Design & Construction Standards, Revised January

Similar documents
A. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials

D. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required.

A. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials

This Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin

SECTION MECHANICAL INSULATION

B. Refer to Section : Air Distribution for lined ductwork requirements.

FIRE STATION 55 June 14, 2010

University of Delaware

SECTION MECHANICAL INSULATION

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

SECTION HVAC INSULATION

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

SECTION MECHANICAL INSULATION. A. Types of insulation specified in this section include the following:

UBC Technical Guidelines Section Edition Thermal Insulation for Piping Page 1 of 5

HVAC INSULATION. A. General Requirements for Flexible Elastomeric Insulation: 3. Use pre-molded roll on pipe sizes 3.5" and below.

A. Section Fire Procection, HVAC & Plumbing Penetration Firestopping. B. Section Interior Painting: Painting insulation jacket.

A. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds.

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.

A. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness.

PROJ. NO SECTION HVAC DUCT INSULATION

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

State of Alaska Section State Office Building HVAC Fan Replacement MECHANICAL INSULATION

SECTION PIPING INSULATION

MECHANICAL INSULATION

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

SECTION (15081) - HVAC INSULATION

SECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

SECTION PLUMBING INSULATION

University of Houston Master Construction Specifications Insert Project Name

BuildingName The Description of the Project P DOCUMENTS

SECTION HVAC INSULATION

UBC Technical Guidelines Section Edition Insulation of Tanks, Steam and Condensate Piping Page 1 of 6

SECTION DUCT INSULATION

Division 15 INSULATION Section 15100

DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION HVAC INSULATION

INSULATION SECTION 15250

SECTION PROJECTED SCHEDULE

SECTION MECHANICAL SYSTEMS INSULATION

Addendum to Specifications

TENOCHCA HALL - PROJECT NO FAN COIL UNITS, RESTROOM AND FINISH RENOVATION

HVAC INSULATION

Revision May 2017 SECTION INSULATION SYSTEMS

.1 The following is a list of standards which may be referenced in this Section:

ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT

TENOCHCA HALL - PROJECT NO FAN COIL UNITS, RESTROOM AND FINISH RENOVATION

This specification describes the minimum requirements for industrial thermal insulation.

*************************************************************************************************************

SECTION PLUMBING PIPING SYSTEM

NCCER Progress Blvd, Alachua, Florida Tel: (888)

Addendum 1 Section THERMAL INSULATION FOR PIPING Burrow Avenue Pumping Station Upgrades Page 1 of 5

HVAC Piping Insulation FIBERGLAS Insulation. General Specification Guide SECTION

10.1 APPLICATION 1 A. HOT PIPING 1 B. ANTI SWEAT PIPING 1 C. COLD PIPING FINISHES 2

SECTION THERMAL INSULATION GENERAL THERMAL INSULATION PART RELATED DOCUMENTS

.1 Thermal insulation for insulated piping and piping accessories affected by construction and new pipe sections as indicated on drawings.

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section PIPE AND EQUIPMENT INSULATION

SECTION HVAC PIPING INSULATION

Mechanical Insulation for Refrigeration Systems

SECTION HANGERS AND SUPPORTS FOR PLUMBING

SECTION PLUMBING INSULATION

SUPERIOR CAL-SHIELDS Features & Benefits FAST

HVAC Piping Insulation- FIBERGLAS Insulation

Section Roof/Ceiling Thermal Insulation

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping

SECTION HVAC PIPING INSULATION

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION

SECTION DUCTWORK INSULATION

1 of 17. PO Box Bellevue Rd, Newark, DE V F

DUKE UNIVERSITY CONSTRUCTION STANDARDS

SECTION THERMAL INSULATION

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

SECTION PLUMBING PIPING INSULATION

SECTION HVAC PIPING INSULATION Updated 8/2018

EcoTouch Insulation with PureFiber Technology

GUIDE SPECIFICATION: DUCT LINER

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

Master Insulation Guide Specification for Mechanical Systems

CHAPTER 26 PLASTIC SECTION 2601 SECTION 2603 GENERAL FOAM PLASTIC INSULATION

GUIDE SPECIFICATION: MECHANICAL SYSTEMS

SECTION PLUMBING INSULATION

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

Knauf Data Sheet AH-DS-5E Friendly Feel. Duct Wrap. with ECOSE Technology

1. ARI 410 Standard for chilled water, hot water and steam coils. 2. ARI 430 Central Station Air Handling Units

SECTION CEMENTITIOUS WOOD FIBER DECKS

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

Recommended Design Considerations. and. Guide Specifications For. Commercial Building Insulation

SECTION HVAC AND BOILER PLANT INSULATION

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

K. All mechanical rooms shall be designed with a minimum 3-1/2 dropped floor.

INSTALLATION GUIDELINE FOR TRYMER INSULATION

Updated 6/4/2012. Table Of Contents SECTION PLUMBING INSULATION

SPECIFICATION FOR COLD INSULATION

. SECTION HANGERS AND SUPPORTS

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

PLASTIC CHAPTER 26. SECTION 2602 DEFINITIONS Definitions. The following terms are defined in Chapter

D-10 OUTLINE SPECIFICATION FOR PRE FAB Undergrd Piping System

SECTION AIR DISTRIBUTION

Transcription:

PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is to apply the principles of this section so that the University may achieve a level of quality and consistency in the design and construction of their facilities. Deviations from these guidelines must be justified through LCC analysis and submitted to the University for approval. 1.02 References: A. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials B. ASTM C533 Calcium Silicate Block and Pipe Thermal Insulation C. ASTM C534 Preformed Elastomeric Cellular Thermal Insulation D. ASTM C547 Mineral Fiber Preformed Insulation E. ASTM C552 Cellular Glass Block and Pipe Thermal Insulation F. ASTM C553 Mineral Fiber Blanket and Felt Insulation G. ASTM C612 Mineral Fiber Block and Board Thermal Insulation H. ASTM C1126 Rigid Cellular Phenolic Thermal Insulation I. ASTM C921 Standard Practice for Determining the Properties of Jacketing Materials for Thermal Insulation J. MSS SP-69 Pipe Hangers and Supports Selection and Application 1.03 Requirements: A. Provide insulation and associated accessories with flame-spread index of 25 or less, and smoke-developed index of 50 or less, as tested by ASTM E84 (NFPA 255) method. B. Provide piping and ductwork insulation thickness and thermal conductivity in conformance with the latest edition of ASHRAE 90.1. C. Provide duct and pipe insulation continuous through walls, partitions, ceiling openings and sleeves. D. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required. E. Provide a continuous, unbroken, vapor seal on all cold pipe surfaces. Guides and anchors Design & Construction Standards, Revised January 2014 23.07.00-1

secured directly to cold surfaces shall be adequately insulated and vapor sealed to prevent condensation.. Pipe Insulation shall run continuously through supports and hangers. Use high compression strength insulation section at support hanger and cover with galvanized steel shield. F. Provide aluminum jackets, 0.016 thick, for exterior pipe and equipment insulation covers. For interior piping in mechanical rooms or exposed locations, provide aluminum jackets, 0.016 thick for all piping below 6 feet above finished floor. Locate seams on bottom side of horizontal pipe. G. Jackets for Piping Insulation shall conform to requirements of ASTM C921, Type II for piping with temperatures above ambient. H. Provide insulation protection shields fabricated from galvanized steel at all pipe hangers in accordance with MSS SP-69. I. Encase pipe fittings insulation with one-piece pre-molded PVC fitting covers, fastened as per manufacturer's recommendations. J. Provide staples, bands, wires, cement, adhesives, sealers, and protective finishes as recommended by insulation manufacturer for applications indicated. K. Provide flexible reusable insulation blankets for equipment requiring access such as pumps, strainers, etc. L. Insulate valves, fittings and similar items in each piping system with equivalent thickness and composition of insulation as applied to adjoining pipe run. Install factory molded, precut units. M. For main loop chilled water piping insulation, utilize the Utilities and Energy Management specifications. The scope of this piping insulation is for the main chilled water loop through the discharge valve of the primary chilled water pumps. PART 2: PRODUCTS 2.01 Piping Insulation Materials: A. Rigid Phenolic Insulation: Shall be CFC free and meet or exceed requirements of ASTM C1126, Type III, Grade 1 to 250 F service. Provide with factory-applied jacket suitable for the installation location. B. Calcium Silicate: Shall meet or exceed the requirements of ASTM C533, Type I. Provide insulation with manufacturer s recommended jacket. C. Fiberglass Piping Insulation: Shall meet or exceed requirements of ASTM C552, Class 1, noncombustible, with factory applied white kraft foil vapor barrier unless otherwise indicated. D. Flexible Elastomeric Closed Cell: Shall meet or exceed requirements of ASTM C534, Type Design & Construction Standards, Revised January 2014 23.07.00-2

I, tubular grade. Provide finish coating. E. Cellular Glass: Shall meet or exceed requirements of ASTM C552, Type II. Provide factory cover and vapor retarder finish. 2.02 Equipment Insulation Materials: A. Mineral Fiber: Shall meet or exceed requirements of ASTM C 547, C553, Types I, II or III or C612, whichever applies. Provide with factory-applied jacket. B. Calcium Silicate: Shall meet or exceed the requirements of ASTM C533, Type I or II. Provide insulation with manufacturer s recommended jacket. C. Flexible Elastomeric Cellular: Shall meet or exceed the requirements of ASTM C534, Grade 1, Type I or II. Provide Type II with vapor retarder skin on one or both sides of insulation. D. Piping Insulation Sealing: On any cold pipe insulation, seal all joints, covering and staples completely with mastic after each section is coated and sealed to pipe with Childen CP 34 mastic or approved equivalent. 2.03 Ductwork Insulation Materials: A. Fiberglass Ductwork Insulation: 1. Fiberglass Blanket insulation with a density of 1 pound per cubic foot and thermal conductivity (k value) of 0.29 @ 75 F mean temperature. The blanket shall have a h vapor barrier facing of an aluminum foil and kraft paper lamination sandwiching a fiberglass scrim for reinforcing. 2. Rigid Fiberglass Board: Three pound per cubic foot minimum density glass fiber rigid board insulation with factory applied white foil reinforced All Service Jacket (ASJ). 3. Semi-Rigid Fiberglass Board: Three pound per cubic foot minimum density glass fiber semi-rigid board insulation with fiber perpendicular to the surface and with factory applied white foil reinforced vapor barrier jacket (ASJ). Insulation shall be equal to E.O. Woods Company Rigid-Wrap:. B. Flexible Unicellular: Flexible Unicellular insulation blanket, protected by Armaflex finish protective coating (minimum 2 coats). C. Ductwork Insulation Accessories; Provide Staples, bands, wires, tape, anchors, corner angles and similar accessories as recommended by insulation manufacturer for applications indicated. D. Ductwork Insulation Compounds: Provide cements, adhesives, coatings, sealers, protective finishes and similar compounds as recommended by insulation manufacturer for applications indicated. E. Ductwork Insulation Sealing: Insulation shall be wrapped tightly on the ductwork with all circumferential joints butted and longitudinal points overlapped a minimum of 2. Adhere insulation to metal with 4 strips of insulation bonding adhesive at 8 on center. On circumferential and longitudinal joints, the 2 flange of the facing shall be secured 9/16 Design & Construction Standards, Revised January 2014 23.07.00-3

flare door staples applied 6 on center and taped with 4 wide fiberglass tape embedded in Childers CP-34 white vapor barrier emulation and covered with Childers CP-34 or approved equivalent until the tape is completely covered. All pin penetrations or punctures in facing shall also be taped. Vapor sealing of joints is not required on hot duct application where concealed. PART 3: EXECUTION 3.01 Piping System Insulation: A. Plumbing System Omissions: Omit insulation on chrome-plated exposed piping (except for handicapped fixtures), air chambers, unions, strainers, check valves, balance cocks, flow regulators, drain lines from water coolers, drainage piping located in crawl spaces or tunnels, buried piping, fire protection piping, and pre-insulated equipment. B. HVAC Piping System Omissions: Omit insulation on hot piping within radiation enclosures or unit C. HVAC Piping System Omissions: Omit insulation on hot piping within radiation enclosures or unit cabinets; on cold piping within unit cabinets provided piping is located over drain pan; on heating piping beyond control valve, located within heated space; on condensate piping between steam trap and union; and on unions, flanges, strainers, flexible connections, and expansion joints. D. Steel piping insulated with rigid phenolic shall be coated with epoxy finish prior to insulation installation. E. Insulate piping systems per table 23.07.1 Table 23.07.1 SERVICE MATERIAL VAPOR BARRIER ChW supply/return Cellular Glass Yes Fin Water Existing wet ChW piping, tunnel ChW piping, primary ChW piping in machine rooms. Heating Hot Water supply/return (max. 250 F), Steam Condensate Low Pressure Steam (max. 250 F) Flexible Elastomeric Closed Cell Cellular Glass Mineral Fiber, Calcium Silicate Calcium Silicate Yes Yes Design & Construction Standards, Revised January 2014 23.07.00-4

Potable Cold Water, make up water. drinking water fountain drain, roof drain piping Potable Hot Water supply/return (max. 200 F) Refrigerant Suction 3.02 Equipment Insulation: Flexible Elastomeric Closed Cellor Phenolic Foam Fiberglass or Phenolic Foam Flexible Elastomeric Closed Cell Yes A. Do not insulate over nameplate or ASME stamps. Bevel and seal insulation around nameplates. B. Insulate the following equipment per Table 23.07.2: Cold refrigeration equipment not factory insulated, drip pans under chilled equipment, cold and hot water storage tanks, water softeners, duct mounted coils, cold and chilled water pumps, air handling equipment not factory insulated, expansion and air separator tanks, heat exchangers, hot water generators, and pumps handling media above 130 F, except pumps on steam condensate return units. This requirement would include condensate receivers. If there is not a flash tank upstream of the receiver, then a leaking low-pressure trap would heat the condensate receiver well above the 212 F. This temperature causes the condensate pumps to fail. Leave the condensate receivers uninsulated to help protect the pumps. Table 23.07.2 EQUIPMENT HANDLING MEDIA AT INSULATION MATERIAL THICKNESS INDICATED TEMPERATURE 1 to 34 degrees F Flexible Elastomeric Closed 1.5 inches Cell or Cellular Glass 35 to 60 degrees F Closed Cell or Cellular Glass 1.0 inches 61 to 200 degrees F Mineral Fiber Calcium Silicate 2.0 inches 2.0 inches 201 to 400 degrees F Calcium Silicate 4.0 inches 401 to 600 degrees F Calcium Silicate 6.0 inches >600 degrees F Thickness necessary to limit external insulation temperature to 120 degrees F 3.03 Duct System Insulation: A. Double-wall ductwork shall be provided where internal insulation or sound absorbing linings have been provided. B. Hot and cold interior ductwork shall be insulated with Flexible Fiberglass insulation. Provide thickness to achieve minimum R-value requirements per ASHRAE 90.1. Design & Construction Standards, Revised January 2014 23.07.00-5

C. Exterior ductwork shall be insulated with Flexible Closed-Cell Elastomeric insulation. Provide with aluminum jacketing sealed water tight. Slope insulation on top of ductwork to promote drainage. Design & Construction Standards, Revised January 2014 23.07.00-6