IMPACT OF SMALL PRODUCERS ON POWER QUALITY IN DISTRIBUTION GRIDS BASED ON ELEKTRILEVI OÜ GRID

Similar documents
DISTRIBUTED GENERATION AND POWER QUALITY

WIND ENERGY INTEGRATION IMPACT ON POWER QUALITY IN ESTONIA

WIND TURBINES IN WEAK GRIDS CONSTRAINTS AND SOLUTIONS. J O G Tande and K Uhlen. SINTEF Energy Research, Norway SUMMARY

Design and Implementation of Power Quality Relaying for Renewable (Inverter-Based) and Synchronous Generation Dominion Virginia Power

World Scientific Research Journal (WSRJ) ISSN: Research on Intelligent Microgrid and its Reliable Grid Connection

WIND ENERGY CONVERTERS AND SOME ASPECTS OF POWER QUALITY

MEASUREMENTS AND SIMULATION FOR POWER QUALITY OF A WIND FARM

Wind Farm Connection to Serbian Distribution Network - Austere Quality Requirements vs. More Economical Power Distribution

ISSN Vol.03,Issue.06, August-2015, Pages:

SYNOPSIS OF THE THESIS. Enhanced Power Quality Management of Grid Connected Wind Farm

IECRE OPERATIONAL DOCUMENT

Voltage Quality Improvement Using Solar Photovoltaic System

ISSN Vol.07,Issue.16, November-2015, Pages:

Electrical Networks and Integration of Wind Energy

Grid Interconnection Issues for Wind Generation

CIGRE/CIRED/IEEE C4.24 power quality in the future grid first introduction

Interconnection of Distributed Generators and Their Influences on Power System

Grid Interconnection Standards for Distributed Resources and Microgrids

The Effect of the Volt/Var Control of Photovoltaic Systems on the Time-Series Steady-State Analysis of a Distribution Network

Analysis of DG Influences on System Losses in Distribution Network

Evaluation of measuring methods for flicker emission from modern wind turbine

CENTRE FOR WIND ENERGY TECHNOLOGY CHENNAI INDIAN WIND GRID CODE

UNOFFICIAL TRANSLATION SUPPLY OF REACTIVE POWER AND MAINTENANCE OF REACTIVE POWER RESERVES

Power Flow Control Scheme for Wind Energy Conversion System

Grid Integration of Renewable Energy. Robert S. Kaneshiro, P.E. Operations Assistant Superintendent Hawaii Electric Light Company (HELCO)

JOURNAL OF APPLIED SCIENCES RESEARCH

Wind Power Harmonic Emission versus Active-Power Production

Smart Grid, Integration of Renewable Sources and Improvement of Power Quality

ELG4126 Distributed Generation and Renewables

GENERATION CURTAILMENT AS A MEANS TO INCREASE THE WIND POWER HOSTING CAPACITY OF A REAL REGIONAL DISTRIBUTION NETWORK

Power Quality Improvement in Distribution System Using Distribution Static Compensator

ISSN MIT Publications

Impacts of the Decentralized Wind Energy Resources on the Grid

Measurements of Complex Harmonic Current on Two Wind turbines

Power control of a photovoltaic system connected to a distribution frid in Vietnam

EDF and Integration of Distributed Energy Resources

Fault Current Limiters for the Smart Grid

Phasor measurement units gain credibility through improved test and calibration standards

Smart Grid. Project Types and Technology EnerNex. All Rights Reserved.

Harmonic Reduction and Power Transmission Enhancement in a Grid Interface of Wind Power Using Shunt-Connected FACTS Device

What makes a Wind Plant Grid Friendly?

Overcoming Barriers to Power Purchasing from Very Small Renewable Energy Producers

POWER QUALITY IMPROVEMENT OF A GRID CONNECTED WIND ENERGY SYSTEM USING STATCOM-CONTROL

Smart grid concepts at TSO level

Large-scale Integration of Distributed Energy Resources within Electric Power Systems. Danish Cell Controller Project Brief

Power Quality Measurements Performed on a Large Wind Park at Low and Medium Voltage Level

Control of a Microgrid in Islanded Mode

Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25, 2012

Renewable Energy in Power Systems

ELECTRICITY SUPPLY - POWER QUALITY AND RELIABILITY Code of Practice

Hybrid Wind-Diesel Generation System

A New Cascaded 2-Level Inverter based STATCOM for Wind Power Applications

ISSN Vol.09,Issue.04, March-2017, Pages:

IMPACT OF WIND POWER PLANT OPERATION ON MV DISTRIBUTION GRIDS

Cost Savings and Efficiency through Power Quality Monitoring. National Instruments

Energy Processing for Smart Grid (4.4)

NORDAC 2014 Topic and no NORDAC 2014 http :// 3.1

Mitigation of Voltage Rise Caused by Intensive PV Development in LV Grid

Prof. Jean-Louis Lilien & Huu-Minh Nguyen University of Liège Belgium

ALSTOM Transmission & Distribution, Protection & Contrôle

Generator Interconnection Affected System Impact Study. Plains & Eastern Clean Line Final Report

A REVIEW ON POWER CONTROL SYSTEM INVERTERS WITH VARIATION POWER SYSTEM

EFFECTIVE INTEGRATION OF WIND GENERATING STATION TO POWER GRID WITH STATCOM

Reduction of Harmonics in Microturbine Generation System

Virtual Power Plant Simulation

A Transmission Planning Case Study for Wind Integration CREZ in ERCOT

Investigation of Wind Farm Interaction with Ethiopian Electric Power Corporation s Grid

DOMESTIC COGENERATION OF HEAT AND ELECTRICITY

Technical considerations for integration of distributed renewables on the grid

AORC Technical meeting 2014

Grid Power Quality Improvement and Battery Energy Storage in Wind Energy System by PI and Fuzzy Based STATCOM Controller

Testing of a Predictive Control Strategy for Balancing Renewable Sources in a Microgrid

Modernization of the Power System

Voltage Disturbances Improvement of Gird-Connected Wind Turbines in Distribution System Using STATCOM at Weak-Grid Connection Point

Integration of Distributed Renewables - Program 174

Impact of Grid Connected Photovoltaic System in the Power Quality of a Distribution Network.

Network Interconnection Studies of Distributed Generation

Generation Application Part B: Technical Form

Variable Renewable Energy Integration today's model vs. electric network of future

Siemens Power Technologies International. DER Integration Planning Distribution Planning

Power Quality Assessment of Large Motor Starting and Loading for the Integrated Steel-Making Cogeneration Facility

TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA

Study on the Application of Advanced Power Electronics in Smart Grid

Renewable Integration in India

ELECTRIC ARC FURNACE WITH STATIC VAR COMPENSATOR PLANNING AND OPERATIONAL EXPERIENCE

The Power Quality of Wind Turbines

A New Connection Concept to Connect an Offshore Wind Park to an Onshore Grid

POTOMAC ELECTRIC POWER COMPANY

Integrating Building Automation Systems with Microgrid Controls. Mingguo Hong, Associate Professor Case Western Reserve University Cleveland, OH

CASE STUDY : ASSESSMENT OF POWER QUALITY IN PRACTICE

Power Quality Improvement in Local Grid by Using STATCOM

International Journal of Advance Engineering and Research Development

Grid interconnection solutions for optimized renewable energy feed-in. Sneha Manohara Project Engineer Grid Interconnections

Mitigation of Voltage Fluctuations in Power System Using STATCOM

THE DISTRIBUTION SYSTEM SECURITY AND PLANNING STANDARDS. Asset Management & Regulation, ESB Networks

Power Quality Monitoring for Wind Farms

Modeling and Operation Analysis of Meshed Distribution Systems with Distributed Generation

ISSN Vol.07,Issue.08, July-2015, Pages:

Utility Tools and Design Modifications to Mitigate the Impact of PV on the Distribution System

Transcription:

IMPACT OF SMALL PRODUCERS ON POWER QUALITY IN DISTRIBUTION GRIDS BASED ON ELEKTRILEVI OÜ GRID Rasmus ARMAS Elektrilevi OÜ - Estonia Rasmus.Armas@elektrilevi.ee ABSTRACT The amount of distributed generation (DG) units in distribution grids has been increasing. DG has a potential for energy savings but can also have an effect on power quality, both positive and negative. This paper gives an overview of the connection procedure for DG units to Elektrilevi OÜ grid, the possible effects of DG units on power quality and present the results of practical measurements carried out at 11 DG units in Elektrilevi OÜ distribution grid. INTRODUCTION Elektrilevi OÜ is a distribution grid operator in Estonia, covering about 90% of the country. The growing interest in distributed generation has led to an increased number of DG units in the Elektrilevi OÜ grid. Since 2010 there have been 33 new distributed generation units connected and there are almost as many in construction or being connected [1]. One of the aspects of distributed generation connections is the effect on local power quality. Some research has been carried out in Estonia regarding this topic: analysis of power quality problems in low voltage networks [2], measurements at wind turbines [3] and solar panel installations [4]. The aim of this paper is to use measurement data from practical measurements at 11 producers to analyze the current situation of power quality and the effects of the DG units to see if they have an effect on local power quality and if the current connection procedure is adequate. CONNECTING SMALL PRODUCERS TO THE DISTRIBUTION GRID In Estonia DG units are usually divided into four groups based on their production capacity: - Micro producers with a production capacity up to 11 kw - Very small producers with a production capacity of 11 kw up to 200 kw - Small producers with a production capacity of 200 kw up to 5 MW - Large producers with a production capacity over 5 MW This paper focuses on small producers with a production capacity of 200 kw up to 5 MW. The connection process for distributed generation units to Elektrilevi OÜ distribution grid consists of four steps [5]: - Application to connect and network analysis - Signing the connection contract - Commissioning the electricity production equipment - Signing the network services contract During the first step of the process the client provides an application to connect, that has the main information about the generation unit. Based on this information a network analysis of the following aspects is conducted [6]: - Rapid voltage changes - Supply voltage variations - Flicker levels - Current harmonics - Short-circuit currents - Transmission capacity Rapid voltage changes ( u) that are caused by the switching of the DG unit cannot exceed 4% at the connection point. This is assessed based on the DG unit s apparent power (S n), power factor angular shift at startup (φ), starting current multiplier (k), the grid s short-circuit power () and fault impedance angle (ψ). u = k S n cos(ψ + φ) For wind turbines the following formula is used: u = k u (ψ k ) S n Supply voltage variations ( u L ) caused by the DG unit cannot exceed 4%. The variations are calculated separately for reactive power consumption and production based on the DG unit s apparent power and power factor angular shift at startup and the grid s short-circuit impedance active (R kv) and reactive parts (X kv) and nominal voltage (U N). u L = S n(r kv cos φ ± X kv sin φ ) U N 2 The long-term flicker levels emitted by the DG unit cannot exceed 0,5 in low voltage and 0,25 in medium voltage grid. This is calculated based on the flicker coefficient (c vär). P lt = c vär S n Current harmonic levels are assessed based on the DG unit s type testing results and compared to allowed levels. CIRED 2015 1/5

Table 1 Current harmonic limits A/MVA UN 0,4 kv 6,3 kv 10,5 kv 15,75 kv 21 kv 3 3 0,097 0,058 0,039 0,029 5 1,5 0,097 0,058 0,039 0,029 7 1 0,137 0,082 0,055 0,041 9 0,7 0,087 0,052 0,035 0,026 11 0,5 0,087 0,052 0,035 0,026 13 0,4 0,063 0,038 0,025 0,019 15-0,037 0,022 0,015 0,011 17 0,3 0,037 0,022 0,015 0,011 19 0,25 0,03 0,018 0,012 0,009 21-0,02 0,012 0,008 0,006 23 0,2 0,02 0,012 0,008 0,006 25 0,15 0,017 0,01 0,007 0,005 27 0,139 0,0157 0,0093 0,0065 0,0046 29 0,129 0,0147 0,0086 0,0060 0,0043 31 0,121 0,0137 0,0081 0,0056 0,0040 33 0,114 0,0129 0,0076 0,0053 0,0038 35 0,107 0,0121 0,0071 0,0050 0,0036 37 0,101 0,0115 0,0068 0,0047 0,0034 39 0,096 0,0109 0,0064 0,0045 0,0032 Sort-circuit current analysis compares the dynamic and thermal ability of the grid elements to the combined shortcircuit currents of the system and the DG unit. Transmission capacity analysis compares the maximum allowed loading of the grid elements to the DG unit s maximum production. SMALL PRODUCERS POSSIBLE EFFECTS ON POWER QUALITY Small producers can have an effect on all aspects of power quality. They can be both positive and negative. The possible effects of a producer depend mostly on the size of the producer compared to the grids short-circuit capacity. Also DG units have more effect on local phenomena such as supply voltage variation, events, flicker etc. DG units are usually not large enough to have significant effect on system frequency and in Estonia islanding is not allowed, but with larger units and a higher ratio of DG units there can be problems [7]. DG units can cause problems with supply voltages due to complications in voltage regulation [8] or due to producing only active power, which can cause overvoltages in nearby substations [7]. The problems get more difficult if the DG unit is very large and/or very deep in the grid [9]. There can also be a positive effect, especially if DG units are allowed to produce reactive power to stabilize the voltage levels [10]. Flicker can be caused by different reasons, for example small changes in the output of the DG unit can cause voltage regulators to constantly switch levels which increases flicker levels [11]. Wind turbines can cause flicker due to wind and tower turbulence [12]. Harmonic problems were serious with earlier thyristor based inverters, but modern inverters with IGBTtransistors and pulse width modulation have reduced these problems [11]. Generators can also produce different harmonics, depending on their construction either 3 rd or 5 th and 7 th. With the wider usage of power electronics there are also higher levels of even- and interharmonics, especially of higher orders [13]. Synchronous generator usually have a positive effect on voltage event duration and depth, especially if they are allowed to produce reactive power [14]. Asynchronous generator on the other hand usually have a negative effect, due to their need for reactive power that either is taken from the grid or has to be generated locally. This can lead to increased reactive power consumption from the grid during a voltage dip, thus making the dip longer and deeper. MEASUREMENT LOCATIONS AND METHODS The measurements were carried out at 11 different measurement points in 9 substations. The main information of the measurement points is presented in table 1. Table 2 Measurement points Nr UC [kv] Type MP1 6,3 Wind, IGBT inverter MP2 6,3 Wind, IGBT inverter MP3 10,5 Cogeneration, async. generator MP4 10,5 Cogeneration, sync. generator MP5 10,5 Cogeneration, async. generator MP6 1 0,23 Diesel and wind, sync. and async. MP7 10,5 Wind, async. generator MP8 10,5 Wind, async. generator MP9 10,5 Cogeneration, sync. generator MP10 15,7 Biogas, sync. generator MP11 10,5 Biogas, sync. generator 1 MP6 is a system with no synchronous connection to an interconnected system The measurements were carried out using stationary power quality analyzers that comply with IEC 61000-4-30 class A requirements and using voltage and current transformers with 0,5 accuracy class. The measurement data was collected from 2013 week 24 to 2014 week 14, that is during 44 weeks. For some measurement points the DG units were connected later and thus the measurement data is not available for the whole period. MP1 and MP2 measurements start from 05.02.2014, MP3 measurements start from 02.08.2014. MP7 data is missing between 2013 weeks 34 and 39 due to equipment malfunction. CIRED 2015 2/5

Measurement results for continuous phenomena are presented using the Power Quality Index (PQI) method. The PQI method has been chosen because measurement results from different voltage levels and systems need to be shown on the same graphs and compared. Also the PQI method gives a simpler overview. The PQI method uses a relative value that indicates the real value relative to the EN 50160 limit for the value. For example THD U values of 3,8% and 10% correspond to PQI values of 47,5% and 125%. For all continuous parameters a summery PQI value is also calculated according to the following rules: - If no parameter exceeds the limits, then the maximum individual PQI value is chosen - If one or more parameters exceed the limits, then the summery PQI value is equal to one plus the sum of the exceedances For example if the PQI values for flicker and harmonics are 1,25 and 1,3 then the summery PQI value would be 1,55 (1 plus the sum of 0,25 and 0,3). MEASUREMENT RESULTS According to the measurement results the overall level of power quality is good with the average PQI value of 44%. The summary results for all continuous parameters are presented in table 2. Table 3 Summery of measurement results Parameter Avg PQI Max PQI Frequency 1 4,5% (0,5% 3 ) Frequency 2 2,6% (1,0% 3 ) Supply voltage 18,5% 66,7% variations 1 Supply voltage 20,1% 35,5% variations 2 Flicker 43,6% 150,0% Asymmetry 22,2% 50,5% THD U 17,4% 46,2% Harmonics 5,4% 57,0% 1 Limit for 100% of time 2 Limit for 99,5%, 99% or 95% of time 3 Results for MP6 using limits for systems with no synchronous connection to an interconnected system parameters have higher values. Supply voltage variations From the measurement results it can be concluded that the supply voltage variation is not very high the average PQI value is 18,5% and the maximum is less than 67%. The variations are somewhat higher at measurement points with asynchronous generators (figure 1). This can be caused by asynchronous generators need for reactive power compensation. If the compensation is inaccurate or done in large steps the reactive power flows to and from the grid can have variations that amplify voltage variations in the grid. Figure 1 Supply voltage variations at measurement points with asynchronous generators The results are in accordance with pervious research and problems with voltage variations were not detected. Overall the DG units have not had a negative effect on voltage variations, but the possible effect from asynchronous generators needs further analysis and measurements. Voltage harmonics and flicker levels The average harmonic levels are low with the average PQI value of 17,4% for THD and 5,4% for individual harmonics. Maximum values were under 47% and 57% respectively. The harmonics levels are somewhat higher at MP6 with an average value of 35% (figure 2). This is likely caused by the grid at MP6 not being synchronously connected to an interconnected system and being very small. From table 2 it can be observed that flicker has the highest PQI values for both average and maximum. The EN 50160 limits have been exceeded only for flicker. During the measurement period there were 6 weeks when the flicker levels were above the allowed limits of EN 50160. It can be also seen that all average PQI values for individual parameters are less than the resulting average summery PQI value of 44%. This shows that individual PQI values are not related and for different weeks different Figure 2 Harmonic levels at measurement points MP1, MP2 and MP6 CIRED 2015 3/5

The flicker levels are higher and there are 6 weeks when the limits of EN 50160 are exceeded in some of the measurement points (figure 3). The average value for flicker is 43,6%. The limits are exceeded at measurement points MP5, MP8 and MP9. Figure 5 Voltage events at measurement points with asynchronous generator Figure 3 Flicker levels Analyzing the correlation between a measurement point s active power and flicker levels shows that higher flicker levels are not related to the DG unit s output (figure 4). This suggest that the DG units are not causing elevated levels of flicker but rather the flicker levels are due to some other grid phenomena. At measurement points with a synchronous generator there are fewer events that are below the ITIC lower limits when the generator is working (figure 6). This suggest that the generator is having a positive effect on voltage events, helping to sustain higher voltages and making dips shorter. Figure 6 Voltage events at measurement points with synchronous generators Figure 4 Flicker and active power scatter plot for measurement point MP5 Voltage dips and swells For voltage events the measurement data shows different results for different technologies used. At measurement points with inverters there is no difference in voltage events durations and depths. At measurement points with an asynchronous generator there are more voltage events with a duration of 1 to 2 seconds when the generator is working (figure 5). This suggest that the generator causes a longer recovery time which could be due to the local reactive power compensation. Long-term effects and seasonal variations The measurement results show no variations between different seasons but the data does show some improvement in general levels of power quality towards the end of the measurement period. During the first 26 weeks of measurements the average PQI value is 50%, but during the latter 18 weeks the average value is 38%. Figure 7 Summery PQI values CIRED 2015 4/5

CONCLUSIONS The measurement results show that overall the DG units have not had a negative effect on power quality in the Elektrilevi OÜ distribution grid and the overall power quality level is good. There are possible negative effects from asynchronous generators on supply voltage variations and voltage dips, but further measurements and analysis is needed. During the measurement period only flicker levels were above the limits set by EN 50160, but there was no correlation between DG units operation and flicker levels. There is also measurement data showing positive effects of synchronous generators on voltage dip duration and depth, but to analyze DG units positive effects the measurements have to include data from before the connection of the DG units. For future research comparative analysis for before and after should be done and measurement data should also be compared to simulation results. REFERENCES [1] "Liitunud elektritootjad," [Online]. Available: https://www.elektrilevi.ee/- /doc/6305157/kliendile/el_info_liitunud_tootjad.p df. [Accessed 19 03 2014]. [2] T. Vinnal, Eesti ettevõtete energiatarbimise uurimine ja soovitused tarbimise optimeerimiseks: doktoritöö, Tallinn: Tallinna Tehnikaülikool, 2011. [3] I. Palu, Pingekvaliteet elektrituulikuid sisaldavas nõrgas elektrivõrgus: magistritöö, Tallinn: Tallinna Tehnikaülikool, 2005. [4] A. Keerme, Päikesepaneelide mõju elektrikvaliteedile: bakalaureusetöö, Tallinn: Tallinna Tehnikaülikool, 2013. [5] Elektrilevi OÜ, "Connection for an electricity producer," Elektrilevi OÜ, [Online]. Available: https://www.elektrilevi.ee/en/kuidas-elektritootjaliitub. [Accessed 20 04 2014]. [6] Elektrilevi OÜ, Ettevõtte standard - Elektritootjate tehniliste lahenduste koostamise juhend, 2014. [7] M. Farhoodnea, A. Mohamed, H. Shareef and H. Zayandehroodi, "Power quality impacts of highpenetration eletric vehicle stations and renewable energy-based generators on power distribution systems," Measurement, vol. 46, pp. 2423-2434, 2013. [8] J. Driesen and R. Belmans, "Distributed generation: challenges and possible solutions," in Power Engineering Society General Meeting. IEEE, Montreal, 2006. [9] S. Quaia, "Distributed Generation and under load transformers operation: Voltage quality problems and possible improvements," in Power Electronics Electrical Drives Automation and Motion. SPEEDAM 2010, Pisa, 2010. [10] S. Abbott and D. J. Morrow, "Using existing distributed generation to mitigate voltage issues on the network," in Universities Power Engineering Converence. UPEC, 45th International, Cardiff, 2010. [11] P. P. Barker and R. W. de Mello, "Determining the Impact of Distributed Generation on Power Systems: Part 1 - Radial Distribution Systems," in Power Engineering Society Summer Meeting, 2000. IEEE (vol 3), Seattle, WA, 2000. [12] A. Latheef, M. Negnevitski, K. Muttaqi and S. Perera, "Present Understanding of the Impact of Distributed Generation of Power Quality," in Power Engineering Conference, 2008. AUPEC '08, Sydney, NSW, 2008. [13] K. Yang, M. H. J. Bollen, E. O. Anders Larsson and M. Wahlberg, "Measurements of harmonic emission versus active power from wind turbines," Electric Power Systems Research, vol. 108, pp. 304-314, 2014. [14] M. Venmathi, J. Vargese, L. Ramesh and E. S. Percis, "Impact of Grid Connected Distributed Generation on Voltage Sag," in Sustainable Energy and Intelligent Systems (SEISCON 2011), Internatinal Conference on, Chennai, 2011. CIRED 2015 5/5