University City MO Street Lighting Study SUMMARY. Funded by the Energy Efficiency and Conservation Block Grant. Authored by.

Similar documents
NYSERDA How-to Guide to Effective Energy-Efficient Street Lighting for Planners and Engineers

How Photometric Design Enhances Energy Savings and Asset Management

GARFIELD COUNTY, COLORADO

LED Equipment Evaluation. PHASE V: 100W HPS Equivalent

POLICY TRAILS LIGHTING

Saving Money with Other White Light Sources

Street Lighting and Public Safety: New Nighttime Lighting Documentation Method

LED applications in street and interior lighting. Bryan Yang Application Design Center Asia 9 th Apr. 2010

CITY OF STRATFORD STREET LIGHTING STUDY

5-1 Street Lights Required Street Lights on Private Roadways Developer s Responsibility...5-1

LED Equipment Evaluation. PHASE V: 400W HPS Equivalent

City of Dallas Dan Koss, PE, LC 8/23/2016

EFFICIENT LIGHTING DESIGN

Seattle City Light LED Streetlight Program Case Study

ILLUMINATING NEIGHBORHOODS

How to Submit Your Question

Parking Lot 5A & Cedar Circle LED Lighting Retrofit

Create Meaningful Performance Metrics for LED Systems

The easiest switch to comfortable white light

Units. Lighting quantity is primarily expressed in three types of units.

ENERGY EFFICIENCY GUIDELINES FOR STREET LIGHTING IN THE PACIFIC

STEP-BY-STEP GUIDE. Improving Efficiency in Municipal Street and Public Space Lighting

Comparison Study between using HPS, LED and C.F Lamps in Roadway Lighting. Bahaa Medkour 1, Mohamed Mehanna 2, Mohamed Abdelmonem 3

Parking Lot 6 LED Lighting Retrofit

Energy Efficiency & Customer Research & Development Technology Brief: LED Canopy Lighting

Ivins City Standard Specifications for Design and Construction Part 2 Engineering and Design Standards

Units. Lighting quantity is primarily expressed in three types of units.

40 Watt 2X2 Troffer Mount LED Fixture - Replacement for Fluorescent Fixtures - 2' x 2' -3,500 Lumens

15-06 Morlot Avenue, Fair Lawn, NJ USA Tel: (201) Fax: (201)

50 Watt Low Bay LED Light Fixture - Outdoor Rated - IP67-4,333 Lumens

Chapter 1: The Benefits of Converting to LED Street Lights in the Mid- Hudson Region

IV ENGINEERING OF ENVIRONMENTAL ENERGY ANALYSIS OF GHG REDUCTION POSSIBILITIES IN LATVIA BY IMPLEMENTING LED STREET LIGHTING TECHNOLOGIES

STUDY OF INDUCTION TECHNOLOGY BASED NEXT GENERATION INDUSTRIAL LIGHTING SYSTEM

Chapter XXX. Outdoor Lighting Standards.

RSLPP Feasibility Study Overview

Interim Report for the Town of Falmouth

Evolution LED High Bay Flood Light Series

Transitioning to LED Lighting Technology Helps Facilities Reduce Lighting Energy Consumption and Costs

Evolution LED Wall Pack Series

LED STREETLIGHT INFORMATION FREQUENTLY ASKED QUESTIONS

LED STREETLIGHT INFORMATION FREQUENTLY ASKED QUESTIONS

National Trends LED STREET LIGHTING LATEST DEVELOPMENTS 2/23/2010. LED Streetlights Why all the Hype?

Road Safety Engineering Award 2010

POLICY NUMBER: C576. August 28, 2013 City Council. Light Efficient Community Policy

ASSIST recommends: Striving for Application-specific Evaluation Methods. N. Narendran, Jean Paul Freyssinier, Yutao Zhou, and Jennifer Taylor

Units. Lighting quantity is primarily expressed in three types of units.

Converting to LED Street Lights: Getting Started

School Outdoor Lighting Audit Guide

GREEN SOLUTIONS Taking fluorescent lighting to the next evolution.

Part 11: Lighting. Contents. Tables. Part 11: Lighting. Christchurch City Council Infrastructure Design Standard 11-1

Welcome to Bright Ideas, your source for information

PRIMES. product group street lighting. Presented by

APEC SOLLIA Street and Outdoor LED Lighting Initiative - Asia Survey Findings

INFRASTRUCTURE DATA SUSTAINABILITY

Exterior and Public LED Lighting Solutions

ELIMINATING THE URBAN TWILIGHT ZONE

EXECUTIVE SUMMARY. led street lighting Case Study. Summary table: original project profile

NEPTUN HIGH

UNRIVALED. green technology. the STERNBERG advantage

Date: June 24, Subject: LED Street Light Conversion Project

APPENDIX E ARTIFICIAL LIGHTING ANALYSIS

NEPTUN HIGH BAYS BDT Product Sales & Support (951)

LIGHTING. The floodlight conforms to the DRB-approved standards for security lights in the cluster.

Class I Division 1 & 2 Explosion Proof 150 Watt High Bay LED Light Fixture 16,000 Lumens- Pendant

Designers Light Forum. Rethinking urban pedestrian lighting metrics. Susanne Seitinger, PhD Leora Radetsky March 14, 2018

Daylighting Used With Task Lighting PHOTO: NJ AGRICULTURAL EXPERIMENT STATION

Lighting Technology Today

LIGHTING. review ProceSS

Smart Cities Start with Smart Streetlighting

Bylaw 3847, 2016 Adopted Mar 21, 2016 SCHEDULE G - REGULATIONS, STANDARDS AND SPECIFICATIONS FOR THE INSTALLATION OF STREET LIGHTING

Dark Skies Rangers Program

Lighting & Controls Solutions. Ports & Rail.

Energy-efficient street lighting Experiences from Melaka, Malaysia

Application Efficacy for Comparing Energy Demand in Lighting Applications

A Lighting Audit of The University of The West Indies St Augustine Campus

B. Prismatic acrylic diffusers for fluorescent fixtures shall be A12 pattern and at least 1/8 thick. Do not use styrene lenses.

Street Lighting Retrofit Implementation Guide

CR Series Architectural LED Troffer. The New Standard in Commercial Lighting

A feasibility analysis of retrofitting existing roadway lighting infrastructure with LED technology

Purchasing Department 530 Water Street Oakland, CA ADDENDUM No. 1. Bid No /03 LED Street Light Conversion Project

Leslie (Les) Pace, CEM, CDSM, CSDP, LC, CLEP Serving K-12 since 1970

Demonstration Assessment of Light-Emitting Diode (LED) Roadway Lighting on Residential and Commercial Streets

STREET LIGHTING SERVICE SCHEDULE SLR-45 (RESIDENTIAL SUBDIVISIONS)

Emerging Technologies Study Lifecycle:

Demonstration Assessment of LED Roadway Lighting

EXHIBIT "A" SCOPE OF SERVICES FOR DISTRICT 7 AREAWIDE LIGHTING DATABASE & ASSESSMENT CONTINUING SERVICES FINANCIAL PROJECT NO.

Overview. Sample Data Verification and Analysis Lighting in General Literature Review (Benchmarking) Recommendations Next Steps

Nadarajah Narendran, Ph.D. Jean Paul Freyssinier, i M.S. Lighting Research Center Rensselaer Polytechnic Institute Troy, New York 12180, U.S.A.

LED Lighting and Retrofit Design

Urban Planning and Land Use

Lighting Commercial Spaces 101. An Introduction to LED and Lighting Controls

The Up and Down of Outdoor Lighting. Michele McColgan Ph. D. Lighting Research Center Rensselaer Polytechnic Institute

IDA-Criteria for Community-Friendly Outdoor Sports Lighting v1.0

Commercial Lighting Renovation Guide

Chapter Sign Code

Welcome to Bright Ideas, your source for information

MASSACHUSETTS ELECTRIC COMPANY STREET AND AREA LIGHTING COMPANY OWNED EQUIPMENT S-1 RETAIL DELIVERY SERVICE

Introduction to LED Lighting

8.6 EXTERIOR LIGHTING

Light Pollution - What Is It?

Transcription:

University City MO Street Lighting Study SUMMARY Funded by the Energy Efficiency and Conservation Block Grant Authored by Jennifer Wendt April 2011

Table of Contents 1. INTRODUCTION... 4 2. DATA RESULTS... 5 2.1. Ameren Inventory... 5 Street Light Types... 5 Bulb Types... 7 2.2. Inventory According to Current Policy: Overages/Shortages... 8 3. ENERGY/COST SAVING OPTIONS... 8 4. STREET LIGHT POLICY... 12 4.1. Street Light Policy Formative Factors... 12 4.2. University City Street Light Policy... 12 4.3. Suggested New University City Policy... 12 5. AMEREN 5M BILL: PROPOSED CHANGES RESULTING FROM RATE CASE... 14 Page 2

Table 1: Summary of Energy/Cost Savings... 10 Table 2: Summary of Energy/Cost Savings acquisition of Ameren Lights Only... 11 Table 3: 5M Rate vs. 6M Rate... 11 Table 4 Comparison of Current Bill With proposed Ameren bill... 14 Page 3

STREET LIGHT STUDY 1. INTRODUCTION Street lighting can have many purposes; but most importantly it is an effective tool in helping provide a safer night driving environment. Numerous before and after nighttime crash studies have shown that roadway lighting helps prevent accidents and that the benefits far exceed the cost. It should be remembered that typically street lighting is to assist the motorist during nighttime driving and any additional area being illuminated is of secondary benefit. The amount of street light preferred by residents can vary greatly. Some neighborhoods feel safe and semirural, and illumination would only serve to annoy residents unless it is imperative for driver safety. Even then, specific drop-offs or other roadside hazards might better be highlighted through use of simple reflectors rather than an elaborate street lighting program. In other cases, residents prefer having the entire neighborhood illuminated. Often in areas that seem more crime-prone, residents want more and more lighting. In fact, uniformity is much more important than brightness. The high light level can cause glare, whereas a consistent but lesser amount of light increases perception of safety. Also the distribution of light on the surface of buildings can increase perception of safety in business districts. Research isn't definitive on whether very high levels of street lighting actually deter crime, one can find results to support either argument. Currently University City pays approximately $650,000 annually in street light costs. These street lights account for over 2,400,000 kilowatt hours (kwh) of electricity per year. This equates to approximately 2000 metric tons of CO 2 emissions per year (Grow, 2008), driving approximately 1400 cars per year, and using 62,000 gallons of oil per year. This street lighting study was performed for three main reasons; first to inventory all of the street lights located in University City, second to provide energy/cost saving options associated with providing street lighting, and third to develop a new street light policy for today-to better reflect the state of the art of new lighting understanding, technology and energy efficiency. Page 4

2. DATA RESULTS 2.1. AMEREN INVENTORY Street Light Types There are 8 different types of light fixtures which make up 2 main groups: Cobra: 2479 cobra lights were located making up 74% of all Ameren owned street lights. There are 4 different types of Ameren owned cobra lights currently in use in University City. Cobra can include Horizontal Semi Cutoff and Horizontal Cutoff. Floodlights and Open Bottom Nema Head Fixture types are listed here for simplicity reasons. On average these lights are 25 30 feet tall. Semi Cut-Off The majority of Cobra light Fixtures are Semi Cutoff which account for 2326 of all cobra lights. The bulbs currently used in Semi Cut-off lights are either 175 or 400 Watt Mercury Vapor (MV); or 100, 250, or 400 Watt High Pressure Sodium (HPS). Cut-Off The Cut-off style light fixtures account for 125 of all cobra light fixtures. The bulbs currently used in Cut-off lights are either 175 Watt Mercury Vapor (MV); or 100 or 250Watt High Pressure Sodium (HPS). Open Bottom The Open Bottom light fixture accounts for 26 of all cobra lights. The bulbs currently used in Open Bottom lights are either 175 Watt Mercury Vapor (MV) or 100 Watt High Pressure Sodium (HPS). Flood Flood light fixtures account for only 2 of all Cobra lights. Only 400 Watt Metal Halide (MH) bulbs are currently used in Flood Lights. Page 5

Post Top: 857 post top lights were located making up 26% of all Ameren owned street lights. There are 4 different types of Ameren owned post top lights currently in use in University City. Post Top includes Colonial, Early American, Contemporary, and Aspen Post Top Fixtures. On average Post Top style lights are 14 16 feet tall. Early American Early American light fixtures account for 316 of all post top light fixtures. The bulbs used currently are either 100 or 175 Watt MV or 100 Watt HPS. Colonial Colonial light fixtures account for 294 of all post top light fixtures. The bulbs used currently are either 175 Watt MV or 100 Watt HPS. Contemporary Contemporary light fixtures account for 246 of all post top light fixtures. The bulbs used can be MV or HPS. The bulbs used currently are either 175 Watt MV or 100 Watt HPS. Aspen Aspen light fixtures account for 1 of all post top light fixtures. The bulb used currently is a 100 Watt HPS. Page 6

Bulb Types Ameren owned street lights are furnished with one of three different bulb types; High Pressure Sodium (HPS), Mercury Vapor (MV), or Metal Halide (MH). The factors used to compare energy efficiency are photopic and scotopic luminous efficacy, S/P Ratio, Color Rendering Index (CRI) and bulb lifetime. These are defined as follows: Photopic luminous efficacy: A measure of how well a light source produces visible light, photopic referring to bright conditions. It is measured in lumens (light output) per watt (power consumed by the source). Scotopic luminous efficacy: A measure of how well a light source produces visible light, scotopic referring to dim conditions. It is measured in lumens (light output) per watt (power consumed by the source). S/P Ratio: The ratio of scotopic light versus photopic light in a light source. (For more information on photopic and scotopic ranges, see section 5.4) Color Rendering Index (CRI): A measure of the light quality of a light source as compared with sunlight (which is given the maximum CRI value of 100). The closer a light-source's CRI is to 100, the better its ability to show true colors. High Pressure Sodium (HPS) HPS bulbs are the main type of bulbs used. 100, 250, and 400 watt bulbs are used, which produce 9500, 25,500 and 50,000 lumens respectively. 2589* of all street lights are HPS. Mercury Vapor (MV) There are still MV bulbs used although they are being phased out. 175 and 400 watt bulbs are used, which produce 6800 and 20,000 lumens, respectively. 745* of all street lights are still MV. Metal Halide (MH) MH bulbs are only used in flood lights. 400 watt bulbs are used, which produce 34,000 lumens. There are 2 MH flood lights. *Totals do not include 3 unknown bulb types HPS Energy Efficiency Photopic luminous efficacy: 80 150 lm/w Scotopic luminous efficacy: 30 60 lm/w S/P Ratio: 0.62 Bulb Lifetime: 24,000 hours or more CRI: 22 HPS have been the most cost/energy efficient bulbs for use in street lighting in recent years. (NYSERDA, 2002) (LGE Lighting, 2011) (Westside Solutions, 2011) MV Energy Efficiency Photopic luminous efficacy: 25 60 lm/w Scotopic luminous efficacy: N/A S/P Ratio: 0.80 Bulb Lifetime: 24,000 hours or more; however, light can diminish significantly after 12,000 hours. CRI: 15 MV lamps are continuously being replaced with HPS. (NYSERDA, 2002) (Westside Solutions, 2011) MH Energy Efficiency Photopic luminous efficacy: 60 110 lm/w Scotopic luminous efficacy of 80 150 lm/w S/P Ratio: 1.49 Bulb Lifetime: 10,000 hours or less CRI: 65 or higher Current development in MH lamps has shown promise for improving lumen maintenance and lamp life; some models are beginning to approach HPS in luminous efficacy and lifetime. (NYSERDA, 2002) (LGE Lighting, 2011) (Westside Solutions, 2011) Page 7

2.2. INVENTORY ACCORDING TO CURRENT POLICY: OVERAGES/SHORTAGES There are 446 lights which are located on streets that are in excess of the current street light policy. (These 446 lights are proposed for decommissioning in Energy/Cost Saving option).these 446 lights are broken down as such: Cobra Post Top Public Private 341 105 373 73 There are 140 areas where additional lighting may be needed to meet the current street light policy. Some of these are areas where city owned historical lights are located and additional lights are not wanted for aesthetic reasons. Some of these areas have an Ameren owned/privately paid for Z light splitting the distance as to meet policy requirements. Decisions need to be made to determine if these areas need additional lighting. There are 14 intersections which do not have a light located directly at the intersections. These areas may be lit by lights located adjacent to the intersection. Decisions need to be made to determine if these areas need additional lighting. 3. ENERGY/COST SAVING OPTIONS Street lighting consumes a great deal of energy. The energy consumption per year of the street lights located in University City is approximately 2.5 million kilowatt hours. This is the same as running 1400 cars on the road. It equals approximately 2000 tons of CO 2 and approximately 62,000 gallons of oil per year. Therefore, a change in energy use is warranted. CITY OWNED LIGHTS University City owned street lights are generally energy efficient and cost effective. Research on retrofitting can be done, particularly for the cobra lights located in The Loop parking lot and at Pershing/Forest Park Parkway. Currently University City is retrofitting pedestrian lights along Olive. Where there are currently a double fixture light with two 100 watt HPS lamps, there will be a single fixture with one 70 watt HPS lamp. This will reduce the energy consumption for these 121 lights by 59%. There are also changes slated for proposal on the lights located around City Hall, and the lights located in the parking lots behind the loop. These will be proposed through Ameren s Business Energy Efficiency Incentives. University City owned lights only account for 1% of the total lighting energy use. The Ameren owned lights, which account for the 99% of lighting energy use and costs are the lights focused on for energy reduction in this report. Page 8

AMEREN OWNED LIGHTS Many options were researched for energy and cost savings. Retrofitting the lights to LED, Induction, Ceramic Metal Halide, Metal Halide, or lower wattage HPS were explored. However, these options are currently not applicable to the Ameren owned lights. Ameren has many restrictions regarding bulb types, fixture types, etc. Options to reduce energy and costs of Ameren owned lights are very limited. Decommissioning lights and retrofitting bulbs are the main options outside of purchasing the entire Ameren lighting system. The following options for energy and cost savings associated with the Ameren owned lights are as follows: 1. RETROFIT: Retrofit bulbs which are currently MV to an equivalent HPS bulb and retrofit a portion of higher wattage HPS bulbs to lower wattage HPS bulbs. 2. DECOMMISSION (300): Decommission lights that are in excess of University City s current policy; 300 spacing between residential street lights (post top or cobra), 200 between non-residential street lights. 3. DECOMMISSION (300/200): Decommission lights that are in excess of University City s current policy (200 spacing for non-residential, 300 spacing for any lights located on residential streets), except using 200 as the maximum spacing between post top style lights due to lower height of pole equalling lower light output. 4. DECOMMISSION UNWARRANTED: Decommission lights which are no longer warranted; former alleys, private driveways, hidden by trees, etc. 5. TRANSFER PRIVATE COSTS (ALL): Transfer ALL costs of private neighbourhood lights currently paid for by University City to the private neighbourhoods in which they are located. 6. TRANSFER PRIVATE COSTS (300): Transfer only the costs of private neighbourhood lights in excess of University City s current policy, 300 spacing between lights located in private neighbourhoods. 7. TRANSFER PRIVATE COSTS (300/200): Transfer only the costs of private neighbourhood lights which are in excess of University City s current policy (300 spacing between any lights located on residential streets) but using 200 maximum spacing between lights which are post top style. 8. TRANSFER WASH U COSTS (ALL): Transfer ALL costs of lights located around Washington University owned property currently paid for by University City to Washington University. 9. TRANSFER WASH U COSTS (300): Transfer only the costs of lights located around Washington University owned properties which are in excess of University City s current policy; 300 spacing between residential street lights (post top or cobra), 200 between non-residential street lights. 10. ACQUISITION OF LIGHTS: Purchase Ameren owned Lights from Ameren. Because Ameren has not provided University City with a cost for purchasing the lights, a price was calculated and amortized based on Clayton purchasing the system in the 1980s.The Municipal League has requested the lawyers on the rate case request realistic costs from Ameren regarding purchasing the lighting systems. It is important to note that currently it is proposed for the monthly costs for Page 9

poles and other charges associated with the 5M bill are removed. It is also proposed there be a 10-22% rate increase on energy use. These changes are to be approved or denied by the Public Service Commission in August, 2011. All calculations for the acquisition of Ameren lights are based on current charges, except for an example under Acquisition of Post Top Style Lights Only. The following table summarizes the cost and energy savings of each option: TABLE 1: SUMMARY OF ENERGY/COST SAVINGS ENERGY/COST REDUCTION OPTIONS SUMMARIZED OPTION % POTENTIAL ENERGY SAVINGS POTENTIAL SAVINGS per YEAR COST ASSOCIATED PAY BACK (YEARS) RETROFIT 23 $19,074 $106,600 5.6 DECOMMISSION (300) 14 $60,339 $44,700 0.7 DECOMMISSION (300/200) 12 $44,775 $36,200 0.8* DECOMMISSION UNWARRANTED 1 $4,210 $3,200 0.8* TRANSFER PRIVATE COSTS (ALL) 0 $68,495 $0 N/A TRANSFER PRIVATE COSTS (300) 0 $14,319 $0 N/A TRANSFER PRIVATE COSTS (300/200) 0 $6,491 $0 N/A TRANSFER WASH U (ALL) 0 $14,485 $0 N/A TRANSFER WASH U (300) 0 $5,284 $0 N/A ACQUISITION OF AMEREN LIGHTS Immeasurable Ranges from $50K to $500K Ranges from $400K to $1.6M Ranges from 1.9 to 15.4 *University City does not have a current contract with Ameren. Ameren indicated that because of this, there would be no cost associated with decommissioning lights. If University City has a current contract, the cost for each light decommissioned would be $100 each. It behooves the City to act now to decommission these fixtures. See the following table for a breakdown of the option Acquisition of Ameren Lights. Page 10

TABLE 2: SUMMARY OF ENERGY/COST SAVINGS ACQUISITION OF AMEREN LIGHTS ONLY OPTION ACQUISITION OF ALL AMEREN LIGHTS Clayton as an Example: $1,558,000 to meter the system and to purchase the lights (at $467 per light) METERED 6M Rate ACQUISITION OF ALL AMEREN LIGHTS UNMETERED 6M Energy Only Rate + Contracted Maintenance (at $280,000 per year) ACQUISITION OF ALL AMEREN LIGHTS UNMETERED 6M Energy and Maintenance Rate ACQUISITION OF AMEREN POST TOP LIGHTS ONLY UNMETERED 6M Energy Only + Contracted Maintenance (at $73,000 per year) ACQUISITION OF AMEREN POST TOP LIGHTS ONLY UNMETERED 6M Energy and Maintenance Rate at a cost of $467 per light ACQUISITION OF AMEREN POST TOP LIGHTS ONLY UNMETERED 6M Energy and Maintenance Rate at a cost of $1000 per light ACQUISITION OF AMEREN POST TOP LIGHTS ONLY UNMETERED 6M Energy Only Rate + Contracted Maintenance (at $73,000 per year) at a cost of $1000 per light ACQUISITION OF AMEREN POST TOP LIGHTS ONLY UNMETERED 6M Energy and Maintenance Rate (based on Ameren proposed 5M billing rates) at a cost of $1000 per light POTENTIAL SAVINGS per YEAR COST ASSOCIATED PAY BACK (YEARS) $260,274 $1,558,000 6 $302,457 $1,020,000 3.4 $526,738 $1,020,000 1.9 $56,394 $405,356 7.2 $114,735 $405,356 3.5 $114,735 $868,000 7.6 $56,394 $868,000 15.4 $171,692 $868,000 5.1 An agreement for the acquisition of Ameren lights must be established with Ameren. At this time Ameren has not provided adequate information regarding the purchase of their lights. The excessive cost of $1000 per light is an amount given by an Ameren representative to O'Fallon. This price is unrealistic as U City has paid pole fees for cobra lights for decades. This price is only used for the "POST TOP LIGHT ONLY" option. It is unknown if Ameren will require the lighting system to be metered for purchase. It is also important to note that it may be more cost effective to hire and employee for in house maintenance and repairs instead of contracting maintenance. TABLE 3: 5M RATE VS. 6M RATE Current 5M rate 6M rate: Metered (based on 2,410,492 kwh/year) 6M rate: Unmetered Energy Only 6M rate: Unmetered Energy and Maintenance Lighting only per month: $37,770 Energy only per month: $7,010 Energy only per month: $6,760 Energy only per month: $11,421 additional monthly charges: $17,552 additional monthly charges: $5.17 per meter (100 meters) additional monthly charges: $5.17 per account additional monthly charges: $5.17 per account Approximate Total per year including addn charges: $663,857 Approximate Total per year: $84,277 Approximate Total per year: $81,176 Approximate Total per year: $137,119 FULL Maintenance Included Maintenance NOT Included Maintenance NOT Included Partial Maintenance Included Page 11

4. STREET LIGHT POLICY 4.1. STREET LIGHT POLICY FORMATIVE FACTORS There are many different factors that can determine where a street light is placed. Many of these factors listed are specific to certain areas and not specific to others. Therefore, these factors are important in final decisions of street light placement but cannot be individualized in a general street light policy. These factors are as follows: Roadway Classification Pedestrian Traffic Light Loss Scotopic, Mesopic, and Photopic Ranges Lighting Configuration Lateral Light Distributions Fixture Type Mounting Height Bulb Type Lumen Output Light Pollution: Sky Glow/Light Trespass/Glare For details of each policy formative factor, please request the full report. 4.2. UNIVERSITY CITY STREET LIGHT POLICY The current University City street light policy for placement and lumen output is as follows: Residential: Minimum 9500 lumens 300 maximum distance between lights Light at intersections Non-residential: Minimum 25,500 lumens 200 maximum distance between lights 4.3. SUGGESTED NEW UNIVERSITY CITY POLICY STREET LIGHTING STANDARDS (UPGRADES/NEW INSTALLATION) The Street light policy is a guideline document for the public and staff outlining the streetlight level-ofservice that is intended for different parts of the City and how that service will be delivered throughout the Page 12

City. It is a standard that the public and staff can fall back upon when requests are made for the installation or removal of street lights or when questions arise about the management and costs associated with street lighting. Lighting levels for roadway street lighting are aimed at promoting efficient traffic movement, assisting in areas of high pedestrian nighttime activity, reducing light pollution, and supporting energy conservation. Street light standards are based on Illuminating Engineering Society of North America (IES) recommendations. Although IES standards are desirable to attain for roadways with high traffic volumes, these recommended standards do not easily translate to residential roadway applications where promoting traffic flow and speed are not the primary concerns. Roadways are broken down into three main classifications; Major, Collector, Local. Generally Collector and Local fall into the category of Residential, and Major falls into the category of Non-Residential. RESIDENTIAL LIGHTING STANDARDS: Street light standards for residential districts include: o Each fixture should be a Post Top or Cobra style and have a bulb installed with a maximum *9,500 initial lumen output (or photometric illuminance equivalent) with a minimum output of 120 lumens per watt. In addition new fixtures should have a scotopic/photopic ration of at least 1.3. o o Each street should have lights installed at a maximum spacing of 300 feet (with the intent that the street lights are at most 300 feet apart).each street should have a light at each intersection and at low visibility curves in roadways. Each street may have other lights in the middle or other sections of the block, in a staggered or single-sided fashion. *Except when a higher or lower lumen output may be acceptable where determined necessary by the Director of Public Works. NON-RESIDENTIAL LIGHTING STANDARDS: Street light standards for non-residential districts include: o o Fixtures at intersections should have a minimum *25,500 initial lumen output (or photometric illuminance equivalent) with a minimum output of 120 lumens per watt. In addition new fixtures should have a scotopic/photopic ration of at least 1.3. Non-intersection fixtures should have a minimum of * 9,500 lumens output. Page 13

o o o Each fixture should generally have a maximum spacing of 200 feet where levels of traffic validate these guidelines (with the intent that each light at most 200 feet apart). A light should be located at a low visibility curve in a roadway. Each street should have a light on opposite corners of an intersection. In the case of a residential/non-residential intersection, the non-residential guidelines shall prevail. *Except when a higher or lower lumen output may be acceptable where determined necessary by the Director of Public Works. 5. AMEREN 5M BILL: PROPOSED CHANGES RESULTING FROM RATE CASE The results of a recent rate case have granted the municipalities the removal of additional charges for poles, wiring, and span. However, a rate increase of 22% will be put in place. This change is scheduled to occur August 2011. This will result in a reduction in the Ameren Bill. This is an example of the October 2010 bill with the changes that are scheduled to be made. TABLE 4 COMPARISON OF CURRENT BILL WITH PROPOSED AMEREN BILL QUANTITY LUMENS BULB WATTS FIXTURE Current Current Proposed Proposed RATE ($) AMOUNT RATE ($) AMOUNT 2 34000 MH 400 DIRECT 15.75 31.5 19.25 38.5 26 50000 HPS 400 ENCLOSED 22.12 575.12 27.03 702.78 100 20000 MV 400 ENCLOSED 12.41 1241 15.17 1517 435 6800 MV 175 ENCLOSED 8.59 3736.65 10.5 4567.5 551 25500 HPS 250 ENCLOSED 12.41 6837.91 15.17 8358.67 1337 9500 HPS 100 ENCLOSED 8.59 11484.83 10.5 14038.5 6 6800 MV 175 OPEN BOTTOM 7.6 45.6 9.29 55.74 20 9500 HPS 100 OPEN BOTTOM 7.6 152 9.29 185.8 2 3300 MV 100 POST TOP 15.04 30.08 18.38 36.76 199 6800 MV 175 POST TOP 15.91 3166.09 19.44 3868.56 658 9500 HPS 100 POST TOP 15.91 10468.78 19.44 12791.52 proposed current total Energy only cost: $37,769.56 rate increase cost: 3336 lights cost: 46161.33 Additional charges (using Oct. 2010 bill as basis): + $17,551.85 + $0.00 Current total monthly 5M bill: $55,321.41 Increased Rate monthly bill: $46,161.33 Current yearly street light charges: $663,856.92 Proposed yearly street light charges: $553,935.96 Page 14

Page 15