DIVISION: CONCRETE SECTION: CAST-IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI, INC.

Similar documents
DIVISION: DIVISION: CONCRETE SECTION: CAST-IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI, INC.

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI, INC.

DIVISION: CONCRETE SECTION: CAST-IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER:

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: MASON WEST, INC.

Trusted ICC ES. Issued 02/2018 SECTION: HILTI, INC. KCM MD. Evaluation. report, or as to any. ICC-ES Evaluation

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: DEWALT

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS DIVISION: CONCRETE ANCHORS REPORT HOLDER: DEWALT

ICC-ES Evaluation Report. ESR-3707 Issued October 2014 This report is subject to renewal November 2015.

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

ESR-2202 Issued May 1, 2009 This report is subject to re-examination in one year.

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Trusted ICC ES CONCRETEE SECTION: TOMARCO STREET. Look. Conformity! Evaluation. ICC-ES Evaluation

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

ESR-2713 Reissued August 1, 2013 This report is subject to renewal September 1, 2014.

Product Submittal/Substitution Request

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: KWIK BOLT TZ MASONRY ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES REPORT HOLDER: NELSON STUD WELDING, INC WEST RIDGE ROAD ELYRIA, OHIO 44036

ICC-ES Evaluation Report

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: ITW BUILDEX 700 HIGH GROVE BOULEVARD GLENDALE HEIGHTS, ILLINOIS 60139

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: POWERS FASTENERS, INC. 701 EAST JOPPA ROAD TOWSON, MARYLAND 21286

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

ESR-1545 Reissued February 1, 2014 This report is subject to renewal March 1, 2016.

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Trusted ICC ES HILTI, INC. Evaluation. report, or as to any. ICC-ES Evaluation

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 5000 SERIES FASTENERS

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

CITY OF LOS ANGELES CALIFORNIA

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW VELOCITY X-U AND X-U 15 UNIVERSAL FASTENERS AND X-P CONCRETE FASTENERS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

To: Firm: Project: Product Specified: Specified Location:

ICC-ES Evaluation Report. ESR-1917 Reissued May 2015 This report is subject to renewal May * * *Deleted by the City of Los Angeles

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

CITY OF LOS ANGELES CALIFORNIA

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

ESR-3122 Issued May 1, 2010 This report is subject to re-examination in one year.

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Trusted ICC ES CONCRETE SECTION: SECTION: 05 HILTI, INC. Look. Conformity! ICC-ES Evaluation

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: 5956 WEST LAS POSITAS BOULEVARD PLEASANTON, CALIFORNIA 94588

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT

Trusted. Issued 03/2015 SECTION: SECTION: 05 ITW ITW BUILDEX FOR. Conformity! ICC-ES Evaluation. Copyright 2015

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: JAACO CORPORATION NE 68 TH STREET, SUITE C 130 REDMOND, WASHINGTON EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 100 PLANO, TEXAS 75024

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Product Submittal/Substitution Request

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: METALS SECTION: METAL FASTENINGS DIVISION: FINISHES SECTION: FASTENERS REPORT HOLDER: HILTI, INC.

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: QUALITY WAY PRODUCTS, LLC 407 HADLEY STREET HOLLY, MICHIGAN 48442

CALIFORNIA ERIC GARCETTI MAYOR

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

ESR-2036 Reissued May 1, 2013 This report is subject to renewal June 1, 2015.

REPORT HOLDER: GRABBER CONSTRUCTION PRODUCTS, INC. EVALUATION SUBJECT: GRABBER FASTENERS FOR USG STRUCTURAL PANELS

Transcription:

0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-4145 Issued 02/2018 This report is subject to renewal 02/2019. DIVISION: 03 00 00 CONCRETE SECTION: 03 15 19 CAST-IN CONCRETE ANCHORS SECTION: 03 16 00 CONCRETE ANCHORS REPORT HOLDER: HILTI, INC. 7250 DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 EVALUATION SUBJECT: HILTI KCM-WF AND KCM-PD HEADED CAST-IN SPECIALTY INSERTS IN CRACKED AND UNCRACKED CONCRETE Look for the trusted marks of Conformity! 2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence A Subsidiary of ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2018 ICC Evaluation Service, LLC. All rights reserved.

ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-4145 Issued February 2018 Revised February 28, 2018 This report is subject to renewal February 2019. A Subsidiary of the International Code Council DIVISION: 03 00 00 CONCRETE Section: 03 15 19 Cast-in Concrete Anchors Section: 03 16 00 Concrete Anchors REPORT HOLDER: HILTI, INC. 7250 DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 (800) 879-8000 www.us.hilti.com HiltiTechEng@us.hilti.com EVALUATION SUBJECT: HILTI KCM-WF AND KCM-PD HEADED CAST-IN SPECIALTY INSERTS IN CRACKED AND UNCRACKED CONCRETE 1.0 EVALUATION SCOPE Compliance with the following codes: 2015, 2012, 2009, and 2006 International Building Code (IBC) 2015, 2012, 2009, and 2006 International Residential Code (IRC) For evaluation for compliance with codes adopted by the Los Angeles Department of Building and Safety (LADBS), see ESR-4145 LABC and LARC Supplement. Properties evaluated: Structural 2.0 USES The Hilti KCM-WF and KCM-PD Headed Cast-In Specialty Insert is used as anchorage to resist static, wind, and seismic (Seismic Design Categories A through F) tension and shear loads in cracked and uncracked normal-weight or lightweight concrete having a specified compressive strength, f c, of 2,500 psi to 10,000 psi (17.2 MPa to 68.9 MPa). There are three models for Hilti KCM-WF. The KCM-WF- 1/4-3/8 model is used with a threaded rod size of 1 / 4 inch or 3 / 8 inch; The KCM-WF-3/8-1/2 model is used with a threaded rod size of 3 / 8 inch or 1 / 2 inch; The KCM-WF-3/8-1/2-5/8 model is used with a threaded rod size of 3 / 8 inch, 1 / 2 inch, or 5 / 8 inch. There are two models for Hilti KCM-PD. The KCM-PD- 1/4-3/8 model is used with a threaded rod size of 1 / 4 inch or 3 / 8 inch; And the KCM-PD-3/8-1/2-5/8 model is used with a threaded rod size of 3 / 8 inch, 1 / 2 inch, or 5 / 8 inch. Reference to inserts in this report refers to the proprietary specialty anchorage products (KCM-WF and KCM-PD) used in concrete; reference to steel insert elements refers to threaded rods or bolts; reference to anchors or insert anchor system in this report refers to the installed inserts in concrete with threaded rods or bolts. The insert anchor system is an alternative to cast-in anchors described in Section 1901.3 of the 2015 IBC, Sections 1908 and 1909 of the 2012 IBC, and Sections 1911 and 1912 of the 2009 and 2006 IBC. The insert anchor system may be used where an engineered design is submitted in accordance with Section R301.1.3 of the IRC. 3.0 DESCRIPTION 3.1 KCM-WF and KCM-PD: Hilti KCM-WF and KCM-PD are steel internally threaded headed cast-in specialty inserts which receive threaded steel insert elements such as threaded rods and bolts in 1 / 4-inch, 3 / 8-inch, 1 / 2-inch, and 5 / 8-inch thread diameters. Inserts are manufactured from carbon steel and have a minimum 5.0 μm (0.0002 inch) zinc coating. The steel outer shell is covered in a thin plastic housing up to the steel head bearing surface. The KCM-WF is illustrated in Figure 1 and KCM-PD is illustrated in Figure 2. The KCM-WF insert is installed into the wood-form for a concrete member using the attached nails prior to the casting of the concrete. The inserted threaded rod or bolt can be installed into the internally threaded section of the KCM-WF after the wood-form is removed from the concrete. The KCM-PD insert is installed into the removable pan joist deck for a concrete member using self drilling screws prior to the casting of the concrete. The inserted threaded rod or bolt can be installed into the internally threaded section of the KCM-PD after the Pan Joist Deck is removed from the concrete. The inserts are color coded as indicated in Table 1. Figures 3 and 4 show a diagram of the installed KCM-WF and KCM-PD in a concrete member. 3.2 Steel Insert Elements: 3.2.1 Threaded Steel Rods and Bolts: Threaded steel rods (all-thread) or bolts must be threaded into the KCM-WF or KCM-PD. Table 3 includes design information ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2018 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 11

ESR-4145 Most Widely Accepted and Trusted Page 2 of 11 or several grades of common threaded rod or bolts for the applicable diameters. Carbon steel threaded rods or bolts must be furnished with a minimum 5.1 μm (0.0002 inch) zinc plating. 3.2.2 Ductility: In accordance with ACI 318-14 2.3 or ACI 318-11 D.1, as applicable, in order for a steel anchor element to be considered ductile, the tested elongation must be at least 14 percent and the reduction of area must be at least 30 percent. Steel elements with a tested elongation of less than 14 percent or a reduction of area less than 30 percent, or both, are considered brittle. Values for common steel threaded rod insert elements are provided in Table 3 of this report. The Hilti KCM-WF and KCM-PD Headed Cast-In Specialty Insert steel bodies are considered brittle elements. Where values are nonconforming or unstated, the steel element must be considered brittle. 3.3 Concrete: Normal-weight and lightweight concrete must conform to Sections 1903 and 1905 of the IBC. 4.0 DESIGN AND INSTALLATION 4.1 Strength Design: 4.1.1 General: Design strength of anchors complying with the 2015 IBC as well as Section R301.1.3 of the 2015 IRC, must be determined in accordance with ACI 318-14 Chapter 17 and this report. Design strength of anchors complying with the 2012 IBC as well as Section R301.1.3 of the 2012 IRC, must be determined in accordance with ACI 318-11 Appendix D and this report. Design strength of anchors complying with the 2009 IBC and Section R301.1.3 of the 2009 IRC must be determined in accordance with ACI 318-08 Appendix D and this report. Design strength of anchors complying with the 2006 IBC and Section R301.1.3 of the 2006 IRC must be in accordance with ACI 318-05 Appendix D and this report. Design parameters provided in this report are based on the 2015 IBC (ACI 318-14) and the 2012 IBC (ACI 318-11) unless noted otherwise in Sections 4.1.1 through 4.1.13. The strength design of anchors must comply with ACI 318-14 17.3.1 or ACI 318-11 D.4.1, except as required in ACI 318-14 17.2.3 or ACI-11 318 D.3.3, as applicable. Strength reduction factors, φ, as given in ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, for cast-in headed anchors, must be used for load combinations calculated in accordance with Section 1605.2 of the IBC, Section 5.3 of ACI 318-14, or Section 9.2 of ACI 318-11, as applicable. Strength reduction factors,φ, as given in ACI 318-11 D.4.4 must be used for load combinations calculated in accordance with ACI 318-11 Appendix C. An example calculation in accordance with the 2015 IBC is provided in Figure 7 of this report. The value of f c used in the calculations must be limited to a maximum of 10,000 psi (68.9 MPa), in accordance with ACI 318-14 17.2.7 or ACI 318-11 D.3.7, as applicable. 4.1.2 Requirements for Static Steel Strength in Tension: The nominal static steel strength in tension, N sa, of a single anchor must be calculated in accordance with ACI 318-14 17.4.1 or ACI 318-11 D.5.1, as applicable, for the threaded steel insert element, N sa,rod, as illustrated in Table 3 of this report. The lesser of φn sa,rod in Table 3 or φn sa,insert provided in Table 2 shall be used as the steel strength in tension. 4.1.3 Requirements for Static Concrete Breakout Strength in Tension: The nominal concrete breakout strength of a single anchor or group of anchors in tension, N cb or N cbg, respectively, must be calculated in accordance with ACI 318-14 17.4.2 or ACI 318-11 D.5.2, as applicable, for cast-in headed bolts. The basic concrete breakout strength in tension, N b, must be calculated in accordance with ACI 318-14 17.4.2.2 or ACI 318-11 D.5.2.2, as applicable, using the values of h ef given in Tables 1 and 2, and with k c = 24. The nominal concrete breakout strength in tension in regions where analysis indicates no cracking in accordance with ACI 318-14 17.4.2.6 or ACI 318-11 D.5.2.6, as applicable, must be calculated with Ψ c,n = 1.25. 4.1.4 Static Pullout Strength in Tension: The Static Pullout Strength in Tension for the KCM-WF and KCM-PD does not control design, and need not be calculated. 4.1.5 Requirements for Static Side-Face Blowout Strength in Tension: For the KCM-WF and KCM-PD, the nominal side-face blowout strength of a headed insert, N sb, must be calculated in accordance with ACI 318-14 17.4.4.1 or ACI 318-11 D.5.4.1, as applicable, for the cast-in headed insert, using the values of A brg as given in Table 1 of this report, as applicable. 4.1.6 Requirements for Static Steel Strength in Shear: For all applications that include resistance to shear loading, only the largest diameter of threaded rod for each insert must be used as the steel insert element. The nominal static steel strength of a single anchor in shear, V sa, must be taken as the threaded steel insert element strength, V sa,rod, given in Table 3 of this report. The lesser of φv sa,rod in Table 3 or φv sa,insert in Table 2 must be used as the steel strength in shear, and must be used in lieu of the values derived by calculation from ACI 318-14 Eq. 17.5.1.2a or ACI 318-11, Eq. D-28, as applicable. The values given in Table 2 are for the insert only. Determination of the shear capacity of the threaded rod or other material inserted into the cast-in insert is the responsibility of the design professional. Shear values for common threaded rods are given in Table 3. 4.1.7 Requirements for Static Concrete Breakout Strength in Shear: For the KCM-WF and KCM-PD, the nominal static concrete breakout strength of a single anchor or group of anchors in shear, V cb or V cbg, respectively, must be calculated in accordance with ACI 318-14 17.5.2 or ACI 318-11 D.6.2, as applicable. The basic concrete breakout strength, V b, must be calculated in accordance with ACI 318-14 17.5.2.2 or ACI 318-11 D.6.2.2 based on the values provided in Table 1. The values of l e (=h ef) and d a used in ACI 318-14 Eq. 17.5.2.2a or ACI 318-11 Eq. D-33, as applicable, are provided in Table 1 of this report. 4.1.8 Requirements for Static Concrete Pryout Strength in Shear: For KCM-WF and KCM-PD inserts, the nominal concrete pryout strength of a single anchor or group of anchors, V cp or V cpg, respectively, must be calculated in accordance with ACI 318-14 17.5.3 or ACI 318-11 D.6.3, as applicable. 4.1.9 Requirements for Seismic Design: 4.1.9.1 General: For load combinations including seismic, the design must be performed in accordance with ACI 318-14 17.2.3 or ACI 318-11 D.3.3, as applicable. Modifications to ACI 318-14 17.2.3 shall be applied under Section 1905.1.8 of the 2015 IBC. For the 2012 IBC, Section 1905.1.9 shall be omitted. Modifications to ACI 318 D.3.3 shall be applied under Section 1908.1.9 of the 2009

ESR-4145 Most Widely Accepted and Trusted Page 3 of 11 IBC, or Section 1908.1.16 of the 2006 IBC. The anchors may be installed in Seismic Design Categories A through F of the IBC. The KCM-WF and KCM-PD inserts comply with ACI 318-14 2.3 or ACI 318-11 D.1, as applicable, as non-ductile steel elements. For the KCM-WF and KCM-PD inserts, the nominal steel strength, nominal concrete breakout strength and nominal concrete side-face blowout strength for anchors in tension; and the nominal concrete breakout strength and pryout strength in shear, must be calculated in accordance with ACI 318-14 17.4 and 17.5 or ACI 318-11 D.5 and D.6, as applicable, using the values in Tables 1, 2 and 3, as applicable. 4.1.9.2 Seismic Tension: For KCM-WF and KCM-PD inserts, the nominal steel strength in tension, N sa, of a single anchor must be calculated in accordance with ACI 318-14 17.4.1 or ACI 318-11 Section D.5.1, as applicable, for the threaded steel element, N sa,rod,eq, as given in Table 3, not to exceed the corresponding values of N sa,insert,eq in Table 2 of this report; the nominal concrete breakout strength for anchors in tension must be calculated in accordance with ACI 318-14 17.4.2 or ACI 318-11 D.5.2, as applicable, as described in Section 4.1.3 of this report; the nominal pullout strength in accordance with ACI 318-14 17.4.3 or ACI 318-11 D.5.3, as applicable, need not be considered as noted in Section 4.1.4 of this report; the nominal concrete side-face blowout strength must be calculated in accordance with ACI 318-14 17.4.4.1 and 17.4.4.2 or ACI 318-11 D.5.4.1 and D.5.4.2, as applicable, and Section 4.1.5 of this report. 4.1.9.3 Seismic Shear: For KCM-WF and KCM-PD inserts, the nominal concrete breakout strength and pryout strength in shear must be calculated in accordance with ACI 318-14 17.5.2 and 17.5.3 or ACI 318-11 D.6.2 and D.6.3, as applicable, as described in Sections 4.1.7 and 4.1.8 of this report. In accordance with ACI 318-14 17.5.1.2 or ACI 318-11 D.6.1.2, as applicable, the nominal steel strength for seismic loads, V sa,eq, must be taken as the threaded steel element strength, V sa,rod,eq, given in Table 3 of this report, not to exceed the corresponding values of V sa,insert,eq, in Table 2. 4.1.10 Requirements for Interaction of Tensile and Shear Forces: For designs that include combined tension and shear, the interaction of tension and shear loads must be calculated in accordance with ACI 318-14 17.6 or ACI 318-11 D.7, as applicable. 4.1.11 Requirements for Minimum Member Thickness, h min, Minimum Anchor Spacing, s min, and Minimum Edge Distance, c min: Requirements on headed cast-in specialty anchor edge distance, spacing, member thickness, and concrete strength must be in accordance with the requirements in ACI 318-14 17.7 or ACI 318-11 D.8, as applicable, for cast-in bolts. 4.1.12 Requirements for Critical Edge Distance: The calculation of the critical edge distance, c ac, is not required, since the modification factor Ψ cp,n = 1.0 for cast-in anchors in accordance with ACI 318-14 17.4.2.5 or ACI-11 318 D.5.2.5, as applicable. 4.1.13 Lightweight Concrete: For the KCM-WF and KCM-PD in lightweight concrete, the modification factor λ, for concrete breakout strength must be in accordance with ACI 318-14 17.2.6 (2015 IBC), ACI 318-11 D.3.6 (2012 IBC), ACI 318-08 D.3.4 (2009 IBC), or ACI 318-05 D.3.4 (2006 IBC). 4.2 Allowable Stress Design (ASD): 4.2.1 General: Design values for use with allowable stress design (working stress design) load combinations calculated in accordance with Section 1605.3 of the IBC, must be established as follows: T allowable,asd = φn n α V allowable,asd = φv n α where: T allowable,asd = Allowable tension load (f or kn). V allowable,asd = Allowable shear load (f or kn). φn n = Lowest design strength of an anchor or anchor group in tension as determined in accordance with ACI 318-14 17.3.1 and 2015 IBC Section 1905.1.8, ACI 318-11, -08 D.4.1, and 2009 IBC Section 1908.1.9 or 2006 IBC Section 1908.1.16, as applicable (f or N). φv n = Lowest design strength of an anchor or anchor group in shear as determined in accordance with ACI 318-14 17.3.1 and 2015 IBC Section 1905.1.8, ACI 318-11, -08 D.4.1, and 2009 IBC Section 1908.1.9 or 2006 IBC Section 1908.1.16, as applicable (f or N). α = Conversion factor calculated as a weighted average of the load factors for the controlling load combination. In addition, α must include all applicable factors to account for non-ductile failure modes and required over-strength. The requirements for member thickness, edge distance and spacing, described in this report, must apply. Examples of allowable stress design value determination for illustrative purposes are shown in Table 4. 4.2.2 Interaction of Tensile and Shear Forces: For designs that include combined tension and shear, the interaction of tension and shear loads must be calculated in accordance with ACI 318-14 17.6 or ACI 318-11 D.7, as applicable, as follows: For shear loads V applied 0.2V allowable,asd, the full allowable load in tension must be permitted. For tension loads T applied 0.2T allowable,asd, the full allowable load in shear must be permitted. For all other cases: TT aaaaaaaaaaaaaa + TT aaaaaaaaaaaaaaaaaa,aaaaaa VV aaaaaaaaaaaaaa VV aaaaaaaaaaaaaaaaaa,aaaaaa 1.2 (Eq-1) 4.3 Installation: For the KCM-WF and KCM-PD inserts, installation parameters are provided in Table 1. Installation must be in accordance with this evaluation report and the manufacturer s printed installation instruction (MPII) as provided in Figures 5 and 6 of this report. In the event of a conflict between this report and the MPII, this report governs. 4.4 Special Inspection: Periodic special inspection is required in accordance with Section 1705.1.1 and Table 1705.3 of the 2015 or 2012

ESR-4145 Most Widely Accepted and Trusted Page 4 of 11 IBC, or Section 1704.15 and Table 1704.4 of the 2009 IBC, or Section 1704.13 of the 2006 IBC, as applicable. The special inspector must make periodic inspections during installation of the headed cast-in specialty inserts to verify insert type, insert dimensions, concrete type, concrete compressive strength, insert spacing, edge distances, concrete member thickness, insert embedment, threaded rod fully seated into insert, and adherence to the manufacturer s printed installation instructions. The special inspector must be present as often as required in accordance with the statement of special inspection. Under the IBC, additional requirements as set forth in Sections 1705, 1706 and 1707 must be observed, where applicable. 5.0 CONDITIONS OF USE The KCM-WF and KCM-PD concrete inserts described in this report are acceptable alternatives to what is specified in the codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 Specialty inserts are limited to dry interior locations. 5.2 Specialty insert sizes, dimensions, minimum embedment depths, and other installation parameters are as set forth in this report. 5.3 Specialty inserts must be installed in accordance with the manufacturer s printed installation instructions (MPII) and this report. In case of conflict, this report governs. 5.4 Specialty inserts must be limited to use in cracked and uncracked normal-weight concrete, and lightweight concrete having a specified compressive strength, f' c, of 2,500 psi to 10,000 psi (17.2 MPa to 68.9 MPa) for the KCM-WF and KCM-PD inserts. 5.5 The values of f' c used for calculation purposes must not exceed 10,000 psi (68.9 MPa). 5.6 The concrete shall have achieved its minimum design strength prior to loading of the specialty inserts. 5.7 Strength design values must be established in accordance with Section 4.1 of this report. 5.8 Allowable design values are established in accordance with Section 4.2. 5.9 Specialty insert spacing and edge distance as well as minimum member thickness must comply with ACI 318-14 17.7 or ACI 318-11 Section D.8 requirements, as applicable, for cast-in-place headed anchors, and Tables 1 and 2 of this report. 5.10 Prior to installation, calculations and details demonstrating compliance with this report must be submitted to the code official. The calculations and details must be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. 5.11 Since an ICC-ES acceptance criteria for evaluating data to determine the performance of the specialty inserts subjected to fatigue or shock loading is unavailable at this time, the use of these inserts under such conditions is beyond the scope of this report. 5.12 Specialty inserts may be installed in regions of concrete where analysis indicates cracking may occur (f t > f r), subject to the conditions of this report. 5.13 Specialty inserts may be used to resist short-term loading due to wind or seismic forces in locations designated as Seismic Design Categories A through F of the IBC, subject to the conditions of this report. 5.14 Where not otherwise prohibited in the code, inserts are permitted for use with fire-resistance-rated construction provided that at least one of the following conditions is fulfilled: Headed cast-in specialty inserts that support a fireresistance-rated envelope or a fire-resistance-rated membrane are protected by approved fireresistance-rated materials, or have been evaluated for resistance to fire exposure in accordance with recognized standards. Headed cast-in specialty inserts are used to resist wind or seismic forces only. Headed cast-in specialty inserts are used to support nonstructural elements. 5.15 Special inspection must be provided in accordance with Section 4.4. 5.16 Specialty inserts are manufactured under an approved quality control program with inspections by ICC-ES. 6.0 EVIDENCE SUBMITTED 6.1 Data in accordance with the ICC-ES Acceptance Criteria for Headed Cast-in Specialty Inserts in Concrete (AC446), dated February 2015, editorially revised January 2016. 6.2 Quality-control documentation. 7.0 IDENTIFICATION The KCM-WF and KCM-PD inserts are identified by packaging labeled with the company name (Hilti, Inc.) and contact information, insert name, insert size, lot number and evaluation report number (ESR-4145). The inserts have various colored plastic housings to identify the product size.

ESR-4145 Most Widely Accepted and Trusted Page 5 of 11 TABLE 1 HILTI KCM-WF AND KCM-PD CAST-IN INSERT INSTALLATION INFORMATION 2,3 DESIGN INFORMATION SYMBOL UNITS 1 / 4"- 3 / 8" 3 / 8"- 1 / 2" 3 / 8"- 1 / 2"- 5 / 8" Insert type - - WF and PD Only WF WF and PD Plastic housing color - - Green Orange Red Effective embedment 1 h ef in. (mm) 1.12 (28) 1.63 (41) 2.04 (52) Min. member thickness h min in. (mm) 2 1 / 2 (64) 2 1 / 2 (64) 3 (76) Outside anchor diameter d a in. (mm) 0.50 (12.8) 0.66 (16.9) 0.87 (22.1) Bearing area A brg in. 2 (mm 2 ) 0.91 (590) 1.00 (643) 1.23 (792) For SI: 1 inch = 25.4 mm. For pound-inch units: 1 mm = 0.03937 inches. 1 See figures 1 and 2. 2 Reference ACI 318-14 17.3.1.1 or ACI 318-11 D.4.1.1, as applicable. The controlling strength is decisive from all appropriate failure modes (i.e. steel, concrete breakout, pryout and side-face blowout, as applicable) and design assumptions. The pullout strength in tension is not decisive for design and does not need to be evaluated. 3 See Section 4.1.9 for requirements for seismic design, where applicable. FIGURE 1 HILTI KCM-WF ANCHOR FIGURE 2 HILTI KCM-PD ANCHOR

ESR-4145 Most Widely Accepted and Trusted Page 6 of 11 TABLE 2 HILTI KCM-WF AND KCM-PD CAST-IN INSERT DESIGN INFORMATION 1,8,9 DESIGN INFORMATION SYMBOL UNITS 1 / 4"- 3 / 8" 3 / 8"- 1 / 2" 3 / 8"- 1 / 2"- 5 / 8" Characterization of insert per D.1 - - Non-Ductile Insert type - - WF and PD Only WF WF and PD Effective Embedment h ef in. (mm) Outside anchor diameter d a in. (mm) Nominal steel strength in tension as governed by the insert 2 Nsa,insert Nominal seismic steel strength in tension as governed by the insert 2,7 Nsa,insert,eq Nominal steel strength in shear as governed by the insert 2,6 Vsa,insert Nominal seismic steel strength in shear as governed by the insert 2,6 Vsa,insert,eq Modification factor for tension in uncracked - ψ concrete c,n Modification factor for tension in cracked - ψ concrete c,n Strength reduction factor ϕ for tension, steel failure of insert 3,5 ϕ - Strength reduction factor ϕ for shear, steel failure of insert 3,5 ϕ - 1.12 (28) 0.50 (12.8) 8,175 (36.4) 8,175 (36.4) 2,955 (13.1) 2,955 (13.1) 1.63 (41) 0.66 (16.9) 13,500 (60.0) 13,500 (60.0) 5,820 (25.9) 5,820 (25.9) Effectiveness factor cracked 4 k cr - 24 Coefficient for pryout strength k cp - 1.0 Strength reduction factor ϕ for tension, concrete failure modes, Condition B 3,5 ϕ - Strength reduction factor ϕ for shear, concrete failure modes, Condition B 3,5 ϕ - Concrete pullout, uncracked N p,uncr - NA Concrete pullout, cracked N p,cr - NA For SI: 1 inch = 25.4 mm. For pound-inch units: 1 mm = 0.03937 inches. 1.25 1.0 0.65 0.60 0.70 0.70 2.04 (52) 0.87 (22.1) 16,800 (74.7) 16,800 (74.7) 9,640 (42.9) 9,640 (42.9) 1 Installation must comply with Section 4.3 and Figures 3 and 4 of this report. 2 The design strength must be in accordance with ACI 318-14 Chapter 17 or ACI 318-11 Appendix D, as applicable, and Section 4.1 of this report. Values are for the insert only. The capacity of the threaded rod or other material threaded into the insert must be also be determined. See Table 3 for steel design information for common threaded rod elements. 3 See ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable. 4 See ACI 318-14 17.4.2.2 or ACI 318-11 D.5.2.2, as applicable. 5 For use with load combinations of ACI 318-14 Section 5.3 or ACI 318-11 Section 9.2, as applicable. Condition B applies where supplementary reinforcement in conformance with ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, is not provided. For cases where the presence of supplementary reinforcement can verified, the strength reduction factors associated with Condition A may be used. 6 Only the largest size of threaded rod specified for each insert must be used for applications resisting shear loads. 7 Only the largest size of threaded rod specified for each insert must be used for applications resisting seismic tension loads. 8 Inserts must be installed in concrete with a minimum compressive strength f ' c of 2,500 psi. 9 The design professional is responsible for checking threaded rod or bolt strength in tension, shear, and combined tension and shear, as applicable. FIGURE 3 KCM-WF INSTALLED IN CONCRETE FIGURE 4 KCM-PD INSTALLED IN CONCRETE

ESR-4145 Most Widely Accepted and Trusted Page 7 of 11 TABLE 3 STEEL DESIGN INFORMATION FOR COMMON THREADED ROD ELEMENTS USED WITH HILTI KCM-WF AND KCM-PD CONCRETE INSERTS 1,2,3,4 DESIGN INFORMATION SYMBOL UNITS 1 / 4-inch 3 / 8-inch 1 / 2-inch 5 / 8-inch Threaded rod nominal outside diameter d rod in. (mm) Threaded rod effective cross-sectional area A se in 2 (mm 2 ) 0.250 (6.4) 0.032 (21) 0.375 (9.5) 0.078 (50) 0.500 (12.7) 0.142 (92) 0.625 (15.9) 0.226 (146) Nominal tension strength of ASTM A36 threaded rod in tension as governed by steel strength for static or seismic loading N sa,rod,a36 or N sa,rod,eq,a36 1,855 (8.2) 4,525 (20.0) 8,235 (36.6) 13,110 (58.3) Nominal tension strength of ASTM F1554, Gr. 105 threaded rod in tension as governed by steel strength for static or seismic loading N sa,rod,f1554 or N sa,rod,eq,f1554 4,000 (17.7) 9,750 (43.1) 17,750 (78.9) 28,250 (125.7) Nominal tension strength of ASTM A193 Gr. B7 threaded rod in tension as governed by steel strength for static or seismic loading N sa,rod,a193 or N sa,rod,eq,a193 4,000 (17.7) 9,750 (43.1) 17,750 (78.9) 28,250 (125.7) Nominal shear strength of ASTM A36 threaded rod in shear as governed by steel strength for static loading V sa,rod,a36 1,105 (4.9) 2,695 (12.0) 4,940 (22.0) 7,860 (35.0) Nominal shear strength of ASTM A36 threaded rod in shear as governed by steel strength for seismic loading V sa,rod,eq,a36 780 (3.5) 1,900 (8.4) 3,460 (15.4) 5,505 (24.5) Nominal shear strength of ASTM F1554, Gr. 105 threaded rod in shear as governed by steel strength for static loading V sa,rod,f1554 2,385 (10.6) 5,815 (25.9) 10,640 (7.3) 16,950 (75.4) Nominal shear strength of ASTM F1554, Gr. 105 threaded rod in shear as governed by steel strength for seismic loading V sa,rod,eq,f1554 1,680 (7.5) 4,095 (18.2) 7,455 (34.2) 11,865 (52.8) Nominal shear strength of ASTM A193 Gr. B7 threaded rod in shear as governed by steel strength for static loading V sa,rod,a193 2,385 (10.6) 5,815 (25.9) 10,640 (7.3) 16,950 (75.4) Nominal shear strength of ASTM A193 Gr. B7 threaded rod in shear as governed by steel strength for seismic loading V sa,rod,eq,a193 1,680 (7.5) 4,095 (18.2) For SI: 1 inch = 25.4 mm, 1 pound = 0.00445 kn, 1 in 2 = 645.2 mm 2. For pound-inch units: 1 mm = 0.03937 inches. 7,455 (34.2) 11,865 (52.8) 1 Values provided for steel element material types, or equivalent, based on minimum specified strength; N sa,rod and V sa,rod calculated in accordance with ACI 318-14 Eq. (17.4.1.2) and Eq. (17.5.1.2b) or ACI 318-11 Eq. (D-2) and Eq. (D-29) respectively. V sa,rod,eq must be taken as 0.7V sa,rod. Materials of other strengths may be used and calculated in similar manner. 2 ϕn sa shall be the lower of the ϕn sa,rod or ϕn sa,insert for static steel strength in tension; for seismic loading ϕn sa,eq shall be the lower of the ϕn sa,rod,eq or ϕn sa,insert,eq. 3 ϕv sa shall be the lower of the ϕv sa,rod or ϕv sa,insert for static steel strength in tension; for seismic loading ϕv sa,eq shall be the lower of the ϕv sa,rod,eq or ϕv sa,insert,eq. 4 Strength reduction factors shall be taken from ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, for steel elements. Strength reduction factors for load combinations in accordance with ACI 318-14 5.3 or ACI 318-11 9.2 governed by steel strength of ductile steel elements shall be taken as 0.75 for tension and 0.65 for shear. The value of ϕ applies when the load combinations of Section 1605.2 of the IBC, ACI 318-14 5.3, or ACI 318-11 Section 9.2 are used in accordance with ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable. If the load combinations of ACI 318-11 Appendix C are used, the appropriate value of ϕ must be determined in accordance with ACI 318-11 D.4.4. TABLE 4 EXAMPLE ASD ALLOWABLE TENSION AND SHEAR DESIGN VALUES FOR ILLUSTRATIVE PURPOSES FOR KCM- WF AND KCM-PD INSTALLED IN NORMAL WEIGHT CONCRETE 1,2,3,4,5,6,7,8,9 Threaded Rod Diameter (in) 1 / 4"- 3 / 8" Tension (s) 3 / 8"- 1 / 2" 3 / 8"- 1 / 2"- 5 / 8" 1 / 4"- 3 / 8" Shear (s) 3 / 8"- 1 / 2" 3 / 8"- 1 / 2"- 5 / 8" 1 / 4 840 N/A N/A N/A N/A N/A 3 / 8 840 1,475 2,065 840 N/A N/A 1 / 2 N/A 1,475 2,065 N/A 1,475 N/A 5 / 8 N/A N/A 2,065 N/A N/A 2,065 For SI: 1 inch = 25.4 mm, 1 pound = 0.00445 kn, 1 in 2 = 645.2 mm 2. For pound-inch units: 1 mm = 0.03937 inches. 1 Concrete strength f c = 2500 psi for KCm-WF and KCM-PD. 2 Values are for single anchors with static tension or shear. 3 Values are for uncracked concrete. 4 Load combinations as given in ACI 318-14 5.4 or ACI 318 9.2, as applicable. 5 30% dead load and 70% live load, controlling load combination 1.2D + 1.6 L. 6 Calculation of ASD conversion α = 0.3*1.2 + 0.7*1.6 = 1.48 7 Values assume no side-face blowout in tension for KCM-WF and KCM-PD. 8 Values are for Condition B where supplementary reinforcement in accordance with ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, is not provided. 9 The allowable loads shown are for the applicable insert only. Design professional is responsible for checking capacity of threaded rod, including tension, shear, and influence of bending on tension capacity when loaded in shear, or other material placed in insert.

ESR-4145 Most Widely Accepted and Trusted Page 8 of 11 FIGURE 5 KCM-WF CONCRETE INSERTS MANUFACTUER PRINTED INSTALLATION INSTRUCTIONS (MPII) FIGURE 6 KCM-PD CONCRETE INSERTS MANUFACTUER PRINTED INSTALLATION INSTRUCTIONS (MPII)

ESR-4145 Most Widely Accepted and Trusted Page 9 of 11 Given: Two 5/8-inch ASTM A36 threaded rods with KCM-PD 3/8-1/2-5/8 inserts, edge distance of 3 inches, and spacing of 12 inches loaded in static tension, N, and static shear, V. h ef= 2.04 in No supplementary reinforcement Condition B per ACI 318-14 17.3.3(c) or ACI 318-11 D.4.3 (c), as applicable Assume normal weight concrete, f c= 3,000 psi Assume cracked concrete Needed: Using strength design provisions of ACI 318-14 Chapter 17 or ACI 318-11 Appendix D, calculate the design shear and tensile strength capacity for this configuration. Calculations per ACI 318-14 Chapter 17 or ACI 318-11 Appendix D and this report. ACI 318-14 ACI 318-11 Report Ref. Step 1. Calculate steel tensile capacity. Nsa,insert = Ase,Nfuta Given in Table 3 Nsa,insert= 16,800. ϕn sa,insert = ϕ(16,800) ϕn sa,insert = 10,920. Nsa,rod,A36 = Ase,Nfuta Given in Table 3 Nsa,rod,A36= 13,110. ϕn sa,rod,a36 = ϕ(13,110) ϕn sa,rod,a36 = 9,833. 17.3.3 17.4.1 D.4.4.1 D.5.1 4.1.2 Table 3 Table 5 Step 2. Calculate concrete breakout of anchor in tension. Ncb = Nb (ANc/ANco)ψ ed,nψ c,n ψ cp,n 17.4.2.1 a) D.5.2.1 a) 4.1.3 Step 2a. Check spacing and edge distance requirements. Given in Table 1 c a,min = 3 in > 1.5 in s anchor = 12 in > 5.22 in okay spacing and edge distance 17.7.1-6 D.8.1-6 4.1.11 4.1.12 Table 1 Step 2b. Determine λ. normal weight concrete λ= 1.0 Step 2c. Calculate basic concrete breakout strength in tension. Nb=24λ f c (hef) 1.5 Nb=24(1.0) 3,000(2.04) 1.5 Nb = 3,830 Step 2d. Determine effective projected concrete breakout area. A Nc = (c a1 + 1.5h ef )(2 1.5h ef ) A Nc = (3 + 1.5 2.04)(2 1.5 2.04) A Nc = 37.1 in 2 Step 2e. Determine idealized projected concrete breakout area. A Nco = 9(h ef ) 2 = 37.5 in 2 17.2.6 D.3.6 4.1.13 17.4.2.2 D.5.2.2 4.1.3 17.4.2.3 D.5.2.3 4.1.3 17.4.2.1 D.5.2.1 4.1.3 Step 2f. Determine ψ ed,n. ψ ed,n = 0.7 + 0.3 c a,min 1.5h ef 17.4.2.5 D.5.2.5 4.1.3 ψ ed,n = 0.7 + 0.3 2 1.5 2.04 Step 2g. Determine ψ c,n. cracked concrete ψ c,n = 1.0 Step 2i. Determine ψ cp,n. cast-in anchor with cracked concrete ψ cp,n = 1.0 17.4.2.6 D.5.2.6 4.1.3 17.4.2.7 D.5.2.7 4.1.12 Step 2j. Calculate ϕn cb. ϕn cb = 0.7 37.1 3,830 0.994 1.0 1.0 37.5 ϕn cb = 2,636 17.3.3 c) 17.4.2.1 a) D.4.3 c) D.5.2.1 a) 4.1.3 Step 3. Check pullout strength of concrete in tension. N pn = ψ c,pn p Step 3a. Determine ψ c,p. cracked concrete ψ c,p = 1.0 Step 3b. Calculate basic concrete pullout in tension. N p = 8A brg f c N p = 8 1.23 3,000 N p = 29,520 17.4.3.1 D.5.3.1 4.1.4 17.4.3.6 D.5.3.6 4.1.4 17.4.3.4 D.5.3.4 4.1.4 FIGURE 7 DESIGN EXAMPLE FOR KCM-PD

ESR-4145 Most Widely Accepted and Trusted Page 10 of 11 Step 3c. Calculate ϕn pn. ϕn pn = 0.7 29,520 ϕn pn = 20,664 17.4.3.1 17.3.3 c) D.5.3.1 D.4.3 c) 4.1.4 Step 4. Calculate concrete side face blowout. h ef < 2.5c a not applicable Step 5. Determine the controlling tensile strength. Steel anchor insert strength ϕn sa,insert = 10,920 17.4.4.1 D.5.4.1 4.1.5 Steel insert element strength ϕn sa,rod,a36 = 9,833 Concrete pullout strength ϕn p,n = 20,664 Concrete breakout strength ϕn cb = 2,636 CONTROLS Step 6. Calculate 5 / 8 steel shear capacity. Vsa,insert = Ase,Nfuta Given in Table 2 Vsa,insert= 9,640. ϕvsa,insert = (0.60) x 9,640/anchor ϕvsa,insert = 5,784 Vsa,rod,A36 = Ase,Nfuta Given in Table 3 Vsa,rod,A36 = 7,860. ϕvsa,rod,a36 = (0.65) x 7,860/anchor ϕvsa,rod,a36 = 5,109 Step 7. Calculate concrete breakout of anchor in shear. V cb = A Vc A Vco V b ψ ed,v ψ c,v ψ h,v Step 7a. Check spacing and edge requirements. Given in Table 1 c a,min = 3 in > 1.5 in s anchor = 12 in 5.22 in okay spacing and edge distance Step 7b. Calculate basic concrete breakout strength in shear. V cb = lesser of 7( l e ) 0.2 d d a )λ a f c (c a1 ) 1.5 a 9λ a f c (c a1 ) 1.5 (7) 0.2 2.04 V cb = 0.87 0.87(1.0) 3,000(3) 1.5 9(1.0) 3,000 3 1.5 V cb = lesser of 2,203 2,561 V cb = 2,203 17.3.1 17.5.1.2 D.6.1.2 D.4.1 4.1.1 4.1.6 Table 3 Table 5 17.5.2.1 D.6.2.1 4.1.7 17.7.1-6 D.8.1-6 4.1.12 4.1.11 Table 1 17.5.2.2 D.6.2.2 4.1.7 Step 7c. Determine ψ ed,v. c a,min c cr,v c a2 ψ ed,v = 1.0 17.5.2.6 D.6.2.6 4.1.7 Step 7d. Determine ψ c,v. cracked concrete ψ c,v = 1.0 Step 7e. Determine ψ h,v. h a,min h cr,v ψ h,v = 1.0 Step 7f. Calculate concrete breakout in shear, ϕv cb. ϕv cb = 0.7 2,203 1.0 1.0 1.0 ϕv cb = 1,542 Step 8. Calculate pryout strength of concrete in shear. Vcp = kcpncb Step 8a. Determine k c,p. h ef=2.04 in< 2.5 in k c,p = 1.0 Step 8c. Calculate concrete pryout, ϕv cp. ϕv cp = 0.7 1.0 3,830 ϕv cp = 2,681 Step 9. Determine the controlling shear strength. Steel anchor strength Steel insert element strength ϕv sa,insert = 5,784 ϕv sa,insert = 5,109 Concrete pryout strength ϕv cp = 2,681 17.5.2.7 D.6.2.7 4.1.7 17.5.2.8 D.6.2.8 4.1.7 17.3.3 c) 17.5.2.1 D.4.3 c) D.6.2.1 4.1.7 17.5.3.1 D.6.3.1 4.1.8 17.5.3.1 D.6.3.1 4.1.8 17.3.3 c) 17.5.3.1 D.4.3 c) D.6.3.1 4.1.8 17.3.1 D.4.1 4.1.1 Concrete breakout strength ϕv cb = 1,542 CONTROLS FIGURE 7 DESIGN EXAMPLE FOR KCM-PD (Continued)

ICC-ES Evaluation Report ESR-4145 LABC and LARC Supplement Issued February 2018 This report is subject to renewal February 2019. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION: 03 00 00 CONCRETE Section: 03 15 19 Cast-in Concrete Anchors Section: 03 16 00 Concrete Anchors REPORT HOLDER: HILTI, INC. 7250 DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 (800) 879-8000 www.us.hilti.com HiltiTechEng@us.hilti.com EVALUATION SUBJECT: HILTI KCM-WF AND KCM-PD HEADED CAST-IN SPECIALTY INSERTS IN CRACKED AND UNCRACKED CONCRETE 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement is to indicate that the Hilti KCM-WF and KCM-PD Headed Cast-In Specialty Inserts in cracked and uncracked concrete, described in ICC-ES master evaluation report ESR-4145, has also been evaluated for compliance with the codes noted below as adopted by the Los Angeles Department of Building and Safety (LADBS). Applicable code editions: 2017 City of Los Angeles Building Code (LABC) 2017 City of Los Angeles Residential Code (LARC) 2.0 CONCLUSIONS The Hilti KCM-WF and KCM-PD Headed Cast-In Specialty Inserts in cracked and uncracked concrete, described in Sections 2.0 through 7.0 of the master evaluation report ESR-4145, comply with LABC Chapter 19, and LARC, and are subject to the conditions of use described in this supplement. 3.0 CONDITIONS OF USE The Hilti KCM-WF and KCM-PD Headed Cast-In Specialty Inserts described in this evaluation report must comply with all of the following conditions: All applicable sections in the master evaluation report ESR-4145. The design, installation, conditions of use and labeling of the Hilti KCM-WF and KCM-PD Headed Cast-In Specialty Inserts are in accordance with the 2015 International Building Code (2015 IBC) provisions noted in the master evaluation report ESR-4145. The design, installation and inspection are in accordance with additional requirements of LABC Chapters 16 and 17, as applicable. Under the LARC, an engineered design in accordance with LARC Section R301.1.3 must be submitted. The allowable and strength design values listed in the master evaluation report and tables are for the connection of the headed cast-in specialty inserts to the concrete. The connection between the headed cast-in specialty inserts and the connected members shall be checked for capacity (which may govern). This supplement expires concurrently with the master report, issued February 2018 and revised February 28, 2018. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2018 ICC Evaluation Service, LLC. All rights reserved. Page 11 of 11