Strategies and Intervention tactics - FC stationary installations

Similar documents
SAFETY STRATEGY FOR THE FIRST DEPLOYMENT OF A HYDROGEN-BASED GREEN PUBLIC BUILDING IN FRANCE

Project Overview. B. L Hostis Final Dissemination Workshop, 11 December 2014

HyIndoor (Contract number ) Béatrice L Hostis Air Liquide, Paris-Saclay Research Center

Combustible Gas Issues in Nuclear Safety Panel Discussion

Consequence Modeling and PSM Wilbert Lee Senior Staff Process Risk Engineer Chevron Energy Technology Company

HyResponse (325348)

Consequence-based Safety Distances and Mitigation Measures for Gaseous Hydrogen Refueling Stations

A Risk Informed Assessment of Hydrogen Dispensing in Warehouses

BASICS OF HYDROGEN SAFETY FOR FIRST RESPONDERS. Lecture. Hazards of hydrogen use indoors

Design of a Laboratory Setup for Water Electrolysis. Joonas Koponen and Antti Kosonen

Latest Advances in Hydrogen Safety R&D

HyResponse (325348)

CHAPTER 5 FLAME & EXPLOSION

SAFETY COST OF A LARGE SCALE HYDROGEN SYSTEM FOR PHOTOVOLTAIC ENERGY REGULATION

The Fuel Cells and Hydrogen Joint Undertaking Past, Present and Future

Consequence Modeling and PSM Wilbert Lee Safety Technology Unit Chevron Energy Technology Company

STUDY ON THE HARM EFFECT OF LIQUID HYDROGEN RELEASE BY CONSEQUENCE MODELING

VCE risks at LNG export facilities

Deliverable D4.1. Elaboration of multi-level operational exercises

Fuel Cells and Hydrogen Joint Undertaking

Hydrogen Safety. Progress Made Knowledge Gaps Role of CFD. Dr. Prankul Middha

Hydrogen & Renewable Energy

STATUS, GAPS AND RECOMMENDATIONS REGARDING STANDARDISATION AND THE USE OF HYDROGEN IN SUSTAINABLE BUILDINGS

SCALING PEM ELECTROLYSIS TO 100MW HANNOVER MESSE APRIL 2017 SIMON BOURNE CTO

SG06UNINC-Series BGA/IP55/P Series in Outdoor Designed

Comparison of Standards Requirements with CFD Simulations for Determining Sizes of Hazardous Locations in Hydrogen Energy Station

Philippe POGGI Professeur, Directeur de la Plateforme MYRTE, Université de Corse

CRYOGENIC FLUIDS CHAPTER 55

Barbara Lowesmith Loughborough University

2G GAS BLENDING SYSTEM

ITM POWER STACK ENERGY STORAGE CLEAN FUEL PRODUCT COMPLIANCE

Hydrogenics Selected References. Grid Balancing, Power to Gas (PtG)

ATEX SOLUTONS FROM AERZEN

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER F: CONTAINMENT AND SAFEGUARD SYSTEMS

TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES

HySTAT ON SITE HYDROGEN Infomoment Waterstof 28/06/2017. Roel De Maeyer, Director Sales & Marketing

welcome to the evolution of energy Energy Station Changing power...powering change

TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES

Preliminary design of hydrogen-driven high speed passenger ferry

TENTS CANOPIES AND OTHER MEMBRANE STRUCTURES

Meeting of April 25 th, 2016 Tampa, FL

NUTC R203. Safety Risks of Hydrogen Fuel for Applications in Transportation Vehicles. Shravan K. Vudumu

How Evolutions in Communications Networks and Fuel Cell Power Have Changed the Site Paradigm Darin Painter. Copyright 2017, Plug Power Inc.

TECHNICAL SPECIFICATION. StirLNG-4 Maritime Stirling Cryogenics gas liquefier for LNG conditioning

TENTS AND MEMBRANE STRUCTURES

Guideline for In-Service Assessment of Ammonia Refrigeration Plants

Introduction to Hydrogen Safety Engineering

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

Advanced Sodium Technological Reactor for Industrial Demonstration

AREVA H 2 Gen. A PEM Electrolyser Manufacturer. H2BZ-Initiative Hessen e.v., 09. November 2015

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

automatic regulation of mixture richness way to emission decrease is in standard equipment of CHP unit

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

Stuart Energy Station. welcome to the evolution of energy

TENTS AND OTHER MEMBRANE STRUCTURES

EuroFID Total Hydrocarbon Analyzer

Hydrogen behaviour when released in confined atmospheres: experimental study and numerical simulations

Consequence analysis OIL & GAS CONSULTANCY SERVICES

ATEX. Potentially explosive dust

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE

APPLICATIONS WITH PROTON EXCHANGE MEMBRANE (PEM) FUEL CELLS FOR A DEREGULATED MARKET PLACE

Fast Deliveries Quality Flare Systems Economical Solutions

Construction of Safety Risk Management Platform for Storage Tank Concentration Zone in the Port Area

TENTS AND OTHER MEMBRANE STRUCTURES

LNG amendments to UN Regulation No. 110: Some background on specific issues

Choose TOTEM, smart heat and power

Safety challenges in view of the upcoming hydrogen economy: An overview

Introduction to the Safe Design of LNG, CNG and Hydrogen Refueling Stations

CRYOGENIC FLUIDS CHAPTER 32

3D Risk Management for Hydrogen Installations (Hy3DRM)

THERMAL PROPAGATION IN LITHIUM-ION BATTERIES

LNG as a Marine Fuel Environmental Impact of LNG in Emergency Scenarios

Hydrogen safety research supporting fuel cell and hydrogen market introduction

ENERGY STORAGE: THE CASE FOR HYDROGEN ALL ENERGY 2014 ABERDEEN 22 ND MAY 2014

EU P2G platform Copenhagen Electrolyzer technology of the BioCat project

Stationary Gas Analysis System Goliath for bio methane, landfill gas, sewage gas, mine gas and biogas

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

Combustion Laboratory Unit C492

SAFETY DISTANCES: COMPARISON OF THE METODOLOGIES FOR THEIR DETERMINATION

UTC R170. Hydrogen Flammability Limits and Implications on Fire Safety of Transportation Vehicles. Umit O. Koylu

Kazarians & Associates, Inc.

Understanding Design Codes and Standards for Biogas Systems

Hydrogen Release Deflagrations in a Sub-Scale Vehicle Tunnel

Solutions for the Oil & Gas Industry

LNG Terminal in Świnoujście. Mutual Joint Visit Workshop for Seveso Inspections 26 September 2017, Nicosia, Cyprus

Consequence analysis of fire and explosion hazards with potential applications to the power generation sector

ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat -

BLIND PREDICTION OF DISPERSION AND EXPLOSION EXPERIMENTS USING CFD

ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200

RL SERIES. Two Stage Light Oil Burners FIRING RATES LIGHT OIL

Explosion Protection of Buildings

Marine Facilities for LNG Carrier Transfer Alternatives

Explosion risk in hydrogen facilities balancing simplified and comprehensive approaches

CRYOGENIC FLUIDS CHAPTER 32

HYTUNNEL PROJECT TO INVESTIGATE THE USE OF HYDROGEN VEHICLES IN ROAD TUNNELS

Short Description (ver. ASAP Build 131)

2012 International Symposium on Safety Science and Technology Safety aspects of the use of LNG for marine propulsion

A, B, C, D VENTILATION SYSTEMS: COMPARISON

Estimating consequences of scenarios of batch operated process in production buildings.

Transcription:

3 rd Pilot Training Session, 06-10 June 2016, ENSOSP, Aix-en-Provence, France Strategies and Intervention tactics - FC stationary installations Franck Verbecke, AREVA Energy Storage

Agenda Hydrogen behavior and properties Fuel Cell and hydrogen stationary applications Basic safety design Hazard identification and typical scenarios Example of deployment of a hydrogen-based green public building in France Example of a hydrogen-based energy storage system: MYRTE platform (Corsica)

Hydrogen behaviour and properties

Hydrogen properties Low density: a safety attribute Combustibles Density Stagnation Hydrogen 0.07 No Low activation energy - at high concentration Methane 0.65 No Propane 1.88 Yes Gasoline (vapors) 4.4 Yes Outdoor, no stagnation Indoor, risk of accumulation

Combustion characteristics in confined geometry A large flammability range Combustibles LFL % vol in air UFL % vol in air Hydrogen 4.0 75.0 Methane 5.3 17.0 Propane 1.7 10.9 Gasoline (vapors) 1.0 6.0 Deflagration of homogeneous mixture: 7,3 % H2 16,5 % H2 10,5 % H2 28.7 % H2 Insignificant pressure effects for combustion of lean H 2 -air mixtures (<10 % H 2 in air)

Ignition of hydrogen jets Flame propagation 10 % Tank Non flammable area Flammable cloud Ignition of a hydrogen jet may produce pressure effects in surroundings More experiments required to adjust classical blast model to better estimate overpressure effects

Fuel Cell and hydrogen stationary applications

Back up system coupled with a data center

Example of hydrogen generator : 10-20 Nm 3 H 2 / h HP PEM Electrolyser Production flow rates Working pressure (without additional mechanical compression) 10-20 Nm 3 H 2 / h 5-10 Nm 3 O 2 / h 35 barg Specific consumption 5,0 kwh/nm 3 Operating Range 10.. 100 % H 2 dewpoint < - 70 C O 2 in H 2 < 5 ppmv O 2 dewpoint < - 70 C H 2 in O 2 < 5 ppmv Increased capacity Lowering specific consumption through power conversion higher efficiency and system optimization Extended operating range (RES coupling) at high pressure 35 barg Fabrication costs breakdown through design to cost conception Optimized footprint (SKID integration) Optional low consumption purification

Hydrogen-based energy storage system

Integrated hydrogen storage solution CERTIFIED Increased building autonomy when coupled with RES Cogeneration: electricity + heat (water temperature 70-90 C) A backup solution Modularity: from 50 kw to several MW Electrical energy stored: Thermal energy available: up to 2.5 MW th /h /day @ 70-90 C > 2 MWh

Basic safety design

CE certification for FCH stationary installations CE certification required for commercialisation of FCH systems throughout Europe Mainly five directives to be compliant with: Machinery Directive - 2006/42/CE Pressure Equipment Directive (PED) - 97/23/CE Low Voltage Directive - 2006/95/CE Electromagnetic Compatibility Directive - 2004/108/EC ATEX directive

Overall safety strategy Safety taken into conception stage : Gas leak prevention Prevention of H2 accumulation in containment Reduction/limitation of ignition sources (e.g. EX zone) Overpressure process prevention Secured installation: Rules of installation Limited access to authorized and trained employees Ensure an instantaneous and automatic continous : Instantaneous measure of process parameters In case of deviation above the defined threshold, the system stops automatically to reach a safe state Maintaining the system in safe operational conditions: Periodic maintenance and inspections

Avoiding hydrogen accumulation in containers/enclosures Natural ventilation Mechanical ventilation Activated at max speed if H2 is detected above 0,4-1 % H2 in air (vol.) h i

Containment issues Context: If failure of high-pressure pipes, fittings or components in confined and obstructed enclosures, may lead to the rapid formation of a turbulent flammable hydrogen-air mixture If ignited, risk from deflagration and DDT t=0.1 s Challenges: minimize the amount of H 2 potentially releasable in the container Passive safety barriers such as Restrictors, excess flow valves, etc. Instrumented safety barriers Dedicated safety control command Fast response time High reliability components to achieve SIL classification (Safety Integrity Level) t=0.4 s t=0.8 s AREVA PROPRIETARY & CONFIDENTIAL

Example of automatic sequence in case of hydrogen leak detection in a container Automatic activation of several safety barriers : Detection of P drop in the hydrogen line Detection Delta P between the hydrogen and air/oxygen lines e.g. for electrolysers, fuel cell systems Hydrogen detection in enclosure/container Typical safety sequence : Process, power conditioning stopped Mitigation of the leak by isolating the hydrogen storage Activation of the mechanical ventilation of the container Major safety event triggered transmitted to the plant manager, project and safety managers and safety intervention teams

Example of safety devices for a FCH system

Example of safety devices for a FC system External Vent Mechanical ventilation Segregation Isolation valves Manual emergency switching device Smoke detectors Hydrogen sensors Natural ventilation

Hazard identification and typical scenarios

Hazardous phenomena for FC stationary application Hazardous phenomena for electrolysers Products Equipment of hazards Potential hazard Hydrogen Container Container explosion Jet fire Hydrogen Gas separators (electrolyser systems) Burst Hydrogen Pipes UVCE VCE Jet Fire Electricity Cable/cabinets Electrocution Hazardous phenomena for FC systems Products Equipment of hazards Potential of Hazard Hydrogen Container Container explosion Jet fire Hydrogen Pipes UVCE VCE Jet Fire Electricity Cable Electrocution

Typical scenario inside a container

Hydrogen accumulation followed by container explosion Hazardous phenomena Volume, m 3 Free volume 70% Significant lethal effects Domino effects 200 mbar (m) Lethal effects 140 mbar (m) Irreversible effects 50 mbar (m) Indirect effects : broken glass 20 mbar (m) Explosion of container 10 feet L x l x H (m): 3 x 2.4 x 2.4 17 Explosion container 20 feet L x l x H (m): 6 x 2.4 x 2.4 34 Explosion container 40 feet L x l x H (m): 12 x 2.4 x 2.4 68 12 24 48 14 17 40 80 17 21 51 102 22 27 64 128

Example of deployment of a hydrogen-based green public building in France

Hydrogen-based energy storage system: installation in a public building Context: Increase of population by a factor 10 in summer End line location on the electrical grid network Deploying hydrogen-based energy storage solution coupled with photovoltaic panels to: Insure the green production of electrical and thermal energy Ensure the partial energy autonomy of the buildings Backup system in case of power cut Decrease the energy bill of the city while promoting sustainable development Develop a reliable and safe solution The first Greenergy Box TM in a Kid Leisure Centre (Public Building)

Integrated hydrogen storage solution : the Green Energy Box TM CERTIFIED Increased building autonomy when coupled with RES Cogeneration: electricity + heat (water temperature 70-90 C) A backup solution Modularity: from 50 kw to several MW Electrical energy stored: > 2 MWh Thermal energy available: up to 2.5 MW th /h /day @ 70-90 C

Challenges 1. No hydrogen-related installation rules in Public Building Codes Define the rules for the first installation of a hydrogen-energy storage system 2. Hydrogen safety and public acceptance Convince the population that the Greenergy Box TM is a safe hydrogen solution 3. Designated installation location with limited surface Offer a solution respecting the client s constrains

Site allocated for the hydrogen chain

Hydrogen-based energy storage system: installation in a public building

Hydrogen-based energy storage system: installation in a public building

French Public Building Regulation In France, a local Safety Commission checks the conformity of architectural plans of a new building with Public Building Code No competent to authorize the installation of a hydrogen system Authorization delivered by a National Public Building Safety Commission Analogy with cogeneration system in Public Building Code Greenergy Box TM similar to a cogeneration module system Installation guidelines defined for combustion heating systems Prescriptive approach Installation location Total power of the system (heat + electricity) <30 kw >30 kw & < 70 kw >70 kw Inside Outside Terrace

Solution of implantation System installation : Non flammable system envelop Inaccessible to public or made inaccessible by the use of a wall or a fence of at least 2 m high 10 m distance from highway, private property limit or other buildings. IF NOT, protective wall of fire resistance of 2 hours and of 2m minimum height 2h fire resistant canopy to protect the system and the storage and/or the façade of the multi-purpose from thermal effects in case of fire

Solution of implantation Storage installation : Zone inaccessible to public and surrounded by a protective wall of fire resistance of 2 hours and of minimum height of 2 m Storage tanks separated by a 2 h fire resistance wall 2h fire resistant canopy above the storage tanks PED certification for the tanks Manual safety valve for each tank Electro-valve close to each tank In case of power cut or activation of a safety function, both the storage tank and the Greenergy Box are isolated by the electro-valves

Solution of implantation Emergency safety devices An Emergency Discharge Device of the tanks, positioned outside of the technical premise in a protected access, enables to discharge the storage tanks in about 10 minutes through the vent Several emergency shut-down bottoms located enables to: isolate the gas supply at the tank and the container, disconnect the Greenergy Box from the electrical grid up to the electrical cabinet, which implies the depressurization of the system through the vents installed on the roof of the building. Residual amount of hydrogen will subsist in the process. Vents Firefighter interface 2h fire resistant Glass window Air intake

Example of a hydrogen-based energy storage system: MYRTE platform (Corsica)

Indoor process system installation High building with large openings for natural ventilation Sizing for limiting H2 accidental leaks Leak and fire detection H2 detectors ΔP Thermal camera Reduction of electrical sources ATEX components (H2, smoke detectors) Electrical switch off at low H2 concentration Emergency discharge bottom Safety distances or fire resistance wall

Example of hydrogen-based energy storage system: MYRTE platform

Hydrogen-based energy storage system: MYRTE platform (Corsica)

Hydrogen-based energy storage system: MYRTE platform

Hydrogen-based energy storage system: MYRTE platform

Hydrogen-based energy storage system: MYRTE platform

Hydrogen-based energy storage system: MYRTE platform

Hydrogen-based energy storage system: MYRTE platform

Thank you for your attention http://www.hyresponse.eu/ HyResponse: Coordination and Support Action funded by Fuel Cells and Hydrogen Joint Undertaking and supported by the European Commission under the 7th Framework Program. Project reference: 325348.