Earthwool 1000 Pipe Insulation

Similar documents
Earthwool 1000 Pipe Insulation

Knauf Data Sheet PE-DS-1e Earthwool TM 1000 Pipe Insulation

Knauf Data Sheet PE-DS-1e Earthwool Pipe Insulation

Earthwool Redi-Klad 1000 Pipe Insulation

Redi-Klad 1000 Pipe Insulation

Earthwool Insulation Board with ECOSE Technology

KwikFlex Pipe & Tank Insulation

Knauf Data Sheet PE-DS-2e Insulation Board. with ECOSE Technology

Knauf Data Sheet PE-DS-2e Insulation Board. with ECOSE Technology

Data Sheet CI-DWA-DS Atmosphere. Duct Wrap. with ECOSE Technology

KwikFlex Pipe & Tank Insulation. Knauf Data Sheet PE-DS

Insulation Board. Knauf Data Sheet PE-DS

Knauf Data Sheet AH-DS-5E Friendly Feel. Duct Wrap. with ECOSE Technology

Atmosphere Duct Liner

Knauf Data Sheet CI-DLS-DS Sonic XP. Duct Liner. with ECOSE Technology

Knauf Data Sheet AH-DS-12e Sonic XP Duct Liner. with ECOSE Technology

Friendly Feel Duct Wrap with KwikStretch Markings. Knauf Data Sheet AH-DS

Atmosphere Air Duct Board

Thermal/Acoustical Insulation. Data Sheet BI-RL-DS 05-18

Atmosphere Air Duct Board

Thermal/Acoustical Insulation. Data Sheet BI-BT-DS 08-17

Thermal/Acoustical Insulation. Data Sheet BI-BT-DS 2-17

Eclipse Air Duct Board

Eclipse Air Duct Board

Thermal/Acoustical Insulation. Data Sheet BI-BT-DS 08-17

Air Duct Board-M with Hydroshield Technology. Knauf Data Sheet AH-DS

Eclipse TM Air Duct Board. Knauf Data Sheet AH-DS

Updated 6/4/2012. Table Of Contents SECTION PLUMBING INSULATION

Tel: Fax:

Thermal/Acoustical Insulation. Data Sheet BI-BT-DS 11-15

A. Section Fire Procection, HVAC & Plumbing Penetration Firestopping. B. Section Interior Painting: Painting insulation jacket.

Offers excellent resistance to heat loss or gain, which saves energy and lowers operating costs. A low thermal conductivity of.23 at 75 F (24 C).

HVAC Piping Insulation- FIBERGLAS Insulation

HVAC Piping Insulation FIBERGLAS Insulation. General Specification Guide SECTION

Sonic XP Duct Liner with ECOSE Technology

SECTION HVAC INSULATION

FIRE STATION 55 June 14, 2010

SECTION HVAC PIPING INSULATION Updated 8/2018

GUIDE SPECIFICATION: DUCT LINER

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

Thermal/Acoustical Insulation. Knauf Data Sheet BI-BT-DS 08-13

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems

PERMATHERM PIPE INSULATION PRODUCTS

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

AK BLANKET Temperature Limit: 650 F (343 C)

Knauf Data Sheet BI-DS Thermal/Acoustical Insulation

DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION HVAC INSULATION

GUIDE SPECIFICATION: MECHANICAL SYSTEMS

.1 Thermal insulation for insulated piping and piping accessories affected by construction and new pipe sections as indicated on drawings.

PERMATHERM, INC. SPECIFICATION FOR COLD/CRYO PIPE INSULATION

PERMATHERM, INC. SPECIFICATION FOR COLD/CRYO PIPE INSULATION

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

A. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials

Design & Construction Standards, Revised January

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

SECTION PIPING INSULATION

PERMATHERM, INC. SPECIFICATION FOR CHILLED WATER PIPE INSULATION

Division 15 INSULATION Section 15100

ITW INSULATION SYSTEMS

ITW INSULATION SYSTEMS

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

A. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials

A. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness.

SECTION PLUMBING INSULATION

D. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required.

A. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds.

INSTALLATION GUIDELINE FOR TRYMER INSULATION

SECTION MECHANICAL INSULATION. A. Types of insulation specified in this section include the following:

Tube Insulation. Fiber Free

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER

PITTWRAP CF JACKETING Product Datasheet

ITW INSULATION SYSTEMS

State of Alaska Section State Office Building HVAC Fan Replacement MECHANICAL INSULATION

B C M T e c h n i c a l, L L C A v o n I n d u s t r i a l D r. R o c h e s t e r H i l l s, M I P h o n e : T o l

PROJ. NO SECTION HVAC DUCT INSULATION

SECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

CONTENTS OF THE DECLARATION. The PCR review was conducted by: 333 Pfingsten Road Northbrook, IL 60611

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section PIPE AND EQUIPMENT INSULATION

Chilled Water. Product performance for insulation of chilled water piping

SECTION HVAC INSULATION

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

SECTION HVAC PIPING INSULATION

Pipe & Equipment Insulations Product Selection Guide

OptiLiner Banded Liner System, Thermal, Metal Building

Air Handling Products

SECTION PLUMBING EQUIPMENT INSULATION Updated 8/2018

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

K-FLEX USA MECHANICAL INSULATION CONTENTS: SPECIFICATION GUIDE PRODUCT SELECTION GUIDE LEED CONTRIBUTION GUIDE

Mechanical Insulation for Refrigeration Systems

Ammonia. Product performance for insulation of ammonia piping

Addendum 1 Section THERMAL INSULATION FOR PIPING Burrow Avenue Pumping Station Upgrades Page 1 of 5

University of Delaware

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

PITTWRAP CW PLUS JACKETING Product Datasheet

SECTION STRUCTURAL INSULATED PANELS

SECTION DUCT INSULATION

Addendum to Specifications

379 Quick Installation Guide

Transcription:

Data Sheet CI-PE-DS 12-15 Earthwool 1000 Pipe Insulation with ECOSE Technology Knauf Insulation Earthwool 1000 pipe insulation is a molded, heavydensity, one-piece insulation made from inorganic glass mineral wool bonded with ECOSE Technology. It is produced in 3' lengths with or without a factory-applied jacket. ASJ+ is the newest generation all-service jacket composed of aluminum foil, reinforced with a glass scrim bonded to a kraft paper interleaving with an outer film layer leaving no paper exposed. A matching ASJ+ butt strip is furnished in the carton for each section. The jacket is white, and the longitudinal lap of the jacket has a self-sealing adhesive. The SSL+ Advanced Closure System creates a strong and lasting bond.

Earthwool 1000 Pipe Insulation with ECOSE Technology earthwool insulation Earthwool insulation is the new benchmark that stands apart for its genuine sustainability, unsurpassed performance and consistently high product quality. ecose technology ECOSE Technology is a revolutionary binder chemistry that enhances the sustainability of our products. The "binder" is the bond that holds our glass mineral wool product together and gives the product its shape and brown color. ECOSE Technology is a plant-based, sustainable chemistry that replaces the phenol/ formaldehyde (PF) binder traditionally used in glass mineral wool products. Products using ECOSE Technology are formaldehyde-free and have reduced global warming potential when compared to our products of the past. application Earthwool 1000 pipe insulation is used to insulate iron and copper piping in industrial applications and in commercial and institutional buildings. Earthwool 1000 pipe insulation is suitable for hot, cold, concealed and exposed piping systems operating at temperatures from 0 F-1000 F (-18 C to 538 C). Additional weather protection is needed outdoors. features and benefits Offers excellent resistance to heat loss or gain, which saves energy and lowers operating costs. ASJ+ faced pipe insulation has a selfsealing lap, which eliminates the need for staples, additional material and tools. Fast, easy installation reduces labor costs Installed properly, the foil vapor retarder and pressure-sensitive lap assure a positive vapor seal. facts at a glance Pipe size, wall thickness and Proto 25/50 Rated PVC fitting cover size are printed in a repeat pattern along the longitudinal lap. Easy identification at job site simplifies restocking Professional finished appearance dimple and wrinkle resistant Cleanable with a wet cloth and soapy water Moisture resistant to intermittent, short duration liquid water exposure, such as precipitation during construction phase ASJ+ has substantially less degradation and discoloration when exposed to UV. The SSL+ Advanced Closure System creates a strong and lasting bond. Low odor-emitting for indoor air quality considerations sustainability Carbon negative: Knauf Insulation products used for thermal insulating purposes recover the energy that it took to make them in just hours or a few days, depending on the application. Once installed, the product continues to save energy and reduce carbon generation as long as it is in place. Earthwool glass mineral wool insulation contains three key ingredients: Sand, one of the world s most abundant resources A minimum of 50% recycled content and UL Environment verification every 6 months ECOSE Technology which reduces binder embodied energy by up to 70%. It also reduces its Global Warming Potential (GWP) by approximately 4%, a significant reduction in our carbon footprint. Specification Compliance in U.S.: ASTM C547; Type I, Type IV ASTM C585 ASTM C795 ASTM C1136 (jackets); Type I, II, III, IV,VIII HH-I-558C; Form D, Type III, Class 12; Class 13 (to 1000 F, 538 C) NFPA 90A and 90B MIL-PRF-22344E (except ph requirements) MIL-I-24244D NRC Reg. Guide 1.36 (certification needs to be specified at time of order) Conforms to Marine Equipment European 1408/13 USCG 164.109/4/1 In Canada: CAN/ULC S102-M88 CGSB 51-GP-9M CGSB 51-GP-52M (jacket) Indoor Air Quality UL Environment GREENGUARD Certified UL Environment GREENGUARD GOLD SM certified UL Environment validated to be formaldehyde free This product complies with Oregon Revised Statue 453.085 and contains less than 0.10% decabromdiphenyl ether (DecaBDE) by mass. Tested and certified to meet all the requirements of EUCEB IgCC Section 806.6 compliant SSL+ Advanced Closure System creates a strong and lasting bond. Earthwool 1000 pipe offers an extended temperature range for all applications from 0 to 1000 F. The Knauf Insulation rotary manufacturing process produces insulation with concentric inside diameters and consistent wall thicknesses.

technical data Earthwool 1000 Pipe Insulation Surface Burning Characteristics UL/ULC Classified Does not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with UL 723, ASTM E84, CAN/ULC S102-M88 and NFPA 255 Temperature Limitation (ASTM C411 & ASTM C447) Up to 1000 F (538 C) at a maximum recommended thickness of 6" Corrosiveness (ASTM C665) Does not accelerate corrosion on steel, copper or aluminum Corrosion (ASTM C1617) The corrosion rate in mils/yr will not exceed that of 5 ppm chloride solution. Microbial Growth (ASTM C1338) Does not promote microbial growth Water Vapor Sorption (ASTM C1104) Less than 0.2% by volume Linear Shrinkage (ASTM C356) Negligible ASJ+ Facing Surface Burning Characteristics UL/ULC Classified Does not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with UL 723, ASTM E84, CAN/ULC S102-M88 and NFPA 255. Specification Compliance ASTM C1136 (jackets); Type I, II, III, IV, VIII Water Vapor Transmission (ASTM E96, Procedure A) Jacket has a water vapor permeance of.02 perms or less. Water Vapor Sorption (ASTM C1104) Less than 0.2% by volume facts at a glance Product Forms and Sizes Produced in 3' (914 mm) sections: For iron pipe from ½" to 24" nominal pipe size (15 mm to 610 mm) For copper tube from 5 /8" to 6 1 /8" (16 mm to 156 mm) Wall thicknesses from ½" to 6" (13 mm to 152 mm) in single layer (for most sizes) All insulation inner and outer diameters comply with ASTM C585 Packaging Four convenient carton sizes for easy ordering, inventory tracking and storage Reinforced carton handles for strength and easy lifting Bar-coded cartons for accurate shipments and tracking Full product range stocked at distributors for fast availability precautions Hot Pipe May be installed while the system is in operation, at all temperatures up to 1000 F (538 C). Knauf Insulation recommends, for insulation thicknesses greater than 6" (152 mm), the temperature must be increased from 500 F (260 C) to maximum temperature at a rate not exceeding 100 F (37.8 C) per hour. During initial heat-up to operating temperatures above 350 F (177 C), a slight odor and some smoke may be given off as a portion of the bonding material used in the insulation begins to undergo a controlled decomposition. If natural convection is not adequate in confined areas, forced ventilation should be provided in order to protect against any harmful fumes and vapors that might be generated. Care must also be taken when using sealants, solvents or flammable adhesive during installation. A maximum of 6" (152 mm) wall thickness is recommended. Cold Pipe Use a continuous vapor retarder on piping operating below ambient temperatures. Seal all joints, surfaces, seams and fittings to prevent condensation. On below freezing applications, and in high-abuse areas, the ASJ+ jacket shall be protected with a PVC vapor retarding outer jacket. In addition, exposed ends of insulation shall be sealed with vapor barrier mastic installed per the mastic manufacturer s instructions. Vapor seals at butt joints shall be applied at 12' to 21' intervals; at the Engineer s discretion and at each fitting to isolate any water incursion. On chilled water systems operating in high humidity conditions, it is recommended that the same guidelines be followed as listed above for below freezing applications. Exterior hanger supports are recommended. Knauf Insulation s "wind-up" forming mandrel process prevents gaps and inconsistent densities, while making it easy to cleanly notch out sections. ECOSE Technology bio-based binder eliminates non-renewable petroleum-based ingredients. No formaldehyde, no phenol, no acrylics. Earthwool insulation contains a minimum 50% recycled bottle glass. ASJ ASJ+ ASJ+ is cleanable with a wet cloth and soapy water.

Outside Application Do not expose pipe insulation to weather. It must be covered with appropriate jacketing, mastic or vapor retardant coatings. All exposed surfaces must be protected. Proto Indoor/Outdoor PVC Jacketing is recommended. See Knauf Guide Specifications for recommended PVC jacketing application guidelines. Apply jacketing, mastics or vapor retardant adhesives per manufacturer s instructions. For metallic jackets, factory-applied moisture retarders are recommended. ASJ+ SSL+ Keep adhesive and contact surfaces free from dirt and water. Seal immediately once adhesive is exposed. Apply when ambient and insulation temperatures are between 20 F and 130 F (-6.7 C and 54 C). If stored below 20 F or above 130 F, allow insulation cartons to stand within recommended temperature range for 24 hours prior to application. Do not store product below -20 F (-29 C) or above 150 F (66 C). When using Knauf Insulation s SSL+ Advanced Closure System, make sure the longitudinal and circumferential joints are properly sealed by rubbing the closure firmly with a squeegee. Use of staples is not recommended. When using Earthwool 1000 pipe insulation, the surface temperature of the insulation should be between 20 F and 150 F (-6.7 C and 66 C) during the life of the insulation. Fittings and Hangers Use Proto 25/50 Rated (ASTM E84) PVC Fitting Covers, applying PVC fittings per Proto s Data Sheet. Fittings should be insulated to same thickness as the adjoining insulation. Apply fittings per manufacturer s instructions. When required by specification, a hard insert of sufficient length should be used to avoid compression of the insulation. Additional Precautions Glass mineral wool may cause temporary skin irritation. Wear long-sleeved, loosefitting clothing, head covering, gloves and eye protection when handling and applying material. Wash with soap and warm water after handling. Wash work clothes separately and rinse washer afterwards. Use a disposable mask/respirator designed for nuisance-type dusts where sensitivity to dust and airborne particles may cause irritation to the nose or throat. application guidelines Storage Protect insulation from water damage or other abuse, welding sparks and open flame. Cartons are not designed for outside storage. Preparation Apply only on clean, dry surfaces. Pipe or vessel should be tested and released before insulation is applied. General Guidelines All sections should be firmly butted. Seal circumferential joint with a minimum 3" (76 mm) wide butt strip. Jackets, coating and adhesives should have a comparable F.H.C. rating. ASJ+ may be painted. As with traditional ASJ, Knauf Insulation does not encourage the painting of ASJ+ because the application of any paint may change the surface burning characteristics and will void the UL Classification and Knauf Insulation Limited Warranty. Insulation Limited Warranty Where painting is necessary use common water, oil, or solvent-based paints. All paints should be tested for compatibility and adhesion before use. All piping should have continuous insulation. Position longitudinal lap downward to avoid dirt and moisture infiltration. Do not expose pipe insulation to excessive vibration or physical abuse. Faced insulation should not have a facing temperature above 150 F (66 C). SSL+ Installation Instructions: 1. To install SSL+, first remove the kraft release liner to expose adhesive. 2. Carefully align the jacketing. Starting in the center of the insulation section, begin initial SSL+ tack using pressure in the direction of the overlap. Again, starting in the center of the insulation section, with a plastic squeegee begin to apply firm pressure to the bonded lap area swiping from the center of the insulation section toward each end. NOTE: After initial SSL+ adhesive tack, it is critical that the closure is not re-opened and repositioned on the facing. Doing so will delaminate the jacket and adhesive, diminishing the bond strength. facts at a glance ASJ+ is moisture resistant to intermittent, short duration liquid water exposure, such as precipitation during construction. Earthwool 1000 pipe insulation with ASJ+ is not intended for unprotected outdoor use. ASJ ASJ+ ASJ+ will provide a professional finished appearance dimple and wrinkle resistant. Size, wall thickness and Proto 25/50 rated PVC fitting cover identification are printed on the jacket.

Butt Strip Installation Instructions: 1. To install Butt Strips, remove the kraft release liner by separating the butt strip from the kraft using the convenient, easy release kiss cut. 2. Simply wrap the butt strip, centered around the joint, and apply firm pressure with a squeegee. NOTE: After initial Butt Strip adhesive tack, it is critical that the closure is not re-opened and repositioned on the facing. Doing so will weaken the adhesive and diminish bond strength. Recommended Thicknesses (ASHRAE 90.1-2013) The minimum thicknesses are based on ASHRAE 90.1-2013 standards and do not necessarily represent the Economic Thickness of Insulation or the thickness required for proper condensation control. Rather, they serve as minimum recommendations for commercial applications. For recommended Economic Thickness, install according to Knauf Insulation or NAIMA 3E Plus programs or as specified. Glass Mineral Wool and Mold Glass mineral wool insulation will not sustain mold growth. However, mold can grow on almost any material when it becomes wet and contaminated. Carefully inspect any insulation that has been exposed to water. If it shows any sign of mold it must be discarded. If the material is wet but shows no evidence of mold, it should be dried rapidly and thoroughly. If it shows signs of facing degradation from wetting, it should be replaced. Notes The chemical and physical properties of Knauf Insulation Earthwool 1000 pipe insulation represent average values determined in accordance with accepted test methods. The data is subject to normal manufacturing variations. The data is supplied as a technical service and is subject to change without notice. References to numerical flame spread ratings are not intended to reflect hazards presented by these or any other materials under actual fire conditions. Check with your Knauf Insulation territory manager to assure information is current. Thermal Efficiency (ASTM C335) Mean Temperature k k (SI) 75 F (24 C) 0.23 0.033 100 F (38 C) 0.24 0.035 200 F (93 C) 0.28 0.040 300 F (149 C) 0.34 0.049 400 F (204 C) 0.42 0.061 500 F (260 C) 0.51 0.074 600 F (316 C) 0.62 0.089 Minimum Pipe Insulation Thickness (in.) a (to meet ASHRAE 90.1-2013 Requirements) Fluid Design Operating Temperature Range, F Insulation Conductivity Conductivity Range BTU-in./ (hr ft 2 F) Mean Temperature Rating, F <1 Nominal Pipe or Tube Size (in.) 1 to <1½ 1½ to <4 4 to <8 8 Heating and Hot Water Systems (Steam, Steam Condensate, Hot Water Heating and Domestic Water Systems) b,c Above 350 0.32-0.34 250 4½ 5 5 5 5 251-350 0.29-0.31 200 3 4 4½ 4½ 4½ 201-250 0.27-0.30 150 2½ 2½ 2½ 3 3 141-200 0.25-0.29 125 1½ 1½ 2 2 2 105-140 0.32-0.28 100 1 1 1½ 1½ 1½ Cooling Systems (Chilled Water, Brine, Refrigerant) d 40-60 0.21-0.27 75 ½ ½ 1 1 1 Below 40 0.20-0.26 50 ½ 1 1 1 1½ For insulation outside the stated conductivity range, the minimum thickness (T) shall be determined as follows: T=r{(1+t/r) K/k -1}. Thermal Conductivity (BTU-in./hr ft 2 F).70.60.50.40.30.20.10.00 0-18 Where T=minimum insulation thickness (in.), r = actual outside radius of pipe (in.), t = insulation thickness listed in this table for applicable fluid temperature and pipe size, K = conductivity of alternate material at mean rating temperature indicated for the applicable fluid temperature {Btu in.(h ft 2 F)}; and k =the upper value of the conductivity range listed in this table for the applicable fluid temperature. These thicknesses are based on energy efficiency considerations only. For piping smaller than 1½" and located in partitions within conditioned spaces, reduction of these thicknesses by 1" shall be permitted (before thickness adjustment required in footnote a) but not to thicknesses below 1". These thicknesses are based on energy efficiency considerations only. Issues such as water vapor permeability or surface condensation sometimes require vapor retarders or additional insulation. The table is based on steel pipe. Non-metallic pipes schedule 80 thickness or less shall use the table values. For other non-metallic pipes having thermal resistance greater than that of steel pipe, reduced insulation thicknesses are permitted if documentation is provided showing that the pipe with the proposed insulation has no more heat transfer per foot than a steel pipe of the same size with the insulation thickness shown on the table. 100 38 200 93 300 149 Mean Temperature 400 204 500 260.101.087.072.058.043.029.014 600 (ûf) 316 (ûc) Thermal Conductivity (Sl Units ) (W/m C)

Knauf Insulation, Inc. One Knauf Drive Shelbyville, IN 46176 Sales (800) 825-4434, ext. 8300 Technical Support (800) 825-4434, ext. 8512 Fax (317) 398-3675 Information info.us@knaufinsulation.com Website www.knaufinsulation.us 2015 Knauf Insulation, Inc. Versions of this product have surface burning characteristics that are classified by Underwriters Laboratories and therefore subject to auditing for fire performance compliance. This product has been tested and is certified to meet the EUCEB requirements. LEED Eligible Product Use of this product may help building projects meet green building standards as set by the Leadership in Energy and Environmental Design (LEED) Green Building Rating System. LEED v2009 MR Credit 4.1-4.2 Recycled Content MR Credit 5.1-5.2 Regional Materials LEED v4 Knauf Insulation offers several products for both envelope and mechancial systems that have ingredient disclosure and transparency. Please contact transparency@knaufinsulation.com for products that currently contribute to MR credits. This product has been tested and is certified to meet the US Coast Guard requirements. UL Environment GREENGUARD Gold Knauf Insulation achieved UL Environment GREENGUARD Gold Certification. UL Environment Validated Formaldehyde Free Earthwool products are formaldehyde free. UL Environment Certified EPD EPD Certification is documentation fully disclosing a product s environmental impact as well as other information regarding human toxicity, risk, and social responsibility. UL Environment Recycled Content Earthwool products contain Claim Validated Post Consumer and Pre Consumer recycled content. For more information, visit ul.com/spg. Declare is a voluntary self-disclosure program aiming to transform the building materials industry towards healthier and more ecological products through ingredient transparency. Participating in Declare means this product has voluntarily self-disclosed all ingredients in order to promote transparency. Living Building Challenge Compliant means this product meets the requirements of the Red-List Imperative of the Living Building Challenge due to a temporary exception. Living Building Challenge Red List Free means this product does not contain any ingredients on the Living Building Challenge s Red List. This product is covered by one or more U.S. and/or other patents. See patent www.knaufinsulation.us/patents