Natural ventilation efficiency in a twin-span greenhouse using 3D computational fluid dynamics

Similar documents
Determining of Some Climatic Parameters with CFD in Naturally Ventilated Greenhouses

BOUNDARY SETTING IN SIMULATING GREENHOUSE VENTILATION BY FLUENT SOFTWARE

Fan and Pad Evaporative Cooling System for Greenhouses: Evaluation of a Numerical and Analytical Model

Greenhouse Design Applying CFD for Indonesian Conditions

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

Computational Fluid Dynamics Analysis of Greenhouses with Artificial Heat Tube

CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space

Interactions of Crop and Cooling Equipment on Greenhouse Climate

Performance Evaluation of Natural Ventilation Devices to Improve Thermal Comfort of a Computer Lab of University Building Using CFD as a Tool

Development of a Greenhouse System for Tropical Lowland in Indonesia

SIMGreen: A Simulation Tool for the Greenhouse Climate

Numerical Investigation of Air Flow and Temperature Distribution in a Trombe Wall System: A CFD Study

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ

On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations

LITERATURE REVIEW OF NATURAL VENTILATION Pedro Romero

Causes of Urban Heat Island in Singapore: An investigation using computational fluid dynamics (CFD)

Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers

On the performance of confluent jets ventilation system in office space

ADVANCES in NATURAL and APPLIED SCIENCES

FLUID STRUCTURE INTERACTION MODELLING OF WIND TURBINE BLADES BASED ON COMPUTATIONAL FLUID DYNAMICS AND FINITE ELEMENT METHOD

Numerical Investigation of the Air Flow in a Novel PV-Trombe Wall Based on CFD Method

A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD

Numerical Simulation of Airflow Organization and Temperature Distribution in Bulk Curing Barn Yong-qiao WANG, Yan-qiong LI, Yan ZHAO

Greenhouse Cooling and Heat Recovery using Fine Wire Heat Exchangers in a Closed Pot Plant Greenhouse: Design of an Energy Producing Greenhouse

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors

We are IntechOpen, the first native scientific publisher of Open Access books. International authors and editors. Our authors are among the TOP 1%

P. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract

VALIDATED CFD STUDY OF INDOOR ENVIRONMENTAL CONDITIONS IN A HIGHLY GLAZED, CROSS-VENTILATED MEETING ROOM

Cabin Heat Removal from an Electric Car

Sustainable Designed Air-Conditioned Mosque For Thermal Comfort

Intelligent Control Technology for Natural Ventilation Used in Greenhouse

A REVIEW OF THE CONCEPT OF DISCHARGE COEFFICIENT FOR DESIGNING NATURAL VENTILATION IN BUILDINGS

Indoor Airflow Modeling and Data Assimilation. Hengye Yang Ph.D. Student, LISC Dec. 21, 2018

Effect of Rotation Speed of a Rotary Thermal Wheel on Ventilation Supply Rates of Wind Tower System

CFD Modelling of an Aerosol Exposure Chamber for Medical Studies G. Manenti, M. Derudi, G. Nano, R. Rota

ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS

Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA

Experimental study and numerical simulation of flow pattern and heat transfer during steam drying wood

Floor-Supply Displacement Ventilation in a Small Office

Vipac Engineers & Scientists Ltd

OPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

Thermal comfort study of a hawker center in Singapore

INVESTIGATION OF FLOW CHARACTERISTICS OF HELLER-TYPE COOLING TOWERS WITH DIFFERENT COOLING DELTA ANGLES

caused by subjective factors such as oversimplified modeling for simulation, nonuniform calculation methods, casual input parameters and boundary cond

An Analytical Solution for Steady Temperature Profiles in a Vertically Stratified Environment

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

Development of a straightforward method of estimating ageof-air

SCIENCE & TECHNOLOGY

Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory

By Kimbal A. Hall, PE. Submitted to: WESTFALL MANUFACTURING COMPANY. May ALDEN RESEARCH LABORATORY, INC. 30 Shrewsbury Street Holden, MA 01520

EasyChair Preprint. Resolving the Non-Productive Periods of Solar Chimney by Integrating with Waste-to-Energy Plant

Postprint.

Fluctuating Inlet Flow Conditions for Use in Urban Air Quality CFD Studies

Sensitivity Analysis of Personal Exposure Assessment Using a Computer Simulated Person Brohus, Henrik; Jensen, H. K.

The Performance of the Passive Ventilation of Vertical Chimney in Taiwan Considering Global Warming

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS

XVII th World Congress of the International Commission of Agricultural and Biosystems Engineering (CIGR)

The Pennsylvania State University. The Graduate School. Department or Architectural Engineering THERMAL AND VENTILATION PERFORMANCE

Heat and Mass Transfer in a Large Evaporative Cooled Greenhouse Equipped with a Progressive Shading

MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD

Numerical Analysis of Solar Updraft Tower with Solar Load applied to Discrete Ordinate Model

Numerical and Experimental Modeling of Producer Gas Carburettor

Analysis of Lecturing Room using Computational Fluid Dynamics Natural and Forced Ventilation

CFD INVESTIGATION OF AIRFLOW AROUND CONIC TENSILE MEMBRANE STRUCTURES

Thermal Management of Densely-packed EV Battery Set

ENVIRONMENT. DESIGN OF SECONDARY FUME CAPTURING HOOD FOR CASTING HALL OF A SiMn PRODUCTION PLANT

Simulated Effects of Dynamic Row Spacing on Energy and Water Conservation in Semi-Arid Central California Greenhouses

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference

Changing the geometry of the Wind Tower and its Influence on Aerodynamic Behavior and Natural Ventilation

Numerical Investigation of Swirl's Effects in the Outer Annulus of a Reverse-flow Gas Turbine Combustor

A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance

Flow Patterns and Thermal Behaviour in a Large Refrigerated Store

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

Energy Consumption and Indoor Environment Predicted by a Combination of Computational Fluid Dynamics and Building Energy Performance Simulation

Numerical study on the thermodynamic characteristics. in a Twin Swirl pulverized coal Combustor

MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2

The Research of CFD applications for thermal fluid simulation of. Building Environment

THEORETICAL RESEARCH REGARDING HEAT TRANSFER BETWEEN GREENHOUSES AND ENVIRONMENT

Evaluation of Combined Application of Fog System and CO 2 Enrichment in Greenhouses by Using Phytomonitoring Data

Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

Modelling Approaches for Displacement Ventilation in Offices

MODELLING COMBUSTION AND THERMAL NO X FORMATION IN ELECTRIC ARC FURNACES FOR THE PRODUCTION OF FERRO-SILICON AND SILICON-METAL

Numerical Modelling of Air Distribution in the Natatorium Supported by the Experiment

Climatic Evaluation of Semi-Closed Greenhouses

CFD ANALYSIS OF SOLAR HEATER WATER PIPE WITH DIFFERENT INCLINATION

H POLLUTANT DISPERSION OVER TWO-DIMENSIONAL IDEALIZED STREET CANYONS: A LARGE-EDDY SIMULATION APPROACH. Colman C.C. Wong and Chun-Ho Liu*

Current Studies on Air Distributions in Commercial Airliner Cabins

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

FAST EVALUATION OF SUSTAINABLE HEATING AND COOLING STRATEGIES FOR SOLAR HOMES WITH INTEGRATED ENERGY AND CFD MODELING

CFD in Ventilation, case studies from REHVA CFD guidebook

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

A study of single-sided ventilation and provision of balconies in the context of high-rise residential buildings

CFD Simulation Studies on Integrated Approach of Solar Chimney and Earth Air Tunnel Heat Exchanger for Building Space Conditioning

NUMERICAL MODELING OF GREENHOUSE FLOOR HEATING

CFD Analysis of Earth-Air Heat Exchanger to Evaluate the Effect of Parameters on Its Performance

XVII th World Congress of the International Commission of Agricultural Engineering (CIGR)

Transcription:

Natural ventilation efficiency in a twin-span greenhouse using 3D computational fluid dynamics Costas Pontikakos, Konstantinos P. Ferentinos, Theodore A. Tsiligiridis, and Alexander B. Sideridis Informatics Laboratory Agricultural University of Athens 75 Iera Odos street, Athens 11855, Greece Abstract. In this work, a statistical analysis on greenhouse simulations to estimate the efficiency of natural ventilation in a commercial twin-span greenhouse is presented. A numerical simulation approach was adopted using the theory of threedimensional computational fluid dynamics (CFD). With this approach, threedimensional patterns for temperature and airspeed inside the greenhouse were generated, using specific boundary conditions. The CFD simulation was applied to an empty twin-span greenhouse with a floor area of 980 m 2 with low density polyethylene cover and two side continuous opening and one roof opening. The simulations assumed a sunny summer day with different airspeeds (0.0, 1.0, 2.0 and 5.0 m/s) in three directions for each non zero airspeed and three different temperature values for each airspeed (20.0, 25.0 and 30.0 o C). Keywords: Computational fluid dynamics, natural ventilation, greenhouses. 1. Introduction The main factors which characterize and influence the greenhouse environment are light, humidity, temperature, carbon dioxide concentration and ventilation rate. Ventilation is the main control method of the greenhouse s high temperatures. Natural ventilation is mostly used nowadays since it requires less energy, equipment and power than other forms of ventilation. The performance of ventilation plays an important role to the production, affecting not only the environmental conditions of the greenhouse, but the qualitative and quantitative properties of the crop product as well. Most of the information which is available up to date on the effect of the factors that influence the internal climate and the production has been collected from sporadic experiments. Most experimental work was done on empty and small houses, isolated compartments and scale models. The reasons for not using large commercial greenhouses are the high cost in time and expense to conduct detailed measurements, the possibility of yield losses during large-scale experiments in operating greenhouses, the limited availability of commercial sized greenhouses for experimental work and the complexity of the measurements. The results from smallscaled greenhouse models experiments do not represent the actual behavior of a modern commercial greenhouse. In the current available literature there is not much information on the design of naturally ventilated greenhouses. Besides, the demand

from the horticultural industry for useful information on the behavior of the greenhouse internal environment is increasing. With the aid of computational flow dynamics, a simulation of real climate conditions and greenhouse structure details can be implemented, based on given conditions. Computational fluid dynamics (CFD) is a simulation approach that is used to study the behavior of all kinds of transport processes which involve fluid flow, heat and mass transfer. Its advantages over conventional experimental studies are the low cost and development time, the availability to study situations where experiments are not possible and the ease of performing a large range of parametric studies for optimization. Typical outputs from CFD simulations are spatial and temporal distributions of flow speed and direction, pressure, temperature and concentration. CFD has been applied in a large range of applications including chemical, automotive, aerospace, nuclear industries and food processing applications. Lately, CFD has been used in horticultural research for modeling the internal climate of greenhouses. Such models can then be used to study the dependence of the internal climate on external weather conditions and control strategies. Reichrath and Davies (2002) have published a review paper that presents the stateof-the-art of the application of CFD for the modeling of greenhouses. Until now, CFD has been used for closed greenhouses (Boulard et al., 1999) and for greenhouses with natural ventilation (Mistriotis et al, 1997; Karcia et al., 1998; Lee and Short, 2000; Lee et al., 2000; Bartzanas et al., 2001). The influence of external climate (Brundrett, 1993; Miguel et al., 1997; Miguel et al., 1998; Bartzanas et al., 2001; Fatnassi et al., 2001), the number of spans (Reichrath and Davies, 2001), the presence of crops (Reichrath et al., 2000; Zhao et al., 2001; Roy and Boulard, 2004), the absence of crops (Boulard et al., 1993; Boulard and Baille, 1995; Reichrath and Davies, 2001) have been investigated on the internal climate of greenhouse. In this work a statistical analysis on the efficiency of natural ventilation in a commercial twin-span greenhouse is presented. A numerical simulation approach was adopted using the theory of three-dimensional computational fluid dynamics (CFD). With this approach, it was able to generate three-dimensional patterns for temperature inside the greenhouse, using specific boundary conditions. The statistical analysis was applied for an empty twin-span greenhouse with the same characteristics and computational parameters as those used by Pontikakos et al. (2005). The greenhouse has a floor area of 980 m 2, low density polyethylene cover and two side continuous and one roof openings. Temperature data of the entire greenhouse environment were generated by CFD simulations and the obtained results were analyzed in order to find the cases that were statistically significant on natural ventilation efficiency. The simulations assumed a sunny summer day with four different airspeeds (0.0, 1.0, 2.0 and 5.0 m/s) in three directions for each no zero airspeed (North-South, South-North and West-East) and three different external temperature values for each airspeed (20.0, 25.0 and 30.0 o C). The statistical results could be useful for the greenhouse s design and for prediction purposes. The continuation of this work will focus on inclusion of specific types of cultivation crop inside the greenhouse.

2. Materials and methods 2.1. Mechanisms Affecting Natural Ventilation Airflow Ventilation is caused by pressure difference across the opening due to thermal effect and wind forces. Natural ventilation is complex and greenhouse design is more difficult than fan ventilation. This phenomenon is induced by external wind force (wind effect) and buoyancy force (thermal effect) based on the temperature rise (temperature difference between internal and external air). Natural airflow inside greenhouses is a combination of the effects of both thermal and wind forces. Natural ventilation rate varies linearly with external wind velocity and area of ventilation openings, while it also varies linearly with the square roots of height of openings and temperature rise (Roy et al, 2002). Thermal effect When two openings are at different heights and the indoor temperature is higher than the outside, a pressure gradient is generated causing the inside air to move out of the higher openings and the outside air into the lower openings. The airflow in this case is dependent on the temperature difference between inlet and outlet as well as the aperture difference in height. Wind Forces The difference in dynamic wind pressure creates a potential for the air to flow from a point to another point where the pressure is lower (Givoni, 1981). When wind strikes a wall perpendicular to its direction of flow, the surface of the wall experiences pressure higher than that of the atmospheric pressure. This pressure difference causes the indoor air to flow from inlet/s to outlet/s located in building walls at lower surface pressure. In addition, even when the measured pressure difference between the two apertures is equal to zero, some airflow can still occur as a result of inertia from wind entering the window (Ernest, 1991; Evans, 1979) or from differences in pressure along the height of each window. 2.2. CFD 2.2.1 Principles CFD is the art and science of analyzing and simulating systems in which a fluid flow is of central interest and in which heat and mass transfer and chemical reaction may take place. Its advantages over conventional experimental studies are substantial reductions in lead times and development cost, availability to study systems where experiments are not possible and ease of performing a large range of parametric studies for optimization. The computational domain, in which a CFD simulation will take place e.g. the greenhouse plus its environment, must be well defined. This domain is divided into small cells, the control volumes, in each of which a value for the simulated variables (e.g. temperature, airspeed) is calculated and conservation principles (equations) are applied to each of these control volumes. Rate equations define the transfer rate of a transportable property. The computational effort required can be large and is dependent on the number of computational cells in the domain, the number of variables solved in each cell and the kind of simulated transport processes. Details of the basic equations and numerical method of CFD are widely available in the literature (Patankar, 1980; Hunt, 1995; Versteeg and Malalasekera, 1995).

2.2.2. Governing Equations The used CFD code (Airpak, 2002) solves the Navier-Stokes equations for transport of mass, momentum, species, and energy when it calculates laminar flow with heat transfer. RNG k-ε transport equations (ReNormalisation Group) (Yakhot and Orszag, 1986) are solved when the flow is turbulent and the Discrete Ordinates (DO) Radiation equations (Raithby and Chui, 1990; Chui and Raithby, 1993) for radiative heat transfer. 2.3. Greenhouse characteristics An empty twin-span greenhouse (Figure 1) with a floor area of 980 m 2 with low density polyethylene cover, two side continuous openings and one roof opening was used. The greenhouse characteristics are presented in the Table 1 and are the same used by Pontikakos et al. (2005). 3. Results 3.1. CFD simulations Airpak 2.10 Fluent Inc. software was used for this study. Tree-dimensional simulations were carried out and all were steady-state. Both buoyancy and thermal effects were considered. The ground characteristics were considered to be dynamic and the air was assumed real and not an ideal gas. The simulation assumed a sunny summer day with four different air speeds (0.0, 1.0, 2.0 and 5.0 m/s) in three directions for each no zero airspeed (North-South, South-North and West-East) and three different temperature values for each airspeed (20.0, 25.0 and 30.0 o C). In particular, in all simulations the computational domain was large enough to eliminate side effects of the boundaries on the pressure distribution around the greenhouse. The size of the computational domain was much larger than the greenhouse (Figure 2). Table 1. Greenhouse characteristics Scale No scale Continuous roof vent Continuous side openings Ridge height 4.2 m Gutter height 3.0 m Width 14.0 m Length 70.0 m Roof vent width 1.10 m Roof Vent pivot point 4.2 m Roof vent opening angle 19 ο Side opening width 1.12 m Latitude 37.58 o Longitude 23.32 o Orientation East-West (parallel to greenhouse length) Ground emissivity 0.9 Cladding material Low density poly-ethylene (LDPE) Cladding thickness 10-4 m Cladding visible transmittance 0.75 Source: Pontikakos et al. (2005)

At the outlet boundary, a fixed static pressure condition was chosen, being in relation to the ambient value. The RNG turbulence model was used since it was proven to give good results for internal flows in greenhouses (Mistriotis et al., 1997). The grid was an unstructured hexahedral mesh with higher density at the near wall regions around and inside the greenhouse. The CFD simulation numerical parameters are presented in Table 2. Internal temperature data of the entire greenhouse environment were generated by means of CFD simulations and the obtained results were statistically analyzed. Figure 3 displays plane cuts for the greenhouse internal temperature. Figure 1. The three-dimensional greenhouse (a) (b) Figure 2. The computational domain (a), enlarged view of the greenhouse (b)

Table 2. CFD simulation numerical parameters CFD simulation numerical parameters Mesh size Width x Height x Length=114m x 40m x 170m Turbulence model RNG model Outer boundary pressure Fixed Outer boundary temperature (T 0 ) Fixed: Cases:20 ο C, 25 ο C, 30 ο C Outer boundary airspeed (U 0 ) Outer boundary airspeed directions (D) Fixed: Cases: 0.0m/s, 1.0m/s, 2m/s, 5m/s Fixed: North-South (NS), South-North (SN) and West-East (WE) U 0 =1 m/s T 0 =30 o C D=SN U 0 =2 m/s T 0 =25 o C D=SN U 0 =5 m/s T 0 =20 o C D=SN Figure 3. Plane cuts for the temperature and airspeed velocity. 3.2. Statistical analysis The program STATGRAPHICS Plus 5.1 for Windows was used for the statistical analysis of CFD data. The statistical models that were developed are depicted in Table 3 and their accuracy is shown in the last two columns of the table.

In Table 4, twenty-three homogenous groups are identified using letters, among the thirty different cases. The levels containing the same letter denote that there are no statistically significant differences. The method that was used to discriminate among the means is Tukey's honestly significant difference (HSD) procedure. With this method, there is a 5% risk of calling one or more pairs significantly different when their actual difference equals zero. Table 3. The equations of the fitted models for internal temperature Boundary The equation of the fitted model for internal airspeed temperature direction R 2 P value No direction (nd) * 1.12633 + 1.00313 T 0 + 0.0628887 SPAN 98.1275% 0.00 ** South-North (SN) 0.955425 + 1.00053 T 0-0.140007 U 0-0.0591079 SPAN 99.7737% 0.00 ** North-South (NS) 0.442496 + 1.00505 T 0-0.209373 U 0 + 0.606219 SPAN 98.8933% 0.00 ** West-East (WE) 1.32774 + 0.998023 T 0-0.219597 U 0 + 0.162969 SPAN 99.2418% 0.00 ** * For boundary airspeed with zero value. ** Since the P-value for each estimated model is less than 0.01, there is a statistically significant relationship between the variables at the 99% confidence level. 5. Conclusions Internal temperature data of the entire greenhouse environment were generated by CFD simulations and the obtained results were analyzed in order to find the cases that were statistically significant on natural ventilation efficiency. This analysis could be useful for the greenhouse s design and for prediction purposes particularly in the case of the presence of some specific cultivation crop in the greenhouse. The continuation of this work will include specific types of cultivation crops inside the greenhouse. Statistical results showed that the external boundary temperature is a crucial parameter on the pattern of the internal greenhouse temperature. In addition, for specific external temperatures and wind directions, airspeed becomes the crucial parameter. Finally, the statistical models that were developed, have very low computational and time demands, in comparison to the original CFD simulation model and can be used for real-time estimation of temperature and airspeed patterns of the greenhouse environment. Acknowledgements This work was supported by the PYTHAGORAS-II research project which is cofunded by the European Social Fund and Greek national resources (EPEAEK II).

Table 4. Multiple Range Tests for Internal Temperature (T) by T0, U0 and D. Method: 95.0 percent Tukey HSD Case Outer Outer Internal boundary boundary Direction Homogeneous temperature temperature airspeed (D) (T 0 ) ( o (T) ( o Groups C) C) (U 0 ) (m/s) 1 20 5 SN 20.2039 a 2 20 5 NS 20.3935 b 3 20 5 WE 20.4072 b 4 20 2 SN 20.4976 c 5 20 1 SN 20.8085 d 6 20 2 NS 20.8878 e 7 20 2 WE 21.0141 f 8 20 1 NS 21.1788 g 9 20 0 ND 21.3027 h 10 20 1 WE 21.4405 i 11 25 5 SN 25.2157 j 12 25 5 NS 25.3988 k 13 25 5 WE 25.4155 k 14 25 2 SN 25.5045 l 15 25 1 SN 25.8342 m 16 25 2 WE 26.0566 n 17 25 1 WE 26.2133 o 18 25 2 NS 26.2394 o 19 25 0 ND 26.2492 o 20 25 1 NS 26.2521 o 21 30 5 SN 30.2097 p 22 30 5 NS 30.4040 q 23 30 5 WE 30.4212 qr 24 30 2 SN 30.4910 r 25 30 1 SN 30.8252 s 26 30 2 NS 30.9138 t 27 30 2 WE 31.1602 u 28 30 1 WE 31.2210 uv 29 30 1 NS 31.2938 v 30 30 0 ND 31.3340 w References Airpak 2.1 Fluent Inc., (2002). User's Guide. Bartzanas T., Boulard T., Kittas C., (2001). Numerical simulation of the airflow and temperature distribution in a tunnel greenhouse equipped with insect-proof screen in the openings. Computers and Electronics in Agriculture, Special Issue on Applications of CFD in the Agri-food Industry, 34, 207 221. Boulard T., Baille A., (1995). Modelling of air exchange rate in a greenhouse

equipped with continuous roof vents. Journal of Agricultural Engineering Research, 61, 37 48. Boulard T., Baille A., Draoui B., (1993). Greenhouse natural ventilation measurements and modelling. Acta Horticulturae Special Issue of the International Workshop on Cooling Systems for Greenhouse, Tel Aviv, May 1993. Boulard T., Haxaire R., Lamrani M.A., Roy J.C., Jaffrin A., (1999). Characterization and modelling of the air fluxes induced by natural ventilation in a greenhouse, J.Agric.Eng.Res.74, 135 144. Brundrett E., (1993). Prediction of pressure drop for incompressible flow through screens. Journal of fluids engineering, 114, 239 242. Chui E. H. and Raithby G. D., (1993). Computation of Radiant Heat Transfer on a Non-Orthogonal Mesh Using the Finite-Volume Method. Numerical Heat Transfer, Part B, 23:269-288. Ernest D. R. (1991). Predicting Wind-Induced Indoor Air Motion, Occupant Comfort, and Cooling Loads in Naturally Ventilated Buildings. Doctoral Dissertation. Berkeley: Department of Architecture, University of California, Berkeley. Evans B. H. (1979). Energy Conservation with Natural Airflow through Windows. ASHRAE Transactions, Vol.85 Part 2, pp. 641-650. Fatnassi H., Boulard T., Bouirden L., (2001). Simulation of air flux and temperature patterns in a large scale greenhouse equipped with insect-proof nets. Acta Horticulturae. Givoni B., (1981). Man, Climate, and Architecture. New York: Van Nostrand Reinhold. Hunt J.C.R., (1995). Practical and fundamental developments in the computational modelling of fluid flows, Proc. Inst. Mech. Eng. 209, 297 314. Karcia M., Short T. H., Stowell R. R., (1998). A CFD evaluation of naturally ventilated, multi-span, sawtooth greenhouses, Trans. Am. Soc. Agric. Eng. 41, 833 836. Lee I., Okushima L., Ikegushi A., Sase S., Short T. H., (2000). Prediction of natural ventilation of multi-span greenhouses using CFD techniques and its verification with wind tunnel test, presented at the 93rd Annu. Int. Meeting of ASAE, Paper No. 005003, Milwaukee, Wisconsin, USA, July 9 12, 2000. Lee I., Short T. H., (2000). Two-dimensional numerical simulation of natural ventilation in a multi-span greenhouse. Transactions of the ASAE, 43(3), 745 753. Miguel A. F., Van de Braak N. J., Silva A. M., Bot G. P. A., (1998). Free convection heat transfer in screened greenhouse. Journal of Agricultural Engineering Research, 69, 133 139. Miguel A. F., Van den Braak N. J., Bot G. P. A., (1997). Analysis of the airflow characteristics of greenhouse screening materials. Journal of Agricultural Engineering Research, 67, 105 112. Mistriotis A., Picuno P., Bot G.P.A., Scarascia-Mugnozza G., (1997). Computational study of the natural ventilation driven by buoyancy forces, Proceedings of the 3rd international workshop on mathematical and control applications in agriculture and horticulture, Pergamon Press, 1997, pp. 67 72. Patankar S.V., (1980). Numerical heat transfer and fluid flow, Hemisphere Publishing Corporation, USA.

Pontikakos C., Ferentinos K. P., Tsiligiridis T., (2005). Web-based estimation model of natural ventilation efficiency in greenhouses using 3D computational fluid dynamics. In: Proceedings of the International Congress on Information Technology in Agriculture, Food and Environment (ITAFE'05), October 12-14, 2005, Adana, Turkey. Raithby G. D. and Chui E. H., (1990). A Finite-Volume Method for Predicting a Radiant Heat Transfer in Enclosures with Participating Media. J. Heat Transfer, 112:415-423. Reichrath S., Davies T. W., (2001). Computational fluid dynamics simulations and validation of the pressure distribution on the roof of a commercial multispanvenlo-type glasshouse, Proceedings of the 1st Workshop on Management, Identification and Control of Agriculture Buildings, MICAB, January 26, UTAD, Vila Real, Portugal, 2001, pp. 78 87. Reichrath S., Davies T. W., (2002). Using CFD to model the internal climate of greenhouses: past, present and future. Agronomie 22, 3-19. Reichrath S., Ferioli F., Davies T. W., (2000). A simple computational fluid dynamics model of a tomato glasshouse, Proceedings of the International Conference and British-Israeli Workshop on Greenhouse Techniques towards the 3rd Millennium, Acta Hortic. No. 534, August, ISHS, 2000, pp. 197 204. Roy J. C., Boulard T., (2004). CFD Predictions of Natural Ventilation and Climate in a Tunnel-type Greenhouse Using a Transpiration Active Crop Model. Proc. XXVI IHC Protected Cultivation 2002. Ed. A.P. Papadopoulos. Acta Hort. 633, ISHS 2004. Roy J. C., Boulard T., Kittas C., Wang S., (2002). Convective and ventilation transfers in greenhouses, Part 1: Greenhouse considered as a perfectly stirred tank. Biosystems Engineering, 83, 1 20, doi: 10.1006/bioe.2002.0107. Versteeg H.K., Malalasekera W., (1995). An introduction to computational fluid dynamics, The finite volume method, Longman Scientific & Technical, Harlow, England. Yakhot V., Orszag S. A., (1986). Renormalization Group Analysis of Turbulence: I. Basic Theory.Journal of Scientific Computing, 1(1):1-51. Zhao Y., Teitel M., Barak M., (2001). Vertical temperature and humidity gradients in a naturally ventilated greenhouse. Journal of Agricultural Engineering Research, 78(4), 431 436.