CBUCK Engineering. Product: Zee-Lock Roof Panel Material: Steel Panel Thickness: 24 gauge Panel Width: 16 Support: Wood Deck

Similar documents
CBUCK Engineering. Evaluation Report Cee Lock Panel Metal Roof Assembly

Evaluation Report SkylightTube Tubular Daylight Device

Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D

Residential, 26 Ga. Roof Panel over 15/32 Plywood. Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

Force Engineering & Testing Inc Ramblewood Drive. Humble,TX Product Evaluation Report SENTRIGARD METAL ROOFING SYSTEMS

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION

technical bulletin ROOFING CORPORATION

DRAFT NOTICE OF ACCEPTANCE (NOA)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

technical bulletin ROOFING CORPORATION

ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95

TRIAD CORRUGATED METAL, INC.

SL175 Panel Technical Data Guide

Product Evaluation Report of. JELD-WEN, inc. Energy Saver/Contour Wood Edge Opaque Steel Outswing Door w/ or w/o Sidelites

ARCHITECTURAL TESTING, Inc. Code Compliance Research Report #0774 CCRR-0131

ATI Evaluation Service A Division of Architectural Testing Certification Services Code Compliance Research Report

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: METAL SALES MANUFACTURING CORPORATION

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

ATI Evaluation Service A Division of Architectural Testing Certification Services

COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Prepared for: Boca Vista Condominium Association, Inc th Avenue Madeira Beach, FL 33708

Uniform Mitigation Verification Inspection Form Maintain a copy of this form with insurance policy

PRODUCT CONTROL SECTION

REPORT HOLDER: RARE MANUFACTURING INC A AVENUE SURREY, BRITISH COLUMBIA V4N 4P2 CANADA EVALUATION SUBJECT: IRONWOOD SHAKE

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

CRITERIA FOR TESTING IMPACT & NON IMPACT RESISTANT BUILDING ENVELOPE COMPONENTS USING UNIFORM STATIC AIR PRESSURE

TECHNICAL INFORMATION

DAN S CUSTOM SHEETMETAL Manufacturer and Distributor

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems

GUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CLAY ROOF TILES REPORT HOLDER: BORAL ROOFING LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203)

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: NCFI POLYURETHANES

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS DIVISION: SIDING REPORT HOLDER: VM ZINC

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: CERTAINTEED CORPORATION

SHEET METAL ROOF TEST REPORT

REPORT HOLDER: FEROOF CO., LTD SEONWON LI SEONNAM MYEON SUNGJU GUN KYEONGSANGBUK DO SOUTH KOREA EVALUATION SUBJECT:

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

Understanding Wind Uplift Ratings

ICC-ES Evaluation Report Reissued March 2014 This report is subject to renewal March 1, 2015

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203)

Through-Fastener Panel UL Listing documentation

Western States 7/8 Corrugated

SECTION TURBINE VENTILATORS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: KP BUILDING PRODUCTS

Code Compliance Research Report CCRR-0194

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: LAPOLLA INDUSTRIES, INC.

EVALUATION REPORT Soprema, Inc. 310 Quadral Drive Wadsworth, OH 44281

NUCOR VR 16 II STANDING SEAM ROOF SYSTEM TABLE OF CONTENTS

I-STUD Shaftwall System

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS LLC

Keri M. Rayborn Silver Rayborn Consultants P.O. Box 1565 Tallahassee, FL P F

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

SL150 Guide Specification

ATI Evaluation Service A Division of Architectural Testing Certification Services

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: SIDING REPORT HOLDER: SHAKERTOWN 1992, INC.

TEST PROCEDURE FOR AIR PERMEABILITY TESTING OF RIGID, DISCONTINUOUS ROOF SYSTEMS

GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION REROOFING ADJUSTABLE FRAMING SYSTEM

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS REPORT HOLDER: HB&G BUILDING PRODUCTS, INC.

A. Product Data: For each type of deck, accessory, and product indicated.

SECTION PLATE CONNECTED WOOD TRUSSES

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE RUBBER SHAKES REPORT HOLDER: DAVINCI ROOFSCAPES, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

RESIDENTIAL ROOFING PRODUCT GUIDE

Metal Roof Panels

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: ROOF PANELS REPORT HOLDER: ROSER CO., LTD.

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015


DIVISION: METALS SECTION: METAL RAILINGS REPORT HOLDER: ULTRALOX 2955 LONE OAK DRIVE, SUITE 180 EAGAN, MINNESOTA 55121

Scope. Definitions. For definitions of terms used in this application standard, refer to ASTM 1079 and the Florida Building Code, Building.

Code Compliance Research Report CCRR-0266

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: MITEK USA, INC.

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)

PRODUCT GUIDE SPECIFICATION

SPECIFICATION GUIDELINE

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER:

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: BOSTITCH FASTENING SYSTEMS

FACT SHEET #2 DECK INFORMATION

Engineered Roof Solutions

Corium Brick Rainscreen System Specifications

Originally Issued: 05/20/2013 Revised: 07/07/2017 Valid Through: 05/31/ Design

Duro-Last Roofing, Inc. 525 Morley Drive Saginaw, MI 48601

Transcription:

Evaluation Report Zee-Lock With Continous Zee-Rib Clip Metal Roof Assembly Manufacturer: 1720 Maury Road Houston, TX 77026 (800) 231-8127 2333 for Florida Product Approval HVHZ # FL 15471.1 Florida Building Code 2010 Per Rule 9N-3 Method: 1 - D Category: Roofing Sub - Category: Metal Roofing Product: Zee-Lock Roof Panel Material: Steel Panel Thickness: 24 gauge Panel Width: 16 Support: Wood Deck Prepared by: James L. Buckner, P.E., S.E.C.B. Florida Professional Engineer # 31242 Florida Evaluation ANE ID: 1916 Project Manager: Diana Galloway Report No. 12-122-ZL-S4W-ER Date: 4 / 16 / 12 Contents: Evaluation Report Pages 1 9 CBUCK, Inc. 1399 N. Killian Drive, Suite 4, West Palm Beach, Florida 33403 Phone: (561)491-9927 Fax: (561)491-9928 Website: www.cbuckinc.net mes L. Buckner, P.E., SECB

Page 2 of 2 Manufacturer: Product Name: Zee-Lock Product Category: Roofing Product Sub-Category Metal Roofing Compliance Method: State Product Approval Rule 9N-3.005 (1) (d) Product/System Description: Product Assembly as Evaluated: Support: Slope: Zee-Lock Double Lock Standing Seam Roof Panel 2 Rib Height, 16 wide, 24 gauge Steel roof panel restrained by continuous Zee- Rib continuous panel clips, fastened into 15/32 Plywood Deck. Refer to Page 4 of this report for product assembly components/materials & standards: 1. Roof Panel 2. Panel Clip 3. Fasteners 4. Underlayment 5. Barrier Board (Optional) Zee Lock Zee Rib continuous clip #14 Per manufacturer s guidelines Approved Fire Barrier Board Type: Wood Deck (Design of support and its attachment to support framing is outside the scope of this evaluation.) Description: 15/32 or greater plywood, or Wood plank (min. specific gravity of 0.42) 2:12 or greater Minimum slope shall comply with FBC 2010, HVHZ Section 1515.2.2 and in accordance with manufacturer s recommendations. Performance: Wind Uplift Resistance: Design Uplift Pressures: (Refer to Table A attachment details herein) Wind Driven Rain: Coated Metal Panel Testing Accelerated Testing of Coating, 2000 hrs: Salt Spray Testing of Coating, 1000 hrs: METHOD 1: - 101 PSF METHOD 2: - 174.25 PSF Results: PASS Results: PASS Results: PASS

Page 3 of 2 Performance Standards: Standards Equivalency: Code Compliance: Evaluation Report Scope: Limitations and Conditions of Use: The product described herein has demonstrated compliance with: TAS 125 03 Standard Requirements for Metal Roofing Systems o UL580 06 Test for Uplift Resistance of Roof Assemblies o UL 1897 04 Uplift test for roof covering systems TAS 100 95 Test Procedure for Wind and Wind Driven Rain Resistance of Discontinuous Roof Systems ASTM G 23 Accelerated Testing of coating, 2000 hours ASTM B 117 Salt Spray Testing of coating, 1000 hours The UL 580-94 & UL 1897-98 standard version used to test the evaluated product assembly is equivalent with the prescribed standards in UL 580-06 & UL 1897-04 adopted by the Florida Building Code 2010. The product described herein has demonstrated compliance with Florida Building Code 2010, Section 1518.9.1. This product evaluation is limited to compliance of this product with the physical properties & structural wind load requirements of the Florida Building Code, HVHZ, as related to the scope section to Florida Product Approval Rule 9N-3.001. Scope of Limitations and Conditions of Use for this evaluation: This evaluation report for Optional Statewide Approval contains technical documentation, specifications and installation method(s) which include Limitations and Conditions of Use throughout the report in accordance with Rule 9N-3.005. Per Rule 9N-3.004, the Florida Building Commission is the authority to approve products under Optional Statewide Approval. Option for application outside Limitations and Conditions of Use Rule 9N-3.005(1)(e) allows engineering analysis for project specific approval by the local authorities having jurisdiction in accordance with the alternate methods and materials authorized in the Code. Any modification of the product as evaluated in this report and approved by the Florida Building Commission is outside the scope of this evaluation and will be the responsibility of others. The design pressures listed herein is applicable to all roof pressure zones. Rational analysis or extrapolation to enhance pressure is not permitted. Maximum panel lengths, valleys & panel accessories shall comply with Roofing Application Protocol RAS 133. Design of support system is outside the scope of this report. Fire Classification is outside the scope of Rule 9N-3, and is therefore not included in this evaluation. All panels shall be permanently labeled with the manufacturer s name and/or logo. All clips shall be permanently labeled with the manufacturer s name and/or logo, and/or model. This evaluation report approves the product assembly as described in this report for use in the High Velocity Hurricane Zone (HVHZ) code section. (Dade & Broward Counties)

Page 4 of 2 Quality Assurance: The manufacturer has demonstrated compliance of roof panel products in accordance with the Florida Building Code and Rule 9N-3.0005 (3) for manufacturing under a quality assurance program audited by an approved quality assurance entity through UL, LLC. (FBC Organization #: QUA 9625). Components & Materials (by Manufacturer): Roof Panel: Material: Thickness: Panel Width: Rib Height: Yield Strength: Steel Grade: Corrosion Resistance: Roof Panel Clips: Type: Material: Thickness: Dimensions: Yield Strength: Corrosion Resistance: Fastener: Type: Size : Min. Penetration thru Deck:: Corrosion Resistance: Standard: Berridge Zee-Lock Steel 24 gauge (0.0245 ) 16 Coverage 2 51.9 ksi 40 In compliance with FBC Sections 1518.9 & 1507.4.3: ASTM A792 coated, or ASTM A653 G90 galvanized steel Berridge Zee-Rib One-Piece, continuous fixed clip Steel 24 Gauge (0.0245 ) 2 (tall) x 1-3/8 (wide) x continuous (w/panel length) 51.9 ksi. Per FBC Sections 1517.6 & 1506.7 Pancake-Head Wood Screw, Type A #12-11 x 1 (or length to meet min. penetration) 3/16 Per FBC Section 1506.6 and 1507.4.4 HVHZ Approved Underlayment: One of the following as a minimum per FBC 2010, Section 1518.4: Double layer Compliant with ASTM D 226, Type I with a 9 headlap Single layer Compliant with ASTM D 226, Type II with 4 headlap Single layer Compliant with ASTM D 2626 with a 4 headlap Or any HVHZ approved underlayment Minimum endlaps shall be 6. Underlayment shall comply with FBC 2010, Section 1518.2. Components & Materials: (by Others) Barrier Board (Optional): Any approved fire barrier with HVHZ approval.

Page 5 of 2 Installation: Installation Method: (Refer to TABLE A below and drawings on Pages 7-9 of this report.) Fastener Spacing Along Continuous Clip: Refer to TABLE A Below (along the length of the panel) Rib Interlock: Mechanically seamed 180 (DOUBLE-LOCK) Minimum fastener penetration thru bottom of support, 3/16. For panel construction at the end of panels, refer to manufacturer s instructions and any site specific design. TABLE A Fastener Spacing Panel Seam METHOD 1 16 Double Lock METHOD 2 8 Double Lock Design Pressure - 101 PSF - 174.25 PSF Install the Zee-Lock roof panel assembly in compliance with the installation method listed in this report, RAS 133 and applicable code sections of FBC 2010. The installation method described herein is in accordance with the scope of this evaluation report. Refer to manufacturer s installation instructions as a supplemental guide for attachment.

Page 6 of 2 Referenced Data: 1. TAS 125-03 Uplift Test (Per UL580-94 and UL 1897-98) By Force Engineering & Testing Inc., Inc. (TST ID: 5328) Report # 49-0008T07A-C, Report Date: 2/16/07, Test Specimen(s) # A-B Report # 49-0008T07A-C, Report Date: 2/16/07,Test Specimen #C 2. TAS 100 95 Wind Driven Rain Test By PRI Construction Materials Technologies, LLC. (FBC Organization ID #TST: 5878) Report #BMC 006 02 01, Dated 8/23/07 3. ASTM G 23 Accelerated Weathering By Valspar Corporation Certified Laboratory Test Report, Dated 3/16/05 4. ASTM B 117 Salt Spray By Valspar Corporation Certified Laboratory Test Report, Dated 3/16/05 5. Quality Assurance By UL, LLC. (FBC Organization ID# QUA 9625) 6. Equivalency of Test Standard Certification By James L. Buckner, P.E. @ CBUCK Engineering (FBC Organization # ANE 1916) 7. Certification of Independence By James L. Buckner, P.E. @ CBUCK Engineering (FBC Organization # ANE 1916) 8. Engineering Analysis By CBUCK Engineering

Page 7 of 2 Installation Method Zee-Lock (24 gauge Steel) Roof Panel attached to Wood Deck Drawings Typical Panel Profile 0.38" 0.13" 2.00" 0.50" Continuous Zee-Rib Panel Clip Profile Side View

Page 8 of 2 Installation Method Zee-Lock (24 gauge Steel) Roof Panel attached to Wood Deck 16 in. Maximum Before Seaming Mechanically Seamed 180 (DOUBLE-LOCK) Fastener: ONE #12 Wood Screw Typical Assembly Profile View (Typical Fastening Pattern Across Width) BEFORE SEAMING 180 SEAM (DOUBLE-LOCK) Typical Panel Seams

Page 9 of 2 Installation Method Zee-Lock (24 gauge Steel) Roof Panel attached to Wood Deck Zee-Lock Double-Lock Panel Per Table "A" Zee-Rib Clip Deck- 15/32" Minimum Plywood or wood plank ONE #12 Wood Screw Typical Roof Assembly Isometric View Refer to Page 4 of this report for underlayment & optional barrier board. TABLE A Fastener Spacing Panel Seam METHOD 1 16 Double Lock METHOD 2 8 Double Lock Design Pressure - 101 PSF - 174.25 PSF