buildings. design of post-frame gyms and multipurpose

Similar documents
Post-Frame Construction and the International Building Code By Amanda Stauffer

Iowa Mutual Insurance Association Wick Buildings, Inc. 405 Walter Road P.O. Box 38 Mazomanie, WI WickBuildings.

2- and 1-Hour Fire-Rated Walls

LEARNING OBJECTIVES. Copyright 2015 National Frame Building Association.

Structural Inspection

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns)

Applying IBC 2000 wind and snow loads to post-frame building posts

Update on Diaphragm Design Value Determination Using the Modified Metal Construction Association Procedure

POST FRAME BUILDING STANDARDS

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

Section 4 - Design and Construction Overview

NOTE: For construction other than new commercial or additions (renovations), only those areas below describing the scope of work will be applicable.

Building Division Informational Handout

1. Frozen food warehouses used solely for storage of Class I and II commodities where protected by an approved automatic sprinkler system.

North Shore at Canton Baltimore, MD Beau Menard Technical Report 1

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings

PRESCRIPTIVE COMPLIANCE METHOD

Type III Fire-Resistant Design and Detailing: Exterior walls, Intersections and Balconies. For Light-Frame Wood Construction

CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE 01. GENERAL ADMINISTRATION 3 % Project Administration 3%

Hansen Pole Buildings Planning Guide. Toll Free / Toll Free FAX

2018 IBC Chapter 6 Types of Construction

BUILDING CODE COMMISSION

Building Plan Submittal Reminder List. What information do I need to include as part of my building plan submittal package?

Title: Building Construction for the Fire Service. Time: 3 hours. Teaching Materials: White board Building Construction for the Fire Service (PDF)

Updated references to SEI/ASCE 7 to the 2016 edition once it is available.

Common Errors in Truss Design

Jackson Crossing Located in Alexandria, VA. Technical Report 1 Michael Bologna

SECTION GYPSUM BOARD & SHEATHING SYSTEMS

Chapter 4: Insulation

Insulated Cold-Formed Steel Wall Panels: A case study of a contractor-manufacturer

General Building Information

2006 International Residential Code Errata (Portions of text and tables not shown are unaffected by the errata)

Prescriptive Design for Pole Barns Using the Larimer County Prescriptive Handout

Common Applications: FRT plywood Type X Gypsum wall board

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: EVALUATION SUBJECT: STRUCTURAL PANELS

Borough of Doylestown Building and Zoning Department

January 14, 2006 Structural Thesis Proposal: Structural and Breadth Redesign Options

Combustible Exterior Wall Cladding Systems: An ICC Perspective

ENTRY FORM. DVASE 2014 Excellence in Structural Engineering Awards Program

assembly an open space between the roof and ceiling of a building attic balloon frame a joist constructed of steel with bars in the verticle web space

CHAPTER 6 TYPES OF CONSTRUCTION

Residential Patio Cover Specifications

UCC Permit Application Procedures

Individual Truss Marking Is it a Building Code Requirement?

130 MPH EXPOSURE B WFCM GUIDE. Guide to Wood Frame Construction in High Wind Areas for One- and Two-Family Dwellings 2015 EDITION

Heel Blocking Requirements and Capacity Analysis. Overview Revised 3/22/2017

research report Cold-Formed Steel Gable End Wall Design Using the Prescriptive Method for One and Two Family Dwellings RESEARCH REPORT RP05-2

Chapter 4 Test. Directions: Write the correct letter on the blank before each question.

Butte County Fire Department Fire Prevention Bureau 176 Nelson Avenue Oroville, CA Office (530)

City of Bemidji Building Office City Hall 317 4th Street NW Bemidji, Minnesota Phone Fax emi mn s

WFCM 90 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

A New Path Forward for Tall Wood Construction: Code Provisions and Design Steps

FIRE AND SMOKE PROTECTION FEATURES

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

Construction Concerns: Steel Truss Double Roof Article by Gregory Havel

WFCM 120 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

WFCM 130 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)

Chapters 4 through 10 address the prescriptive methods. Building Construction PART. Chapters 4 through 10

CHAPTER 7 STRUCTURAL SYSTEMS

RESIDENTIAL SEISMIC RETROFITS

INTERIOR FINISHES CHAPTER 8

Framing Methods Structural Components

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION

R CODE CHANGE PROPOSAL FORM (See instructions on page 2)

WFCM 110 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

WFCM 100 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

GENERAL FRAME INFORMATION

2003 International Residential Building Code

Copyright Materials. Learning Objectives. Design is in the Details: Solutions to Common to Mid Rise Design. Challenges

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 7 Ventilation Lightweight Construction Revised

SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION

#402 New Residential Submittal Checklist

INTERIOR FINISHES CHAPTER 8

WFCM 130 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

The Lexington Division of Fire and Emergency Services. Fire Chief Robert G. Hendricks

ResearcH + Technology

ACCESSORY STRUCTURES (Garages/Sheds) BUILDING AND ZONING REQUIREMENTS (REVISED 4/21/16)

Recommendations on Proposed International Code Changes

Project. San Jose City College Physical Education Building. Prepared For. Prepared By PLACE IMAGE HERE. Ken Bauer, AIA Principal

Tier 1 Assessment Linderman Gymnasium Polson, MT

INTRODUCTION TO POST FRAME DESIGN. Copyright Materials. Presentation prepared by Harvey B. Manbeck, P.E., PhD. National Sponsors

THE STEELFORM GOLD STANDARD. Product Data Sheet. Non-loadbearing Steel Studs (NLB)

Introduction to Construction, June 2013, page 1 of 6

WELCOME TO: ARCH 2330 BUILDING TECHNOLOGY III

WASHINGTON STATE ENERGY CODE, APPENDIX CHAPTERS

PLASTIC CHAPTER 26. SECTION 2602 DEFINITIONS Definitions. The following terms are defined in Chapter

Heartland Perma-Column 1841 E 1450 Rd. Lawrence, KS (785)

City of Hughson Building Safety Division 7018 Pine Street Hughson, CA (209)

STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E.

ELMIRA HIGH SCHOOL GYMNASIUM ANNEX NOVEMBER 19, 2015

WOOD USE IN NONCOMBUSTIBLE BUILDINGS

Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION

10/23/2011. Plan Examination. Plan ExaminationPurpose. Catch problems in advance of construction.

Structural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity

Garage/Accessory Structures

CODE 101 How To Read The California Building Code

Transcription:

Research + Technology Xxxxx design of post-frame gyms and multipurpose buildings by Timothy Royer, PE, and Amanda Stauffer Post-frame construction is ideal for non-code-exempt buildings of many shapes and sizes. One category of such structures that is often overlooked by post-frame builders is gymnasiums and multipurpose recreational buildings. Gymnasiums and multipurpose recreational buildings are a perfect fit for post-frame construction for several reasons. Post-frame walls feature columns that run continuously from the foundation to the roof framing. These columns can be designed to accommodate the high ceilings that gymnasiums require. Long clear-span trusses allow for an open floor plan for basketball, volleyball and other sports, with scissors-style trusses used to create pitched ceilings that are higher in the center of the building. Large wall cavities allow plenty of room for insulation to meet or exceed energy code requirements. A variety of exterior siding and roofing materials can be used to create aesthetically pleasing architectural designs. The end result is post-frame gym and multipurpose recreational building designs that are cost efficient, highly functional, energy efficient and architecturally pleasing. Building Code Classification and Requirements Building codes classify buildings by type of occupancy and by type of construction. Occupancy type defines the end use of the building. Buildings (or parts of buildings) with the same end use are assumed to have similar life-safety characteristics, combustible contents and fire hazards. Construction type is used to define minimum fire ratings of building components (e.g., beams, columns) and assemblies (e.g., walls, floors, roofs). It is the combination of occupancy type (or use group) and construction type that largely dictates maximum building height and area. Descriptions of the various occupancy and construction types can be found in Chapter 3 of the International Building Code. Two other IBC chapters of related importance are Chapters 5 and 9. Chapter 5 contains maximum allowable building heights and areas. Chapter 9 contains requirements for fire protection systems based on the occupancy type (note: Chapter 9 requirements are independent of construction type). Chapter 9 provides the parameters of fire areas and occupant loads and is used to determine whether a project will require an automatic sprinkler system. Chapter 9 is used in conjunction with Chapter 7 to determine fire barrier and firewall requirements. In accordance with the IBC, gymnasiums and multipurpose recreational buildings are typically assigned an Assembly (A) type of occupancy. If the building does not have spectator seating, it is classified as A-3. If it includes spectator seating, it is classified as A-4. All or part of these buildings may be classified as a Business (B) type of occupancy under the IBC if the building includes areas for training and skill development conducted outside of a school or academic program. This could include, for example, a building at a summer camp that is used for dance lessons or another business venture, rather than a typical gymnasium setting where games and practices are held. Typical post-frame construction is classified as construction type VB, which means that the primary building elements are wood frame elements that don t require fire protection. Assembly (A) buildings of type VB construction are limited to an allowable area of 6,000 square feet and to one story, per IBC Table 503. The maximum allowable area can be increased if all or a portion of the area surrounding the building meets access criteria (i.e., open perimeter requirements) for firefighting. The addition of an automatic sprinkler system will also provide an allowable area increase of 200 percent as well as an increase in the number of allowable stories from one to two. Post-frame buildings with primary structural building elements that have a 1-hour fire resistance rating can be classified as VA construction. Assembly (A) buildings of type VA construction are limited to an allowable area of 11,500 square feet and two stories, per IBC Table 503. Again, the maximum allowable area can be increased by providing firefighting access, automatic sprinklers or both. The inclusion of automatic sprinklers will also allow an increase in the maximum number of stories from two to three. The maximum fire area in assembly A-3 and A-4 buildings is limited to 12,000 square feet or less, per IBC Section 903.2.1, regardless of construction type. If the fire area exceeds 12,000 square feet, then an automatic sprinkler system is required. The use of 2-hourrated fire barriers, per IBC Section 706, can create separate fire areas and eliminate the need for the sprinkler system. Occupant load can be a major controlling factor in gymnasium and multipurpose recreational building design. The IBC bases occupant load on an allowable number of persons per square www.framebuildingnews.com 1

foot (i.e., how many individuals could fit in the space), not on the anticipated number of occupants in the building (see IBC Section 1004). Regardless of construction type, the maximum number of occupants in an A-3 or A-4 fire area is 299 before a sprinkler system is required. Gymnasiums and recreational buildings typically have large open floor plans, and applying the person-persquare-foot requirement results in a very high occupant load, and thus a load that typically requires a sprinkler system. If the calculated occupant load results in a number that is unrealistic, the issue can be discussed with the building code official, who has the authority to accept a lesser number or adjust the squarefoot-per-person total in order to get a more reasonable result, per IBC Section 1004.1.1. When this is done, maximumoccupant-load signs must be posted at or near the main entrance and exit doors. The structural design of post-frame gyms and multipurpose recreational buildings must conform to the structural load requirements compiled in IBC Chapter 16. Section 2306 of the IBC requires adherence to the National Design Specification for Wood Construction published by the American Wood Council (2015). The NDS establishes minimum design standards for all wood frame buildings. IBC Section 2306 also requires adherence to three documents of the American Society of Agricultural and Biological Engineers: EP484. Diaphragm Design of Metal-Clad, Wood-Frame Rectangular Buildings; EP486. Shallow- Post Foundation Design; and EP559. Design Requirements and Bending Properties for Mechanically Laminated Columns. Use of the NDS and ASABE documents for post-frame building design is covered in the Post-Frame Building Design Manual published by the National Frame Building Association (Bohnhoff, 2015). Design Examples Following are three examples of gym or multipurpose recreational building designs that use post-frame construction. The scope of this article does not include the entire building analysis; only a few key concepts specific to postframe design (including some structural design tips and some code-related details) are provided. Please keep in mind that two of these examples were designed in accordance with the 2006 IBC and one in accordance with the 2003 IBC. The IBC is constantly being updated and revised. The status of the latest code adoption varies from state to state and sometimes from municipality to municipality. As always, be sure to check which edition of the code is currently in use before starting a project. Example 1: Small School Gymnasium Figure 1. Example 1: Small school gymnasium in an urban setting Figure 2. Example 1: Side wall Designed in accordance with the 2006 IBC and built in 2007, Example 1 (Figures 1 9) is an 80- by 94- by 20-foot post-frame gym featuring bleachers, a locker room and restrooms. It is located in an urban area next to a school building. Another building was removed to open up space for this gym. Two walls were designed to bear on an existing retaining wall, and one sidewall was firerated because of its proximity to a property line. This building was designed to meet VA construction type requirements (i.e., it was designed with 1-hour-rated walls and ceiling) and an A-4 occupancy. Figure 3. Example 1: Gable wall with retaining wall 2 FRAME BUILDING NEWS november 2016

Example 1: Small School Gymnasium Continued Figure 4. Example 1: Gable wall, full height Figure 7. Example 1: Floor plan Figure 5. Example 1: Interior view Figure 6. Example 1: Interior view The actual area of the building was 7,520 square feet. Because this was less than the maximum allowed value of 11,500 square feet for an A-4 building of type VA construction, per IBC Table 503, there was no need (from the perspective of maximum allowable area) to increase perimeter access for firefighting or to add a sprinkler system. However, the occupancy load calculation (based on an IBC Table 1004.1.1 value of 7 square feet per person for an A-4 occupancy) provided an occupant load of greater than 300, so a sprinkler system would have been required, according to IBC Section 903.2.1.4. The school board met with the building official to review the sprinkler system requirement and requested a variance. A variance was granted, with the requirement that an interconnected fire alarm system and additional exit doors be added to this one-story building. The structural design used embedded post foundations on some walls and posts fastened to the top of retaining walls on others. The embedded post Figure 8. Example 1: Cross-section www.framebuildingnews.com 3

Example 1: Small School Gymnasium Continued Figure 9. Example 1: Foundation detail foundations were designed according to ASABE EP 486 Shallow-Post Foundation Design. The connections of the posts to the top of the retaining walls were based on methods described in the NDS. A unique feature of this gym was the scissors truss roof system that provided a ceiling 20 feet high at the sidewalls and 25 feet high at the center of the gym floor. As previously mentioned, walls and ceilings with 1-hour fire-resistance ratings are required for type VA construction. This was accomplished by applying 5/8- inch-thick type X gypsum to the inside face of the walls (in accordance with Underwriters Laboratory [UL] design U528) and to the underside of the truss bottom chord (in accordance with a fire resistance calculated per IBC Section 721.6). Diaphragm action was used to provide lateral and longitudinal stability. Diaphragm design was performed in accordance with ASABE EP484 Diaphragm Design of Metal-Clad, Wood-Frame Rectangular Buildings. Example 2: Multipurpose Recreational Building for a Camp/Retreat Center Example 2 (see Figures 10 12) features an 80- by 120- by 20-foot post-frame building designed in accordance with the 2006 IBC and constructed on top of a cast-in-place concrete foundation wall in 2007. Main characteristics include an open floor plan (except for the restroom and mechanical room in one corner of the building) and a cast-in-place rear concrete wall that functions as a retaining wall. This camp/retreat center was designed for an A-3 occupancy and type VB construction. Per IBC Table 503, the maximum allowable area for an A-3 building of VB construction is 6,000 square feet. Because this was less than the actual designed building size of 9,600 square feet, an allowable increase for firefighting access (calculated in accordance with the IBC Section 506.2 open-perimeter formula) was used. The occupant load for this building using 5 square feet per person for the open floor plan would have resulted Figure 10. Example 2: Floor plan 4 FRAME BUILDING NEWS november 2016

Example 2: Multipurpose Recreational Building for a Camp/Retreat Center Continued in an occupant load greater than 299, which would have required installation of an automatic sprinkler system. The owners met with their building official, and the building official accepted an occupant-load calculation based on 50 square feet per person, similar to that of an exercise room. This resulted in a much more reasonable occupant load. The maximum occupant load of 180 people was required to be posted on signs next to all the entrance and exit doors. As previously stated, this design used post-frame construction on top of cast-in-place concrete foundation and retaining walls. Posts were spaced 4 foot on center at the request of the owner. A design featuring embedded posts spaced 8 foot on center might have been more cost effective. Note that all gable columns extend to the roof line, a detail that we would suggest for most post-frame building designs. A scissors truss roof system was used to create a 25-foot-high ceiling at the center of the building. Individual trusses were spaced 2 foot on center so that plywood roof sheathing and metal ceiling panels could be installed directly onto the trusses. This eliminated the need for purlins. Figure 11. Example 2: Cross-section Figure 12. Example 2: Header and beam connection Example 3: Community Center Gymnasium Presented as Example 3 (Figures 13 15) is an 82- by 114- by 24-foot gym that was erected in 2005 and designed in accordance with the 2003 IBC. Gable trusses cover the main gymnasium area, and attached offices, storage space, classrooms, a concession area and restrooms are located alongside the gym in a leanto area framed with mono-slope trusses. The project design team included an architect who provided architectural plans that covered the building code review. Our structural design was used, in addition to the architectural plans, to create a complete set of plans for submission to obtain the required permits. The foundation for the Example 3 building is a grade beam foundation system installed on top of a driven piling system. Columns were fastened directly to the concrete grade beam Figure 13. Example 3: Floor plan www.framebuildingnews.com 5

Example 3: Community Center Gymnasium Continued with appropriately designed brackets. The main gym area features 24-foothigh sidewalls and flat-bottom-chord gable trusses spaced 4 foot on center. Distance to the underside of the mono-slope trusses in the lean-to area is 10 feet. The mono-slope truss roof system and support framing were designed for the added drifting and sliding snow loads resulting from the higher roof of the main gym. Headers, beams, connections and bracing are all critical components of the post-frame design system and must be specified on the construction documents. Summary These three examples give an introduction to the possibilities available to designers and builders interested in constructing post-frame gyms and multipurpose recreational buildings. The authors strongly believe that no other building framing system is better suited for smaller gyms and multipurpose recreational buildings than post frame. Without doubt, many schools and small communities would benefit greatly from the economical construction costs and energy efficiency of post-frame gyms and multipurpose recreational buildings. Post-frame building construction companies may want to consider establishing standard plans for gyms and community centers as turnkey packages. In addition to the building shell itself, these standard packages could include special flooring, sports hardware options, bleachers, concession areas and locker rooms. We hope that this article will encourage conversation about these possibilities and encourage the use of post-frame construction in this market. Timothy Royer is president of TimberTech Engineering, Inc., Denver, Pennsylvania, and can be reached at trr@timbertecheng.com. Amanda Stauffer is building code specialist and computer-aided design drafter at TimberTech Engineering and can be reached at ant@timbertecheng.com. Figure 14. Example 3: Cross-section Figure 15. Example 3: Eave connection details References American Society of Agricultural and Biological Engineers. ANSI/ ASABE EP484. Diaphragm Design of Metal-Clad, Wood- Frame Rectangular Buildings. St. Joseph, Mich.: ASABE. American Society of Agricultural and Biological Engineers. ANSI/ ASABE EP486. Shallow-Post Foundation Design. St. Joseph, Mich.: ASABE. American Society of Agricultural and Biological Engineers. ANSI/ ASABE EP559. Design Requirements and Bending Properties for Mechanically Laminated Columns. St. Joseph, Mich.: ASABE. American Wood Council. 2015. National Design Specification for Wood Construction. Leesburg, Va.: AWC. Bohnhoff, D. (2015). Post-Frame Building Design Manual, Second Edition. Chicago, Ill.: National Frame Building Association. International Code Council. 2003, 2006, 2015. International Building Code. Country Club Hills, Ill.: ICC. 6 FRAME BUILDING NEWS november 2016