Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai

Similar documents
Performance Evaluation under the Actual Operation Condition of a Ground Source Multiheat Pump System

Measurement of COPs for Ground Source Heat Pump (GSHP) System in Heating and Cooling Mode

*Corresponding authors. Tel.: x415, address: (N. Zhu)

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Welcome Everyone. Not Quite this kind! Geothermal Heat Pumps are a indirect solar heating system! Introduction to Geothermal

FIELD TEST STUDY ON THE PERFORMANCE OF AIR SOURCE HEAT PUMP IN LOW TEMPERATURE IN BEIJING

Heat exchanger performance of ground source heat pump by water cooling method

J. Martos Departamento de Ingeniería Electrónica, Universidad de Valencia Av. Vicent Andrés Estellés S/N, Burjassot, Spain

DEVELOPMENT OF A DESIGN AND PERFORMANCE PREDICTION TOOL FOR THE GROUND SOURCE HEAT PUMP SYSTEM

Heat Pump Water Heaters: Eco-cute Living Lab Tests

Performance enhancement of a photovoltaic thermal (PVT) and ground-source heat pump system

Recent U. S. R&D results from IEA HPP Annex 41

EXPERIMENT FOR VERIFICATION OF GROUND SOURCE HEAT PUMP USING THE DIRECT EXPANSION METHOD

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

Cold Climate Heat Pump using Tandem Vapor-Injection Compressors

Song Pan et al. / Energy Procedia 142 (2017)

The Influence of Operation Modes, Room Temperature Set Point and Curtain Styles on Energy Consumption of Room Air Conditioner

Borehole storage coupled with heat pump for domestic heating system and space free cooling

Performance investigation of multiple-tube ground heat exchangers for ground-source heat pump

Investigation on A Ground Source Heat Pump System Integrated With Renewable Sources

State of the Art of Air-source Heat Pump for Cold Regions

DOE Webinar Residential Geothermal Heat Pump Retrofits

CO 2 Transcritical Cycle for Ground Source Heat Pump

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

Experimental analysis of heat-pump integrated with solar energy

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA

Long-Term Heating Test Using the Semi-open Loop Ground Source Heat Pump System

Ground Temperature Variation Around the Horizontal Collectors of a Heat Pump

EXPERIMENT AND NUMBERICAL ANALYSIS OF THE DISCONTINUOUS OPERATION FOR GROUND HEAT EXCHANGERS

Research on single hole heat transfer power of ground source heat pump system

Simulation Studies on Performance of Solar Cooling System in UAE Conditions

Ground Source Heat Pumps

A Investigation of the Performance of Two-Stage Compression Refrigeration/Heat pump System with Dual-cylinder Rolling Piston Compressor

Identified technologies for the InfraSUN pilot plant

Edwards, Killian C.; Finn, Donal; Corberan, J. M.; et al.

International Geothermal Days Romania 2012 ENERGY EFFICIENCY IN FIXED, STAGED AND VARIABLE CAPACITY GROUND SOURCE HEAT PUMPS

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

Technical and Economic Analysis on the Large-scale Application of Renewable Energy in Buildings

Modeling and analyzing solar cooling systems in Polysun

BIPV/T + ASHP - TECHNOLOGIES FOR NEAR AND NET- ZERO ENERGY BUILDINGS

Performance Analysis of a Solar Powered Adsorption Cooling System

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang

Ground Source Heat Pump System Performance: Measuring the COP

Experimental investigation on a ceiling capillary radiant heating system

Value of Air Source Heat Pumps in Light of Variable Energy Prices. Jeff Haase. Energy Design Conference February 27, 2013

Study on Water-Cooled Solar Semiconductor Air Conditioner

Design and Experiments of a Solar Low-temperature Hot Water Floor Radiant. Heating System 1

A PILOT PROJECT OF THE CLOSED-LOOP GROUND SOURCE HEAT PUMP SYSTEM IN CHINA

DIRECTIONAL-BORE GROUND SOURCE HEAT PUMP FIELD REPORT

Energy performance of a ventilation system for a block of apartments with a ground source heat pump as generation system

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

ENERGY MODELLING OF A GAS-FIRED ABSORPTION HEAT PUMP IN A RESIDENTIAL HOME FOR COLD CLIMATE USING TRNSYS

Experimental Research and Performance Analysis of a Solar-Powered. Air-conditioning System in a Green Building

HRAI Annual General Meeting. Jeremy Sager, CanmetENERGY-Ottawa, Buildings Research Group

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Heat Pump Hot Water Supply Systems

additional cooling energy consumption. Because the thermal resistance of windows has always been a weak point, even with vacuum glass or low-e glass,

Experimental analysis of a solar absorption system with interior energy storage

September Hybrid Air, Solar, and Ground Source Heat Pump Designs. Gaylord Olson, Yao Yu

Influencing Factors on Ground Heat Balance of GSHP System Xiaohong Zhang1, a *, Zehua Liu2,b, Chao Zhang3,c and Long Ma4,d

High temperature heat pump operational experience as a retrofit technology in domestic sector

The American Council for an Energy-Efficient Economy Emerging Technologies Report. Residential Ground-Source Heat Pumps July, 2007

TWO DOE-2 FUNCTIONS. Tianzhen Hong, Charles Eley, and Erik Kolderup Architectural Energy Corporation 142 Minna Street, San Francisco, CA 94105, USA

> HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION. Available range. Unit description. Options. Accessories

FIRST LARGE-SCALE SOLAR SEASONAL BOREHOLE THERMAL ENERGY STORAGE IN CANADA

Performance optimization of an air source heat pump water heater using mathematical modelling

GEOTHERMAL OVERVIEW. Presented by John Cole East Coast Account Rep. for RENEWABLE ENERGY. Construction Automotive Industry

The basic elements of the system include: Buried loops of piping (the ground loop); A biodegradable liquid antifreeze;

Introduction to Geothermal Comfort Systems in INDIA

Detailed performance assessment of variable capacity inverter-driven cold climate air source heat pumps

Geothermal Heat Pump Systems Being Green by using the Ground

Thermal Performances Of Three Types Of Ground Heat Exchangers In Short-Time Period Of Operation

SOLAR COOLING WITH SMALL SIZE CHILLER: STATE OF THE ART

Energy Efficient Solar Milk Chiller

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS

The Novel Solar Water Heating by Means of Thermoelectric Modules

STUDY ON OPTIMAL ENERGY SYSTEM DESIGN FOR APARTMENT HOUSE USING GENETIC ALGORITHMS. 375 Seosuk-dong, Dong-gu, Gwangju Korea METHODS

Application Of Oil Flooded Compression With Regeneration To A Packaged Heat Pump System

Optimal Design for a Hybrid Ground-Source Heat Pump

Thermally operated mobile air-conditioning system

Study of Performance Improvement of Air Conditioning using Various Heat Recovery Techniques

Experimental investigation of single-phase and twophase closed thermosyphon solar water heater systems

Comparison Between Simulation and Experimental Results for a Monitored Ground Coupled Heat Pump System

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE

Thermodynamic analysis of a direct expansion solar assisted heat pump water heater

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Thermal Performance and Design Guidelines of Thermo-Active Foundations

Experimental Study of a CO2 Thermal Battery for Simultaneous Cooling and Heating Applications

ASSESSMENT OF NATIONAL BENEFITS OF RETROFITTING EXISTING SINGLE-FAMILY HOMES IN UNITED STATES WITH GROUND-SOURCE HEAT PUMP SYSTEMS 1

Performance of Ductless Heat Pumps in the Northeast

A Study on Engineering Application of Solar Heating System Assisted by Heat Pump

Inverter Drive Control and Seasonal Performance Analysis of a Single Speed Unitary Air-Source Split-System Heat Pump

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

Bifluid Geothermal System New Generation

EVALUATION OF GROUND COUPLED HEAT PUMPS FOR THE STATE OF WISCONSIN

Fresh air pre-cooling and energy recovery by using indirect evaporative cooling in hot and humid region a case study in Hong Kong

Renewable Energy Based Active Cooling System

A Solar Wall System Utilized in Rural Houses of Northeast China

Transcription:

Comparative Heating Performances of Ground Source and Air Source Heat Pump Systems for Residential Buildings in Shanghai Zhaohui Liu 1,2, Hongwei Tan 1,2,3* 1 School of Mechanical Engineering, Tongji University, Shanghai, China 2 Research Center of Green Building and New Energy, Tongji University, Shanghai, China 3 C UNEP-Tongji Institute of Environment for Sustainable Development, Tongji University, Shanghai, China * Corresponding email: hw_tan@tongji.edu.cn SUMMARY As the main heat sources/sinks of heat pump systems, the ambient air and ground may have different performance characteristics. In this study, the performance comparison of an Air Source Heat Pump (ASHP) and a vertical Ground Source Heat Pump (GSHP) for space heating is presented. Both systems were installed in a residential building in Shanghai, and the ASHP and GSHP were tested in a same room under the similar weather conditions. The performance of the ASHP system largely depends on the ambient conditions. Under the same outdoor air temperature conditions, the power consumptions of the ASHP on rainy days were higher than that on sunny days, and the COPs of the heat pump unit and the heat pump system on sunny days were higher than that on rainy days. During the heating season, the weighted average COPs of the ASHP unit and the heat pump system are 2.44 and 1.9, respectively. The seasonal average COPs of the GSHP unit and the heat pump system are 5.21 and 3.03, respectively. The experimental results indicate that the GSHP system was preferable to the ASHP system in terms of energy efficiency for space heating. PRACTICAL IMPLICATIONS The aim of the present work is to analyze the relative heating performance of ASHP and GSHP system in a residential building. The purpose is to help the designer and user make decision in selection of cold and heat sources for references. KEYWORDS Power consumption, Transmission power ratio, Outdoor air temperature, Coefficient of performance, Weather condition 1 INTRODUCTION Heat pumps are increasingly popular for heating and cooling in commercial and residential buildings due to their features of sustainability and superior energy efficiency. Among these, the air source heat pump (ASHP) and ground source heat pump (GSHP) systems are probably the most competitive technologies in the current market. Because of the different properties

between the ambient air and ground, the ASHP and GSHP system may have different performance characteristics. GSHP systems are promising due to their consistent performance year round (Nagano et al. 2006). In contrast to ground, ambient air is a superior source for heat pump in terms of availability, but the ambient air annual temperature fluctuation is detrimental to the performance of the ASHP system (Soltani et al. 2015), and The major problem of ASHP systems is that their heating capacity degrades as the outdoor air temperature drops below 0 ºC (Bertsch et al. 2008). However, the energy performance differences between the ASHP and GSHP system are not very clear. The performance comparison based on the laboratory data is not representative of site running performance, which take into account the typical transient behaviour and load patterns of real life systems (Urchueguía et al. 2008). Therefore, the performance comparison between the actual operation of the ASHP and GSHP systems during similar conditions is needed. Because the ground has relatively stable temperature, the coefficient of performance (COP) of GSHPs is usually higher than that of ASHPs (Rad et al. 2013; Wang et al. 2012). Petit et al. (1997) presented a techno-economic comparison of the ASHP system and horizontal GSHP system in South Africa. And Esen et al. (2007) reported a techno-economic comparison between a GSHP system and an ASHP system in Turkey. The aim of the present work is to analyze the relative heating performance of ASHP and GSHP system in a residential building. Both systems ASHP and GSHP were installed in parallel in the same building, and large amounts of monitoring data were obtained to analyze the heating performance and characteristics. 2 EXPERIMENTAL SETUP 2.1 House description The house demonstrates the environmental-friendly and sustainable building technologies, which is located at Tongji university, Shanghai, China. The Vacuum Insulation Panel (VIP) is employed in the source-side walls. The high-level insulation and source-side shading allow the cooling/heating load for HVAC system much less time than the ordinary house. The building area is about 58 m 2, and the Load peak value in heating mode was sized at 3 kw. 2.2 Description of the heat pump systems Figure 1. Schematic diagram of ASHP and GSHP system

The ground source heat pump and the air to water heat pump are installed for space heating/cooling. Figure 1 shows a schematic diagram for the heat pump systems. The both heat pumps are linked in parallel. However, only one of the heat pumps can work at the same time. The ASHP system is composed of four circuits: condenser fan, air circuit, the refrigerant circuit, water circuit and Air Handling Unit (AHU) circuit. The GSHP system consists of four circuits: the ground heat exchanger (GHE) circuit, the refrigerant circuit, water circuit and AHU circuit. The GSHP system consists of one vertical GHE of 100m depth. The specification and characteristics of the heat pump systems for the house are given in Table 1. Table 1. The specification of the ASHP and GSHP systems Equipment Technical information Heat pump Heat pump Ground heat exchanger(ghe) Manufacturer: DAIKIN; Model: NRZQA56AV2C; Heating capacity: 5.75KW; Power Input: 1.16KW Refrigerant: R410A COP: 4.96; Cooling capacity: 5.12KW; Power Input:1.57KW COP:3.26 Manufacturer: DAIKIN; Model: NRZQA56AV2C modified; Heating capacity: 5.75KW; Power Input: 1.16KW Refrigerant: R410A; COP: 4.96 Cooling capacity:5.12kw; Power Input:1.57KW COP:3.26 Type: vertical single U-tube; Pipe diameter:0.032m material: polyethylene; Pipe thickness:0.0035m borehole depth:100m 2.3 Test apparatus and measuring equipment The data acquisition system was designed to characterize the system performance. Several sensors were installed to monitor the most relevant parameters of the system. T-type thermocouples were installed to measure the temperature the indoor air temperature, the outdoor air temperature. Three wire PT100 temperature sensors were used to measure the inlet and outlet water temperature of source-side (GSHP) and the inlet and outlet water temperature of user-side (AHU), The source-side fluid flow rate (GSHP) and user-side (AHU) fluid flow rate were measured using an ultrasonic flowmeter. The power consumption of GSHP, ASHP, source-side circulating pump, refrigerant-water heat exchange unit (HD) and Air Handling Unit (AHU) were measured using power meters. Data from the temperature sensors are collected by a data acquisition module ICPCON I-7015P. 3 RESULTS AND DISCUSSION 3.1 Power consumption Figure.2 and Figure.3 respectively demonstrate hourly average power consumption for the ASHP system and the GSHP system in heating mode during a special day. The daily average power consumptions of the ASHP system and GSHP system are 2.25kW and 1.21kW, respectively. The power consumption of the GSHP system is more stable compared with the ASHP system. It is due to the performance of the ASHP system depend on the ambient conditions more than the GSHP system. The daily average power consumptions of the ASHP system is 86% higher than that of the GSHP system. For the ASHP system, the power

Figure 2. Hourly electrical energy consumption for the ASHP system in heating mode during a special day Figure 3. Hourly power consumption for the GSHP system in heating mode during a special day consumption of energy transport components (user-side circulating pump and AHU) accounts for about 19% of the total power consumption. For the GSHP system, the power consumption of energy transport components (the source-side circulating pump, the user-side circulating pump, AHU) accounts for about 43% of the total power consumption. The transport power ratio of the GSHP system is higher than that of the ASHP system, it can be attributed to two factors. First, the average power consumption (0.69 kw) of the GSHP unit is 38% of that of the ASHP system. Second, compared to the ASHP system, the source-side circulating pump for the GHE is employed in the GSHP system, and it leads to increasing of the power consumption of energy transport components. To a large extent, the performance of the ASHP system depends on the ambient conditions. Figure. 4 and Figure.5 display the power consumption results on sunny days and rainy days, respectively. From Figure.4 and Figure.5, it can be seen that the power consumption increased with the decreasing of the outdoor air temperature. Under the same outdoor air temperature condition, the power consumptions of the heat pump unit on rainy days were higher than that on sunny days. Take the same outdoor air temperature 4 ºC on both sunny days and rainy days Figure 4. The power consumption variations with outdoor air temperature for the ASHP system on sunny days (for heating) Figure 5. The power consumption variations with outdoor air temperature for the ASHP system on rainy days (for heating)

for instance, the power consumptions of the ASHP unit were 1.49 kw and 2.06 kw, respectively. And the power consumption on rainy days increased by 38% over that on sunny days. The power consumption of heat pump was higher when it was defrosting. Because the evaporator of heat pump frosted more easily on rainy days. The relative humidity is high on rainy days. From the instantaneous power consumption, it can be found that the heat pump began to defrost when the outdoor air temperature was lower than 6 ºC in rainy days. And in the sunny day, the heat pump began to defrost when the outdoor air temperature was lower than -5 ºC. In other words, the temperature range for defrosting condition on rainy days was wider than sunny days. Figure 6. The transmission power ratio variations with outdoor air temperature for the ASHP system on sunny days (for heating) Figure 7. The transmission power ratio variations with outdoor air temperature for the ASHP system on rainy days (for heating) Figure. 6 and Figure.7 indicate the transmission power ratio variations with outdoor air temperature for the ASHP system on sunny days and rainy days, respectively. At runtime, keeping the power consumption of energy transport components constant. The transmission power ratio increased with the increasing of the outdoor air temperature due to the power consumption of the heat pump unit decreased with the increasing of the outdoor air temperature. Under the same outdoor air temperature condition, the transmission power ratio of the ASHP system on sunny days was higher than that on rainy days. Take the same outdoor air temperature 4 ºC on both sunny days and rainy days for instance, the transmission power ratios of the ASHP system were 0.22 and 0.17, respectively. And the transmission power ratio of the ASHP system on sunny days increased by 29% over that on rainy days. 3.2 Coefficient of performance (COP) of the heat pump system It can be found that the changing trend of COP was consistent with the trend of outdoor air temperature. From several days experimental data, the COPs of the ASHP system on sunny days and rainy days were investigated with respect to the outdoor air temperature as shown in Figure.8 and Figure.9, respectively. From Figure.8 and Figure.9, it can be seen that the COPs of the ASHP and the ASHP system increased with the increasing of the outdoor air temperature. As the outdoor air temperature increased from -6 ºC to 6 ºC on sunny days, the COP of the ASHP unit itself increased linearly from 1.85 to 2.42 by 31%, and the COP of the ASHP system

Figure 8. Hourly average COP variations with hourly average outdoor air temperature for ASHP system on sunny days (for heating) Figure 9. Hourly average COP variations with hourly average outdoor air temperature for ASHP system on rainy days (for heating) increased linearly from 1.55 to 1.89, by 22%. In addition, as shown in Figure.9, as the outdoor air temperature increased from 1.5 ºC to 8.5 ºC on rainy days, the COP of the ASHP unit itself increased linearly from 1.33 to 1.82 by 37%, and the COP of the ASHP system increased linearly from 1.15 to 1.44, by 25%. Under the same outdoor air temperature conditions, the COPs of the heat pump unit and the heat pump system on sunny days were higher than that on rainy days. The power consumption of heat pump was higher when it was defrosting and the higher power consumption results in lower COP. Take the same ambient condition of outdoor air temperature 4 ºC on both sunny days and rainy days for instance, the COPs of the ASHP unit were 2.33 and 1.51, respectively. And the power consumption decreased by 35%. Figure 10. Hourly average COP variations with the difference between the indoor air temperature and the outlet temperature of GHE (for GSHP heating) Figure 11. Hourly average COP variations with the difference between the indoor air temperature and the outdoor air temperature (for ASHP heating)

Shown as Figure.10, the COPs of the GSHP system decreased with the increasing of the difference between the indoor air temperature and the outlet temperature of GHE. And the average COPs of the GSHP unit and GSHP system are 5.21 and 3.03, respectively. And Figure 11. displays that the COPs of the ASHP system decreased with the increase of the difference between the indoor air temperature and the outdoor air temperature. Compared Figure.11 with Figure.10, it can be found that the difference between the indoor air temperature and the outlet temperature of GHE was smaller than that between indoor air temperature and the outdoor air temperature, and the temperature difference had effects on the performance of heat pump. To compare the performance of ASHP system with GSHP system, assuming the ASHP system run under the outdoor air temperature 5.8 ºC which is the monthly average temperature of January, February and December. According to the relationship between COP and the outdoor air temperature shown as Figure 10. The COPs of ASHP unit itself and the ASHP system under the outdoor air temperature 5.8 ºC can be calculated to be 2.41 and 1.88, respectively. The COPs of GSHP unit and GSHP system increase 116 percent and 61 percent than that of ASHP unit and ASHP system, respectively. The significant improvements in COPs of the GSHP system over the ASHP system can be ascribed to several main factors. Firstly, the temperature difference between the evaporation and condensation of GSHP system is lower than ASHP system. And it is because of the average outdoor air temperature is lower than the ground temperature. Besides, the specific of air is significantly lower than that of water, which resulted in higher power consumption of the ASHP unit over GSHP unit. In addition, the frosting and defrosting conditions of the ASHP system lead to the higher power consumption. 3.3 Heating seasonal performance Figure 12. Bin distribution for the heating season (Nov.27th - Mar. 21th) in Shanghai, China The relationship between COP and the outdoor air temperature was employed to estimate the heating seasonal performance of ASHP system. The bin data for Shanghai city in China were utilized to calculate the hourly COPs during the heating season. The heating season starts on November 27th and ends on March 21th, assuming the outdoor air bin temperature range was

varied from -6 ºC to 15 ºC for space heating. The bin distribution of this range in 1 ºC increments shown as Figure 12. According the relationship between COP and the outdoor air temperature described in Fig 8, the weighted average COPs of the ASHP unit and the heat pump system are 2.44 and 1.9, respectively, during the heating season. The seasonal average COPs of the GSHP unit and the heat pump system are 5.21 and 3.03, respectively. During the heating season, the average COPs of GSHP unit and GSHP system increase 114 percent and 59 percent than that of ASHP unit and ASHP system, respectively. 4 CONCLUSIONS In this study, a performance comparison between the ASHP system and GSHP system for space heating was conducted in hot summer and cold winter zone. The performance of the ASHP system largely depends on the ambient conditions. Under the same outdoor air temperature conditions (4 ºC) the power consumptions of the ASHP on rainy days were higher (38%) than that on sunny days, and the COPs of the heat pump unit and the heat pump system on sunny days were higher (54%)than that on rainy days. For the ASHP system and the GSHP system, the power consumption of energy transport components accounts for about 19% and 43% of the total power consumption, respectively. The average COPs of GSHP unit and GSHP system were 114% and 59% higher than that of ASHP unit and ASHP system, respectively. In sum, for space heating, the GSHP system could perform better than the ASHP system in terms of energy efficiency. 5 REFERENCES Bertsch, S.S., Groll, E.A. 2008. Two-stage air-source heat pump for residential heating and cooling applications in northern U.S. climates. International Journal of Refrigeration, 31(7), 1282-1292. Esen, H., Inalli, M., Esen, M. 2007. A techno-economic comparison of ground-coupled and aircoupled heat pump system for space cooling. Building and Environment, 42(5), 1955-1965. Nagano, K., Katsura, T., Takeda, S. 2006. Development of a design and performance prediction tool for the ground source heat pump system. Applied Thermal Engineering, 26(14), 1578-1592. Petit, P., Meyer, J. 1997. A techno-economic analytical comparison of the performance of airsource and horizontal-ground-source air-conditioners in South Africa. International Journal of Energy Research, 21(11), 1011-1021. Rad, F.M., Fung, A.S., Leong, W.H. 2013. Feasibility of combined solar thermal and ground source heat pump systems in cold climate, Canada. Energy and Buildings, 61, 224-232. Soltani, R., Dincer, I., Rosen, M.A. 2015. Comparative performance evaluation of cascaded air-source hydronic heat pumps. Energy Conversion and Management, 89, 577-587. Urchueguía, J.F., Zacarés, M., Corberán, J.M., Montero, Á., Martos, J., Witte, H. 2008. Comparison between the energy performance of a ground coupled water to water heat pump system and an air to water heat pump system for heating and cooling in typical conditions of the European Mediterranean coast. Energy Conversion and Management, 49(10), 2917-2923. Wang, E., Fung, A.S., Qi, C., Leong, W.H. 2012. Performance prediction of a hybrid solar ground-source heat pump system. Energy and Buildings, 47, 600-611.