CHAPTER 11 CONDUITS AND FITTINGS

Similar documents
CONDUITS AND FITTINGS

CHAPTER 12 HANDHOLES, PULLING VAULTS, AND JUNCTION BOXES

HANDHOLES, PULLING VAULTS AND JUNCTION BOXES

CHAPTER 13 GROUNDING AND BONDING

New Conduit Specification

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS

12/21/2018 WHAT S NEW SINCE What's New Since SPEC BOOK 2018 SPEC BOOK 2018 SPEC BOOK WHAT S NEW SINCE 2014

1/5/2018 WHAT S NEW SINCE B & B QUALIFICATION OF WORKERS. What's New Since SPEC BOOK 2018 SPEC BOOK 2018 SPEC BOOK

TS 803 DUCTS DUCT INSTALLATION, PROTECTION AND MARKING WITHIN A TRENCH OPEN TRENCH DUCT INSTALLATION PROFILE

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF DUCTS

Section 2: Underground

SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

WIRING METHODS CHAPTER 38

OKLAHOMA DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR BRIDGE NAVIGATION LIGHTING

CITY OF UNION, OREGON TECHNICAL SPECIFICATIONS SECTION 9 UNDERGROUND UTILITIES

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF DUCTS

Please check with your local inspection authority for any additional requirements before installation.

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes.

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF DUCTS

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF DUCTS

A. Section Includes: Electrical site utilities and coordination of requirements with the utility company and service specifications.

Youngstown State University

SPECIAL SPECIFICATION 6664 Level (3) Communications System

SPECIAL SPECIFICATION 6658 Time Warner Communications System

If a new residence s electrical service is not located within 200 feet of existing

DEPARTMENT OF TRANSPORTATION STATE OF GEORGIA SPECIAL PROVISION. Section 550 Storm Drain Pipe, Pipe-Arch Culverts, and Side Drain Pipe

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

Student Services & Classroom Addition

Merrimac Municipal Light Department. Commercial Developments Policy

YAKIMA COUNTY, WASHINGTON. Special Provisions For Water Main Construction

SECTION ELECTRICAL SITE UTILITIES

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY

UNIVERSITY OF MISSOURI Hydronic Energy Distribution 2016 Q1

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

DMS CONDUIT EFFECTIVE DATE: APRIL

CONSTRUCTION SPECIFICATION FOR TRAFFIC ACTUATION EQUIPMENT

SUPPLEMENTARY SECTION: STANDARD SPECIFICATIONS PAGE 1 STORMWATER MAINS & CULVERTS MAY 2018

Contact Clark Public Utilities Construction Services department at (360) to initiate a request for service.

TS 804 CABLES TABLE OF CONTENTS TRAFFIC SIGNAL EQUIPMENT POLE WIRING DIAGRAM LOCATIONS WITH CENTRE MEDIANS

DIVISION 26 - ELECTRICAL Section Conduit for Electrical Systems 1. GENERAL 1.1 WORK INCLUDES

Specifications Electrical Metallic Tubing (EMT)

CITY OF OCEANSIDE. Electrical Lines, Plumbing and Mechanical Burial & Support Requirements. Informational Bulletin

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

CONSTRUCTION SPECIFICATION FOR GROUNDING

SECTION ELECTRICAL UTILITY SERVICES

DIVISION 1100 TRAFFIC

GLENWOOD PLACE 2 MAR 2015

DIVISION 32 EXTERIOR IMPROVEMENTS IRRIGATION

SECTION A. Underwriters Laboratories, Inc., listed and NEC approved

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

CW 3620 INSTALLATION OF UNDERGROUND TRAFFIC SIGNAL SERVICES TABLE OF CONTENTS

Specifications Rigid Metal Conduit / PVC Coated Rigid Metal Conduit

CONSTRUCTION SPECIFICATION FOR THE INSTALLATION OF ELECTRICAL CHAMBER

H. Underground Transmission System Design

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

SECTION CONDUIT AND FITTINGS

A. This section is intended to provide design guidelines for Utility Direct Buried Piping and Conduit Systems.

DIVISION 32 EXTERIOR IMPROVEMENTS IRRIGATION

SPECIAL SPECIFICATION 6666 Charter Communications System

UNIVERSITY OF MISSOURI Electrical Manholes and Handholes 2016 Q1

Huntsville Utilities Underground Residential Service Requirements

A. Bellcore CAO-8546 Specification for Type B, C, and D Plastic Conduit. B. NEMA TC 6& PVC Plastic Utilities Duct for Underground Installation.

CITY OF FARGO SPECIFICATIONS SEWER AND WATER SERVICE CONNECTIONS

UNDERGROUND SERVICES SECONDARY

SECTION 1 GENERAL NOTES

SECTION ELECTRICAL CABLE. 1. Trench excavation, backfill, and compaction; Section

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Material will comply with those standards as established by UL or NEMA and shall be commercial grade. All materials will be new and free from defects.

SPECIAL SPECIFICATION 7191 Illumination

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

SECTION FACILITY LIGHTNING PROTECTION

ITEM NO. 824 SERVICE SUPPLY LINES (WATER)

SECTION UTILITY POLYETHYLENE CONTAINMENT PIPE SYSTEMS

SANITARY WASTE AND VENT PIPING

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

Electric Service Standards

UNM IT/Telecommunications Guide Specification Communications Underground Ducts, Raceways and Structures /27/06

ITEM 432 TUNNEL CONSTRUCTION

SECTION CONDUITS AND BOXES

Section 7: Specifications

CONSTRUCTION STANDARDS SECTION CS 15 STREET LIGHTING

Special Specification 6016 Intelligent Transportation System (ITS) Multi-Duct Conduit

GENERAL NOTES PEDERNALES ELECTRIC COOPERATIVE, INC. RESIDENTIAL AND COMMERCIAL AMP METER LOOP SPECIFICATIONS

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

SECTION CONDUIT AND BOXES

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF ELECTRICAL CHAMBERS

NEC 2014 Code Changes

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

Transcription:

CONDUITS AND FITTINGS CHAPTER 11 CONDUITS AND FITTINGS The standards and requirements for conduits and fittings used for traffic control signal and lighting systems are presented in this chapter. 11.1 Conduits A conduit is defined as a tube or duct for enclosing wires or cables. 11.1.1 GENERAL REQUIREMENTS FOR NON-METALLIC CONDUIT MnDOT allows the use of either rigid polyvinyl chloride (PVC) conduit (rigid sectional lengths) or high-density polyethylene (HDPE) (continuous length) conduit. All rigid PVC and HDPE conduit and fittings must be Schedule 80 and listed by a Nationally Recognized Testing Laboratory (NRTL) as being compliant with the requirements of UL 514B and UL 651 for underground use. All nonmetallic conduit must be either red or gray in color. See contract documents for the specific requirements for all non-metallic conduits. Figure 11-1: Rigid PVC Sectional and Continuous Length (HDPE) Conduit Installation Requirements Before cables and conductors are installed, standard non-metallic conduit end bells must be installed to prevent damage to the cables and conductors. The contractor must trim the inside and outside of cut ends to remove rough edges. Cut ends of sectional conduit must butt or come together for the full circumference thereof. All open ends of non-metallic conduit must be immediately capped to keep moisture and debris out. When rigid PVC conduit sections are installed using the directional boring method the rigid PVC conduit sections must be pre-glued at least six hours prior to installation under roadway 11-1

surfaces. Long-line couplings must be used when rigid PVC conduit sections are installed under roadway surfaces. HDPE continuous length conduit must not be spliced under roadway surfaces. HDPE continuous length conduit must not be used between concrete foundations and the nearest handhole. Underground conduit runs must have provisions for drainage of moisture. Horizontal conduit runs must be sloped to drain at a rate of not less than 0.25 percent, and all low points must be drained. At the low points (not at the open ends of conduit runs) a standard tee conduit fitting must be installed and a nipple at least six inches long must be extended into a hole approximately two feet square by two feet deep and backfilled with crushed rock or approved granular material. The contractor must pull cables and conductors through the non-metallic conduit in such a manner as not to damage the conduit due to pull rope abrasion. The contractor will be required to pull a ground wire through the conduit system as required by the contract documents. Additional considerations include: The material for all conduit bushing grounding lugs used on RSC conduit must consist of stainless steel, brass, copper or bronze with lay in ground lugs. Transformer to source of power (SOP): 2-inch RSC or as specified in the contract documents. Liquid Tight Flexible Non-Metallic Conduit (LFNC-B) - Specification 3804: MnDOT primarily uses liquid tight flexible non-metallic conduit when installing bridge underpass luminaires. Installation requirements are covered in 2565.3D. 11.1.2 TYPES OF CONDUIT FOR TRAFFIC CONTROL SIGNAL CONSTRUCTION MnDOT uses three types of conduits in traffic control signal construction: Rigid Steel Conduit - Specification 3801 Non-Metallic Conduit - Specification 3803 PVC Coated Hot Dipped Galvanized Rigid Steel Conduit - Specification 3805: MnDOT uses PVC Coated RSC on bridges. The conduit can hang under the bridge deck and will be encased in concrete when required. Installation requirements are covered in Specification 2565.3D. 11.1.3 TYPES AND SIZES OF CONDUIT FOR LIGHTING SYSTEM CONSTRUCTION Lighting plans will indicate the size of conduit to be used in the construction of a lighting system and the following are the typical sizes of conduit used: Median Barrier: 1-1/2-inch rigid PVC conduit. Under traveled roadway: 4-inch rigid PVC conduit, or HDPE conduit marking each end with a red ball locator (See Chapter 12 for ball locator information). Bridges: 1-1/2-inch PVC coated hot dipped galvanized rigid steel conduit and retaining walls use 1-1/2-inch rigid PVC conduit or as specified in the contract documents. PVC conduit may also be used in rest areas and/or in plans within city limits. Conduit size will be according to the plan. 11-2

11.1.4 STANDARD SPECIFICATIONS FOR CONDUIT (TRAFFIC CONTROL SIGNALS AND LIGHTING SYSTEMS) Standard specifications include the following: All conduits and fittings must be the size and type specified in the contract documents If conduit size is not specified, the minimum conduit size must be 3/4 inch. Conduit installation must be in accordance with the National Electrical Code (NEC). The conduit in a run must be the same size and type and must be continuous from outlet to outlet. Conduit must be installed in as straight a run as practicable and will enter handhole and foundations in line with the general direction of the conduit run. Conduits with sharp kinks or reduced cross section will be rejected. Figure 11-2: Damaged Conduit Damage may occur when: The conduit is bent without using the proper equipment. An attempt is made to relocate the end of the conduit without proper excavation and the conduit is forced so that it lines up with the handhole or foundation. Conduit Bends (2565.3D) Conduit bends other than those done in the factory must have a radius no less than six times the normal diameter of the conduit. Bends must not damage the conduit or effectively reduce its internal diameter. In addition, bends must not exceed 360 degrees of bend per conduit run between handholes or foundations. Refer to the NEC 344.26 or 352.26 for requirements (text referenced in Figure 11-3 below). 344.26 Bends Number in One Run. There shall not be more than the equivalent of four quarter bends (360 degrees total) between pull points, for example, conduit bodies and boxes. Figure 11-3: NEC 344.26 Bends Above Ground (2565.3D) All cables must be run in conduits except as otherwise specified in the contract documents. When conduits are attached to wood poles, the conduit must be secured with the appropriate two-hole type conduit straps that meet the current edition of the NEC. The conduit straps must not be more than four feet apart and the conduit must be supported within three feet of the termination point or fitting. Figure 11-3: Conduit on Wood Pole 11-3

Conduits attached to metal poles require a minimum of 3/4-inch stainless steel bindings that are spaced not more than five feet apart. Conduits attached to other structures must be secured as indicated in the contract documents to the satisfaction of the engineer. Figure 11-4: Conduit Attached to Bridge Underground (2565.3D) Underground conduits must be placed no less than 18 inches below the surface of any ground area and not less than 24 inches below any roadway surface. It should be noted that the depth of the conduit is measured from the top of the pipe. For example, a trench for a 4-inch conduit is 22 inches from the finished ground to the bottom of the trench. Figure 11-5: Underground Conduit Installation Conduits placed under railroad tracks must be placed no less than 57 inches below the bottom of the ties or as required by the railroad company. Figure 11-6: Conduit under Railroad Tracks For RSC and rigid PVC conduit, trenching is the accepted method of conduit installation except when the conduits are being installed under existing roadways. Conduits must not be placed until the trench has been inspected. Except for under existing pavements, HDPE (continuous length) conduit must be placed by trenching, vibratory plow with feed blade or directional boring. Figure 11-7: HDPE Conduit If installing conduit under an existing roadway using a method other than directional boring and a distortion in excess of 1/4-inch is created in the existing roadway surface due to conduit installation, the contractor must remove the distortion and restore at no expense to the department the roadway surface to its original condition. Figure 11-4: Trenching 11-4

2545.3G.2 Install direct buried lighting cable in rigid PVC or HDPE conduit if located under bituminous, concrete, or other material not considered a top soil. Provide 3 in conduit if the contract does not specify size of Figure 11-5: Conduit Requirements for Direct Buried Lighting Cable Under Hard Surfaces Direct buried lighting cable must be installed in rigid PVC or HDPE conduit under paved surfaces. If boring operations through a roadbed are abandoned for any reason, the voids must be grouted at the contractor s expense and to the satisfaction of the engineer. For handholes used on lighting systems, the contractor must install a 36-inch rigid PVC conduit stub out with the appropriate end bell for all direct buried lighting cable entering a handhole. Figure 11-9: Conduit Stub Out/End Bell Position conduit terminating in concrete foundations, and equipment pads so the conduit extends inside the pole bases, structure bases, or service cabinets as indicated in the standard plates or plan details. Slope the conduit away from the foundation and toward the handhole opening for drainage. Figure 11-6: Conduit Positioning Conduits that are stubbed out underneath the foundation for future use must extend 18 inches to 24 inches beyond the foundation or sidewalk in the direction specified by the engineer, and capped on both ends with standard pipe caps. After the cap is secured, a permanent marker should be used to draw an arrow, on the cap, indicating the direction of the conduit (as indicated in Figure 11-13). Figure 11-7: Direction of Conduit Arrow 11-5

Open Ends (2565.3D) The open ends of conduits that are located in handholes or those that extend above foundations must be capped until the wiring is installed. Figure 11-8: Capped Conduit Ends Due to some confusion with regards to rigid PVC conduit ends MnDOT has defined the ends as presented in Figures 11-13 and 11-14 (2545.1C and 2565.1C). Figure 11-10: End Bell Figure 11-9: Bell End When the RSC caps are removed a threaded insulated grounding bushing with lay in ground lug for RSC (UL Std. 467) must be installed and be compatible with a solid bare No. 6 copper bonding conductor. The lug material shall consist of stainless steel, copper, brass or bronze. Each bushing must be covered with a corrosion inhibiting compound (see 2545.3.R and 2565.3.D.4.b). Figure 11-11: Insulated Grounding Bushing 11-6

The open ends of conduits in a cabinet or foundation must be sealed in accordance with 2565.3D.2.b. After the installation of the cables and conductors use a duct seal compound NRTL classified under general use tapes. This prevents moisture from entering the cabinet or pole. The sealant also helps in preventing rodents from entering the foundation through the conduit system. Figure 11-12: Conduit Duct Seal Compound RSC Joints (2565.3D) When standard length RSC conduit is cut the end must be threaded and reamed to remove burrs and rough edges. Field cuts must be made square and true so that all ends joined by coupling butt together for the full circumference. This provides an electrical bonding and grounding connection throughout the entire length of the conduit run. If the galvanized coating on the conduit is damaged during handling or installation, the damaged areas must be painted with MnDOT approved paint to the satisfaction of the engineer. Figure 11-13: Threading and Reaming the RSC Conduit End Existing Conduit (2565.3D) If the existing underground conduit is incorporated into a new traffic control signal or lighting system, it must be cleaned and blown out with compressed air before the new wires are installed. If a new handhole is installed into an existing conduit run, the conduit must be cut, threaded and extended into the new handhole as directed by the engineer. A new bushing with an integral lug and ground wire must be installed and the sides of the handhole must be made water tight before the installation of any new wires. Thread less couplings and bushings are not permitted unless otherwise authorized by the engineer. Figure 11-18: Existing Underground Conduit 11-7

Expansion and Deflection/Expansion Fittings for Conduits used on Bridges (2565.3D.7 & 3839) Because bridges are subjected to flexing, expansion and contraction, special PVC coated expansion and expansion/deflection conduit fittings as well as hangers are required. Improper installation of conduits can cause severe damage to the electrical system and may cause damage to the bridge structure itself. The expansion fitting provides eight inches of linear Figure 11-19: Expansion Fitting movement. The deflection/expansion fitting provides 3/4 of an inch of movement in any direction. MnDOT requires contractors to obtain a separate installation certification training from at least one PVC coated RSC conduit manufacturer. Repair of damaged PVC coating shall be made in accordance with the conduit manufacturer s repair requirements. Figure 11-14: Deflection/Expansion Fitting All conduits must be attached to bridge as specified in the contract documents. 11.2 Chapter 11 Resources MnDOT Standard Specifications for Construction 3801, 3803, 2565.3D, 2545.3G.2, 2545.1C, 2565.1C, 2545.3.R, 2565.3.D.4.b, 2565.3D.7 & 3839 National Electrical Code (NEC) 11-8