A Simplified Thermal Model for a CO2 Compressor

Similar documents
Surface of Flow and Force Effective Areas Applied to Development of Reciprocating Compressors

Experimental Investigation of Heat Transfer in Components of a Hermetic Reciprocating Compressor

Noise and Vibration Studies in a CO2 Compressor

Compressor Performance Comparison When Using R134 and R1234YF as Working Fluids

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

Noise Reduction of Commercial Applications: Compressor Approach

Compressor Mechanism Comparison For R744 Application

Low-Grade Waste Heat Recovery for Power Production using an Absorption-Rankine Cycle

Investigation of the Discharge Flow of a Reciprocating Compressor Using PIV

Multi-Variable Optimisation Of Wet Vapour Organic Rankine Cycles With Twin-Screw Expanders

Experimental Study of a CO2 Thermal Battery for Simultaneous Cooling and Heating Applications

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

Deformation Control of Scroll Compressor for CO2 Refrigerant

The Benefit of Variable-Speed Turbine Operation for Low Temperature Thermal Energy Power Recovery

Challenges on Converting an Upright Ice-Cream Freezer from R404a to R290 Complying with 150g Refrigerant Charge Restriction

Measurement and Simulation of Startup and Shut Down of Heat Pumps

Experimental Performance of a Prototype Carbon Dioxide Compressor

Heating Performance with a Volume Ratio on 2-Stage Compressor

Application of Taguchi Robust Design Method for Energy Efficiency Ratio and Noise of Compressors

Experimental Investigation of a Hermetic Scroll Expander-Generator

AREN 2110: Thermodynamics Spring 2010 Homework 7: Due Friday, March 12, 6 PM

Optimization of the Compressor Efficiency: A DOE Approach

Fundamental Investigation Of Whole-Life Power Plant Performance For Enhanced Geothermal Systems

Component-Based Vapor Compression Simulation Tool With Integrated Multi-Objective Optimization Routines

A Comprehensive Evaluation of Regression Uncertainty and the Effect of Sample Size on the AHRI-540 Method of Compressor Performance Representation

Void Fraction of CO2 and Ammonia in Multiport Aluminum Microchannel Tubes

The Part-Load Efficiency Benefit of Oil-Free, High- Speed, Direct-Drive Centrifugal Compressors

Using Simulation Model to Reduce System Design Time and Cost

Parametric Study of a Vapor Compression Refrigeration Cycle Using a Two-Phase Constant Area Ejector

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy

COP Improvement Of A CO2 Refrigeration System With An Expander-Compressor-Unit (ECU) In Subcritical And Transcritical Operation

Heat Pump With a Condenser Including Solid- Liquid Phase Change Material

A Study of a New Oil Injection to Compression Chambers on Scroll Compressors

A Study on the Polytrupic Exponent of Reciprocating Hermetic Compressors

Application Of Oil Flooded Compression With Regeneration To A Packaged Heat Pump System

PERFORMANCE EVALUATION OF HEAT PUMP SYSTEM USING R744/R161 MIXTURE REFRIGERANT

Performance Mapping for Variable Ductless Heat Pump Systems in Heating, Cooling and Defrost Operation

Modelling of Phase Change Material Implemented Into Cold Storage Application

ENERGY AND EXERGY ANALYSIS OF HEAT PUMP USING R744/R32 REFRIGERANT MIXTURE

A Trans-critical CO2 Heat Pump System for Waste Heat Utilization in Warm Weather Condition Applied to a Milk Refrigeration Plant

Performance Benefits for Organic Rankine Cycles with Flooded Expansion

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Normalized Effect Of Condenser Fouling And Refrigerant Charge On Performance Of Vapor Compression Air Conditioning Systems

Secondary Loop System for Automotiv HVAC Units Under Different Climatic Conditions

Flow Mal-Distribution In Micro-channel Evaporator

Performance Characteristics and Mapping for a Variable-Speed Ductless Heat Pump

Refrigeration Cycle. Definitions , , 11-46, 11-49,

A Scroll Expander with Heating Structure and Their Systems

Reducing Operating Costs with Optimal Maintenance Scheduling

High efficient heat reclaim with CO2

Experimental Study on Journal Bearing Characteristics in Reciprocating Compressors for HFC-134a

Ejector Expansion Refrigeration Systems

Investigations Of Low Pressure Two-Phase Steam- Water Injector

A Investigation of the Performance of Two-Stage Compression Refrigeration/Heat pump System with Dual-cylinder Rolling Piston Compressor

Assessment of C6F as Working Fluid for Organic Rankine Cycle Applications

Investigations of N 2 O Transcritical Refrigeration Cycle Using Dedicated Mechanical Subcooling. Sanjeev Kumar 1 and Dr. D.K.

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING FINAL EXAMINATION, DECEMBER 2008 MIE 411H1 F - THERMAL ENERGY CONVERSION

PERFORMANCE ANALYSIS OF A TRANSCRITICAL, CO2 HEAT PUMP WATER HEATER INCORPORATING A BRAZED-PLATE GAS-COOLER

Vapor injected heat pump using non-azeotropic mixture R32/R1234ze(E) for low temperature ambient

Performance of Scroll Expander for CO2 Refrigeration Cycle

Performance of Scroll Expander for CO2 Refrigeration Cycle

DESIGN OF VAPOUR ABSORPTION REFRIGERATION SYSTEM OF 1.5TR CAPACITY BY WASTE HEAT RECOVERY PROCESS

Dynamic Parameter Optimization of an Automobile A/C Compressor Using Taguchi Method

CO 2. transcritical refrigeration cycles: potential for exploiting waste heat recovery with variable operating conditions

OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS

Modelica-based Heat Pump Model for Transient and Steady-State Simulation Using Low-GWP Refrigerants

Development of Small Hermetic Compressors for R600a

Computational Analysis Of Ejector With Oscillating Nozzle

Sede Legale: Via IV Novembre, n CERANO (NO) Italy Fax R439A

Unitary Air Conditioner Field Performance

ABSTRACT 1. INTRODUCTION

A semi-empirical prediction model for the discharge line temperature of hermetic compressors

THEORETICAL STUDY OF HEAT PUMP SYSTEM USING CO 2 /DIMETHYLETHER AS REFRIGERANT

Experiments on Flow Boiling Heat Transfer of Pure CO2 and CO2-Oil Mixtures in Horizontal Smooth and Micro-Fin Tubes

Liquid-Flooded Ericsson Power Cycle

COMPATIBILITY TEST OF HERMETIC COMPRESSOR WITH LPG (HYDROCARBON BLEND)

Economic Model Predictive Control for Variable Refrigerant Systems

Heat Transfer Characteristic in Ice Slurry Generator

Application of Viper Energy Recovery Expansion Device in Transcritical Carbon Dioxide Refrigeration Cycle

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency:

BINARY BLEND OF CARBON DIOXIDE AND FLUORO ETHANE AS WORKING FLUID IN TRANSCRITICAL HEAT PUMP SYSTEMS

Permanent City Research Online URL:

Seasonal Energy Efficiency Rating Improvement Of Residential HVAC Systems Using A Low Power Inverter With A PSC Compressor

K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India

Scroll Expander for Carbon Dioxide Air Conditioning Cycles

Experimental Results on a New Prototype Packaged Heat Pump System Retrofitted with Oil Flooded Compression and Regeneration Technology

Opportunities and Limitations of Building Precooling

Conversion Factors for Comparing the Performance of Variable Refrigerant Flow Systems

Design And Manufacturing Of An Accelerated Lifetime Tester For Non-Metallic Materials Used For Compressor Valve Sealing Elements

CO2 Stirling Heat Pump for Residential Use

Two-Phase Distribution of R-134a in a Header of a Parallel Flow Heat Exchanger

Low GWP Chiller Refrigerants: Weighing the Tradeoffs

CO 2 Transcritical Cycle for Ground Source Heat Pump

Problems in chapter 9 CB Thermodynamics

Faculty of Engineering 2 nd year 2016 Mechanical Engineering Dep. Final-exam (code: M 1222)

Methodology of Modeling and Comparing the Use of Direct Air-Cooling for a Supercritical Carbon Dioxide Brayton Cycle and a Steam Rankine Cycle

PERFORMANCE ANALYSIS OF ORGANIC RANKINE CYCLES USING DIFFERENT WORKING FLUIDS

Practice Final Exam (A) Six problems. (Open-book, HW solutions, and notes) (Plus /minus 10 % error acceptable for all numerical answers)

Transcription:

Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2010 A Simplified Thermal Model for a CO2 Compressor Gustavo C. Weber Embraco Francisco Lajus Federal University of Santa Catarina Fernando A. Ribas Embraco Jose Nilton Fonseca Embraco Follow this and additional works at: http://docs.lib.purdue.edu/icec Weber, Gustavo C.; Lajus, Francisco; Ribas, Fernando A.; and Fonseca, Jose Nilton, "A Simplified Thermal Model for a CO2 Compressor" (2010). International Compressor Engineering Conference. Paper 1984. http://docs.lib.purdue.edu/icec/1984 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

1286, Page 1 A Simplified Thermal Model for a CO 2 Compressor. Gustavo C. Weber 1, Francisco Lajus Jr. 2, Fernando A. Ribas Jr. 1, José Nilton Fonseca Jr.* 1 1 EMBRACO, Rui Barbosa, 1020, Joinville, 89219-901, Brazil Phone: +55 47 3441-2977 2 POLO - Federal University of Santa Catarina Florianópolis, 88.040-900, Brazil Phone/FAX: 55 48 3234-5166 * Corresponding Author jose_fonseca@embraco.com.br ABSTRACT This paper aims to present a simplified thermal model to predict the thermal profile of a CO 2 reciprocating compressor. The methodology was firstly presented by Todescat (1992), considering a standard reciprocating compressor. This paper applied this thermal model for a CO 2 compressor which has a different thermal network. The governing equations and numerical methodology for the CO 2 platform are detailed. The numerical results are validated through comparisons with experimental data for different operating conditions. 1. INTRODUCTION In recent years environmental aspects are increasingly becoming an important issue in the design and development of refrigerant systems. The banning of CFCs and HCFCs in vapor compression systems, because of their negative environmental impacts, has made way for the HFCs refrigerants. In this situation, HFCs seem to be only a temporary solution and taking into account regulations for greenhouse gas emissions, natural fluids are viable alternatives as refrigerant fluids. If non-toxicity and non-flammability are required, the focus comes to carbon dioxide. The transcritical cycle, shown in Figure 1.a, is that one in which the compressor discharge pressure is above the refrigerant critical point, while the suction pressure is located below it. In other words, there is no condensation at the high side of the heat exchanger and the refrigerant vapor and liquid phases co-exist in only one distinguishable phase. Since usual ambient temperatures can exceed 31ºC (CO 2 critical temperature), a CO 2 refrigerating system does not exhibit condensation at the high side of the heat exchanger, as shown by the heat rejection process 2-3 in the figure, and temperatures and pressures are not linked as in saturation (dome) region. In a refrigeration cycle where temperature conditions range from subcritical to supercritical, CO 2 reaches high pressures, as much as 100 bar (10MPa) or even more at high ambient temperature and/or extreme operating conditions. The use of R744 implies in high operating pressures as shown in Figure 1b. The differential pressure between discharge line and suction line for the R744 transcritical cycle is around four times higher than R22 Rankine cycle and up to twelve times higher than R600a. As reflect of high operational pressures, the

1286, Page 2 CO 2 compressor present high temperatures which have strong influence in the thermal efficiency and, by consequence, in the performance. Figure 1: (A) CO 2 pressure-enthalpy diagram. (B) Pressure difference for common refrigerants and CO 2. The compressor thermal efficiency is a result of a global thermal network that involves almost all the compressor components (Ribas Jr., 2007). Thus, for improving the thermal efficiency, it is needed to know thermal profile and heat flow paths, aiming to reduce the superheating effects. Then, based on the HFC compressor thermal model (Todescat, 1992), a numerical model was developed to predict the thermal profile of a CO2 compressor, regarding the constructive differences and their influences in the global thermal networks. 2. CO 2 COMPRESSOR The CO 2 compressor has a particular design when compared to households ones using HFC, CFC and HC, as showed in the Figure 2. As it is possible to notice, a expressive difference is already verified in the shell shape and it is extended to the layout of components inside compressor. (a) Figure 2: HFC compressor (a) present expressive differences when compared to CO2 compressor. (b)

1286, Page 3 In both type of compressor, the manifold head is the main heat source due to the high temperatures generated during the discharge process. Considering HFC compressor, the suction and discharge chambers are not close like in CO 2 compressor, where the both chambers are separated by the same wall. In this case, superheating effect increases due to the intense heat exchange between suction and discharge chamber. Then, as the thermal behavior is function of geometry and components layout, it is important to adjust the thermal model for HFC compressor to CO 2 compressor. 3. THERMAL MODEL For complete understanding of proposed thermal model, the HFC thermal model is explained and CO 2 ones is presented, where the main differences are analyzed. 3.1. HFC Compressor Thermal Model The methodology (Todescat, 1992), can be divided in two parts: the thermal behavior of the gas inside the cylinder and the global heat transfer to compressor components. The compression chamber is solved using a simulation methodology developed by Ussyk (1984). Considering geometric relations, the variation rate of cylinder volume and the gas properties are solved using the first law of thermodynamics, in a transient regime. The model estimates the valves dynamics, the mass flow through them and cylinderpiston leakage. When the compression process reaches steady-state, some interest properties are calculated and considered in the second part of the simulation. Applying energy conservation equation to compressor components, they are used to evaluate the global heat transfer coefficient, UA [W/K]. Thus, the non-linear system, formed by these energy balance equation, are solved through its coupling to thermodynamics model of compression chamber. In the simulation procedure, firstly, it is necessary to load data base of interest compressor, according Schreiner (2008). Thus, the compressor is analyzed in a determined condition, aiming to obtain associated energies and the mass flow. The temperatures are obtained through an experimental measurement and they are used in the energy balance equation, resulting in the global heat transfer coefficients (UA's). After the coefficient definition, it is possible to estimate the compressor thermal profile by an iterative numerical process. Figure 3: Schematic view of a HFC compressor for the energy balance, according Todescat (1992).

1286, Page 4 3.2. CO 2 Compressor Thermal Model Initially, based in the HFC compressor thermal model, it was developed two simplified thermal model of CO 2 compressor, aiming to obtain a non-linear energy balance equation system. In the both models, six main heat fluxes are considered and the difference between them is defined by cylinder heat flux direction. In the first model, the heat from cylinder is exchanged to the internal environment, as it occurs in the HFC model. Considering the second one, the cylinder heat is transferred to the shell which occurs in CO 2 compressors due to its components layout. Figure 4: Second thermal model configuration and the heat fluxes direction. Considering the second thermal model, main six heat fluxes are expanded in terms of global heat transfer coefficient and temperature differential. So, they are: - Heat exchanged between motor and internal environment: MI MI ( T TIE ) M (1) - Heat exchanged between cylinder and shell: CH CH ( T T ) H W (2) - Heat exchanged between internal environment and shell: IH IH ( T T ) H - Heat exchanged between discharge and suction chamber: DS DS MS ( TMD TMS - Heat exchanged between discharge chamber and external environment: DA DA ) ( T TEE ) MD (3) (4) (5)

1286, Page 5 - Heat exchanged between shell and external environment: HA HA ( T TEE ) H (6) These heat fluxes are used to determined global heat transfer coefficient when the compressor thermal profile is given, in a specified condition. Then, it is possible to use them to predict thermal profile in other condition. 4. METHODOLOGY After model defined, it is necessary to validate the results comparing to experimental data. So, the validation method is composed by: numerical model calibration, numerical results and experimental comparison. In the first step, the compressor model database must be loaded by the EMBRACO internal program. An experimental thermal profile is used to obtain each global heat transfer coefficient, for a determined condition. Thus, it is possible to initiate the next step. The global heat transfer coefficients are kept the same, while the condition is changed and the thermal simulation is initiated. In the end of the simulation, the model gives whole compressor thermal profile for that specified condition and the numerical accuracy can be evaluated. The last step will show how much accurate are the numerical results when they are compared with experimental one, as will be showed in the following section. 5. RESULTS AND ANALYSIS To evaluate the results, it was considered a reference experimental thermal profile and, based on that, other conditions was numerically simulated. In the table below, it is showed the experimental thermal profile for the condition -23,3ºC/85bar. Table 01: Experimental Thermal Profile in different condition Reference Condition Experimental Thermal Profile Evaporating Temperature (ºC) -23.3 Discharge Pressure (bar) 85 Temperatures (ºC) Suction Line 32.4 Internal Environment 71.1 Suction Chamber 56.5 Cylinder Wall 83.8 Discharge Chamber 148.7 Shell 49.7 Motor 76.3 External Environment 32.5 Bearings 72.6 Oil 70.7.

1286, Page 6 In the first simulation, it was used the global heat transfer coefficients obtained by the condition - 23.3ºC/85bar, and thermal simulation was done for evaluating the condition -10ºC/85bar and 0 ºC/85bar. Thus, the numerical results were compared with respective experimental one. Table 02: Comparison between numerical and experimental results for each condition Numerical-Experimental Results Comparison ( T) Evaporating Temperature (ºC) -10 0 Discharge Pressure (bar) 85 85 Temperature Difference ( T=Numerical - Experimental) Internal Environment 5.4 8.7 Suction Chamber 5.0 5.2 Cylinder Wall 1.8 2.5 Discharge Chamber 6.8 10.8 Shell 1.8 5.1 Motor 5.0 9.3 Analyzing the Table 02, there is an evaporating temperature range where numerical results are closer than experimental ones. In another words, the thermal profile prediction is more accurate when the simulated condition is located near reference condition. The figure 05 shows the effect of evaporating temperature increase in the thermal profile prediction quality. Figure 05 : Comparison results showing the temperature differential behavior.

1286, Page 7 In the results, the discharge chamber presented an higher temperature difference compared to experimental data. On the other hand, the other temperatures differences are smaller than 10ºC, which indicates the methodology accuracy for thermal analysis involving LBP and MBP condition. Thus, it is possible to use thermal profile in LBP, as reference, and simulating the thermal profile in MBP condition. Then, this methodology allows a set of analysis, like: heat transfer area of specific component and heat transfer variation externally. The global heat transfer coefficients calibration, obtained through the experimental temperatures, considers any heat transfer mechanism inside the compressor globally and this compensates the heat diffusion effect, which it is not considered in the numerical model. However, it is evident that material changes or flow pattern changes are not sensible in this kind of model, as well as local temperature gradients analysis. For this last case, it is recommended other methodologies where the spatial temperature effect is better represented by the heat diffusion simulation considering the real geometry. In the Figure 06, from Ribas Jr. et al (2008), is showed the thermal profile of CO2 compressor shell as result of more complete methodology. Figure 6: CO2 compressor temperature profile. 6. CONCLUSIONS The present work presents a model to perform thermal energy analysis of reciprocating hermetic compressor adapted for CO 2 compressor platform. In the adaptation phase, the heat fluxes were evaluated regarding design differences and two thermal models were proposed. After preliminary evaluations, it was chosen one model and the comparison between experimental and numerical results is presented. This thermal model offers good agreement with experimental temperatures, considering conditions inside an evaporating temperature range. Then, the presented model can be successfully employed for CO2 compressors evaluation.

1286, Page 8 7. REFERENCES PEREIRA, E. L. L., Automatic Valve System Analysis of Reciprocating Compressors. Master Dissertation in Mehanical Engineering Mechanical Engineering Department, Santa Catarina Federal University, Florianópolis, Brazil, 2006. RIBAS Jr., F. A., DESCHAMPS, C. J., FAGOTTI, F., MORRIESEN, A., DUTRA, T., Thermal Analysis of Reciprocating Compressor A Critical Review. International Compressor Engineering Conference at Purdue, Julho, 2008. SCHREINER, J. E., Simulation Methodologies Development for Thermal Management Solution Analysis Applied to Refrigeration Reciprocating Compressor. Master Dissertation in Mehanical Engineering Mechanical Engineering Department, Santa Catarina Federal University, Florianópolis, Brazil, 2008. TODESCAT, M.L., FAGOTTI, F., PRATA, A.T., FERREIRA, R.T.S., Thermal Energy Analysis in Reciprocating Hermetic Compressors, Proc. Int. Compressor Engineering. Conf. at Purdue, pp. 1417-1428, 1992. USSIK, M. S., Numerical Simulation of Reciprocating Compressor Performance. Master Dissertation in Mehanical Engineering Mechanical Engineering Department, Santa Catarina Federal University, Florianópolis, Brazil, 1984.