Footfall vibration analysis of a high precision manufacturing facility

Similar documents
Long-Span Truss Structures for Low-Vibration Environments

Introduction. Engineering, Universiti Tun Hussein Onn Malaysia, Johor, MALAYSIA. Universiti Tun Hussein Onn Malaysia, Johor, MALAYSIA

Analysis of the Effect of Vibration from Footfalls on Office Building

Human-Induced Vibrations in Buildings

GARAGE STRUCTURE VIBRATION TRANSMISSION TO HUMAN OCCUPIED SPACES

Comparative Impact Performances of Lightweight Gym Floors

Vibration analysis and design of a structure subjected to human walking excitations

CTBUH Technical Paper

COMPARISON OF POOL ISOLATION SYSTEMS

Minimum slab thickness of RC slab to prevent undesirable floor vibration. Technology, Dhaka-1000, Bangladesh. 2.

EFFECT OF FIT-OUT AND CONSTRUCTION TYPE ON DYNAMIC PROPERTIES OF FLOOR SYSTEMS UNDER HUMAN EXCITATIONS

Stability of Optical Elements in the NIF Target Area Building

Revision and Errata List, March 1, 2003 AISC Design Guide 11: Floor Vibrations Due to Human Activity

FINITE ELEMENT ANALYSIS OF HOLLOW-CORE SLABS. E. Frăţilă a, *, Z. Kiss a

Control of variable frequency vibration in large span composite construction floor in a high rise building

Forced vibration testing of a thirteen storey concrete building

THE EFFECTS OF LOCAL MODES ON VIBRATION REDUCTION OF BUILDING ISOLATION. Hong Kong SAR. Hong Kong SAR.

The Effects of Building Parameters on the Modal Displacement Shapes of Tall Buildings

Application Note Vibration Criteria for Facilities with Sensitive Equipment. Vibration Measurement

Effect of Mass and Stiffness of Vertically Irregular RC Structure

NODALIZATION OF ISOLATOR FOR FLOATING FLOOR DESIGN. C.K. Hui and C. F. Ng

Building Isolation Design for Noise Critical Applications

Experimental observation of forklift-induced vibrations on a PSC floor

VIBRATION EVALUATION OF A PARKING STRUCTURE 1

DETERMINING THE STATIC STIFFNESS OF STRUCTURES: A COMPARISON OF METHODS INVOLVING MEASUREMENT OF DISPLACEMENT AND MEASUREMENT OF ACCELERATION RESPONSE

The Influence of the Shape of Slab on Heavyweight Impact Sound Reduction for an Apartment Building

Analysis of Reinforced Concrete. Workshop Prague, March 30-31, 31, 2007 COST Action C26

A NEW EMPIRICAL PREDICTION APPROACH FOR GROUNDBORNE VIBRATION IN BUILDINGS

Vibration Serviceability Design and Field Tests of Long-Span Ultra- Slim Composite Floor System for Super Tall Residential Buildings

Part III Special Topics of Bridges

Relationship between flanking noise through a common ceiling plenum and plenum absorption George van Hout, John Pearse and Brian Donohue

Ozone Panel 120 Acoustic Assessment and Optimization

An Economical Approach to Floor Vibration through Appropriate Design Criteria and Analytical Methods 2017 SEAOC Convention

Structural Dynamics and Earthquake Engineering

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

Determination of damage location in RC beams using mode shape derivatives

SEISMIC DESIGN CHARACTERISTICS OF THE NEW BUILDING FOR DIGITAL AUTOMATION EQUIPMENT FOR LOVIISA NUCLEAR POWER PLANT

VIBRATION EVALUATION OF FLOOR SYSTEMS FOR FOOTFALL USING ADAPT-FLOOR PRO

WESTSIDE PURPLE LINE EXTENSION PROJECT, SECTION 2 ADVANCED PRELIMINARY ENGINEERING Contract No. PS

CHAPTER III DYNAMIC BEHAVIOR OF A LABORATORY SPECIMEN

Dynamic Performance on Multi Storey Structure Due to Ground Borne Vibrations Input from Passing Vehicles

Vibration Assessment of Adelaide's new Riverbank Foot-Bridge

INFRASOUND AND BLADE PASS FREQUENCY LEVELS IN AREAS ADJACENT TO WIND FARMS

SEISMIC DESIGN OF STRUCTURE

Effectiveness of strong-back/wood I-blocking for improving vibration performance of engineered wood floors

Non Linear Analysis of Composite Beam Slab Junction with Shear Connectors using Ansys.16

VIBRATION ANALYSIS OF AN OIL PRODUCTION PLATFORM

A Study on Seismic Analysis of High Rise Irregular Floor Plan Building with Different Position of Shear Walls

LASD Coatings Optimized for Damping of Aluminum Intensive Vehicle Bodies

Modal Analysis as a Tool to Resolve Pump Vibration Issues

S. Gandhi *1, Syed Rizwan 2

Soil-Structure interaction effects on seismic response of a 16 storey RC framed building with shear wall

SPECIFICS OF NATURAL FREQUENCY MEASUREMENTS FOR FLOOR VIBRATION. Riga Technical University, Latvia

Transactions, SMiRT-22 San Francisco, California, USA - August 18-23, 2013 Division V

Simplified Finite Element Modelling of Multi-storey Buildings: The Use of Equivalent Cubes

Optimum Design for Passive Tuned Mass Dampers Using Viscoelastic Materials

Vibration effects in healthcare facilities

Seismic Evaluation of a 1930 Steel Bridge with Lightly Reinforced Concrete Piers

Measurements of junction vibration level differences of timber framed constructions

A case study for base isolation design: Spark data centre facility Auckland

Accuracy of Dynamic and Acoustic Analysis of Lightweight Panel Structures: A Comparison of ABAQUS and ANSYS

DYNAMIC RESPONSE ANALYSIS OF THE RAMA 9 BRIDGE EXPANSION JOINT DUE TO RUNNING VEHICLE

Seismic Rehabilitation of Selby Condominium Complex, Montreal (Quebec), Canada

Tests and Analysis on Vertical Vibration of Long-Span Prestressed Concrete Floor Sysstem Abstract: Keywords: INTRODUCTION Corresponding Author:

The Effect of Axial Force on the Behavior of Flush End-Plate Moment Connections

ANALYSIS OF 3-D VIBRATIONS OF THE BASE ISOLATED SCHOOL BUILDING "PESTALOZZI" BY ANALYTICAL AND EXPERIMENTAL APPROACH

A study on the prediction of the noise reduction performance according to applying the rail web-damper in curved track section

For handling vibration, negative-stiffness isolators can offer big improvement over air tables

Comparison of Chevron and Suspended Zipper Braced Steel Frames

POWER PRESSES. Vibration Control, Mounting and Levelling of: Power Presses APPLICATIONS. Presses come in various categories including:

Seismic Analysis and Design of Vertically Irregular RC Building Frames

Dynamic Design of the Foundation of Reciprocating Machines for Offshore Installations in Persian Gulf

Modal analysis and flanking sound insulation in connected panels of cross-laminated-timber at low frequencies

Dynamic Analysis of Turbo-generator Machine Foundations

Computer Aided Design of Modern High-Rise Building

FEM UPDATING OF THE HERITAGE COURT BUILDING STRUCTURE

Does EMI Shielding Increase Vibration?

Warwick FRP Bridge: Design and Performance

The Concrete Centre Hospital Floor Vibration Study Comparison of Possible Hospital Floor Structures With Respect To NHS Vibration Criteria Black

This report assesses the outward noise and vibration impact of the proposed development on its surrounding environment.

Influence of Boundary Conditions on Building Behavior

PREDICTING SOUND INSULATION PERFORMANCE

3.5 Tier 1 Analysis Overview Seismic Shear Forces

SSRG International Journal of Civil Engineering ( SSRG IJCE ) Volume 4 Issue 6 June 2017

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Simulation of Ground-borne Vibration and Noise Due to High -speed. Trains through Changsha Railway Station

1. INTRODUCTION 1.1 FLAT SLAB. 275 P a g e

Vibration Serviceability and Dynamic Modeling of Cold-Formed Steel Floor Systems

Progressive Collapse Resisting Capacity of Moment Frames with Infill Steel Panels

ACCELERATED REPLACEMENT OF STEEL PLATE RAILWAY BRIDGES USING MOVING CRANES ON RAILROAD

Optimization Design of Cold Roll-beating Experiment Device Based on ANSYS Workbench

Classical soil-structure interaction and the New Zealand structural design actions standard NZS (2004)

Proceedings of Meetings on Acoustics

Abstract. 1. Introduction

Torsion in tridimensional composite truss bridge decks

EXPERIMENTAL STUDY ON VIBRATION BEHAVIOR OF COLD-FORM STEEL CONCRETE COMPOSITE FLOOR

7 LOCAL BUCKLING OF STEEL CLASS 4 SECTION BEAMS

II-100 II-101 INTRODUCTION

Int. Journal for Housing Science, Vol.34, No.2 pp , 2010 Published in the United States

Roma to Brisbane Pipeline Dalby Compressor Station Upgrade Environmental Management Plan. Appendix 8. Noise Assessment

Transcription:

Footfall vibration analysis of a high precision manufacturing facility Jason GAEKWAD 1 ; Yong Keat LEE 1 ; Neil MACKENZIE 1 1 Aurecon Pty Ltd, Australia ABSTRACT High tech manufacturing facilities often have specific requirements regarding vibration of floor structures to ensure precision manufacturing is not compromised by vibration induced displacement of components. This paper outlines the design methodology used to mitigate footfall-induced vibration in one such proposed facility. The vibration design process involved an on-site assessment of a similar existing building within the facility to determine the response of typical spans (elevated or on grade) to footfall excitation. Finite element modelling and analyses of proposed constructions were then conducted. The results of this study allowed for floor constructions meeting the specified ASHRAE Vibration Criteria to be accurately determined and priced during the concept stage of the project. Keywords: Sound, Insulation, Transmission I-INCE Classification of Subjects Number(s): 51.4 (See. http://www.inceusa.org/links/subj%20class%20-%20formatted.pdf.) 1. INTRODUCTION This paper outlines the experimental and numerical modelling methodology used to mitigate footfall vibration in a proposed high precision manufacturing facility. The project brief for the facility required specific vibration design and costing options. A vibration survey of a similar existing facility was undertaken to assess the impact of multiple vibration sources, including external vehicular movements, HVAC plant, and footfall. In order to facilitate structural design for vibration mitigation and costing, finite element modelling was conducting using the General Structural Analysis (GSA) package. Dynamic analysis was performed, including footfall excitation analysis, using the methodology outlined by The Concrete Centre (4). Several structural configurations meeting various vibration criteria were designed and costed, with the final structural design incorporating ground stiffness obtained from geotechnical survey and modelling. 1.1 Project Suary The project involved construction of a new manufacturing facility to produce high precision electronic components. The proposed 3-storey manufacturing facility included a floor area of approximately 42,000 m 2, with manufacturing spaces and clean rooms on all floors. The proposed site was close to an existing manufacturing facility of the same function. The project brief required a cost study to be conducted on various structural configurations, with each floor meeting specific vibration criteria, selected from the ASHRAE Vibration Criteria (VC) (1) as shown in Table 1. Table 1 Project brief ASHRAE Vibration Criteria options Configuration 1 2 3 4 Ground floor VC-D VC-D VC-D VC-D 1 st floor VC-D VC-D VC-D VC-C 2 nd floor VC-D VC-D VC-C VC-B 3 rd floor VC-D VC-C VC-B VC-B 1 jason.gaekwad@aurecongroup.com, yongkeat.lee@aurecongroup.com, neil.mackenzie@aurecongroup.com Inter-noise 2014 Page 1 of 9

Page 2 of 9 Inter-noise 2014 2. VIBRATION CRITERIA Coon vibration criteria for sensitive equipment and human perception specify vibration limits in terms of Root Mean Square (RMS) velocity. Table 2 presents the ASHRAE Vibration Criteria (1) which outline vibration limits for sensitive equipment. The ISO 2631 (2) Operating Theatre (Base Curve) criterion has also been included. The various criteria curves can be described by the response factor, R, which is a multiplication factor of the ISO Base Curve (R=1). Table 2 Vibration criteria and descriptions (4) Criterion Curve Max Level Detail size Description of Use µm/s, RMS* microns** Operating theatre (ISO) Base Curve R=1 100 25 Vibration not perceptible. Suitable for sensitive sleep areas. Suitable in most instances for microscopes to 100X and for other equipment of low sensitivity. VC-A (ASHRAE) R=0.5 50 8 Adequate in most instances for optical microscopes to 400X, microbalances, optical balances, proximity and projection aligners, etc. VC-B (ASHRAE) R=0.25 25 3 An appropriate standard for optical microscopes to 1000X, inspection and lithography equipment (including steppers) to 3 micron line widths. VC-C (ASHRAE) R=0.125 VC-D (ASHRAE) R=0.0625 12.5 1 Standard for most lithography and inspection equipment to 1 micron detail size. 6 0.3 Suitable in most instances for the most demanding equipment including electron microscopes (TEMs and SEMs) and E-Beam systems, operating to the limits of their capability. VC-E (ASHRAE) R=0.03125 3 0.1 A difficult criterion to achieve in most instances. Assumed to be adequate for the most demanding of sensitive systems including long path, laser-based, small target systems and other systems requiring extraordinary dynamic stability *As measured in one-third octave bands of frequency over the frequency range 8 to 100 Hz **The detail size refers to the line widths for microelectronics fabrication, the particle (cell) size for medical and pharmaceutical research, etc. The values given take into account the observation that the vibration requirements of many items depend upon the detail size of the process Page 2 of 9 Inter-noise 2014

Inter-noise 2014 Page 3 of 9 3. VIBRATION SURVEY A vibration survey was conducted on areas of the existing manufacturing facility adjacent to the proposed facility site. The existing facility served a similar purpose to the proposed facility, containing manufacturing areas and clean rooms across multiple levels. All likely sources of vibration, including footfall, plant, lab equipment, and nearby vehicular traffic were considered as part of the vibration survey. 3.1 Characterising vibration In order to characterise the existing vibration conditions of the proposed development site, measurements of ambient vibration were performed. High-sensitivity accelerometers and a portable spectrum analyser were used to carry out the measurements. Baseline outdoor ambient ground vibrations due to nearby road traffic movements (heavy vehicle pass-bys etc.) and background conditions (i.e. without traffic pass-by) were recorded. The ambient vibration survey was used to evaluate site suitability and preferred setbacks for the facility from a planning perspective. Vibration sources inside the facility were next considered, with HVAC systems and footfall identified as the major sources of vibration. To assess the vibration impact of HVAC systems, ambient indoor facility-wide vibration measurements were undertaken with major base-building HVAC systems operating. Testing locations were carefully inspected and selected such that they were representative of typical zones within the building. Similarly, footfall vibration was characterized through as-built walk-by tests of operational clean room facilities. For these tests, the vibration response at workstations close to mid-span was simultaneously measured with the slab response. The walk-by tests provided a rapid method of assessing footfall vibration within the sensitive areas of the facility. The results of the vibration survey identified the sources of the vibration in existing facility and allowed comparison between the existing as-built floor response performance against the design brief requirements of the new facility. Footfall excitation was identified as the primary cause of vibration in the existing facility, with all other sources of vibration negligible relative to the brief vibration requirements. 3.2 Footfall vibration survey The footfall vibration survey of the existing facility was conducted at two critical areas. The first area (Area A) was on the Ground Floor, in a vacant area normally used for manufacturing. This area was critical as VC-D was required for the Ground Floor of the proposed facility. The second area (Area B) was located on the top (3 rd ) floor, again in an unused manufacturing area. Measurements at this location provided the opportunity to test a typical span. The structure in each of these critical areas is described in Table 3. Area Span, m Slab thickness, Table 3 Structural configuration of areas surveyed Primary beam, Primary beam Secondary beam, Secondary beam A 7 x 14 300 600 x 1,000 3,500 500 x,1000 7,000 B 7 x 14 250 500 x 1,200 7,000 300 x 700 14,000 For footfall tests, the accelerometer was positioned at the center of the floor span, and floor vibration measurements were recorded with footfall excitation at different pacing frequencies in a straight line across the span and close to the position of the accelerometer. The footfall vibration survey indicated that the Area A construction comfortably met VC-E (7% exceedance of VC-F), and the Area B construction met the ISO Operating Theatre criterion, noting that Area B exceeded VC-A by 14%. Typical results of the vibration survey are presented in Table 4, with the typical response with frequency shown in Figure 1. Inter-noise 2014 Page 3 of 9

Page 4 of 9 Inter-noise 2014 Table 4 Footfall vibration survey results Area Floor Vibration Criterion achieved A Ground floor VC-E (exceeds VC-F by 7%) B Fourth floor ISO Operating Theatre (exceeds VC-A by 14%) Figure 1 Typical frequency content of footfall vibration response As the design brief required a minimum of VC-B for the upper floors, the existing structural configuration could not be used for the proposed building. The response of the Ground Floor indicated that the existing construction was overdesigned, indicating potential cost savings in the construction of the proposed Ground Floor slab. 4. FINITE ELEMENT MODELLING In order to assess and cost various structural configurations, Finite Element (FE) modelling was used. This methodology allowed a number of structural configurations to be assessed within the prograe and budget of the conceptual design phase of the project. 4.1 Software Description Footfall response modelling was undertaken using the FE package GSA. This package uses the finite element method, with the concrete slab represented by plate elements and two-dimensional members (columns, beams) represented by beam elements. Generation of the numerical mesh was performed manually by element subdivision. GSA features an eigenvalue solver, allowing for dynamic analysis of structures to be carried out. The resultant natural frequencies and mode shapes are necessary for the calculation of response to dynamic loads, including footfall. GSA also features a footfall response solver based on the Concrete Centre methodology (4), as discussed in Section 4.1.1. This solver automates the response calculation process, producing response factors which may then be visualized across the structure. Page 4 of 9 Inter-noise 2014

Inter-noise 2014 Page 5 of 9 4.1.1 GSA Methodology GSA separates footfall response into harmonic (resonant) response and impulse response methods. A coon feature of both of these methods is the use of empirically determined footfall load factors. The Concrete Institute measured a number of footfall time traces, which were non-dimensionalised by the person s static weight to produce a Dynamic Load Factor (DLF). The design DLF used in the GSA method is the 75 th percentile, or DLF with a 25% chance of exceedance. Refer to (4) for a detailed outline of the GSA calculation method, noting that a number of footfall calculation methods are offered within the GSA solver suite. The acceleration response to harmonic footfall excitation at any location is weighted by the mode shape at both the excitation and response points. There is also an empirical correction factor (with a value of 0 to 1) which accounts for the number of footsteps taken to cross the span, assuming that the walker crosses the span in a straight line through the centre. The calculated accelerations are then normalized by the acceleration of the base curve to calculate a response factor. The response factors are sued for each harmonic of the walking frequency, to produce a total response factor for that walking frequency. Calculations are carried out for several walking frequencies, to identify the maximum response factor. As aforementioned, GSA uses empirically determined footfall loads. The impulse loads are related to the walking frequency and the natural frequency of the structure. As with harmonic footfall excitation, the response is weighted by the mode shape at both the excitation and response points. The RMS response across all the modes is sued, and normalized by the velocity at the base curve to calculate a response factor. 4.2 Finite Element Model of the Existing Facility The structural configuration measured in Area B was modelled in GSA, in order to validate the accuracy of GSA and the Concrete Centre footfall methodology. An image of the finite element model (excluding the slab plate elements) is presented in Figure 2, with a contour of the footfall response factor over the slab presented in Figure 3. The maximum calculated response factor was within 25% of the measured value. This level of error was considered suitable for preliminary design and costing purposes. Figure 2 FE model of existing facility (plate elements not shown) Inter-noise 2014 Page 5 of 9

Page 6 of 9 Inter-noise 2014 5. APPLICATION TO DESIGN Figure 3 Footfall response of existing facility 5.1 Study and Costing of Proposed Structures The objective of the survey and FE modelling was to provide design and costing advice for the proposed facility at a very early stage. To aid in this process, a number of structural configurations were proposed to the client, each meeting a different ASHRAE Vibration Criterion. These benchmark structures had a different span than found on the existing building, as such the structural design had to be modelled. A live load of 15 kpa was applied to the entire slab face, representing the weight of manufacturing equipment. This live load was advised in the project brief. A typical FE model of the benchmark structures (excluding the slab) is shown in Figure 4. The benchmark structures included 3 beams, B3 (red), B2 (yellow) and B1 (purple). The mode shape (including plate elements) with the highest mass participation and the footfall response for the below structure are shown in Figure 5 and Figure 6 respectively. The structural configuration of each Vibration Criterion design is presented in Table 5. Figure 4 FE model of typical structure (plate elements not shown) Page 6 of 9 Inter-noise 2014

Inter-noise 2014 Page 7 of 9 Figure 5 Typical mode shape (highest mass participation) Figure 6 Footfall response of typical structure Inter-noise 2014 Page 7 of 9

Page 8 of 9 Inter-noise 2014 Table 5 Structural configurations for ASHRAE VC (note that beam depths given are measured from the top of the slab) Model Span, Slab B3, B3 B2, B2 B1, B1 Column, m thickness, VC-A 175 600 x 1,000 VC-B 300 3,000 9 x 12 600 x 1,200 1,200 VC-C 600 x 1,550 350 VC-D 600 x 1,850 1,500 250 x 450 250 x 1,175 4,000 600 x 1,400 From the FE model, preliminary costing of each structural configuration was calculated as presented in Table 6. Table 6 Estimated cost of ASHRAE VC compliant structures Vibration Criterion (9 m x 12 m span) Cost Ratio VC-A 1 VC-B 1.15 VC-C 1.33 VC-D 1.52 5.2 Final Design Based on data detailing the weight of manufacturing equipment it was recoended that the live load be revised down to 10 kpa. The design brief also changed from Structures 1 to 4 as detailed in Table 1 to VC-E for the ground floor and VC-C for all upper floors. Further FE modelling of the proposed designs was therefore necessary. The FE model of the ground floor required translational and rotational stiffness of the soil to be accounted for. Based on extensive geotechnical investigations on site detailing soil type, properties, and depth, a model of the geotechnical environment was created. This allowed for equivalent soil spring stiffness to be calculated. The properties of the soil are detailed in Table 7. As there was considerable variation in height of the sandy clay layer across the site, the soil stiffness calculations were based on the area with the thickest clay layer after the site cut. This resulted in a conservative stiffness result. Details of the final brief compliant design are provided in Table 8. Table 7 Soil properties used for geotechnical modelling Depth, m Soil Description Young s Modulus, MPa Poisson s Ratio 0 to 2.0 Compacted fill 150 0.5 2.0 to 6.0 Soft to firm sandy clay 7.5 0.5 Below 6.0 Decomposed siltstone/sandstone Considered incompressible Table 8 Final structural configuration - Model Span, Slab B3, B3 B2, B2 B1, B1 Column, m thickness, VC-C 9 x 12 300 600 x 1,125 12 600 x 1,500 3,000 250 x 1,125 4 600 x 1400 VC-E 9 x 12 300 None. Stiffness provided by ground support. Page 8 of 9 Inter-noise 2014

Inter-noise 2014 Page 9 of 9 6. CONCLUSION Using experimental and numerical methods, the strict vibration criteria for a proposed high precision manufacturing facility were achieved and costed at an early stage in the design process. A footfall survey was carried out in an existing facility of similar purpose, in order to assess the impact of various vibration sources, including vehicular movements, HVAC plant, and footfall. As footfall was determined to be the vibration source with the highest response, a separate footfall vibration survey was carried out in the existing facility. The finite element package GSA was used, with the Concrete Cnstitute footfall methodology used to assess footfall response of various structural configurations. This methodology allowed for a number of structures to be designed and costed, each meeting a certain ASHRAE Vibration Criterion. The final structural design addressed a change to the project brief, and incorporated ground stiffness obtained through geotechnical survey and modelling. ACKNOWLEDGEMENTS The authors would like to acknowledge Aurecon Thailand and particularly Thiti Ariyakul for his structural engineering support, Anh Tran of Aurecon Melbourne and Bill Dawson of Aurecon Adelaide for their finite element modelling support and Dr Peter Mitchell of Aurecon Adelaide for his geotechnical engineering expertise. REFERENCES 1. ASHRAE. HVAC Applications: Chapter 48 Sound and Vibration Control. Atlanta, USA. America Society of Heating, Refrigerating and Air-Conditioning Engineers; 2011. 2. ISO. Mechanical vibration and shock-evaluation of human exposure to whole body vibration, Part 2: Vibration in buildings. Geneva, Switzerland. International Organisation for Standardisation; 2003. 3. Murray TM, Allen DE, Ungar EE. Floor Vibrations Due to Human Activity. USA. American Institute of Steel Construction; 2003. 4. Willford MR, Young P. A Design Guide for Footfall Induced Vibration of Structures Surrey, UK. The Concrete Centre; 2006. Inter-noise 2014 Page 9 of 9