TWENTY FIVE YEARS OF PRODUCTION HISTORY AT THE MOMOTOMBO GEOTHERMAL FIELD, NICARAGUA

Similar documents
The Momotombo Reservoir Performance upon 27 Years of Exploitation

Benefits from the Utilization of a Calcium Carbonate Inhibition System for Production Wells at the Miravalles Geothermal Field

GEOCHEMICAL CHARACTERIZATION AND INTEGRAL ANALYSIS OF DATA LAS PAILAS GEOTHERMAL FIELD, COSTA RICA

COSTA RICA COUNTRY UPDATE

Geothermal Development in Central America

RESPONSE OF OLKARIA EAST FIELD RESERVOIR TO PRODUCTION

NOTICE CONCERNING COPYRIGHT RESTRICTIONS

SUSTAINABILITY ANALYSIS OF THE BERLIN GEOTHERMAL FIELD, EL SALVADOR. Manuel Monterrosa, LaGeo El Salvador

NOTICE CONCERNING COPYRIGHT RESTRICTIONS

Performance Improvement of Single-Flash Geothermal Power Plant Applying Three Cases Development Scenarios Using Thermodynamic Methods

INCREASED PRODUCTION LOAD IN TONGONAN GEOTHERMAL FIELD, PHILIPPINES: RESERVOIR RESPONSE AND FIELD MANAGEMENT STRATEGIES

The model was developed on the TETRAD reservoir simulator.

FIRST SEVEN YEARS OF EXPLOITATION AT THE MIRAVALLES GEOTHERMAL FIELD

Improved Efficiency of Solid Trap Installed in Brine Injection Pipeline of Leyte Geothermal Production Field, Philippines

COUNTRY UPDATE REPORT FOR KENYA

Geothermal Energy in El Salvador

Production/Injection Optimization Using Numerical Modeling at Ribeira Grande, São Miguel, Azores, Portugal

Fig. 1. Well field location

NGAWHA GEOTHERMAL FIELD EXPANSION PROJECT. GEOTHERMAL FLUID CONVEYANCE SYSTEM

PHASES OF GEOTHERMAL DEVELOPMENT

GEOTHERMAL DEVELOPMENTS IN CENTRAL AMERICA

REINJECTION STRATEGY FOR GEOTHERMAL SYSTEMS

PROJECTS AND CHALENGES STRASBOURG 2006 ORMAT

ORMAT Nevada, Inc. Expansion and Improvements Raise Power Production 20%

Ahmad Yani PT. Pertamina Geothermal Energy Lahendong, Jl. Raya Tomohon no. 420, North Sulawesi

Experiences, Successes and Challenges in Sustaining Long-Term Production at the Tiwi Geothermal Field

NOTICE CONCERNING COPYRIGHT RESTRICTIONS

Binary Power Plants in New Zealand

The First Two-Phase Tracer Tests at the Matsukawa Vapor-Dominated Geothermal Field, Northeast Japan

OPERATIONAL EXPERIENCE GAINED ON REHABILITATION OF THE ALUTO LANGANO GEOTHERMAL POWER PLANT

NOTICE CONCERNING COPYRIGHT RESTRICTIONS

ANALYSIS OF WORKOVER TECHNIQUES IN GEOTHERMAL WELLS OF CERRO PRIETO FIELD, MEXICO

Performance Analysis and Stimulation of Dry Steam Wells in Mak-Ban Geothermal Field, Philippines

IRON METERS FOR PRODUCTION WELLS AT THE MIRAVALLES GEOTHERMAL FIELD

Steam Supply Sharing Through Steamline Interconnection The Tongonan Geothermal Field Experience, Philippines

Organic Rankine Cycle Configurations

REASSESSMENT OF THE THELAMÖRK LOW TEMPERATURE GEOTHERMAL SYSTEM IN N-ICELAND FOLLOWING SUCCESSFUL DEEPENING OF WELL LÞN-10

WELLHEAD POWER PLANTS

SIMULATION AND PERFORMANCE ANALYSIS OF THE NEW GEOTHERMAL CO-GENERATION POWER PLANT (OV-5) AT SVARTSENGI

MAINTENANCE OF OLKARIA 1 ADDITIONAL UNITS (AU) POWER PLANT

EXERGY ANALYSIS FOR THE AHUACHAPAN AND BERLIN GEOTHERMAL FIELDS, EL SALVADOR

Sustainable Utilization of Geothermal Resources through Stepwise Development

Field Performance Evaluation of the Largest Geothermal Organic Rankine Cycle Plant

Injection Management in Kawerau Geothermal Field, New Zealand

Geothermal Resources and Development in Guatemala Francisco Alberto Asturias

Key words: Ethiopia, country update, geothermal exploration, development, pilot power plant

Evolution of Balçova Geothermal District Heating System Turkey

NOTICE CONCERNING COPYRIGHT RESTRICTIONS

ALCOHOL TRACER TESTING AT THE MATSUKAWA VAPOR-DOMINATED GEOTHERMAL FIELD, NORTHEAST JAPAN

The Geysers Geothermal Field, an Injection Success Story

Geothermal Development in El Salvador Update

An assessment of renewable energy generation in a conventional steam power plant with geothermal feedwater preheating

Decline Curve Analysis for Production Forecast and Optimization of Liquid-Dominated Geothermal Reservoir

Maintenance history of surface pipes and plants case history of the Svartsengi geothermal plant

MASTERING REINJECTION IN THE HELLISHEIDI FIELD, SW-ICELAND: A STORY OF SUCCESSES AND FAILURES

Binary Cycle Geothermal Power Systems

ph MODIFICATIONS FOR SILICA CONTROL IN GEOTHERMAL FLUIDS

ORC Binary solutions for high enthalpy resources. Daniel Jira - GIM Joseph Bonafin Turboden Mitsubishi Heavy Industries

Neutralization of Acid Fluids from Well H-43 (Superheated Steam), Los Humeros Geothermal Field, Mexico.

Costa Rica Country Update Report

Tracer Dilution Measurements for Two-Phase Geothermal Production: Comparative Testing and Operating Experience

GEOFAR : Innovative geothermal technologies Last modifications: BINARY PLANTS

RESOURCE ASSESSMENT II: COMPUTER MODELLING AND NUMERICAL SIMULATION

ABSTRACT. Figure 1. Geothermal areas of interes in Guatemala 2. AMATITLÁN GEOTHERMAL FIELD

Multiple Zone Geothermal Stimulation Case Study: Fluid Diversion Using Thermo-Degradable Zonal Isolation Materials

The Potential for Energy Recovery and Electricity Generation in High-Pressure Production Wells and Gathering Systems Using Turboexpanders

McGinness Hills Case Study of a Successful Expansion

Water Dependency of Geothermal Power Generation Systems

Proven Geothermal Technologies Provide Clean, Reliable Power

GEOTHERMAL POWER PLANTS FOR MEDIUM AND HIGH TEMPERATURE STEAM AND AN OVERVIEW OF WELLHEAD POWER PLANTS

Discrete Fracture Embedding to Match Injection Returns in a Single Porosity Model

Guidance page for practical work electricity production from geothermal energy

NOTICE CONCERNING COPYRIGHT RESTRICTIONS

Reservoir Management at the Miravalles Geothermal Field, Costa Rica

Project LOW-BIN Efficient Low Temperature Geothermal Binary Power

OLKARIA III OPERATIONS & MAINTENANCE SIX YEARS OF EXPERIENCE

Guido Cappetti', Paolo Fabio and Bruno. ENEL Via Andrea PISA Via G NOVARA

Numerical Analysis of MCY01 Production Well Mechanism: Understanding of Well Coughing Phenomenon and Irregular Productivity

20/06/2011 Seminar on Geothermal Exploitation Santiago de Chile

Renewable Energy Systems 10

Isotope Techniques and Geothermal Resources Management

PARABOLIC TROUGH PROJECT IN CERRO PRIETO, MEXICO

Nicaragua. Geothermal Development in Nicaragua Ing. Donald Espinosa Ing. Mario González Ministry of Energy and Mines

Energy Recovery Using Turboexpanders in Production Wells and Gathering Systems With High Pressures

F. Kabus, G. Möllmann, F. Hoffmann and J. Bartels

EVALUATION OF MICROGRAVITY BACKGROUND AT THE UNDISTURBED OGUNI GEOTHERMAL FIELD, JAPAN

Geothermal Energy Future Development

Realizing the Potential of Base Load Electricity Generation from Geothermal Sources: the San Jacinto-Tizate Field

Geothermal Steam Turbines for Various Purposes

Resource Risk Assessment in Geothermal Greenfield Development; An Economic Implications

Sustainable Management of Geothermal Resources and Utilization for Years

Evolution of the Miravalles Geothermal Field in Costa Rica after Ten Years of Exploitation

MODELING OF THE MUTNOVSKY GEOTHERMAL FIELD EXPLOITATION IN CONNECTION WITH THE PROBLEM OF STEAM SUPPLY FOR 50 MWe PP

ENEL strategy for development of Geothermal and other Renewable energy in Central America. Carlos Esquivel ENEL Latinamerica

EDUARDO E. GRANADOS PRESENT POSITION. Senior Advisor - Drilling and Well Testing

Magma On the other hand, molten rock is under active volcanoes at accessible depths. The temperatures excess 650 o C.

SILICEOUS SCALING ASPECTS OF GEOTHERMAL POWER GENERATION USING BINARY CYCLE HEAT RECOVERY

31.3 GEOTHERMAL CYCLES

Flow Testing Results from Habanero EGS Project

Geomizer - A Tool to Predict Optimum Dose for Mitigating Scale in Geothermal Systems, Especially Power Plants

Transcription:

GEOTHERMAL TRAINING PROGRAMME 3 th Anniversary Workshop Orkustofnun, Grensásvegur 9, August 26-27, 28 IS-18 Reykjavík, Iceland TWENTY FIVE YEARS OF PRODUCTION HISTORY AT THE MOMOTOMBO GEOTHERMAL FIELD, NICARAGUA Enrique A. Porras M. ORMAT Momotombo Power Company Centro FINARCA detrás antiguo SANDY S Carretera a Masaya, Módulos 1 y 11, Managua NICARAGUA eporras@ormat.com ABSTRACT The Momotombo geothermal field in Nicaragua is a good example of field management how revitalizing and improving steam production of the field succeeded after improper operation of the field for years. This paper presents the production history of the field from 1983 to 28. Till 1999 the geothermal system of Momotombo suffered from over-exploitation that induced excessive flashing and intrusion of cold water in the reservoir resulting in a drastic decline of electricity generation and brine was discharged into Lake Managua. In 1999 ORMAT took over the concession for 15 years, invested more than US$ 45 million to drill four production wells, installed a 7 MWe bottoming unit, and implemented a full reinjection. Today, the Momotombo geothermal field can produce 32 MWe of its 77 MWe installed capacity. The geophysical studies and reservoir modelling show that even with an intensive well maintenance program more steam cannot be produced from the present concession area. To supply steam to the second steam turbine of 35 MW additional wells have to be drilled outside the boundaries of the present concession. ORMAT has proposed to make the necessary investment if the concession area is increased and its term is extended beyond the 6 remaining years to enable recovery of the additional investment. 1. INTRODUCTION Nicaragua is endowed with the largest geothermal potential of the Central American countries due to the presence of the Marrabios range along the Pacific coast. Geothermal surveys started in Nicaragua in 1966. An exploration program in the western part of the country was carried out in the early 7 s that led to the selection of ten geothermal areas (Figure 1): Momotombo, San Jacinto, El Hoyo, Granada-Masaya-Nandaime, Cosiguina, Casita - San Cristóbal, El Ñajo, Chiletepe-Managua, Masaya-Tipitapa and Ometepe with an estimated power potential in the order of 11 MWe COSIGUINA HONDURAS CASITA - SAN CRISTOBAL LEGEND SAN JACINTO Volcano Geothermal area EL ÑAJO EL HOYO CHILTEPE - MANAGUA MANAGUA LAKE GRANADA - MASAYA - NANDAIME MOMOTOMBO MANAGUA CITY MASAYA - TIPITAPA ZAPATERA OMETEPE NICARAGUA LAKE COSTA RICA FIGURE 1: Location map of the geothermal areas in Nicaragua 1

Porras 2 3 th Anniversary Workshop (Porras, 25). Currently, Momotombo and San Jacinto are the only geothermal areas producing steam for power generation with an installed capacity of 77 and 1 MWe, respectively. 2. EXPLOITATION HISTORY Electricity generation using geothermal steam began in 1983 when a 35 MWe condensing type unit was commissioned in Momotombo. Between 1983 and 1989, five shallow wells were drilled and started producing steam and water mixture. These wells are MT9, MT12, MT2, MT23 and MT27. Separated water from wells MT9, MT23 and MT27 (Figure 2) were connected to the reinjection system, and consequently an average of 2% of the produced brine was reinjected back into the reservoir during this period with four reinjection wells. Power output started decreasing from the end of 1986 (Figure 3) when well MT9 stopped discharging because of a casing collapse. 2.1 Over exploitation of the field MT16 OM52 MT1 2 4 6 8 1 m Even though reservoir engineering studies suggested that the field was not capable of sustaining 7 MWe by only shallow production wells (DAL SpA, 1989), the second 35 MWe condensing type unit was installed and commissioned in March 1989 when additional six shallow wells were online for this unit without any new reinjection well. Among others, over-exploitation of the reservoir and a lack of Power Generation (MWe) 7 6 5 4 3 2 1 MT43 2 RMT2 LEGEND WELL MT43 ELEVATION, m DIRECTIONAL WELL INJECTION WELL RMT2 MT38 on line MT43 MT41 MT42+43 on line MT31 MT33 MT8 MT36 MT11 OM53 MT34 MT27 MT38 MT28 MT4 MT23 MT14 MT5 MT37 MT4 MT2 MT21 MT22 MT26 MT35 MT12 MT17 MT13 MT9 OM54 MT25 MT24 MT2 MT42 MANAGUA LAKE MT32 MT7 MT19 POWER PLANT RMT15 OM51 3 MT3 RMT6 FIGURE 2: Location map of wells MT8 on line MT4+4 on line MT5 on line ORMAT RMT18 RMT2 MT29 MT1 RMT1 RMT3 N PUNTA SALINITAS 1983 1984 1986 1988 199 1992 1994 1996 1998 2 22 24 26 28 FIGURE 3: Power generation history of Momotombo geothermal field, Nicaragua

3 th Anniversary Workshop 3 Porras a proper field development strategy, resulted in a fast decline of the power output from 69 MWe in 199 down to 9 MWe in 1999. Such a quick decrease of power output promoted drilling of four makeup wells and work over for one well. Furthermore, two existing wells were investigated and found to be productive. They were connected to the steam gathering system. These operations resulted in recovery of steam production. All these wells were on line between 1992 and 1997. In spite of these additional wells, decrease of output still remained. Wellbore surveys in 1996 and 1997 revealed that most of the shallow wells located in the central part of the well field were damaged by scaling, and other shallow wells in the eastern part were suffering from cooling. In 1999, the output dropped down to about 8 MWe when only 7 wells were producing (Figure 3). These wells have deep feed zones (8 and 2 m b.s.l.) except MT27 (3 m b.s.l.) (Figure 2). The results of the over-exploitation of the field and lack of reinjection of separated brine to the reservoir are described in the following sections. 2.2 Cooling of main feed zones Figure 4 shows the histories of specific enthalpy of the produced fluid (solid red line) and total flow rate (open circles) for wells MT2 and MT12. We can see that both wells produced high-enthalpy fluid for most of the time. However, a quick decrease in enthalpy started in both wells in 1997 and 1996, respectively, when they failed to produce at the required separator pressure due to low temperature at feed zones. 2.3 Calcite scale within wellbore Figure 5a shows a picture of wellbore MT35 at about 862 m depth taken with a down hole video (DHV). It is clearly shows calcite Qt (kg/s) Qt (kg/s) 1 8 6 4 2 1 8 6 4 2 (a) MT12 83 87 91 95 99 3 scale deposit on the surface of the wellbore and how it clogged the wellbore and thus reducing production rate of this well, which also failed to discharge at required separator pressure. Other problems found in producer and reinjection wells were mechanical damages. For example, Qt Ht MT2 (b) 83 87 91 95 99 3 3 25 2 15 1 5 3 25 2 15 1 5 FIGURE 4: Production history of wells MT12 and MT2 Ht (kj/kg) Ht (kj/kg) (a) (b) (c) Calcite scaling Well MT35 Hole in Casing Well MT36 Casing collapse Well MT42 FIGURE 5: Different mechanical problems found in Momotombo wells through a down hole camera survey

7 Porras 4 3 th Anniversary Workshop Figure 5b shows a picture at about 514 m depth within the production casing of well MT36 where cold shallow groundwater flowing into the well through a hole can be clearly seen. Inflow of such cold fluid into the production well decreases the enthalpy of the produced fluid and results in reducing steam production and unstable discharging. Figure 5c shows a picture taken at 168 m deep in well MT42. A casing collapse is also found in this picture. Such failures are commonly due to an inadequate cementing job during drilling. 3. REHABILITATION OF MOMOTOMBO BY ORMAT As a result of an international bid, ORMAT signed a 15-year concession and power purchase agreement (PPA) contract with Nicaraguan Electric Company (ENEL) in March 1997 to exploit the Momotombo field and manage the power plant for improving reservoir management and increasing the power output. Since then, the installed capacity of the plant has increased to 77 MWe and currently it produces between 3 and 35 MWe supported by intensive well maintenances (Figure 6). In July 1999, ORMAT started to manage the Momotombo geothermal field and power plant, right after a power output recovery program started which is described in the next section together with results. 3.1 Geophysical survey An integrated geophysical exploration program was executed in 2 to define production target areas and specific drilling targets using integrated suite of geophysical methods that included: self potential, gravimetry, aeromagnetics, microearthquake monitoring, review of existing resistivity data, remote sensing data including aerial photo, LandSat and RadarSat images, and temperature survey at 1 m depth. As a result, two target areas were chosen and recommended; one area was located within the well field, and the other area was identified in the surrounding exploration concession. 4 Power Outpu (MWe) 3 2 1 ORMAT Geophysical and geological studies Work over : 27 operations Drilling : Four deep wells Calcite Scale Inhibitors : 7 out of 11 production wells Acid Stimulation : Three wells Full Reinjection OEC start up New pumping system for full reinjection All producer wells connected to the gathering reinjection system Second Acid stimulation: Three Acid jobs in wells MT35 and 42 Down hole Video Survey A new reservoir assesment Assesment of mechanical failure of casings in active wells Power output recovery program continues by a third acid stimulation campaign of ten wells and workover of three wells Turbines mechanical failures Silica scale inhibitor + Cold injection system 1999 2 21 22 23 24 25 26 27 28 FIGURE 6: Gross power output generation from 1999 to 28

3 th Anniversary Workshop 5 Porras 3.2 Drilling of four deep wells Four deep wells were drilled by ORMAT between 21 and 22, following the geophysical study results. A total length of 797 m was drilled from which well OM53 resulted to be commercially productive and has become the best steam producer of the field. Another well, OM52, is now used as a brine injector. Geophysical studies suggest deep drilling targets (deeper than 25 m) for production wells. Of the four wells drilled by ORMAT, none except OM52 (> 28 m) did reach 21 m. The deep targets are still considered promising for steam production in order to increase the current power output up to the current installed capacity of 77 MWe. ORMAT is willing to invest in new studies and drillings only if concession term is extended beyond the remaining six years. 3.3 First work over campaign Parallel to the drilling deep wells, ORMAT carried out a work over program on selected wells. This program included deepening, mechanical cleaning of calcite scale, running new liners, cementing and fishing jobs. A total of twenty seven operations in eleven wells were carried out. An increase of 15.4 MWe in power output was the result of the work over program (Figure 6). 3.4 Calcite scale inhibitors Due to the high risks and costs of the mechanical cleanings, it was decided to install calcite scale inhibition systems in seven out of eleven producer wells. The inhibition system has been working continuously with high efficiency for the last seven years. 3.5 First acid stimulation campaign Cleaning and acid stimulation were carried out between June 15 th and July 7 th 22 using a 2 ⅜ coiled tubing and scale blaster. The cleaning operation was conducted by Schlumberger in wells MT4, 35 and 42. These three wells were identified to be suffering from calcite scale within wellbore and formation, as well as from formation damage due to drilling mud. As a result, an increase of 4 MWe was achieved with this acid stimulation campaign (Figure 6). 3.6 Commissioning of an ORMAT Energy Converter (OEC) A 7 MW ORMAT Energy Converter (OEC) unit was installed in October 22 at the Momotombo geothermal field. The decision to install this unit was taken after a 6 six months field test with the brine from producer wells (Kaplan, 24). The test results showed that brine temperatures could be dropped down to 1 C without changes to heat exchange capacity due to silica scaling on heat exchange pipes. However, reinjecting heat depleted brine of 1 C after installing the OEC unit was a concern from the viewpoint of reservoir management. Therefore, a tracer test was carried out in the field for quantitative evaluation of connectivity among wells. On January 23 four different tracer materials were pumped into the reinjection wells. Water samples were collected at all the production wells. The test results suggested that reinjection wells RMT2 and RMT6 effectively support reservoir pressure with only limited thermal cooling on production zone. Reinjection well RMT18 has a better communication with the production zone compared with the previous two reinjection wells. Finally, the excellent connection between reinjection well RMT15 and the production zone was confirmed, thus it was concluded that this well could cause marked cooling in the Momotombo reservoir. As a result of the tracer test, a new reinjection strategy was adopted. A limited amount of injection fluids went into well RMT15, maximizing reinjection both in RMT2 and RMT18. Two old wells (MT1 and MT3) located in the eastern part of the field were connected to the reinjection system in order to increase injection capacity of the well field.

Porras 6 3 th Anniversary Workshop Once the heat of the produced brine has been converted to electricity in the bottoming unit, ORMAT will have fulfilled one of its commitments to environment which is to reinject 1% of the produced brine. This is an important part of the field management scheme that ORMAT started to implement in 1999 after taking over the project. 3.7 Second acid stimulation campaign Soon after the OEC came on line, the maximum power output was attained (38 MWe, Figure 6). However, months later some producer wells showed scale problems such as MT42 and MT35. The second acid stimulation campaign took place in 24, but ORMAT designed and built its own acid mixing and pumping unit for this project. Then, well MT42 was stimulated twice and MT35 once. This resulted in a power output recovery of 2 MWe which was contributed solely by well MT42. 3.8 Work over and the third acid stimulation campaign (26) Ten wells were identified from the analysis of production data; produced fluid chemistry and DHV survey carried out in 25 to have both mechanical and scaling problems. Two wells, MT42 and MT36, had casing collapse and broken casing. Other wells were selected for deeper redrilling (MT35 and MT27) and acid stimulation (MT35, 18, 3, 27, 42, 53 and 31). The results were an increase in production rate of steam 6 t/h and brine 2 t/h that was equivalent to 8 MWe. 3.9 Silica scale inhibition After operating for about one year, silica scale and deposition started to occur in the OEC s heat exchangers. Silica concentration of the brine sent to the flash vessels is approximately 65 ppm. This level of silica becomes over saturated as the brine temperature drops from 148 to 19ºC through the OEC heat exchangers. Under these conditions, silica is over saturated approximately 1.4 times and silica scale can occur in the heat exchangers tubes. Furthermore, silica scale was observed in the outlet section of the preheater and vaporizers, and flow rate of brine through the OEC was reduced together with power output. As a first countermeasure, preheaters and vaporizers were cleaned six times with HF acid solution between 24 and 27. Time intervals for cleaning became shorter with time. Hence, it was decided to run a six months test with the Geosperse 511 to control silica scaling and injection lines to wells. Amorphous silica and co-precipitated silica scales have been effectively controlled using this chemical after six months of testing. Figure 7 shows flowrate of brine (blue solid dots) and power generation history (red solid dots) of the OEC. The figure shows that both values become stable after the inhibitor started to be pumped at the entrance of the OEC in January 28. The feed rate of chemicals has been kept to 4 ppm for brine at a flow rate of about 1 t/h. The chemical injection system is composed of a chemical metering pump, stainless steel injection quill and ¼ capillary tubing has been used as injection system. Scale control performance has been monitored since the beginning of the test by using retractable deposition coupons at the inlet of OEC and the farthest injection well from the inhibitor injection point. Deposition coupons were weekly inspected, measured, and weighted in order to detect any changes with time and to compare with the operational activities of the OEC. 4. CONCLUSIONS 1) From 1983 to 1999 the geothermal system of Momotombo suffered overexploitation that induced excessive flashing and intrusion of cold water in the reservoir. This resulted in a significant decline of steam production as well as electricity generation and clogging of the injection wells and the improper management of the reinjection system which led to the discharge of the brine into Lake Managua.

3 th Anniversary Workshop 7 Porras 1 Gross Power Brine Flow rate 15 8 Gross Power (MWe) 6 4 1 Brine Flow rate (t/h) 2 Acid Cleaning 1/23 1/24 1/25 1/26 1/27 1/28 Date FIGURE 7: Brine flow rate and gross power generation histories of the OEC Unit 2) Since ORMAT took over the Momotombo geothermal field and power plant, most of the problems that ORMAT inherited from the past operations have been solved by applying all available technologies for exploiting the resource under a sustainable environmentally responsible scheme including full reinjection. 3) Production records, geophysical studies and reservoir modelling show that in spite of ORMAT s more than US$ 45 Million investment, the area presently allocated to the geothermal reservoir of Momotombo can not supply steam for more than 32 MWe of power output (23-24 MWe net from one 35 MWe steam turbine and 6-7 MWe from the ORMAT bottom unit). 4) To supply steam to the second steam turbine of 35 MW additional wells have to be drilled outside the boundaries of the present concession. ORMAT has proposed to make the necessary investment if the concession area is increased and its term is extended beyond the 6 remaining years to enable recovery of the additional investment. 5 REFERENCES DAL SpA, 1989: Campo Geotérmico de Momotombo: Optimización del sistema Campo-Planta. Informe final. DAL SpA, report for INE (Nicaraguan Institute of Energy), 342 pp. Kaplan, U., 24: Geothermal cold brine injection two years experience in the Momotombo Field, Nicaragua. Geothermal Resources Council, Transactions, 28, 59-64. Porras, E., 25: Development of numerical model of the Momotombo geothermal field, Nicaragua. Kyushu University, Fukuoka, Japan, PhD thesis, 27 pp. Zúñiga, A., 25: Nicaragua country update. Proceedings of the World Geothermal Congress 25, Antalya, Turkey, 5 pp.