URSA MINERAL WOOL URSA Cavity Batts

Similar documents
URSA Cavity Batts URSA GLASSWOOL.

URSA MINERAL WOOL URSA Timber Frame Roll & URSA Timber Frame Slab

URSA TF Roll URSA GLASSWOOL.

URSA MINERAL WOOL URSA Façade N32 & Façade N35

URSA MINERAL WOOL URSA Timber Frame Roll & URSA Timber Frame Slab

URSA MINERAL WOOL URSA 10 & URSA 20 DIVERSO Loft Roll

URSA MINERAL WOOL URSA HOMETEC Cladding Roll

URSA MINERAL WOOL URSA Acoustic Roll

URSA GLASSWOOL URSA 10 Loft Roll

URSA ACOUSTIC ROLL URSA GLASSWOOL.

URSA 10 Loft Roll Insulation for Cold Pitched Roofs

URSA 20 Plus and URSA 20

URSA Acoustic Roll Acoustic Insulation for Floors and Walls

APPROVALS. Jabwall has been approved for this application since 1979, and was the first partial-fill insulation product to gain BBA approval.

URSA PARTIAL AND FULL FILL CAVITY WALL INSULATION URSA CAVITY BATT 32 INSULATION

HP Partial Fill. Robust, long-lasting protection

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade)

ROCKWOOL BUILT IN CAVITY WALL INSULATION BATTS ROCKWOOL CAVITY WALL BATT

PlyLok. Product Guide PIR and Plywood Laminate Insulation for Warm Flat Roofs.

Owens-Corning Building Products (UK) Ltd P O Box 10 St Helens Merseyside WA10 3NS Tel: Fax:

Jabfill High Performance (HP)

Product. Regulations. Rockwool Ltd Pencoed Bridgend CF35 6NY Tel: Fax: Agrément Certificate No 93/2884 Second issue*

ROCKWOOL BUILT IN CAVITY WALL INSULATION BATTS ROCKWOOL CAVITY WALL BATT

ISOVER CAVITY WALL INSULATION CWS 36, CWS 34 AND CWS 32 FULL FILL CAVITY WALL SLABS

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade)

Superior Performance Phenolic Insulation. SR/CW Insulation for Partial Fill Cavity Walls. Walls AS LOW AS 10/4803

June Residential New Build Timber Frame Walls

Superior Performance Phenolic Insulation. SR/FB Insulation for Steel and Timber Frame. Walls AS LOW AS 10/4803

Superior Performance Phenolic Insulation. SR/FB Insulation for Steel and Timber Frame. Walls AS LOW AS 10/4803

Eco-Versal. insulation. Polyisocyanurate (PIR) foam core with aluminium foil composite to both sides BASELINE TOPLINE SLIMLINE

Agrément Certificate 18/5560 website: Products Sheet 1

ROCKSILK DRITHERM CAVITY SLAB Isolation de murs à double paroi Kerndämmung. Regulations B3(4) C2(a)(b) L1(a)(i) L2(a)

Eurothane EuroDeck. Product Guide PIR insulation for Warm Flat Roofs.

Best Prac ce Guide No. 2. (Version 1 April 2015) Design and Installa on guidelines for par al fill cavity wall boards

Superior Performance PIR Insulation. XO/FB Insulaton for Steel & Timber Frame. Walls 12/4956

Superior Performance PIR Insulation XO/FB. Insulaton for Steel & Timber Frame. Walls 12/4956

PowerDeck F. PIR insulation for Warm Flat Roofs. Product Guide

A Handbook of thermal bridging details incorporating aircrete blocks

TW50. Insulation STANDARD DETAILS FOR 50 MM INSULATION BOARD IN A 100 MM CAVITY. Low Energy Low Carbon Buildings. Wall lining. Inner leaf blockwork

Floors Walls Roofs. Jabfill Premium. APPLICATION: Full-fill Cavity Wall Insulation PRODUCTS: Vencel Resil Limited

PIR Insulation XT/CW (T&G) Insulation for Partial Fill Cavity Walls. Walls 08/ /0183

A Handbook of thermal bridging details incorporating aircrete blocks

Rockwool Ltd Pencoed Bridgend Mid Glamorgan CF35 6NY Tel: Fax:

Multi-layer Insulation Blanket for Walls

Multi-layer Insulation Blanket for

Agrément Certificate 89/2231 website: Product Sheet 2

Light steel frame walls

Concrete Soffit Direct Fix

Wall lining Inner leaf blockwork. K106 Cavity Board. Flexible sealant STANDARD DETAILS FOR 115 MM INSULATION BOARD IN A 125 MM CAVITY

Superior Performance Phenolic Insulation SR/UF. Insulation for Ground Supported and Suspended Floors. Floors AS LOW AS 10/4803

XTRATHERM SAFE-R INSULATION XTRATHERM SAFE-R PARTIAL FILL CAVITY BOARD

Agrément Certificate 16/5343 website: Product Sheet 2

CELOTEX INSULATION CELOTEX CF5000 PIR INSULATION FOR FULL FILL CAVITY WALLS

Thermal Laminate Board.

KINGSPAN KOOLTHERM RANGE FOR FLOORS, WALLS AND PITCHED ROOFS KOOLTHERM K8

KOOLTHERM K8 CAVITY BOARD Isolant pour murs creux Kerndämmung

PIR Insulation. XT/UF Insulation for Ground Supported and Suspended Floors. Floors 08/ /0183

PRODUCT SHEET 1 SUNDOLITT EPS CAVITY WALL BOARDS

KNAUF INSULATION EARTHWOOL DRITHERM CAVITY SLAB

SURECAV CAVITY WALL SYSTEM SURECAV CAVITY WALL SPACER SYSTEM

Agrément Certificate 95/3212 website: Product Sheet 1

An introduction to Part L U-values

RECTICEL INSULATION. Date of Second issue: 11 September 2013 John Albon Head of Approvals Claire Curtis-Thomas

PIR Insulation XT/TL-MF. Insulation for Drylining Walls (Mechanically Fixed) Walls 04/ /0183

PRODUCT SHEET 1 CROWN DRITHERM CAVITY SLAB

Multi-layer Insulation Blanket for Walls

ECOTHERM ECO RANGE FOR FLOORS, WALLS AND PITCHED ROOFS ECOTHERM ECO-CAVITY

ALREFLEX RANGE OF CAVITY WALL INSULATION AND CAVITY RAIN BARRIERS ALREFLEX 1L-1 AND ALREFLEX 1L-1 SUPER R CLASS 0

KINGSPAN THERMAWALL TW50 ZERO ODP Isolant en polyurethanne pour murs creux Kerndämmung. Regulations. Certificate.

RECTICEL INSULATION RECTICEL EUROWALL +

PIR Insulation XT/TF. Insulation for Timber Framed Walls. Walls 08/ /0183

BALLYTHERM PARTIAL FILL CAVITY WALL INSULATION BALLYTHERM BTCW CAVITY WALL INSULATION

ALREFLEX RANGE OF CAVITY WALL INSULATION AND CAVITY RAIN BARRIERS ALREFLEX 2L-2, ALREFLEX 2L-1 AND ALREFLEX 2L-2 SUPER R CLASS 0

Superglass Superwall Cavity Wall Batts Installation Guide - Full-Fill

Superior Performance Phenolic Insulation SR/PR. Insulation for Pitched Roofs. Roofs AS LOW AS 10/4803

SWIP SOLID WALL INTERNAL WALL INSULATION SYSTEM

JABLITE FULL FILL CAVITY WALL INSULATION JABFILL - HIGH PERFORMANCE (HP)

Regulation: 10 Fitness of materials Standard: B2.1 Selection and use of materials and components Comment:

Multi-layer Insulation Blanket for Walls

June Non - Residential New Build Masonry cavity walls

InstaFibre Ltd Insta House, Ivanhoe Road Hogwood Business Park Finchampstead, Wokingham Berks RG40 4PZ Tel: Fax:

PRODUCT SHEET 1 ECOTHERM CAVITY WALL BOARD

wall TW50 zero ODP PARTIAL FILL CAVITY WALL INSULATION For more information on Kingspan Insulation visit

June Residential Refurbishment Separating walls

ALUMINIUM FOIL BUBBLE INSULATION AIRTEC DOUBLE DOUBLE BUBBLE CAVITY WALL INSULATION

Agrément Certificate 10/4803 website: Product Sheet 2

PIR Insulation. XT/PR Insulation for Pitched Roofs. Roofs 08/ /0183

August 2008: Issue 1. Non - Residential New Build Masonry Cavity Walls

Xtratherm Thin-R Underfloor Board (XT/UF Grade)

Multi-layer Insulation Blanket for Walls

JABLITE FULL-FILL CAVITY WALL INSULATION JABFILL PREMIUM

CELOTEX INSULATION CELOTEX CW4000 AND CG4000 PIR INSULATION FOR CAVITY WALLS

Isolation de murs à double paroi Kerndämmung. Regulations. Certificate.

Cavity closers, fire & acoustic stops Thermo-loc standard cavity closers Thermo-loc plus X and plus C cavity closers Thermo-loc

SAINT-GOBAIN ISOVER CAVITY WALL INSULATION WALLTHERM(2) CAVITY WALL INSULATION

RW SEMI-RIGID AND RIGID SLABS (RWA45, RW3, RW4, RW5 & RW6)

June Residential Refurbishment Masonry cavity walls

Superior Performance Phenolic Insulation SR/TB. Insulation for Drylining Walls Fixed with Adhesive Dabs. Walls AS LOW AS

InstaFibre Ltd Insta House, Ivanhoe Road Hogwood Business Park Finchampstead, Wokingham Berks RG40 4PZ Tel: Fax:

K8 Cavity Board. Insulation PARTIAL FILL CAVITY WALL INSULATION P E R F O R M A N C E BBA BRITISH

Transcription:

s 073_Layout 1 02/10/2017 10:18 Page 1 UK LTD Crest House 102-104 Church Road Teddington, Middlesex TW11 8PY United Kingdom Tel : 020 8977 96 97 Fax : 020 8977 94 56 Web : www.ursa-uk.co.uk E-mail : ursauk@ursa.com MINERAL WOOL s Insulation for Masonry Cavity Walls BROUK-0026-09/17

s 073_Layout 1 02/10/2017 10:18 Page 3 The Company As a leading supplier of insulation and insulating systems, has succeeded in fully addressing user requirements for thermal and acoustic insulation. Quality products for every application and excellent customer support are the cornerstones of the corporate culture. is the number two manufacturer of glass wool and extruded polystyrene products in Europe. At 13 production sites, has 2,000 employees generating sales revenues of over 500 million. mineral wool is manufactured in Spain, France and Belgium, at two sites has in Germany, in Slovenia, Hungary and Poland as well as in two Russian plants. Our closely-woven network of sales offices stretches across Europe and Russia. Almost everywhere is amongst the market leaders. In Russia and in a number of other Eastern European countries, we are number one in the glasswool segment. We have also enjoyed a strong position particularly on the growth markets of the new EU partner countries from the very beginning. Cavity Batts is a lightweight, semi rigid glass mineral wool slab treated with silicon based water repellent. It is suitable for use in both fully and partially filled masonry cavity walls up to 25m high. 32 has a thermal conductivity of 0.032 W/mK and 35 has a thermal conductivity of 0.035 W/mK. Benefits Wider choice s, in a wide range of thicknesses, will assist in meeting the appropriate Building Regulation standard with any form of cavity wall construction. Quality Outstanding product quality manufactured to ISO 9001 Quality Systems. User friendly Our new generation TERRA mineral wool has a soft touch feel making it easier to handle and install whilst still maintaining its excellent mechanical properties. Environment mineral wool is manufactured from an abundant, sustainable resource and utilises at least 50% glass waste. Global warming potential s do not use chemical blowing agents and so the Global Warming Potential (GWP) arising from them is zero. Insulation savings If a lightweight block is used for the inner leaf construction it is possible to meet the Building Regulation requirement with only 100mm. Adaptable One product may be used for both full and partial fill systems. Full fill systems Minimal overall wall width and most cost effective for a given U-value. s may be used in any exposure zone in buildings up to 25m high. Partial fill systems The risk of wind driven rain penetration increases on exposed or coastal locations. The use of a residual 50mm clear cavity means s may be used in any exposure zone. British Board of Agrément approval means that in many instances only a 25mm residual cavity need be maintained. The design data in BBA Certificate 09/4624 should be carefully followed. Acoustic s have excellent sound insulation characteristics and enhance the acoustic comfort of the building. Reduced risk of condensation Walls fitted with s create evenly warm conditions so reducing the risk of condensation. Effective below DPC s may be used below the damp-proof course in order to offer a degree of edge insulation to the floor. Handling s are lightweight yet tough, resilient and easy to install. They are easily cut using a sharp knife. Durability s are rot-proof, durable and maintenance free. They are non-hygroscopic and will not slump in normal use. All of our products carry the CE Mark to show compliance with the harmonised European Standard BS EN 13162 and are quality assured to ISO 9001. 2 s 3 s

s 073_Layout 1 02/10/2017 10:18 Page 5 Design Full Fill Systems The use of high efficiency insulation has benefits when achieving high standards of insulation without a great increase in the overall wall thickness. Fully filled cavity wall systems give minimal overall wall width and are the most cost effective solution for a given U-value. The system is satisfactory for use in buildings up to 12m high between 12m and 25m extra precautions, including continuous cavity trays, are required; The maximum height of continuous cavity must not exceed 12m from ground level. Above 12m the maximum continuous cavity height should not be greater than 7m. The area to be insulated must not be an infill panel. The scheme must be assessed for its suitability for fully filling. Extra care is needed with both workmanship and site supervision. Follow the design data and information in BBA Certificate 09/4624. Figure 1 Wall/Floor Junction Insulation Below Slab DPC 150mm (min) Perimeter insulation Concrete slab VCL Floor insulation DPM Figure 4 Window Head Detail Insulated lintel Window/door frame Figure 5 Sill Detail Window/door frame Insulated cavity closer Partial Fill Systems When using a partial fill system in buildings up to 12m high a minimum residual cavity width of 25mm may be acceptable depending on the exposure zone. It is important to ensure that the 25mm residual cavity is maintained, kept clean and clear of all debris and obstructions. Above 12m the residual cavity must be 50mm minimum. To comply with NHBC Standards a 50mm residual cavity must be provided in all cases irrespective of the exposure zone. Follow the design data and information in BBA Certificate 09/4624. Figure 2 Wall/Floor Junction Insulation Above Slab DPC 150mm (min) VCL Floor insulation Figure 3 Wall/Floor Junction Timber Floor 200mm (min) Floor insulation Rainwater Penetration Above door, window and other openings the lintel should be protected by the use of a cavity tray with appropriate stopends and weep holes. Projections and discontinuities within the cavity such as changes in wall or insulation thickness or ring beams also require a cavity tray. Thermal Bridging With increasing levels of insulation it is vitally important to ensure continuity of the insulation at the junction of elements and around door and window openings. At the junction of the floor and the wall a vertical section of insulation at the floor edge, the use of lightweight insulating blocks or extended cavity insulation can all help to reduce thermal bridging. (See Figures 1, 2 & 3). Around door and window openings careful detailing of the cavity wall insulation along with the use of proprietary insulated cavity closers and insulated lintels can help to reduce thermal bridging. (See Figures 4, 5 & 6). Figure 6 Jamb Detail Insulated cavity closer Window/door frame DPM DPC Perimeter insulation 4 s 5 s

s 073_Layout 1 02/10/2017 10:18 Page 7 Design At the eaves ensure the cavity insulation extends to link with the roof insulation. In a cold pitched roof gable the cavity insulation should extend at least 300mm above the ceiling line and should be protected by the use of a cavity tray. At gable walls with warm roof construction the insulation should be continued to the underside of the roof to ensure continuity of the wall and roof insulation. (See Figures 7, 8, 9 & 10). Figure 7 Pitched Roof Eaves Detail Loft Roll Figure 8 Cold Pitched Roof Gable Detail Workmanship Studies by the BRE show that most failures of cavity insulation systems are due to poor workmanship and detailing. The following points should be carefully considered: Ensure the residual cavity is kept clean and free from mortar droppings and other debris. Clean the top edges of the s and the wall ties before installing the next row of slabs. The use of a timber cavity board is recommended to help keep this area clean. Do not push slabs down into a partially built section of cavity wall as this may dislodge mortar and bridge the cavity. Small, cut sections of slab should be installed with the face against the masonry i.e. with the fibres running vertically. Carefully cut, rather than tear, the slabs to fit around wall ties and other penetrations that cross the cavity. Fire Performance s are non-combustible. When used within a masonry cavity wall constructed in accordance with the Building Regulations and BBA Certificate 09/4624 Cavity Batts will not prejudice the fire resistance properties of the wall. Cavity barriers are not required but the cavity must be closed at the top of the wall and around any openings. Figure 9 Warm Pitched Roof Eaves Detail Breather type membrane Mastic sealant Eaves packed with mineral wool Plasterboard ceiling and air & vapour control layer Cavity Batt Figure 10 Warm Pitched Roof Gable/Verge Detail Cavity tray Roof tiles Tiling batten 300mm (min) Loft Roll Plasterboard ceiling and air & vapour control layer Verge packed with mineral wool Breather membrane Cavity Batt 6 s 7 s

s 073_Layout 1 02/10/2017 10:18 Page 9 Installation Full Fill Systems (See Figure 11) The wall may be constructed leading with either leaf. It is good practice however to construct the outer leaf first as this allows the mortar joints on the cavity face to be cleaned and to check that the mortar joints are all fully filled. The s are then installed as the wall is built. The usual procedure for construction is; 1. The leading leaf of masonry, normally the outer leaf, is built with the first row of wall ties at 600mm centres where the insulation is to begin. 2. The first row of s, cut to size if necessary, may begin below the DPC in order to offer edge insulation to the floor. 3. The inner leaf is then built, normally level with the top of the s. It is permissible to build the outer leaf one brick higher to secure the next row of slabs ensure mortar is cleaned from the cavity face. 4. Raise the leading leaf to the level of the next row of wall ties, normally at 450mm vertical centres (maximum 900mm centres horizontally). Ensure that the drip is positioned at the centre of the cavity and that the ties slope down towards the outer leaf. Excess mortar should be cleaned from this leaf before fitting the Cavity Batts onto the lower ties. 5. The inner leaf is then built to the level of the top of the slabs and the process repeated. 6. The subsequent rows of slabs should be fitted with vertical joints staggered i.e. brick bond with all joints tightly butted. Slabs with damaged edges or corners should not be used. 7. As work proceeds ensure that the top edge of the Cavity Batts is clean and free from mortar droppings. The use of a cavity batten will help to protect the slab edges as the next section is built. 8. Cut sections of slab will be required around openings or at corners. It is essential that these be cut accurately to fill the space they are intended for and are adequately secured. Do not bend the batts around external or internal corners. 9. Ensure that partially completed walls are protected from inclement weather (wind, rain and snow) and at the end of the day s work. Permitted Deviation in Cavity Width (Full Fill) (mm) Permitted Deviation (mm) 75 75-90 85 85-100 100 100-115 Figure 11 - Full Fill Inner block leaf Cavity Batt Wall tie Outer brick leaf Partial Fill Systems (See Figure 12) Generally the inner leaf is constructed ahead of the outer leaf with the s fastened to the cavity face of the inner leaf using the wall ties or clips. Wall ties with collars are required to hold the slabs in position. s are 455mm wide to fit the 450mm vertical spacing of the wall ties. The horizontal spacing may vary but should be no more than 900mm to ensure adequate retention of the slabs. Spacing of the wall ties should follow the recommendations given in BS EN 1996, Eurocode 6. To prevent rainwater penetration across the wall a minimum 25mm clear cavity must be maintained at all times. A 50mm clear cavity is inherently safer and is a requirement of NHBC Standards. The usual procedure for construction is; 1. The inner leaf is built with the first row of wall ties at 600mm centres where the insulation is to begin. 2. The first row of s, cut to size if necessary, may begin below the DPC in order to offer edge insulation to the floor. 3. Raise the leading leaf to the level of the next row of wall ties, normally at 450mm vertical centres. Excess mortar should be cleaned from the inner leaf before fitting the slabs onto the lower ties and securing with a retaining collar. 4. The next row of wall ties (and collars) is fitted at maximum 900mm centres to retain the tops of the slabs. Ensure that the drip is positioned at the centre of the residual cavity and that the ties slope down towards the outer leaf. 5. Additional ties may be required for structural stability or to ensure adequate retention of the s. 6. The outer leaf is then built to the level of the top of the slabs and the process repeated. 7. The subsequent rows of slabs should be fitted with vertical joints staggered i.e. brick bond with all joints tightly butted. Slabs with damaged edges or corners should not be used. 8. As work proceeds ensure that the top of the slabs and the residual cavity are kept clean and free from mortar droppings or other debris. The use of a cavity batten will help to protect the slab edges and keep the cavity clean as the next section is built. 9. Cut sections of slab will be required around openings or at corners. It is essential that these be cut accurately to fill the space they are intended for and are adequately secured. Do not bend the batts around external or internal corners. 10. Ensure that partially completed walls are protected from inclement weather (wind, rain and snow) and at the end of the day s work. Figure 12 - Partial Fill Inner block leaf Cavity Batt 25mm (min) cavity Wall tie with retaining collar Outer brick Leaf 125 125-140 150 150-170 8 s 9 s

s 073_Layout 1 02/10/2017 10:18 Page 11 Heat Loss Calculations The normal method of calculating U-values in floors, walls and roofs is the Combined Method (see BS EN ISO 6946) which as well as assessing the thermal bridge effect of mortar joints, timber studs etc also accounts for air gaps in the insulation and mechanical fasteners penetrating the insulation. Compliance with the Building Regulations is shown by limiting the overall CO 2 emissions from the building this gives considerable design flexibility but there are no specific U-values, except the worst allowable, that must be achieved. In new build a U-value of 0.22 W/m 2 K or better will help ensure compliance. In extensions a U-value of 0.28 W/m 2 K is required and in refurbishment work 0.30 W/m 2 K is required. The Building Regulations (Scotland) require a U-value of 0.22 W/m 2 K or better. The Building Regulations (Wales) require a U-value better than 0.21 W/m 2 K in new dwellings. 32 Full Fill Typical Construction, Full Fill; 103mm brick 32 (0.032 W/mK). 100mm block (density and thermal properties as shown). 12.5mm plasterboard on dabs and skim. Wall ties with a thermal conductivity of 17.0 W/mK and cross sectional area of 12.5mm 2. 32 Partial Fill Typical Construction, Partial Fill; 103mm brick 25mm (minimum) clear cavity. 32 (0.032 W/mK). 100mm block (density and thermal properties as shown). 12.5mm plasterboard on dabs and skim. Wall ties with a thermal conductivity of 17.0 W/mK and cross sectional area of 12.5mm 2. Block Density Block λ-value U-Value (W/m 2 K) (kg/m 3 ) (W/mK) 75mm 85mm 100mm 125mm 150mm 450 0.11 0.28 0.26 0.23 0.19 0.17 600 0.15 0.29 0.27 0.24 0.20 0.17 800 0.19 0.30 0.28 0.24 0.21 0.18 1000 0.34 0.32 0.29 0.26 0.21 0.18 1200 0.44 0.33 0.30 0.26 0.22 0.18 1400 0.57 0.33 0.30 0.26 0.22 0.19 1600 0.99 0.34 0.31 0.27 0.22 0.19 1800 1.13 0.34 0.31 0.27 0.22 0.19 2000 1.33 0.34 0.31 0.27 0.22 0.19 2200 1.59 0.34 0.31 0.27 0.22 0.19 2400 1.93 0.34 0.31 0.27 0.22 0.19 Block Density Block λ-value U-Value (W/m 2 K) (kg/m 3 ) (W/mK) 75mm 85mm 100mm 125mm 150mm 450 0.11 0.27 0.25 0.22 0.19 0.16 600 0.15 0.28 0.26 0.23 0.19 0.17 800 0.19 0.29 0.26 0.23 0.20 0.17 1000 0.34 0.30 0.28 0.25 0.21 0.18 1200 0.44 0.31 0.28 0.25 0.21 0.18 1400 0.57 0.31 0.29 0.25 0.21 0.18 1600 0.99 0.32 0.29 0.26 0.21 0.18 1800 1.13 0.32 0.29 0.26 0.21 0.18 2000 1.33 0.32 0.29 0.26 0.21 0.18 2200 1.59 0.32 0.29 0.26 0.21 0.18 2400 1.93 0.32 0.29 0.26 0.22 0.18 10 s 11 s

s 073_Layout 1 02/10/2017 10:18 Page 13 Heat Loss Calculations 35 Full Fill Typical Construction, Full Fill; 103mm brick 35 (0.035 W/mK). 100mm block (density and thermal properties as shown). 12.5mm plasterboard on dabs and skim. Wall ties with a thermal conductivity of 17.0 W/mK and cross sectional area of 12.5mm 2. 35 Partial Fill Typical Construction, Partial Fill; 103mm brick 25mm (minimum) clear cavity. 35 (0.035 W/mK) 100mm block (density and thermal properties as shown) 12.5mm plasterboard on dabs and skim. Wall ties with a thermal conductivity of 17 W/mK and cross sectional area of 12.5mm 2. Block Density Block λ-value U-Value (W/m 2 K) (kg/m 3 ) (W/mK) 75mm 85mm 100mm 125mm 150mm 450 0.11 0.30 0.27 0.24 0.21 0.18 600 0.15 0.31 0.29 0.25 0.22 0.19 800 0.19 0.32 0.29 0.26 0.22 0.19 1000 0.34 0.34 0.31 0.28 0.23 0.20 1200 0.44 0.35 0.32 0.28 0.23 0.20 1400 0.57 0.36 0.32 0.28 0.24 0.20 1600 0.99 0.36 0.33 0.29 0.24 0.20 1800 1.13 0.37 0.33 0.29 0.24 0.21 2000 1.33 0.37 0.33 0.29 0.24 0.21 2200 1.59 0.37 0.33 0.29 0.24 0.21 2400 1.93 0.37 0.34 0.29 0.24 0.21 Block Density Block λ-value U-Value (W/m 2 K) (kg/m 3 ) (W/mK) 75mm 85mm 100mm 125mm 150mm 450 0.11 0.28 0.26 0.23 0.20 0.18 600 0.15 0.29 0.27 0.24 0.21 0.18 800 0.19 0.30 0.28 0.25 0.21 0.18 1000 0.34 0.32 0.30 0.26 0.22 0.19 1200 0.44 0.33 0.30 0.27 0.22 0.19 1400 0.57 0.33 0.30 0.27 0.23 0.19 1600 0.99 0.34 0.31 0.27 0.23 0.20 1800 1.13 0.34 0.31 0.28 0.23 0.20 2000 1.33 0.34 0.31 0.28 0.23 0.20 2200 1.59 0.35 0.32 0.28 0.23 0.20 2400 1.93 0.35 0.32 0.28 0.23 0.20 12 s 13 s

s 073_Layout 1 02/10/2017 10:18 Page 15 Technical Details Specification Clause Full Fill Systems The full fill cavity wall insulation shall be... mm thick 32/35, semi rigid mineral wool batt. Insulation to be installed as work proceeds in accordance with UK Ltd instructions and the requirements of BBA Certificate No. 09/4624. Partial Fill Systems The partial fill cavity wall insulation shall be... mm thick 32/35, semi rigid mineral wool batt. Insulation to be installed as work proceeds in accordance with UK Ltd instructions and the requirements of BBA Certificate No. 09/4624. Thermal Conductivity Declared thermal conductivity of 32 is 0.032 W/mK. Declared thermal conductivity of 35 is 0.035 W/mK. Declared thermal conductivity tested to BS EN 13162. Density Nominal density of 32 is 29 kg/m 3. Nominal density of 35 is 19.5 kg/m 3. Reaction to Fire Euroclass A1 to BS EN 13501-1. Moisture Vapour Transmission s have minimal resistance to the passage of water vapour thus allowing the wall to breathe. A practical value for the moisture vapour resistivity is 5 MNs/gm. Specific Heat Capacity The specific heat capacity is 0.84 kj/kgk. Designation Code MW EN 13162 T4 DS(70,-) WS. s Dimensions Thickness Length Width (mm) (mm) (mm) 75, 85, 100, 125 & 150 1200 455 Environmental Information BRE Green Guide All mineral wool products achieve the best possible A+ rating under the BRE Green Guide. Manufactured to BS EN ISO 14001. Durability When correctly installed, mineral wool products are maintenance free and have an indefinite life at least equal to that of the building. Storage mineral wool products are supplied wrapped in polythene to provide short-term protection. On site the slabs should be stored clear of the ground, on a clean level surface and preferably under cover to protect them from prolonged exposure to moisture or mechanical damage. Chemical Compatibility mineral wool products are compatible with all common construction materials, alkalis, dilute acids, mineral oil and petrol. Products that have been in contact with harsh solvents, acids or saturated with water should not be used. Health and Safety mineral wool products are inherently safe to handle. During cutting or handling any dust generated is of nuisance value only; the wearing of dust masks, gloves and long sleeved clothing is recommended. Large scale machining should be connected to a dust extraction system. A comprehensive Health and Safety data sheet is available from UK Ltd upon request. Availability s are available nationally through insulation distributors and builders merchants. References Agrément Certificate No. 09/4624. The Building Regulations and supporting documents. Thermal Insulation: avoiding risks (2002). Accredited Construction Details and Accredited Construction Details (Scotland). CIBSE Guide A3 Thermal Properties of Buildings and Components. BS EN 845 Specification for Ancillary Components for Masonry. Ties, Tension Straps, Hangers & Brackets. BS 5250 Code of Practice for Control of Condensation in Buildings. BS EN 13914 Design, Preparation and Application of External Rendering and Internal Plastering. BS EN 1996, Eurocode 6; Design of Masonry Structures. BS 8000 Workmanship on Building Sites. Part 3 Code of Practice for Masonry. BRE Digests, Information Papers and Good Building Guides. 14 s 15 s