REPORT ON COMPARATIVE AIR LEAKAGE PERFORMANCE:

Similar documents
TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey

KNIGHT WALL SYSTEMS GUIDE DETAILS:

KNIGHT WALL SYSTEMS GUIDE DETAILS:

LATICRETE International Inc. One LATICRETE Park North Bethany, CT USA

Fire Testing Laboratory

SECTION STAINLESS STEEL WALL PANELS

Test Summaries: AWP 1818 & 3030

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

TEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia

(Project Location) (your firm's name)

Cladding Attachment Through Exterior Insulation Using Long Screws PHIUS 10 TH ANNUAL NAPHC, CHICAGO COLIN SHANE M.ENG, P.ENG 11 SEPTEMBER 2015

Prepared for: American Frame Manufacturing Co Bristow Court, Unit B San Diego, CA Phone: Web:

SHEET METAL ROOF TEST REPORT

Thermal Performance of Northern Facades ISO Clip System Summary

KNIGHT WALL SYSTEMS GUIDE DETAILS:

Prepared for: American Frame Manufacturing Co Bristow Court, Unit B San Diego, CA Phone: Web:

MOCK-UP TEST REPORT. Report No: NCTL Test Dates:06/22, 07/23-27/10 Test Dates: 08/23-25/10 Report Date: 08/26/10

Energy equivalent R-value

Product Test Summaries Nichiha Fiber Cement Products Sierra Premium Boards

DUPONT TYVEK COMMERCIAL SOLUTIONS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: CITADEL ARCHITECTURAL PRODUCTS, INC.

SECTION GYPSUM BOARD

All Metals Fabrication AMF FUSION DRILLFREE ALUMINUM COMPOSITE METAL (ACM) WALL PANEL SPECIFICATION

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Carter Fabricating Inc. 326 Deerhurst Drive Brampton, Ontario L6T 5H9. Mr. Mike Libreiro

AIR INFILTRATION TESTING

KNIGHT WALL SYSTEMS GUIDE DETAILS:

Carter Architectural Panels Inc. 221 E. Willis Road A Unit 18 Chandler, AZ Mr. Bruce Bourne

Why test a system that has already been tested? Typical Manufacturers information for window to wall interface and basis for reported test results.

Ultra-High Performance Wall System Glass Fiber Reinforced Concrete

Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.

Johns Manville MinWool Water & Fire Block Mineral Wool Insulation

Insulation manufacturer to submit dew point analysis free of charge for typical wall section. Analysis by:

PROJECT LOCATION SECTION COPPER METAL PLATE WALL PANELS

THERMAL AND AIR BARRIER WALL SYSTEM

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC

SECTION REFLECTIVE-FACED, MASONRY CAVITY WALL INSULATION

Evaluation of a PanElizEd Eifs wall assembly system

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: RIEDER FASERBETON ELEMENTE GmbH

Quality Control of Air Barriers During Construction

SECTION COPPER WALL PANELS. ***This section has been updated to IBC. Verify for specific project conditions.***

Building Envelope Enclosures That Work, What Owners Want!

Corium Brick Rainscreen System Specifications

PROJECT DIRECTIVE # FOR KALISPELL PUBLIC SCHOOLS

2015 IEC Code Compliance

CRITERIA FOR TESTING IMPACT & NON IMPACT RESISTANT BUILDING ENVELOPE COMPONENTS USING UNIFORM STATIC AIR PRESSURE

Thermal Bridging From Cladding Attachment Strategies Through Exterior Insulation

Thermal Performance of Nvelope NV1 Clip System

Insulated Composite Panels Designed for Brick Back-up

PERFORMANCE EVALUATION OF THE RIVETLESS PANEL SYSTEM IN ACCORDANCE WITH AAMA FOR PRESSURE EQUALIZATION BEHAVIOR & WATER PENETRATION RESISTANCE

TEST REPORT. Rendered to: All Weather Insulated Panels Vacaville, California. PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series

REPORT NUMBER: COQ-003 ORIGINAL ISSUE DATE: July 19, 2013

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER-CEMENT SIDING REPORT HOLDER: TAKTL, LLC

Air Infiltration & the Knauf Insulation EcoSeal

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

Genesis Panel Systems LLC Dura-Max Brick Panel Siding Installation Instructions

Short Form Guide Specification. Specifying Extruded Polystyrene Roof Insulation- STYROFOAM DECKMATE Plus Tapered

Impact Resistance of Advanced Framed Wall Systems with Insulating Sheathing as the Primary Sheathing

C.R. Laurence Co., Inc. Los Angeles, California

Page 1 of 5

Welcome to this continuing education seminar. This is the first of three parts of the Building Enclosure Fundamentals series.

NRCC Guarded Hot Box Testing (ASTM C ) for Energy Efficiency of a Total Roof Assembly

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES

SECTION COLD-FORMED METAL TRUSSES

SOTA THERMO 3 SERIES SPECIFICATION FOR PREGLAZED & UNITIZED THERMO 3 CURTAINWALL SYSTEM

Central Dartmouth Section Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Dartmouth, NS

TEST REPORT ON 26 GA. PBR PANELS AT 5' 0" PANEL SPANS WITH 26 GA. SEALED N SAFE THERMAL BLOCKS IN ACCORDANCE WITH ASTM E AND AISI S907-08

Magnum Board Section Digicon Information Inc. Page 1

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

ASTM C 1363 Thermal Performance Test Report

Building Enclosure Commissioning

Architectural Wall Products Guide Specifications

1.52mm 1.52mm. Exterior Siding Sheet: Fabricated from Z275 steel material conforming to ASTM A653M grade 230 steel

Installation Guide and Safety Manual Resilmount A237R (Resilient Sound Isolation Clips)

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH

Attachment of Exterior Wall Coverings Through Polyiso to Wood or Steel Wall Framing

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

Instruction and Safety Manual Resilient Sound Isolation Clips (SIC Clips)

SECTION PRE-ENGINEERED BUILDING INSULATION

7000 Series Curtain Wall Information Specifications

3-Dimensional Thermal Analysis of Lenmak EnvaTherm and SpandrelTherm Backpan Assemblies

AUTHORIZATION TO MARK

Structural and Hygrothermal Field Monitoring of Thick Continuously Insulated Wall Assemblies Utilized in a Multi-Story Residential Building

Inigo Console Table INSTALLATION INSTRUCTIONS P74300, P A Page 1 of 5

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 8" Thick 3 Hour Fire Rated Panels SPEC ID: 29868

Welcome to this continuing education seminar. This is the first of two parts of the High- Performance Building series.

Product and System Specifications DuPont Flashing Systems

Duct Wrap Flexible Wraps

SECTION ALUMINUM COMPOSITE WALL PANELS. ***This section has been updated to IBC. Verify for specific project conditions.***

A. Omega-Lite aluminum-faced composite panels, air and vapor barrier, attachments and sealants.

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT SUMMARY. Rendered to:

NFPA 285 Assemblies. Table of Contents

FIRE RESISTANCE TESTS OF BRICK VENEER / WOOD FRAME WALLS J. GREGG BORCHELT

TECH NOTES INSULATING SOLUTIONS: THERMAX TILT WALL FIT OUT. THOMCO, Inc

2014 British Columbia Building Code Changes

Installation Guide and Safety Manual

OSHA Title 8 General Industry Safety Orders Floor Openings, Floor Holes, Skylights and Roofs

Transcription:

REPORT ON COMPARATIVE AIR LEAKAGE PERFORMANCE: Knight Wall with Carlisle 705FR-A and Dow Styrofoam Ultra SL Compared To Z-Girts with Carlisle 705FR-A and Roxul CavityRock PROJECT: LOCATION: Knight Wall and Z-Girt Air Leakage Evaluation Sanford Contracting 1400 Iron Horse Park North Billerica, Massachusetts TEST DATE: March 28, 2017 PREPARED FOR: PACE Representatives Inc. One Rockdale Street, Suite 200 Braintree, MA 02184 SUBMITTED BY: REPORT DATE: PROJECT NUMBER: Edward Mannix Vice President of Operations 31855 BUILDING ENCLOSURE ASSOCIATES, LLC Charlestown Navy Yard 31 Fifth Street, Boston, MA 02129 Tel: (617) 520 9555 Fax: (617) 520 9554 BuildingEnclosureAssociates.com DOCUMENT CONTROL NO.: R9.1.12.08.13

Page 2 of 23 INTRODUCTION Building Enclosure Associates LLC (BEA) was retained by Pace Representatives to evaluate the air leakage rate differences between Knight Wall System s HCI System and a typical Z-Girt wall assembly. The specific objective of the mockup design and testing was to determine whether Knight Wall s increased the number of screw penetrations and fasten through the rigid insulation and AVB would result in a measurable increase in the air leakage. Pace Representatives, BEA and Sanford Contracting collaborated on the design of a mockup wall assembly and testing protocol that could provide accurate comparative performances. As a secondary priority, Pace also requested that a thermal review be performed of the fully assembled wall mockup using infra-red imaging. This report documents the construction of the wall assemblies tested along with the results of the air infiltration and thermal performance tests performed by BEA and witnessed by the following personnel: Thomas Sanford Christopher Armstrong Ed Mannix Russell Young Eric Illich PACE Representatives BEA BEA BEA PURPOSE OF TESTING The intent of the testing program was to evaluate the difference in the air infiltration rate and thermal performance of Knight Wall System s HCI System and a typical Z-Girt wall assembly. PERFORMANCE SPECIFICATIONS Air Infiltration Criteria: Since project specific criteria were not stated for this testing: BEA tested at 1.57 psf, the most common pressure differential for testing air leakage in air barriers, wall assembles and building envelopes. Air infiltration rate was measured continuously throughout the construction of the exterior wall systems in accordance with an adaptation of the ASTM E 2357 testing procedure. TEST DESCRIPTION: Apparatus Tests were conducted using a portable test unit consisting of a regulated vacuum blower, a digital flow meter and digital manometer all connected to the mockup wall assembly. Calibration of all measurement equipment maintained with National Institute of Standards and Technology (NIST) traceability. Additionally, two remote thermometers were utilized throughout the testing to record variations in temperature and humidity inside and outside the test chamber.

Page 3 of 23 Pressure Measuring Apparatus: Dwyer Series 475 Mark III digital manometer with an accuracy of ±0.5% F.S. Air Flow Metering System: Digital air flow meter with the range of 0.00035 cfm to 7.06 cfm and an accuracy ±2% of reading (or ±0.002 cfm if greater) and resolution of 0.0000353 cfm. This test was the first use of the air flow meter since its calibration at an NIST lab on February 10, 2017. Thermal Imaging: A FLIR T620 Thermal Imaging Camera with an accuracy of ±2% within the working temperature range and calibrated to the International Temperature Scale (ITS-90) at the SP Technical Research Institute of Sweden was used to obtain thermal images and record surface temperatures on the inboard side of the mockup assembly. Two wireless thermometers were used to document the air temperature on the exterior side (inside thermal chamber) of the mockup assembly during the thermal performance testing. Test Methods Unless noted otherwise testing was performed in accordance with the following specifications and methods. Air Infiltration - ASTM E 2357 Standard Test Method for Determining Air Leakage of Air Barrier Assemblies The ASTM E2357 test method is intended to simulate the performance of various air barrier materials/accessories when combined into an assembly. Based on the results of the measurements, this procedure then assigns an air leakage rating for the air barrier assembly. This test method was modified to measure the air infiltration rate difference between the installation of Knight Wall System s brackets and a traditional Z-Girt system. To eliminate and\or minimize the potential influence of extraneous factors a single mockup wall assembly was utilized to measure both conditions and the tests were run contiguously to mitigated environmental variations. Multiple air flow measurements were made of the wall assembly before securing any portions of the exterior wall assembly and again after installing the exterior wall assemblies. For control purposes, four 3/16 holes were drilled in the inboard side of the mockup assembly and then sealed with tape. Multiple measurements were taken with the holes sealed and unsealed prior to any other measurements being taken and again after all other testing had been completed. The before and after measurements of the control holes provided assurance that extraneous factors did not influence the test results. The air flow rate measured prior to beginning the testing is considered to be from extraneous sources. This measurement served as the baseline from which the change in air flow rate was measured. The baseline air flow is subtracted from the flow rate measurement taken upon completion of the first specimen to determine the net increase in air flow from the construction of the specimen. The total air flow rate after completion of the first specimen also serves as the baseline for determining the net increase in air flow rate of the second specimen.

Page 4 of 23 To increase the statistical significance of the evaluation, the sampling rate was increased by decreasing the stud spacing to half the typical distance of 16 on center. This effectively doubled the number of penetrations per square foot over a typical wall construction. Thermal Evaluation In order to compare the relative thermal behavior of the two systems the following protocol was utilized: After completion of the air infiltration measurement, the interior side of the mockup wall assembly was removed and the studs and inboard side of the sheathing exposed. On the exterior side of the wall, an enclosure was constructed of DOW Styrofoam insulation panels to form a thermal chamber. The Styrofoam panels were secured to the top and ends of the mockup assembly and an insulated panel was placed on the concrete floor at the base of the wall. The thermal chamber had a depth of approximately three feet off the face of the mockup wall. Remote thermal sensors were placed on the face of the cladding (approximately 4 off the floor) in the middle of each of the two wall systems. Liquid Nitrogen was introduced through the top of the thermal chamber at the mid-point between the two systems being evaluated. The temperature inside the chamber was lowered to approximately 70 o F (seventy) below the ambient room temperature and maintained throughout the testing. Temperature readings were taken on the inboard side of the specimens throughout the test at the same three spots along the vertical centerline of each system. Temperature sampling locations were between the girt and screw locations to avoid the spots subjected to the most severe thermal influence.

Page 5 of 23 SITE CONDITIONS Indoor - Tests performed inside Sanford Contracting s fabrication facility Temperature: 56 F Relative Humidity: 50-60% TEST SPECIMEN DESCRIPTION A mockup wall assembly was constructed by Sanford Contracting to the following design specifications: Framing and Sheathing Dimensions: Height: 8, Width: 16 128 Square Feet 16 gauge 2 X 6 perimeter panel frame 16 gauge 2 X 6 vertical steel stud framing spaced 8 O.C ½ DensGlass sheathing secured to steel stud framing using ¼ X 2 self-tapping screws spaced approximately 1 O.C. DensGlass was installed on both interior and exterior side of metal studs. Carlisle 705FR-A Fire Resistant Air and Vapor Barrier applied to exterior side of mockup wall For the purpose of measuring air flow, the inboard side of the wall assembly was enclosed in DensGlass covered with Carlisle CCW 705 Air and Vapor Barrier. The sides, top and bottom of the wall assembly were also sealed to create an air tight unit. Knight Wall System HCI System The following Knight Wall System was constructed on the left (from exterior) half of the mockup wall assembly. 18 gauge Horizontal HCI-GIRT vertically spaced 12 O.C., Top HCI GIRT spaced 16 O.C. Every other HCI-GIRT fastened with 2 fasteners, 8 O.C. Other HCI-Girt fastened with 2 fasteners, 16 O.C. Self-tapping fasteners installed with ThermaStop thermal insulating washer. 3 Dow Styrofoam Ultra SL Insulation Z-Girt System The following Z-Girt system was constructed on the right (from exterior) half of the mockup wall assembly. 16 gauge Horizontal Z-Girt spaced 12 O.C., Top Z-Girt spaced 16 O.C. Every other Z-Girt fastened with one ¼ x 2 self-tapping fastener spaced 8 O.C. Other Z-Girts fastener spacing is 16 O.C. 1 /8 plastic shim placed between Z-girt and AVB at each fastener location. 4 Roxul CavityRock mineral fiber insulation Dow Corning 790 silicone sealant over fastener heads

Page 6 of 23 Exterior Cladding (applied to both halves of the mockup wall assembly) Rieder Oko Skin 5.79 x 70.87 x ½ with 1 /8 space between boards. Cladding installed vertically. 14 total boards installed on each system. Exterior cladding only fastened to girts where fastener spacing is 16 O.C. TEST RESULTS Air Infiltration tests ASTM E 2357 at a negative pressure differential of 1.57 psf (Minimum of five readings taken at each stage) Specimen Net CFM Change from wall construction Fastener Penetrations Includes 2 missed screws In each specimen cfm @ 1.57 Resulting from assembly Knight Wall HCI System 138 0.0071 Z-Girt system 70 0.0064 Total CFM Measurements at 1.57 PSF Pressure Differential Test Stage Before Installation of Exterior Wall Assemblies After Installation of Exterior Wall Assemblies a) Control hole: #1 unsealed 0.3765 0.3909 b) Control holes: #1 & #2 unsealed 0.4686 0.4866 c) Control holes: #1, 2 & 3 unsealed 0.5594 0.5686 d) Control holes: #1, 2, 3 & 4 unsealed 0.6353 0.6491 e) Total chamber with control holes sealed: 0.2942 0.3077 f) Total with Z-Girt half of wall installed: 0.2942 0.3006 g) Total with Knight Wall installed: 0.3006 0.3077

Page 7 of 23 Thermal Tests Temperature readings in degrees Fahrenheit taken from inboard side of sheathing at end of 2.5 hour test Temperature Reading Location Z-girt system Knight Wall HCI System Ambient Room Temperature 56.0 56.0 Interior Chamber, on cladding @ 4 feet from floor -12.0-12.0 Inboard side of sheathing @ 1½ feet from floor 39.9 48.8 Inboard side of sheathing @ 4 feet from floor 50.2 52.5 Inboard side of sheathing @ 7 feet from floor 50.7 53.4 The readings listed above were taken on the inboard side of the mockup during the thermal test and the sample locations deliberately avoided the coldest spots at the screw penetrations. Readings were taken at the midpoint between the studs and the midpoints between the screws. The readings listed above with taken with a laser thermometer from approximately two feet off the surface off the inboard surface of the wall to limit the size of the area being sampled. Random readings taken of broader areas from further off the wall indicated that the Knight Wall half of the mockup was between 2 to 6 degrees warmer overall than the Z-girt side. Cold transfer began to appear on the Z-Girt half of the mockup wall approximately 30 minutes into the thermal test. The infrared images revealed horizontal lines at the locations of the z-girts. As the testing progressed the images became more defined and the outline of the 1/8 plastic pads used as thermal isolators became apparent. Although the spacers set the z-girts a 1/8 off the face of the wall, the transfer of cold through the DensGlass was clearly visible. The thermal images on the Knight Wall half of the mockup were considerably less dramatic and the thermal image appeared relatively uniform when viewing the entire wall at once. In close up views, cooler areas were observed along the edges of the studs at the screw penetration locations. The cooler locations along the studs began to appear approximately an hour and a half into the test. The most pronounced cool spots on the Knight Wall half were at the two screw misses (double screws). After approximately one and half hours, the expansion of the cooler locations seemed to subside. The supply of liquid nitrogen was exhausted after two and half hours of testing and the testing was terminated at that time. We did not observe an appreciable change in the thermal image during the final hour of the test.

Page 8 of 23 APPENDIX A MOCKUP DESIGN

Page 9 of 23

Page 10 of 23

Knight Wall and Z-Girt Air Infiltration Evaluation. Page 11 of 23 APPENDIX B PROJECT PHOTOGRAPHS

Page 12 of 23 Photograph No. 1 Air Infiltration Chamber Backside of Mockup wall with Carlisle CCW-705 AVB. Photograph No. 2 Air Infiltration test apparatus installed

Page 13 of 23 Photograph No. 3 Front side of mockup with Carlisle 705FR-A AVB prior to installation of Z-Girt or Knight Wall system. Photograph No. 4 Z-Girts being installed on right (from exterior) half of mockup assembly

Page 14 of 23 Photograph No. 5 Z-Girt installation Thermally isolations spacers behind each fastener. Missed stud resulting in second penetration Photograph No. 6 Z-Girt Installation Sealant being applied over all fasteners

Page 15 of 23 Photograph No. 7 Z-Girt Installation 4 mineral fiber insulation installed to z- girts Photograph No. 8 Knight Wall Installation 3 rigid Dow insulation placement for Knight Wall System

Page 16 of 23 Photograph No. 9 Knight Wall Installation HCI-GIRTs being installed Photograph No. 10 Knight Wall Installation Fastener placement. 16 O.C. 8 O.C

Page 17 of 23 Photograph No. 11 Cladding installed to both Z-Girt and Knight Wall System Photograph No. 12 Densglass removed from back (interior) side of mockup wall to expose studs and inboard side of sheathing.

Page 18 of 23 Photograph No. 13 Interior of thermal chamber Mockup wall to right of photo Remote thermometer Photograph No. 14 Liquid Nitrogen Tank above thermal chamber

Page 19 of 23 Photograph No. 15 Z-Girt KWS Mockup wall. Z-Girt system on left. Knight Wall System (KWS) on right Photograph No. 16 Temperature distribution approximately 5 minutes into test. Inboard side of sheathing is fairly uniform at 55 F Dark areas below mock up wall indicate locations of cold air escaping chamber.

Page 20 of 23 Photograph No. 17 Approximately 30 minutes into test, thermal imaging revealed transfer of cold from Z-Girt beginning to appear. Photograph No. 18 Approximately 1 hour into test, thermal imaging began to clearly indicate location of thermal isolation pads used on the Z-Girt system.

Page 21 of 23 Photograph No. 19 Approximately 1.5 hours into test. Photograph No. 20 Approximately 2.5 hours into test. No obvious change observed in last hour of test.

Page 22 of 23 Photograph No. 21 Close up of Z-Girt section of mockup wall. Darker locations along the horizontal lines are the location of the thermal spacer. This was verified by the screw penetrations at these locations. Photograph No. 22 Close up of missed stud penetration in Knight Wall System.

Knight Wall and Z-Girt Air Leakage Evaluation Page 23 of 23 Photograph No. 23 Knight Wall system. Thermal transfer was considerably less noticeable on the Knight Wall half of the mockup. Cool areas were observed at fastener locations at the stud Missed screw Bright yellow areas along edge of studs is reflection of heat sources in room such as people. Photograph No. 24 Exterior side of mockup wall after opening the thermal test chamber following the test. Z-Girt half of wall to right of image and Knight wall to left of image. Extreme cold at base of wall