geba fire damper WFK according to EN 15650

Similar documents
NEW. FR90 fire dampers. Maintenance-free

Fire damper BSK-RB Contents Description...3 Models and dimensions...4 Installation...8 Technical data... 12

Operating and Installation Manual Fire damper Type FKR-EU

1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations...

1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations...

UL, KUL, WG-KUL, ARK, ARK-1

Voie Romaine F Maizières-lès-Metz Tel.: +33 (0) Fax.: +33 (0) Operating vacuum pressure: - 500Pa

2500 Series Fire Smoke Dampers

Declaration of Performance (DOP)

1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations...

Pipeline Accessories. PSI Wall Sleeves. General Information Selection Guide Technical Data Installation Instruction

PRODUCT CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE

Conergy SolarFamulus II

0160 Series Curtain Fire Dampers

Fire damper. Type FKS-EU. Installation and operating manual. GB/en. according to Declaration of Performance DoP / FKS-EU / DE / 003

Fire Protection Valves

mcr Silboard self-supporting ventilation and smoke extraction ducts

Declaration of Performance (DOP)

Installation instructions

Operating and Installation Manual Fire Damper Type FKA-EU

HST -B Interlocking device (Translation of Original Manual)

3. Dimensions, weights Placement and Assembly Statement of installations Electrical Components, Connection Diagrams...

Expansion Joints Guide Module 6 - Low Pressure Expansion Joints General - Standard Program (EFB) - Installation Instructions - Technical Data

Z5378 E6 Horizontal bracket Mounting instructions (1.0 EN)

Bridge Drainage Systems

Guide book AS 300 G. Waste water filtration unit. Im Geer 20, D Isselburg. Description / Type-No.: AS 300 G Type 523

Z5351 E8 Horizontal bracket Mounting instructions (1.1 EN)

Z5054 Ci60/Ci90 Flying adapter Mounting instructions

Instruction manual AS 300 CG. Waste water filtration unit. Im Geer 20, D Isselburg. Descriptioin / Type-No.: AS 300 CG Typ 539

Z5043 MAX Horizontal bracket Mounting instructions

Date of update January 25, 2018 Valid until

Z5377 E6 Swivel bracket Mounting instructions (1.2 EN)

Z5010 (Version 2) TV spigot with fixing plate Mounting instructions

Declaration of performance

Z5033 E3 Ball joint adapter Mounting instructions

De Montfort Mark 7 Incinerator (Flatpack)

GypWall TM ROBUST 4.4. GypWall ROBUST. Durable impact resistant partition system. Key facts. Sector Guide

Reinforced concrete double walls

Installation instruction

INSTALLATION INSTRUCTION IM 317 E

Reinforced concrete double walls

Industrial flue gas probes. Instruction manual

FD Damper Installation, Operating and Maintenance Instructions

Installation Instructions

DT 23 DT 24 DT 32 DT 33 DT 34 DT 44

lindab we simplify construction Fire dampers EN tested and CE marked according to EN fire dampers

F Ü R D I E ZU K U N FT G E DAC HT. Flat roof vents. Soil vent pipes Refurbishment vents Cold roof vents

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Welding and Solder Flange

Rainscreen Ventilated Fire Barrier

*1MUBWK25EN* *1MUBWK25EN-LIND* rev rev *1MUBWK25EN-LIND* WK25. RECTANGULAR SERIES WK Pa. Cert. N 1812-CPR-1045 EN 15650

ASF FR Board PRO RANGE Coated Mineral Wool Board for the Professional

ABACO LITTLE GIANTLIFTER

Z5028 E3/Ci80 Horizontal bracket Mounting instructions

Smoke Control Damper ESAM Instructions for installation, operation and maintenance 10/2014

Installation Instructions Easy Climb 1 Art

No part of this manual may be reproduced in any form or by any means, without prior written permission of Darrera.

Z5352 E12 Flying bracket Mounting instructions (1.0 EN)

FIRE PROTECTION. GTEC Shaftwall systems 244 GTEC Shaftwall Stairwell systems 248 GTEC Horizontal Shaftwall systems 249 GTEC Encasement systems 250

Fire damper WK25. Dimensions

Assembly Instruction. FLAMRO Variant N II A according to ETA-13/0922. Content

LUX ELEMENTS -TUB shower base elements

KRIWAN Wind Sensors. Operating Instructions Accessories and Application Information

Sika KAB combination joint waterbars waterstopping systems

FERMACELL Powerpanel H 2 O for Wet & Moisture affected areas

Operating and Maintenance Manual. for. HADEF locking device for monorail trolleys

For door closer systems with hydraulic damping (overhead door closers and floor springs)

LVH-A Series Intumescent Fire Dampers Alternative Mounted Systems 1, 2 & 4 hour Fire Rating

Annex to the Accreditation Certificate D-ZE according to DIN EN ISO/IEC 17065:2013

*1MUBWKS25EN* *1MUBWKS25EN-LIND* rev rev *1MUBWKS25EN-LIND* WKS25. RECTANGULAR SERIES WKS Pa. Cert. N 1812-CPR-1046 EN 15650

LUX ELEMENTS -TUB-BOL shower base elements

Trimbox NO2 Filter. Product Manual. ventilation systems

GLADIATOR. GLADIATOR Telescopic Steel Covers

POLYLACK F, K, KR and KG FIRE PROTECTION INTUMESCENT MATERIALS

Richter Chemical Control Valves

City of Westerville Guide to Commercial Inspections

QGO Oxygen Sensor. Building Technologies HVAC Products

InoxSabiana 25 Flues. Stainless Steel Double Wall

Pilkington Reglit. Technical Information on Pilkington Reglit Profiled Glass with System. - English Edition -

AESTUVER fire-protection mastic For the AESTUVER expansion joint M

RESEARCH REACTOR FRJ-1 (MERLIN) THE CORE STRUCTURES OF THE REACTOR BLOCK ARE DISMANTLED

Operating instructions - Translation of the original -

Air flue duct for use with ecotec boilers

PRODUCT APPLICATION MANUFACTURER INTRODUCTION CERTIFICATION PROCEDURE. Date of update April 6, 2018 Valid until

Pipe Joints. Requirements and Test Methods. VdS-Guidelines for water extinguishing systems. VdS en. VdS en : (01)

BIRCOsir. Installation Instructions. A number of details must be observed when installing BIRCOsir. For a comprehensive description please read here.

ENGLISH Compact Half Coupler 50 mm, SWL: 50 kg

EFECTIS France Voie Romaine F Maizières-lès-Metz Tel.: +33 (0) Fax.: +33 (0) A Revision 1

TRAPEZOIDAL SHEET METAL RAIL

Fire Prevention K90 and K30 dampers in accordance with DIN Part I 09/2006

Exterior Wall Solutions Building Shell

PETREX -CNT. Pipe systems for petrol stations Technical details

Operator s Manual for Morse Heavy-Duty Kontrol-Karrier with 3-Piece Drum Holder

Advantix bathroom drain. Instructions for Use from 01/2008. en_int

Spray Booth Guideline

MULTIBLADE FIRE DAMPER BSK-J/EI90

SLIDING -SUPPORT-BEARINGS

Assembly instructions Fortuna Play Course Art part

Tehnical Data Sheet Astro HS FM Compound. UIC of product-type: HSFMC CPR-JA5013 ETA-14/0047. ETAG 026-Part 1 ETAG 026-Part 2

KLINGER BALLOSTAR KHA

Ordering example: BKI-K90/SFR1.90T/B=1000xH=1000xH=1000xL=250. Standard damper length; special dimensions are available on request

Transcription:

Installation- and operation instruction geba fire damper WFK according to EN 15650 with a free cross-section for the usage in ventilation systems in buildings Abbildung 1 DN 250 Tested according to EN 1366, part 2 Stand: 10/2017

Table of content General information... S. 3 Security and intended use... S. 3/4 Transport and storage.... S. 4 Product description.... S. 5 General installation details... S. 6/7 1. Distance WFK - WFK... S. 6 2. Distance to bearing components... S. 7 3. Important information... S. 7 Wet installation - solid ceiling... S. 8 Wet installation - solid walls.... S. 9 Installation in drywall.... S. 9 Functional test...s. 10 Commissioning...S. 10 Maintenance...S. 10 2 2

General information This installation and operation instruction describes fire damper of type WFK. In order to secure the proper function of the fire damper, it is mandatory to read the included installation and operation instruction before any kind of usage and to pay attention to the information therein. Upon system hand-over, the system operator has to be provided with the instructions. The system operator has to attach the instruction to the system documentation. Malfunctions or damages, which occur by nonobservance of this instruction manual or non-compliance to legal provisions, do not lead to liability claims against the manufacturer. This installation and operation instruction is addressed to planners, developers and operators of plants, in which the fire dampers are to be integrated. Aurthermore, the instruction is addressed to persons, who execute the following works: Transport and storage Installation Commissioning, operation and maintenance Decommissioning and disposal Apart from this installation and operation instructions, the applicable standards and technical regulations are to be observed. Security and intended use Only qualified personnel should execute the described actions at the fire damper. There must be enough space for unimpeded activities during the installation, inspection and maintenance at the fire damper. During all works at the fire damper, the following regulations and guideslines are to observed: German Equipment and Product Safety Act (Geräte- und Produktsicherheitsgesetz) Industrial Safety Regulation German Building Regulations Accident Prevention Regulation (BGV A1, BGV A3) The fire damper WFK is a security component which has been developed for fire protection. Certificates and standards Certificate of constancy of performance 1322-CPR-08678/01 Declaration of performance DoP/WFK/DE/2017/001 Classification according to DIN EN 13501-3:2010-02 Solid ceiling, wet installation (mortar) min. 100 mm: Solid wall, wet installation (mortar) min. 100 mm: Light partition wall with panels on both sides (mortar) min. 100 mm: Tested according to DIN EN 1366-2 Damper leakage according to EN 1366-2 Case leakage according to EN 1751, class C All other relevant fire protection standards and regulations are to be observed. Intended Use EI 120 (ho i o)-s (300 Pa) EI 90 (ve i o)-s (300 Pa) EI 90 (ve i o)-s (300 Pa) The fire damper is used as thermal shut-off device in order to prevent fire and smoke transmission via air ducts. The fire damper can be used in supply and exhaust air systems, with and without waste heat recovery. Intended installation sites are solid walls, solid ceilings and light partition walls. The installation is vertically possible with any direction of air stream. Suitable for the installation in ceilings, solid walls and shaft walls ( 100 mm). Connection of air ducts made from flammable and inflammable materials, also single-sided with cover grill. In Europe, it can be used without double-sided pipe connection, if no national requirements indicate otherwise. Provided that the damper is installed and operated in accordance to the intended use, the fire damper WFK has performance class DIN EN 13501-3:2010-02 + A1:2009; solid ceiling, wet installation EI 120 (ho i o)-s; solid wall, wet installation EI 90 (ve i o)-s; Light partition wall with panels on both sides EI 90 (ve i o)-s. Furthermore, the general maintenance guidelines DIN 31051 and EN 13306 are to be applied. 3 3

Improper Usage The fire damper must not be used under the following circumstances: Usage as smoke exhaust damper Usage in ex-zones Outdoor usage without sufficient protection against weather conditions Usage in exhaust air systems in commercial kitchens Usage in air ventilation systems, in which the proper function is impaired by heavy pollution,extreme moisture or chemical contamination Usage in installation situations, in which an internal inspection, e. g. camera inspection, and cleaning of the fire damper is impossible in installed condition. Modifications at the fire damper and the usage of replacement parts, which are not authorised by Bartholomäus GmbH, are prohibited. Residual hazards geba-fire dampers are subject to strict quality controls. Additionally, a function test will be executed before delivery. Functional impairment is possible due to damages during transport or installation. The proper damage-free condition of the fire damper has to be checked before installation and commissioning. Transport and storage Inspection of shipment Please check the shipment immediately after delivery for transport damages and completeness. In case of transport damages or incomplete shipment, please inform the carrier and your supplier without delay. The complete shipment includes: Fire damper Attachment parts/accessories, if applicable MInstallation and operation instructions Transport at the construction site If possible, please transport the fire damper to the construction site in the despatch packaging. Storage Please consider the following, when you store the fire damper temporarily: Please protect the fire damper from dust and dirt. Please protect the fire damper from moisture and direct sun light. Please do not expose the fire damper (even if properly packed) directly to weather conditions. Please do not store the fire damper below -40 C and above 50 C. Packaging Caution! Danger of injury due to edges and sheet metal parts. Please wear protection gloves during transport and installation. Please dispose the packaging material correctly after unpacking the fire damper. 4 4

Product description Fire dampers of the series WFK are used as safety-related components within ventilation systems. The fire damper prevents fire and smoke transmission via the air duct. During operation at normal temperatures, the fire damper is open in order to secure the air delivery in the ventilation system. Function description (Fig.2) The fire damper includes two thermal release devices, which trigger if the temperature rises above 70 C. Thereby, the pre-loaded closing caps swing from the Open to the Closed position. Maintenance-free double torsion bars made from stainless steel are used as drive. Release unit Sealing cap Fig.2 Double torsion bar made from stainless steel Case dimensions Fig.3 40 40 D D2 75 Nominal size DN in mm 100 125 160 200 250 D 98 123 158 198 248 D1 145 177 211 251 300 D2 130 155 190 230 280 L1 168 168 168 178 188 L2 32 41 60 76 101 L3 110 110 110 120 130 LG 245 255 270 300 335 Weight in kg 1,2 1,7 2,2 3,3 4,9 5 5

General installation information 1. Distance WFK - WFK Illustration: installation on the ceiling Fig.4 Mortar casting gap Mounting bracket as mounting aid min. immersion depth >50 mm X1 X2 X3 X1 Solid ceiling Solid wall Light Partition wall* WFK-WFK (inside) approx. 20-25 mm approx. 20-25 mm approx. 190-195 mm Core drilling (Fig.5) Installation Ring gap S X2 Solid ceiling Solid wall Light Partition wall* Centre distance DN + 70 mm DN + 70 mm DN + 240 mm DN 100 170 mm 170 mm 340 mm DN 125 195 mm 195 mm 365 mm DN 160 230 mm 230 mm 400 mm DN 200 270 mm 270 mm 440 mm DN 250 320 mm 320 mm 490 mm Solid ceiling Solid wall Light Partition wall* Fig.5 45 mm 50 mm 50 mm X3 Solid ceiling Solid wall Light Partition wall* WFK-WFK (outside) DN 100 315 mm 315 mm 485 mm DN 125 372 mm 372 mm 542 mm DN 160 441 mm 441 mm 611 mm DN 200 521 mm 521 mm 691 mm DN 250 620 mm 620 mm 790 mm *Light partition wall: Light partition walls with metal support and panels on both sides, classified according to EN 13501-2 or comparable national classifications LTW made from gypsum fiberboard or gypsum- or cement-bound panel building material (wall thickness 100 mm) Distance of the metal support 625mm Connection of the air duct with elastic connection piece DN + 2 S Core drilling Core drilling = DN + 2 x S 6 6

2. Distance to bearing components Y1 Y2 Solid ceiling 67 mm 75 mm Solid wall 67 mm 75 mm Light partition wall 67 mm 75 mm Fig.6 Y1 Y2 Bearing component 3. Important information Caution! Malfunction of the fire damper due to contamination or damage. Please protect the fire damper during installation from contamination and damages: Please protect the fire damper before installation from possible contamination. Caution! Danger of injury due to edges and sheet metal parts. Please wear protection gloves during transport and installation. Connection of ventilation duct The installation is vertically and horizontally possible with any direction of air stream. Suitable for the installation in ceilings, solid walls, shaft walls and reinforced steel wall systems ( 100 mm). Connection of air ducts made from flammable and inflammable materials, also single-sided with cover grill. In Europe, it can be used without double-sided pipe connection, if no national requirements indicate otherwise. Mounting bracket Please attach the included mounting and stop bracket on both sides of the case cover using wing nuts. The brackets are attached with the shorter side on the cover and adjusted according to figure 7. Fig.7 Permitted mortar for wet installation The cavities between fire damper and wall/ceiling are to be filled completely with mortar. Air pockets must be avoided. The depth of the mortar bed must be at least 100mm. Zulässige Mörtel: DIN 1053: Group II, IIa, III, IIIa or fire protection mortar of group II, III EN 998-2: Class M2,5 to M10 or fire protection mortar of class M2,5 to M10 Alternatively equivalent mortar according to the above mentioned standards, gypsum mortar or standards Tragkonstruktionen nach DIN EN 1363-1:2012 - Massivkonstruktion mit hoher Rohdichte: Mauerwerk oder Massivbeton mit einer Gesamtdichte von 850 kg/m³ - Massivkonstruktion mit geringer Rohdichte: Porenbeton mit einer Gesamtdichte von (650 ± 200) kg/m³ - Leichtbauweise: leichte Trennwände in Stahlständerbauweise mit Bekleidung aus Gipskartonplatten, gemäß Punkt 7.2.2.4 7 7

Wet installation - solid ceilings Minimum distance from outer edge of the case to bearing components 67 mm (please see page 7, picture 6) Installation during preparation of the ceiling The fire damper can directly be encased in the mortar during preparation of the ceiling. This can also be done without gap s. 1. Remove the transport lock from the fire damper 2. Attach the mounting bracket with wing nuts on the case (please see pictures 7, 8) 3. Bring the fire damper in the intended installation position using the mounting bracket (mounting brackets must be flush with the ceiling, use a screw connection if needed) 4. Please protect the inner fire damper from mortar and contamination 5. Please encase the fire damper in concrete/mortar Installation after completion of the ceiling If the fire damper ist installed after completion of the ceiling, the following work stages are necessary: 1. Remove the transport lock of the fire damper 2. Attach the mounting bracket with wing nuts on the case (please see pictures 7, 8) 3. Create an installation opening by core drilling or breakthrough >0 Solid ceiling Core drilling DN + 90 mm DN 100 190 mm DN 125 215 mm DN 160 250 mm DN 200 290 mm DN 250 340 mm 4. Insert the fire damper in the installation opening and position it using the mounting bracket (mounting brackets must be flush with the ceiling, use a screw connection if needed) 5. Close the circumferential gap S (s 45 mm) with permitted mortar (page 7) in full wall thickness Fig.8 8 8

Wet installation - solid walls Installation during erection of the wall The fire damper can be directly encased during the erection of the wall. This can also be done without gap s. 1. Remove the transport lock from the fire damper 2. Attach the mounting bracket with wing nuts on the case (please see pictures 7, 8) 3. Insert the fire damper during the erection of the wall in the intended installation position on a mortar bed and position it using counting brackets (mounting brackets must be flush with the ceiling, use a screw connection if needed) 4. Protect the inner fire damper from mortar and contamination 5. Immure the fire damper in the wall using a circumferential mortar bed Installation after erection of the wall (core drilling) The following work phases are necessary during the installation of the fire damper after the erection of the wall: 1. Remove the transport lock from the fire damper 2. Attach the mounting bracket with wing nuts on the case (please see pictures 7, 8) 3. Create an installation opening by core drilling or breakthrough >0 Solid wall Core drilling DN + 100 mm DN 100 200 mm DN 125 225 mm DN 160 260 mm DN 200 300 mm DN 250 350 mm 4. Insert the fire damper in the installation opening and position it using the mounting bracket (mounting brackets must be flush with the ceiling, use a screw connection if needed) 5. Protect the inner fire damper from mortar and contamination 6. Close the circumferential gap (s 50mm) with permitted mortar (page 7) in full wall thickness Installation in drywall Installation information for wet installation. General information for installation in light partition wall, please see page 6 (*light partition wall) The fire damper can be built in the drywall in any position considering the required distance rules without latch and change 1. Remove the transport lock from the fire damper Fig.10 2. Attach the mounting bracket with wing nuts on the case (please see pictures 7, 10) 3. Create an installation opening by core drilling or breakthrough >0 Light partition wall Core drilling DN + 100 mm DN 100 200 mm DN 125 225 mm DN 160 260 mm DN 200 300 mm DN 250 350 mm 4. If applicable, close the existing gap between wall insulation and panels 5. Position the fire damper in the intended installation position with mounting brackets in the shaft wall (mounting brackets must be flush with the ceiling, use a screw connection, if needed) 6. Case in and close existing ring gap (s 45 mm) with permitted mortar (page 7) Fig.9 9 9

Function test Function tests or inspection openings on each floor are dispensable. The air duct should have a inspection opening at the upper and lower end, as well as at the duct warping, which allows a camera inspection. Commissioning After installation of the fire damper WFK and before the duct is sealed, it is mandatory to check the proper installation of the WFK, from the inside by camera inspection and from the outside by visual inspection. Single dampers can be checked by visual inspection only, e. g. by using a mirror. Maintenance Maintenance is to be performed at intervals of five years through a camera inspection, where a video documentation and the associated assessment of the inspection data obtained are prepared by a competent employee. These data are to be handed over to the customer in paper form and as a file on a suitable medium. If the pipe is contaminated, a pipe cleaning must be arranged. The WFK will also be cleaned in this process. Single dampers can be checked by visual inspection only, which has to be recorded, e. g. that a mirror has been used for the inspection. The VdS-tested release element is 100 % corrosion-free, including the release unit. The double torsion bars made from stainless steel are covered and without hinge. The release unit has been used a million times by geba in the last 15 years and has been proven in practice. All components are abrasion-proof. The free cross-section allows a low pipe resistance with higher air velocity, e. g. more than 3m/s, which prevents dust from settling. The air flow without turbulences substantially contributes to the pipe cleaning. The Hermann Rietschel Institute determined, according to a CCI publication, dust precipitation with an air velocity of less than 3m/s. It was found that 4 5 m/s would be ideal. This also benefits the dimensioning of the pipe. Dampers in the air flow represent a resistance, lead to turbulences and thereby reduce the efficiency of a ventilation system. This inevitably results in lower air velocity, which then again requires larger pipe dimensions and makes the system more expensive. The building regulations are to be observed. Cleaning instructions -Do not use cleaning agents -Use only soft plastic brush for cleaning; brush hair: Ø 0.5 Ø 0.8mm maximum -Brush diameter: 2 cm larger than diameter DN -Cleaning with 100-200 rotations/minute (possibly reduced speed at the sealing) The delivered components are to be checked for completeness, type and damages according to operation and installation instructions. Components are to be used for the intended purpose. Bartholomäus GmbH cannot be held responsible for damages, which arise from improper installation and/or use due to non-compliance with this instructions and/or applicable standards or legal provisions. Technical changes reserved. Bartholomäus GmbH Bachstraße 10 D-89607 Emerkingen Phone +49 (0)7393 95 19-0 Fax +49 (0)7393 95 19-40 info@geba-brandschutz.de www.geba-brandschutz.de 10