SANTA ANA RIVER/ SAN TIMOTEO CREEK 1 LEVEE SYSTEM SAN BERNARDINO COUNTY, CALIFORNIA NLD SYSTEM ID #

Similar documents
SAN LUIS REY RIVER 3 LEVEE SYSTEM SAN DIEGO COUNTY, CALIFORNIA NLD SYSTEM ID #

SANTA ANA RIVER 1 LEVEE SYSTEM (UPSTREAM REACH) ORANGE COUNTY, CALIFORNIA NLD SYSTEM ID #

LOS ANGELES RIVER/ COMPTON CREEK 2 LEVEE SYSTEM LOS ANGELES COUNTY, CALIFORNIA NLD SYSTEM ID #

MILL CREEK LEVEE SYSTEM SAN BERNARDINO COUNTY, CALIFORNIA NLD SYSTEM ID #

COYOTE CREEK 3 LEVEE SYSTEM LOS ANGELES COUNTY AND ORANGE COUNTY, CALIFORNIA NLD SYSTEM ID #

LOS ANGELES RIVER 7 LEVEE SYSTEM LOS ANGELES COUNTY, CALIFORNIA NLD SYSTEM ID #

SAN GABRIEL RIVER 1 LEVEE SYSTEM LOS ANGELES COUNTY, CALIFORNIA NLD SYSTEM ID #

SAN GABRIEL RIVER/SAN JOSE CREEK 1 LEVEE SYSTEM LOS ANGELES COUNTY, CALIFORNIA NLD SYSTEM ID #

INDIAN BEND WASH 2 LEVEE SYSTEM MARICOPA COUNTY, ARIZONA NLD SYSTEM ID #

LOS ANGELES RIVER/COMPTON CREEK 2 LEVEE SYSTEM LOS ANGELES COUNTY, CALIFORNIA NLD SYSTEM ID #

LOS ANGELES RIVER/RIO HONDO DIVERSION 2 LEVEE SYSTEM LOS ANGELES COUNTY, CALIFORNIA NLD SYSTEM ID #

LOS ANGELES RIVER/RIO HONDO DIVERSION 2 LEVEE SYSTEM LOS ANGELES COUNTY, CALIFORNIA NLD SYSTEM ID #

LOS ANGELES RIVER/COMPTON CREEK 2 LEVEE SYSTEM LOS ANGELES COUNTY, CALIFORNIA NLD SYSTEM ID #

SAN GABRIEL RIVER/ COYOTE CREEK 2 LEVEE SYSTEM LOS ANGELES COUNTY, CALIFORNIA NLD SYSTEM ID #

SAN GABRIEL RIVER 1 LEVEE SYSTEM LOS ANGELES AND ORANGE COUNTIES, CALIFORNIA NLD SYSTEM ID #

SAN DIEGO RIVER 2 LEVEE SYSTEM SAN DIEGO COUNTY, CALIFORNIA NLD SYSTEM ID #

COYOTE CREEK 4 LEVEE SYSTEM LOS ANGELES COUNTY, CALIFORNIA NLD ID #

VENTURA RIVER 1 LEVEE SYSTEM VENTURA COUNTY, CALIFORNIA NLD ID #

SAN GABRIEL RIVER/COYOTE CREEK 2 LEVEE SYSTEM LOS ANGELES AND ORANGE COUNTIES, CALIFORNIA NLD SYSTEM ID #

SAN DIMAS WASH 6 LEVEE SYSTEM LOS ANGELES COUNTY, CALIFORNIA NLD SYSTEM ID #

COYOTE CREEK 3 LEVEE SYSTEM LOS ANGELES COUNTY AND ORANGE COUNTY, CALIFORNIA NLD ID #

SAN DIMAS WASH 7 LEVEE SYSTEM LOS ANGELES COUNTY, CALIFORNIA NLD SYSTEM ID #

AGUA FRIA RIVER 5 LEVEE SYSTEM MARICOPA COUNTY, ARIZONA NLD SYSTEM ID #

SANTA MARIA RIVER 3A LEVEE SEGMENT SANTA BARBARA COUNTY, CALIFORNIA NLD SYSTEM ID #

INDIAN BEND WASH 4 LEVEE SYSTEM MARICOPA COUNTY, ARIZONA NLD SYSTEM ID #

BALLONA CREEK 4 LEVEE SYSTEM LOS ANGELES COUNTY, CALIFORNIA NLD SYSTEM ID #

USACE SPL Levee Safety Program Driving Risk Down NEVADA

LEVEE DEFICIENCY CORRECTION PROCEDURES

LEVEE DEFICIENCY CORRECTION PROCEDURES

ARKANSAS & LOUISIANA LEVEE AND DRAINAGE DISTRICTS MEETINGS

Flood Damage Reduction Segment / System Inspection Report

Flood Damage Reduction Segment / System Inspection Report

Regulation 18 August 2009 NO Operations and Maintenance LEVEE ENCROACHMENT STANDARDS AND PROCEDURES

Flood Damage Reduction Segment / System Inspection Report

Prince George s County, MD Levee Response and Remediation Plan

Flood Damage Reduction Segment / System Inspection Report

Chapter A-13 STRUCTURAL ANALYSIS ARGENTINE RAISE

FEMA Levee Certification Ventura County, California

Current / Recent Construction Projects

(b) The written request must include 5 components: 1 The Permit Review and Approval Process. (1) Step 1: Pre-Coordination.

ENGINEERING REPORT ANALYSIS OF CLOSURES. HOUSATONIC RIVER and NAUGATUCK RIVER FLOOD PROTECTION PROJECTS SECTION 1. ANSONIA and DERBY, CONNECTICUT

Regional Vegetation Variance

Memorandum. April 15, 2010 CITY OF DALLAS. David A. Neumann (Chairman) Carolyn R. Davis. Steve Salazar (Vice-Chair) Vonciel Jones Hill

Dawson County Public Works 25 Justice Way, Suite 2232, Dawsonville, GA (706) x 42228

ENGINEERING REPORT STRUCTURAL STABILITY ANALYSIS FLOODWALLS. HOUSATONIC RIVER and NAUGATUCK RIVER FLOOD PROTECTION PROJECTS SECTION 1

Flood Damage Reduction Segment / System Inspection Report

DESIGN & CONSTRUCTION BUDGET AND FIVE YEAR CIP PROJECT SUMMARY - ZONE 1 FISCAL YEARS THROUGH

CONSTRUCTION PLAN CHECKLIST

DTE Energy St. Clair Power Plant

DESIGN & CONSTRUCTION BUDGET AND FIVE YEAR CIP PROJECT SUMMARY - ZONE 1 FISCAL YEARS THROUGH

Flood Damage Reduction Segment / System. Public Sponsor Pre-Inspection Form

09 July 2013 Revision

CODORUS CREEK FLOOD RISK MANAGEMENT PROJECT - STAKEHOLDERS MEETING

2. MAINTENANCE OF PROJECT FEATURES

Appendix B. Design. Page i. Design

DRAFT FINDING OF NO SIGNIFICANT IMPACT (FONSI) LEVEE VEGETATION MAINTENANCE MILL CREEK FLOOD CONTROL PROJECT WALLA WALLA, WASHINGTON JULY 2015

POST CLOSURE PLAN. CFR (d) Pond 1. Clinch Power Plant Russell County, West Virginia. November Prepared for: Appalachian Power Company

PUBLIC NOTICE U.S. ARMY CORPS OF ENGINEERS

Chapter A-15. CID-MO Structural Analysis

Flood Fighting and Surveillance

General Instructions for the Inspection of Flood Damage Reduction Segments / Systems

Standards for Soil Erosion and Sediment Control in New Jersey May 2012 STANDARD FOR SLOPE PROTECTION STRUCTURES. Definition

The Vegetation Challenge Sacramento, California August 28-29, 29, 2007

CHECKLIST FOR STREETS, INLETS, AND STORM SEWER DESIGN

DTE Energy Monroe Power Plant

USACE LEVEE RISK ASSESSMENT PROCESS LESSONS LEARNED

Dam Safety Inspection Checklist

Urban Levee Design Criteria and Central Valley Flood Protection Plan Levee Vegetation Management Strategy

Chapter A-10 GEOTECHNICAL ANALYSIS NORTH KANSAS CITY - LOWER (NATIONAL STARCH AREA)

REROUTING DRAINAGE SYSTEMS

Supplemental Watershed Plan Agreement No. 10 for Neshaminy Creek Watershed Core Creek Dam (PA-620) Bucks County, Pennsylvania

Sump Pumps Office procedures for the Drainage & Grading section

Chapter A-9 GEOTECHNICAL ANALYSIS NORTH KANSAS CITY - LOWER (HARLEM AREA)

Patterson Irrigation District Policy Regarding Urban Developments and Encroachments

Formal Annual Inspection It is recommended that you customize this form to fit your dam. Pre-Inspection Information

REMOVING/RELOCATING DRAINAGE LIFT STATIONS

Report. Inflow Design Flood Control System Plan Belle River Power Plant East China, Michigan. DTE Energy Company One Energy Plaza, Detroit, MI

Public Sponsor Representative Name Organization Team

WATER QUALITY MANAGEMENT PLAN PROCEDURES

U.S. Army Corps of Engineers Los Angeles District. US Army Corps of Engineers BUILDING STRONG

REVIEW PLAN For Plans and Specifications For Toe Drain Repairs Falls Lake Dam Wake County, North Carolina Wilmington District

Appendix J: The Project Stormwater Control Plan by Lea & Braze Engineering, Inc.

DEPARTMENT OF THE ARMY U.S. ARMY CORPS OF ENGINEERS 441 G STREET NW WASHINGTON, D.C MEMORANDUM FOR COMMANDERS, MAJOR SUBORDINATE COMMANDS

Coal Combustion Residuals Unit Structural Stability Assessment

III. INVENTORY OF EXISTING FACILITIES

LEVEE DISTRICT NO. 1 OF SUTTER COUNTY

Paul Brunner, Larry Dacus, Doug Handen. Repairs to Concrete-Lined V-Ditch Alternatives Evaluation

REVISED ETL Guidelines for Landscaping and Vegetation Management

MODEL Stormwater Local Design Manual. City of Centerville

CCR Rule Annual Inspection Report 2

This is a digital document from the collections of the Wyoming Water Resources Data System (WRDS) Library.

4. ACTIONS DURING HIGH WATER EVENTS

Application for a Dam Permit Ash Basin No. 1

SUBDIVISION CHECKLIST. Subdivision Name. Prior To Review. Preliminary plan approved by Planning Commission / Council as required.

Extended Detention Basin Maintenance Plan for [[== Insert Project Name ==]]

(b) Discuss in brief shaft spillway with neat sketches. Marks 04. OR Q (2) Explain in brief USBR stilling basin. Marks 08

INITIAL RUN-ON AND RUN-OFF CONTROL PLAN 40 C.F.R. PART 257

AMERICAN ELECTRIC POWER (SWEPCO)

CCR Annual Inspection (b) for the West Ash Pond at the F. B. Culley Generating Station. Revision 0

Stormwater Local Design Manual For Houston County, Georgia

Transcription:

SANTA ANA RIVER/ SAN TIMOTEO CREEK 1 LEVEE SYSTEM SAN BERNARDINO COUNTY, CALIFORNIA NLD SYSTEM ID # 3805030015 PERIODIC INSPECTION REPORT NO. 1 GENERALIZED EXECUTIVE SUMMARY FINAL SYSTEM RATING: UNACCEPTABLE FINAL RATING DATE: 25 JUNE 2015 PERIODIC INSPECTION REPORT PREPARED BY THE U.S. ARMY CORPS OF ENGINEERS, LOS ANGELES DISTRICT SUBMITTED: MARCH 2015 INSPECTED: AUGUST 20, 2014

EXECUTIVE SUMMARY This Executive Summary provides an introduction to the periodic inspection, an overview of the Santa Ana River/San Timoteo Creek 1 (SARSTC1) Levee System, a summary of the major findings of the periodic inspection of the SARSTC1 Levee System, and the overall rating for the SARSTC1 Levee System. 1.1 Scope and Purpose of Periodic Inspections The purpose of the SARSTC1 Levee System periodic inspection is to identify deficiencies that pose hazards to human life or property. The inspection is intended to identify the issues in order to facilitate future studies and associated repairs as appropriate. This assessment of the general condition of the SARSTC1 Levee System is based on available data and visual inspections. Detailed investigation and analysis involving hydrologic design, topographic mapping, subsurface investigations, testing, and detailed computational evaluations are beyond the scope of this levee system inspection. 1.2 System Summary The SARSTC1 Levee System is located on the left/west bank of the San Timoteo Creek (STC) Channel and the left/east bank of the Santa Ana River in the state of California, in San Bernardino County, in the city of Colton (Figure 1.1). The SARSTC1 Levee System was federally authorized and subsequently constructed by the U.S. Army Corps of Engineers, Los Angeles District (USACE LAD). Construction of the SARSTC1 Levee System along the San Timoteo Creek Channel and along the Santa Ana River was completed in October 1996 and December 1979, respectively (USACE LAD 2006 & USACE LAD 1984). The SARSTC1 Levee System is now entirely operated and maintained by San Bernardino County Flood Control District (SBCFCD). The National Levee Database Number (NLD No.) for the SARSTC1 Levee System is 3805030015. The SARSTC1 Levee System has an earthen embankment, a rectangular channel lined with reinforced concrete, a trapezoidal channel with a riverward slope lined with either reinforced concrete, grouted stone, the invert of which is either soft bottom or lined with reinforced concrete or derrick stone, nine side-drainage structure pipes, nine side-drain junction structure pipes, one gate outlet drain, utility crossings, bridge crossings, access ramps, a drop structure, baffle blocks, a sill, a training dike, a grade stabilizer, and landscaping. The SARSTC1 Levee System extends from the San Timoteo Creek (STC) Station 24+45 to STC 11+97 and Santa Ana River (SAR) Station 3201+68 to SAR Station 3090+00, a distance of approximately 13,268 feet (2.1 miles). It should be noted, that the earthen spoil bank located at the downstream end of the levee system from SAR Station 3090+00 to SAR Station 3081+48, was originally recommended to be included as part of the levee system, because it was constructed by the USACE LAD and is labeled as a levee embankment on the 1987 as-built drawings (USACE LAD 1987). However, during the Periodic Inspection, no levee slope was observed on the landside of the spoil bank and the area appears to have been filled in. In addition, the general topography of the area located to the landside/east of the spoil bank slopes towards the channel. Therefore, the spoil bank was not included as part of the levee system. A channel reach was identified during the Periodic Inspection of the SARSTC1 Levee System. These are reaches where the landside levee embankment height was observed to be level with the landside ground surface and therefore not leveed. The channelized reach was along the San Page 2 of 5

Timoteo Creek Channel from STC Station 21+50 to STC Station 14+60. All the deficiencies noted along this reach were included in the Flood Damage Reduction Channel checklist. 1.3 Summary of Major Deficiencies Found and Subsequent Repairs The Periodic Inspection of the SARSTC1 Levee System was conducted on August 20, 2014 and SBCFCD staff was present. During the inspection of the levee system, deficiencies were noted for which remedial actions are required. The following main deficiencies of the project features were noted during the Periodic Inspection: Levee Embankment: o Non-Compliant Vegetation Growth: Significant vegetation growth including trees with trunks larger than 2-inches in diameter and shrubs were present within the vegetation-free zone. The vegetation-free zone extends 15 feet outward from both the landward and riverward toes of the levee. Most of the vegetation was planted as part of the landscape drawings in USACE LAD 1976. o Closure Structures: The stop logs were not available for the closure structure and a 6-inchgap was observed between the stop-log hinge and the parapet wall. In addition, the top of levee elevation was lowered by as much as 4.7 feet during the construction of the bike path. Additionally, a retaining wall on the levee crown was cut for the bike path. o Underseepage Relief Wells/Toe Drainage Systems: Along San Timoteo Creek Channel, the subdrainage system outlets along a portion of the channel were not located during the Periodic Inspection because they were covered with vegetation and sediment. Along the Santa Ana River, some of the weep holes through the riverward concrete slope paving were clogged with vegetation. In addition, a subdrainage system outlet was rusted and corroded shut. In addition, the maintenance records were not available to verify cleaning of the subdrainage system per the Operation and Maintenance Plan (SBCFCD 2009) and the Operation, Maintenance, Repair, Replacement, and Rehabilitation Manual, San Timoteo Creek Channel (USACE LAD 2006). Floodwalls o Encroachments: Approximately 90 feet of the floodwall has been removed on the levee crown when the bike path was constructed in 2005 (San Bernardino County Department of Public Works [SBCDPW] 2005). Interior Drainage System o Vegetation and Obstructions: There was sediment and vegetation blocking more than 10 percent of the inlet and/or outlet of five side-drainage structures. o Culverts/Discharge Pipes: Video inspection was not available for any of the side-drainage structures or side-drain junction structures. o Flap Gates/Flap Valves/Pinch Valves: The flap gate at the outlet of a 24-inch-diameter reinforced concrete pipe (RCP) side-drainage structure was buried by sediment and vegetation. A flap gate was missing at the outlet of an 18-inch-diameter gate outlet. There was no flap gate at the outlet of a 12-inch-diameter corrugated metal pipe (CMP) side-drain junction structure, but there were no construction drawings available to determine if it was required. Page 3 of 5

Flood Damage Reduction Channels: o Vegetation and Obstructions: Woody vegetation was growing in the channel on established sediment shoals. This woody vegetation impaired the channel flow capacity. o Shoaling: Shoaling up to three feet deep, stabilized by saplings, brush, and other vegetation, was observed along the invert of the San Timoteo Creek Channel. 1.4 Overall Rating The Levee Safety Out-Brief Meeting was held on January 28, 2015. An engineering determination has concluded that the observed deficiencies could prevent the SARSTC1 Levee System from performing as intended during the next significant runoff event. Therefore, the Levee Safety Officer (LSO), Los Angeles District, has determined the overall rating of the SARSTC1 Levee System to be Unacceptable. An Unacceptable system rating is defined as, One or more items are rated as Unacceptable and would prevent the segment/system from performing as intended, or a serious deficiency noted in past inspections (which had previously resulted in a minimally acceptable system rating) has not been corrected within the established timeframe, not to exceed two years. The local sponsor will be notified of the overall rating of the levee system by letter with instructions to correct the Unacceptable rated items as soon as possible, not to exceed two years, and to correct the Minimally Acceptable rated items so that they do not deteriorate further and become Unacceptable. Page 4 of 5

Page 5 of 5 Figure 1