2-Stage Compressor

Unitary Air Conditioner Field Performance

Recent U. S. R&D results from IEA HPP Annex 41

> HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION. Available range. Unit description. Options. Accessories

i-chiller 125 to 169 kw ic640 to ic660 ABOUT THE i-chiller RANGE ENERGY & PROCESS EFFICIENCY: RELIABILITY: EASE OF OPERATION & MAINTENANCE:

COOLING BENCHMARKING STUDY Part 3: Testing Component Report

The Part-Load Efficiency Benefit of Oil-Free, High- Speed, Direct-Drive Centrifugal Compressors

Performance Mapping for Variable Ductless Heat Pump Systems in Heating, Cooling and Defrost Operation

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

i-chiller COMPACT 1 to 4 kw 0 C to 30 C ic03c to ic10c RELIABILITY:

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

Normalized Effect Of Condenser Fouling And Refrigerant Charge On Performance Of Vapor Compression Air Conditioning Systems

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

Seasonal Energy Efficiency Rating Improvement Of Residential HVAC Systems Using A Low Power Inverter With A PSC Compressor

Inverter Drive Control and Seasonal Performance Analysis of a Single Speed Unitary Air-Source Split-System Heat Pump

Seasonal performances and compression technology

Application Of Oil Flooded Compression With Regeneration To A Packaged Heat Pump System

Heat Pumps. and energy labelling regulations

AIR-TO-AIR HEAT PUMPS EVALUATED FOR NORDIC CLIMATES- TRENDS AND STANDARDS

Integrated Air Conditioning System

The Benefit of Variable-Speed Turbine Operation for Low Temperature Thermal Energy Power Recovery

Water Heating Technologies To Meet Energy & Environmental Challenges

Zeta Rev HP XT. High efficiency air source reversible heat pumps heating kw. blueboxcooling.com. KINDERGARTEN Sofia - Bulgaria

Rooftops High performance, proven reliability and easy installation

Performance Characteristics and Mapping for a Variable-Speed Ductless Heat Pump

Water-cooled Chillers with High Speed Centrifugal Compressors

SIMPLICITY OR INTELLIGENCE? Heat pumps and water-cooled chillers Cooling capacity kw Heating capacity kw 30WG / 61WG / 30WGA

Experimental Results on a New Prototype Packaged Heat Pump System Retrofitted with Oil Flooded Compression and Regeneration Technology

Detailed performance assessment of variable capacity inverter-driven cold climate air source heat pumps

The Impact of Evaporator Fouling on the Performance of Packaged Air Conditioners

Characteristics of Energy Consumption by building type of a U.S. Navy Installation in Hot and Humid Climate

EHPA suggestion We thus suggest to integrate waste heat recovery into the aligned test standards.

Energy labelling and ecodesign requirements for heat pumps

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 7 to 16 KW

The impact of the work under partial load on the energy efficiency of an air-to-water heat pump

Design and development of a residential gas-fired heat pump

Executive Summary. Final July Introduction

Conversion Factors for Comparing the Performance of Variable Refrigerant Flow Systems

IT COOLING CHILLERS. NEW GENERATION OF AIR COOLED CHILLERS FOR IT COOLING APPLICATIONS. CAPACITY RANGE kw, SCROLL COMPRESSORS AND R410A

AIR CONDITIONING & HEATING SOLUTIONS. AquaFORCE. Fixed-speed screw chiller. 250 kw 1700 kw 30XB & 30XBP

Experimental Study of a CO2 Thermal Battery for Simultaneous Cooling and Heating Applications

Air-Cooled Screw Chillers RTAF-G kw. The best bundled in one. Our best.

Eurovent Association Eurovent Certification Activities related to ENERGY EFFICIENCY

City Multi VRF. Seasonal Efficiency Explained

technical bulletin Subcooler Control

Development of high efficiency VRF systems under partial heat load for commercial buildings

Økodesign Chiller med naturlige kuldemedier

RHA TECNICAL MANUAL AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION O L S E A F RA N

Center for Environmental Energy Engineering Department of Mechanical Engineering University of Maryland College Park, MD

COPs, EERs, and SEERs

Reducing Operating Costs with Optimal Maintenance Scheduling

WORKING DOCUMENT. (Text with EEA relevance) Warm air heaters using gaseous fuel

Labelling and certification of HVAC products

Investigation on effects of piping on heating performance of multi-split variable refrigerant flow system

kw. Tetris W. High efficiency water cooled chillers and heat pumps. Bullet points. General. Configurations

LCCP Analysis of Energy-Saving Effect of Defaulting to Recirculated Cabin Air in EV Mobile Air Conditioning System

Building Energy Analysis for a Multi-Family Residential Building (Multi V III VRF Heat-Pump System)

Air Cooled Chiller (50Hz) Air Cooled Scroll. Air Cooled Screw ACC 05/15

A Study on Engineering Application of Solar Heating System Assisted by Heat Pump

ACTIVA Rooftop. YKN2open. ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw. Nomenclature A R C 045 B B. Features

1 Project Information. 2 Building Type. 3 Trade Ally/Contractor Information. HVAC Rebate Worksheet. Retrofit New Construction

Development of a compact single room ventilation unit with heat recovery dedicated to tertiary building

Investigation on A Ground Source Heat Pump System Integrated With Renewable Sources

Component-Based Vapor Compression Simulation Tool With Integrated Multi-Objective Optimization Routines

Steady State Modeling of Advanced Vapor Compression Systems with Multiple Air and Refrigerant Loops

HITACHI Modular Chiller Solutions

Performance Evaluation under the Actual Operation Condition of a Ground Source Multiheat Pump System

Air Cooled Packaged Air Conditioning

Performance Testing of Cold Climate Air Source Heat Pumps

Omicron Rev S4 Multi-functional units for 4-pipe systems

(Notices) EUROPEAN COMMISSION

WATER CHILLER / HEAT PUMP. The high performance packaged solutions for all your needs

Standardizing Smart/Connected Products in a Highly Innovative and Dynamic Market

Enhanced Refrigeration Diagnostics for an Improved Air Conditioning Tune-Up Program

Energy and Comfort Performance Analysis of Monitored Thermally Activated Building Systems Combined with Geothermal Heat Pumps

Modelica-Based Heat Pump Model for Transient and Steady-State Simulation Using Low-GWP Refrigerants Paper 2264

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

Ductless Heat Pumps OTP Series

Opportunities and Limitations of Building Precooling

Water Cooled Screw Chillers And Water/Water Heat Pumps

Smardt Water Cooled Chillers

CO2 solutions February 2018

SorTech package solution description

High Efficiency. 7 % on average. EFFICIENCY RATIO WHAT'S IMPROVED? APF: Annual Performance Factor. NS Type

Eurovent certification programmes for HVAC products with verified performances

Air Conditioners 4AC13

FLOWRATE DEPENDENT HEAT-PUMP MODEL

YKN2open A R C 032 A B

Fundamental Investigation Of Whole-Life Power Plant Performance For Enhanced Geothermal Systems

A Performance Based Method to Determine Refrigerant Charge Level For Commissioning Unitary AC and HP Systems

Utilizing Heat Dump Capacity of a Small Pond Attached to Infloor Slab of a Net-Zero Energy House

MPE 4-76 kw. Outdoor packaged unit. Air/water chillers and heat pumps MPE. Efficiency under all operating conditions. 152 galletti.

Secondary Loop System for Automotiv HVAC Units Under Different Climatic Conditions

Cold Climate Heat Pump using Tandem Vapor-Injection Compressors

A Comprehensive Evaluation of Regression Uncertainty and the Effect of Sample Size on the AHRI-540 Method of Compressor Performance Representation

Water-Cooled Screw Chillers and Water/Water Heat Pumps

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors Stephane Bertagnolio Emerson Climate Technologies, Aachen, Germany, stephane.bertagnolio@emerson.com Eric Winandy Emerson Climate Technologies, Aachen, Germany, eric.winandy@emerson.com Dina Koepke Emerson Climate Technologies, Aachen, Germany, dina.koepke@emerson.com Follow this and additional works at: http://docs.lib.purdue.edu/iracc Bertagnolio, Stephane; Winandy, Eric; and Koepke, Dina, "An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors" (2016). International Refrigeration and Air Conditioning Conference. Paper 1784. http://docs.lib.purdue.edu/iracc/1784 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2528, Page 2 An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors Stephane BERTAGNOLIO 1 *, Eric WINANDY 1, Dina KOEPKE 1 1 Emerson Climate Technologies Gmbh, Aachen, Germany stephane.bertagnolio@emerson.com * Corresponding Author ABSTRACT For a couple of years already, variable speed compressor technology has become a standard for residential heating and cooling applications. Indeed, as a response to increasing performance requirements, small capacity variable speed scroll compressors optimized for heating and cooling applications were released and progressively adopted on the market. In January 2018, the first tier of the Ecodesign Directive (2009/125/EC) requirements defined for commercial AC chillers will enter into force across European Union. The application of this new regulation will most likely drive the European commercial AC market toward a similar direction than the residential market and a more intensive adoption of the variable speed technology, especially for systems below 400kW rating cooling capacity. This paper presents integrated solutions targeting efficient implementation of variable speed technology in commercial water chillers, allowing system manufacturers to face new regulatory challenges. The considered solution integrates multiple configurations of variable speed and fixed speed scroll compressors, variable frequency drive, electronic expansion valve and control. Compressors envelopes management and protection as well as superheat control capabilities are presented. Seasonal performance simulations have been realized according to EN14825 to quantify the gain of variable speed technology. Laboratory testing has been performed to develop and qualify the considered solution. Testing on a real Air-to-Water chiller has also been realized to fine-tune the control and measure the achieved efficiency levels. 1. INTRODUCTION Until today, no regulation imposes minimal energy performance requirements (MEPS) for chillers on the European market. Only nominal rating performance in cooling (Energy Efficiency Ratio EER) and heating (Coefficient Of Performance COP) had to be measured according to EN14511 and published. Seasonal performance in cooling mode was also often indicated by manufacturers in the form of Eurovent s ESEER certified value, but only on voluntary basis. Since January 2015, minimal seasonal performance requirements are in application for heating systems (including residential and commercial heat pumps, up to 400 kw rating capacity) as defined in the Lot 1 of Energy-related Products (ErP) Ecodesign Directive (2009/125/EC). European energy labels, intended to inform end-users, have also to be provided for systems below 70kW rating capacity. In January 2018, a similar regulation for AC systems will entry into force and the first tier of the requirements defined for chillers will be in application across European Union.

2528, Page 3 This new regulation provides also the methodology and reference normative by which obtaining the seasonal primary energy efficiency, η % value, which is directly related to the seasonal efficiency ratio (SEER) defined in EN14825. It is anticipated that the entry into force of this regulation, as well as other regulatory aspects (such as Energy Performance of Buildings Directive and European F-Gas Regulation aiming at reducing the environmental impact of high GWP refrigerants) and technology trends, will have very significant and very different impacts on the market and the design of chillers of rating cooling capacity below and above 400kW. The first part of this paper includes a description of upcoming performance regulation impacting the European commercial AC market. General principles of the testing and calculation method, based on EN14825, used to measure seasonal performance of chillers are presented. In the second part of the paper, the development of integrated solutions for efficient implementation and operation of Variable speed technology in commercial chillers is described. Conducted experimental and modeling activities are also introduced. 2. SEASONAL ENERGY PERFORMANCE REQUIREMENTS The upcoming European Commission Regulation setting minimal performance requirements for cooling products is being established in the frame of implementation of ErP directive, and being currently finalized. Minimal requirements are defined in terms of seasonal primary energy efficiency and can be converted into seasonal energy efficiency ratio (SEER) values, as shown in Table 1 for space cooling water chillers. Table 1: Minimal seasonal performance requirements for space cooling chillers A/W W/W Tier 1 Jan 2018 Tier 2 Jan 2021 <400 kw 3.80 4.10 400 kw 4.10 4.55 <400 kw 4.98 5.08 400 kw and <1500 kw 5.75 6.38 1500 kw 6.20 6.88 While first tier of requirements is achievable with today technology, it is expected that tier 2 will require significant redesign of existing chiller systems available on the market. 2.1 Seasonal Performance of Systems The methodology defined in EN14825 to establish the seasonal performance index of chillers can be defined in three successive steps: 1. Unit performance measurement at 4 reference test conditions 2. Performance interpolation across standard European cooling season to establish active mode performance 3. Calculation of seasonal energy efficiency ratio (SEER) First the steady-state performance (declared capacity and energy efficiency ratio) of the full unit (including compressors, air and water side auxiliaries and controls) has to be measured at 4 reference conditions (Table 2) representing different full load and part load regimes and operating conditions (ambient and water temperatures). Three water temperature regimes are considered for fan coil applications (12/7 C) with fixed or variable outlet setpoint and cooling floor application (23/18).

2528, Page 4 Rating Point Ambient Temperature ( C) Table 2: Reference conditions for Air-to-Water chillers Part Load Ratio (%) Fan Coil inlet/outlet water temperature ( C) Fixed outlet Variable outlet Cooling Floor inlet/outlet water temperature ( C) A 35 100 12/7 12/7 23/18 B 30 74 */7 */8.5 */18 C 25 47 */7 */10 */18 D 20 21 */7 */11.5 */18 In part load regime (conditions B, C and D), impact of ON-OFF cycling of the unit (i.e. between smallest capacity stage and zero) has to be integrated according to equation (1) and may end in severe degradation of the declared performance (EERd), depending on the capacity ratio (CR) and degradation coefficient (CC). = (1) For example, assuming a capacity ratio (CR) of 50% between cooling demand and unit capacity at a given condition and a degradation factor (CC) of 0.9, EER degradation reaches 9.1%. Then, a steady state EERd of 4 in operation would actually be recognized as 3.6 in part load (EERpl) by the method. EN14825 provides the method to establish the actual value of the cycling degradation coefficient. If this test has not been performed, a default value of 0.9 should be applied. In case of ON-OFF cycling of the unit, water temperature set point has also to be lowered to take into account outlet temperatures variations. This correction further impacts performance of the unit since evaporating temperature is changing accordingly. In a second time, measured full load and part load performance at A, B, C and D conditions are interpolated in order to establish the active seasonal performance, SEER ON. The calculation method includes finding an EERpl value for each temperature bin within the temperature interval of the climate zone. Interpolated values are used for temperatures between the determined reference test points. For temperatures outside the test points, closest measured values are used. Figure 1: Cooling Energy & Part Load curves for a 80kW unit Since significant number of operating hours occur at medium-low ambient (and cooling load), part load performance of the unit is crucial in order to achieve high overall seasonal performance. On the contrary, only limited number of hours are considered for full load operation (Figure 1).

2528, Page 5 Finally, unit energy consumption during auxiliary modes has to be integrated to deduce the reference SEER which is the ratio between the reference annual cooling demand (in kwh) and the annual energy consumption (Equation 2). The annual electricity consumption (Equation 3) includes thermostat off mode, standby mode, crankcase heater mode, and off mode; each mode corresponding to a particular power consumption (P) and a number of running hours defined in the regulation (H). = = (2) + + + + (3) Of course, auxiliary modes have also a considerable impact on final seasonal performance and particular attention has to be paid to reduce energy consumption in such modes to the minimum. 2.2 Seasonal Performance Simulations A simulation tool has been developed internally to allow seasonal performance calculations on non-reversible and reversible chiller systems according to the related standard. To allow system seasonal performance simulation, the calculation tool has to integrate, not only compressors performance data, but also heat exchangers performance and auxiliaries consumptions (fans, pumps, crankcase heaters...). Simulations of an R410a Air-To-Water chiller have been carried out to compare different compressors configurations and technologies. Assumptions regarding heat exchangers have been defined to reflect state-of-the-art chiller technology: - Evaporator plate heat exchanger approach of 3K in nominal full load operation (Water inlet/outlet temperatures: 12/7 C and evaporating temperature of 4 C) - Fin-and-tube condenser coil with an approach of 15K in nominal full load condition (35 C outdoor temperature and 50 C condensing temperature) In a single compressor systems, cycling losses are critical. For a single fixed speed compressor, compressor gross EER is progressively degraded due to system auxiliaries (EERnet) and then due to cycling losses (EERpl). Of course, cycling losses become significant at low load (low capacity ratio), leading to a degradation of the unit EER up to 70% (Figure 2). Part of this performance degradation is due to water setpoint correction which can reach 3 to 4 K. CR~20% Figure 2: Cooling Load & EER Curves For Fixed Capacity Compressor System. When properly designed and used, variable speed technology allows to cover most of the capacity demand without any ON-OFF cycling. EER degradation is then mainly due to water-side and air-side auxiliaries (Figure 3). Overall seasonal performance gain comparing to a fixed speed system may reach 15 to 20%.

2528, Page 6 Figure 3: Cooling Load & EER Curves for Variable Speed Compressor System. While variable speed brings significant performance gain for small and medium-size systems, in larger systems with multiple fixed capacity compressors (ex: dual-circuit unit with one tandem of compressors per circuit), gain is relatively limited and typically reaches a few percent (Table 3). Indeed, in such configurations, the presence of multiple capacity stages allows strongly reducing the impact of cycling losses. Table 3: Normalized Seasonal Performance for Various A/W Chiller Configurations System Configuration Number of Number of Normalized Refrigerant Circuits Compressors SEER Fixed Capacity Compressor 1 1 100% (Reference) Variable Speed Compressor 1 1 117% Fixed Capacity Tandem 1 2 113% Variable Speed Tandem 1 2 119% 2 x Fixed Capacity Tandem 2 4 121% 2 x Variable Speed Tandem 2 4 122% 2 x Fixed Capacity Trio 2 6 122% 2 x Variable Speed Trio 2 6 122% As already mentioned, power consumptions of auxiliaries (pumps, crankcase heaters ) also have a negative impact on overall seasonal performance of the systems, of about 6 to 7% in average. Medium and large chillers (250 kw rating cooling capacity and above) often embark multiple compressors and can continue to rely on proven and efficient fixed speed compressors, used in tandem or trio on one circuit or more. However, design of smaller systems usually using one or two compressors will have to be adapted and integrate variable speed technology. 3. INTEGRATED SOLUTION FOR SYSTEMS USING VARIABLE SPEED SCROLL COMPRESSORS 3.1 Variable Speed Scroll Technology In 2012, cooling optimized and heating optimized high efficiency variable speed scroll compressors have been released and we very successful on European residential heat pump market, covering a range from 4kW to 23kW rating capacity. Those compressors are qualified with R410A refrigerant and are controlled by an Emerson drive (Dardenne et al., 2014). In 2013, an integrated Refrigerant Module for Heating (RMH) has been developed using this technology. This is a refrigerant circuit designed for use in split air-to-water heat pump applications, where the evaporator is located outdoors. RMH integrates the aforementioned vapor injection variable speed compressor, its drive, the indoor refrigerant circuit (i.e. economizer, liquid receiver ) and its Refrigerant Circuit Controller (RCC).

2528, Page 7 In 2014, the existing range of variable speed compressors has been extended with larger capacity variable speed scroll compressors, dedicated to commercial AC market. This last generation of variable speed scroll compressors provides the following advantages - Expanded operating envelope providing great flexibility in design of reversible systems - Expansive 900-7200 RPM speed range for enhanced light load efficiency - Optimized scroll elements for variable speed performance and efficiency boost in part load operation - Low oil circulation compressor plus scroll oil injection for low speed performance and reliability - Permanent magnet motor technology for highest efficiency - Capability to build tandems and trios with fixed speed compressors for maximum flexibility in system design These compressors were not released alone but were integrated with the range of fixed speed compressors, allowing proposing multiple combinations (tandem and trio combinations of fixed and variable speed compressors) to cover various needs and capacities. Paralleling of variable speed scroll compressors has been made possible by paying particular attention to oil balancing and piping robustness (Figure 4). Figure 4: 15hp Variable Speed Scroll Compressor & Inverter Drive (left). Fixed & Variable Speed Scroll Compressors Tandem (right) Variable speed scroll technology brings also many other advantages, such as: enhanced control accuracy, continuous capacity management, reduced startup current, low sound emissions at part load and during cycle reverse transitions of reversible systems. Compressor-drive matching is also critical and requires particular attention in order to deliver the best performance in terms of motor and inverter drive efficiency and reliability. Active protection algorithms incorporated into the motor control drive safeguard the compressor and drive from many adverse operating conditions, including: - Motor & scroll temperature protection - Locked rotor detection - Phase protection and correction - Maximum operating current detection - Anti-short cycling 3.2 Integrated Solution for Reversible Chillers Implementation of variable speed technology in chiller systems also represent a significant challenge for system manufacturers, in terms of system design, control and qualification. For that reason, some integrated solutions have been developed to:

2528, Page 8 - Allow easier and effective implementation of variable speed technology in systems by proposing prequalified sets of optimized components (compressors, drive, expansion valve and controls), ready for assembly, to system manufacturers - Increase performance of systems, not only through the use of variable speed technology, but also through more efficient system control and management in steady-state and transient operation - Reach maximal reliability by integrating active protection and fault detection capabilities Typically, the integrated solution includes (Figure 5): - the fixed and a variable speed scroll compressors (up to three per circuit), installed in tandem or trio, - the inverter drive with Modbus communication capability - the bipolar stepper motor electronic expansion valve - the pressure transducers and temperature sensors - the circuit controller, managing the main components of the refrigerant circuit Figure 5: Typical arrangement of the main elements of the integrated solution for a fixed & variable speed scroll compressors tandem chiller The peculiarity of the solution resides in the parallel management of compressors and electronic expansion valve. The control uses predictive algorithms relying on compressors and valve performance mapping data allows achieving more accurate and dynamic control of the system as well as active protection of the system. The circuit control ensures variable speed compressor envelope management and drives the compressor in a smooth way across the different regions of its operating envelope (Figure 6). The fixed speed compressor is also driven (i.e. started or stopped) by the circuit controller according to the capacity request provided by the unit or plant controller. In parallel, the electronic expansion valve (EEV) is driven to maintain compressors suction state within acceptable range to ensure efficient and reliable operation, avoiding too high superheat (typically >20K) or liquid floodback. EEV control during transient is crucial and has to match fast systems capacity variations (speed ramp-up/ramp-down and fixed speed compressor cycling) and transitions (cycle reversing for defrost or cooling/heating modes transitions, oil recovery cycles). To this end, smart control logics, including fuzzy logic, adaptive PID and dynamic valve prepositioning, have been implemented. EEV control is critical to ensure optimal system efficiency in steady-state operation. Indeed, too high superheat may quickly lead to inefficient operation due to excessive approach temperature in evaporator plate heat exchanger, leading to lower evaporating temperature levels and higher compressor power consumption. While lowering evaporator superheat is beneficial for system overall performance, it also increases the risk of liquid floodback to the compressor. Then, smart control algorithms relying on compressor and valve performance mapping equations are used to increase control robustness and achieve optimal superheat levels, below standard 5K thresholds, in a safe and reliable way.

2528, Page 9 Figure 6: Variable Speed Compressor Envelope with Different Speed Regions Of course, integrating compressors and EEV control can bring significant advantages in terms of active compressor protection, such as anticipation of high/low evaporating or high condensing limits crossing or floodback and activation of adapted corrective actions (compressor speed or valve opening adjustment) 4. SOLUTION PROTOTYPING AND TESTING To validate and fine-tune the advanced control and protection logics embedded in the circuit controller, the whole solution (compressors, drive, valve, sensors and controllers) were implemented in a real-life environment. A commercial reversible A/W chiller (Figure 7) has been installed and connected to an existing process cooling glycol loop (maintained at approx. 15 C all year long by several large A/W chillers). Figure 7: A/W Chiller Equipped with Variable Speed Scroll Solution (left) and test results (right) The 2-circuits unit, originally equipped with two tandems of fixed speed compressors has been modified. Compressors have been replaced by new generation variable and fixed speed scroll compressors. A new EEV has also been installed. Both steady-state and transient tests were performed between July and November 2015, mainly in cooling operation. During the test, the gain of low superheat control on evaporator approach, and then, on system performance was highlighted (Figure 7) especially at part load. Seasonal performance gain vs standard superheat control was estimated to 5 to 6%.

2528, Page 10 6. CONCLUSIONS European systems manufacturers are facing challenging times. New regulations are strongly impacting the commercial AC business and the design of new chiller systems. To meet upcoming minimal seasonal performance requirements, light commercial systems (below 250 kw rating cooling capacity) are likely to widely adopt variable speed compressor technology as residential AC and heat pump market did a few years ago. Implementation of variable speed technology in chiller systems will allow significant performance gain comparing to standard design but also represents a significant challenge for system manufacturers, in terms of system design, control and qualification. To support system manufacturers and allow them developing efficient and reliable systems with variable speed scroll technology, an integrated solution was developed, comprising a range of fixed speed and variable speed compressors able to work in tandem/trio configurations, inverter drives, electronic expansion valves and corresponding sensors and controls. The complete solution was implemented, tested and validated on a real A/W chiller. REFERENCES Dardenne, L., Fraccari, E., Maggioni, A., Molinarolli, L., Proserpio, L., Winandy, E. 2014. A Wet-Vapour Injection and Variable Speed Scroll Compressor Air to Water Heat Pump Model and its Field Test Validation. Proceedings of the 11th IEA Heat Pump Conference, Montreal, Canada. European Commission. 2013. Commission Regulation (EU) No 813/2013 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for space heaters and combination heaters. Official Journal of the European Union. European Committee for Standardization. 2013. pren 14825 - Air conditioners, liquid chilling packages and heat pumps, with electrically driven compressors for space heating and cooling Testing and rating at part load conditions and calculation of seasonal performance.