H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES

Similar documents
E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 492 AND ASTM E Rendered to REGUPOL AMERICA

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door

FOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test

KINETICS NOISE CONTROL TEST REPORT #AT001067

Acoustic Testing of CLT and Glulam Floor Assemblies Nordic Engineered Wood Report No. A August 2016 CONSTRUCTION

RSIC-1 ACOUSTIC ASSEMBLY

KINETICS NOISE CONTROL TEST REPORT #AT001035

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

DIVISION: FINISHES SECTION: ACOUSTIC TREATMENT REPORT HOLDER: ECORE INTERNATIONAL, INC.

This page was. intentionally. left blank

ASTM D 4541 ADHESION STRENGTH PERFORMANCE TEST REPORT. Rendered to: BAUTEX SYSTEMS. PRODUCT: AMB 20-WN Liquid Applied Membrane

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

ARCHITECTURAL AND STRUCTURAL NOISE CONTROL SOLUTIONS

GIB Quiet Clip GIB CBI March Features and Benefits

RESILIENT SOUND ISOLATION CLIPS

Floor Insulation Underlayment Section Sound Control Matting

GenieMat FF. Floating Floor Systems for Airborne & Impact Sound and Vibration Isolation. It s not magic, it s engineering. Impact Sound Control

Evaluation VerteTek Coat of Silence

Presented By: Jim O Neill. Acoustics

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.

ENKASONIC FLOOR UNDERLAYMENT 9110

HACKER SOUND MAT II, to create a quieter living environment while meeting demanding project specifications in multi-family construction.

TEST REPORT. Rendered to: KEYLINK FENCING & RAILING, INC. For: PRODUCT: Lancaster Series. TYPE: Aluminum Level Guardrail System

PERFORMANCE TEST REPORT. Rendered to: SIMTEK FENCE. TYPE: SimTek Privacy Fence System

Architectural Testing

REPORT HOLDER: KINETICS NOISE CONTROL 6300 IRELAN PLACE DUBLIN, OHIO EVALUATION SUBJECT: KINETICS NOISE CONTROL WAVE HANGER

WHY I SHOULD SPECIFY AND USE FAS TRACK 1000?

Delia Chamberlain, Vice President, Kolay Floors Steve Hedback and Joel Esselstrom, SSA Acoustic, LLP

DIVISION 9 - SECTION QTscu Re-bonded Recycled Rubber Impact Sound Insulation Patent No. RE 41,945

Installation Products

FIRE & SOUND MANUAL ARCHITECT VERSION 6.17

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued January 1, Legacy report on the 1997 Uniform Building Code

NATIONAL GYPSUM COMPANY Wood Frame Walls And Ceilings Single- And Double-Layer Construction

Reinventing construction

A. Section includes hydraulic-cement-based, polymer-modified, self-leveling underlayment for application below interior floor coverings.

DIVISION 13 - SPECIAL CONSTRUCTION SECTION ACOUSTICAL PANEL ENCLOSURE

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

PRODUCT GUIDELINES Hacker. Industries, Inc.

The Perfect Choice for Mezzanines in Custom Metal Buildings

TEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window

RMF Intercell. NBS Specification 2013 K41

METHOD STATEMENT FOR Dry Ceiling With Resilient Hanger

AND ACCESSORIES FOR DRYWALL CONSTRUCTION

ULTIMATE SOUND CONTROL SYSTEMS

I-STUD Shaftwall System

DIVISION: FINISHES SECTION: ACOUSTIC TREATMENT REPORT HOLDER: HOMASOTE COMPANY

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued October 1, Legacy report on the 1997 Uniform Building Code

Guide for Sound Insulation in Wood Frame Construction

ESR-1826 Reissued February 1, 2013 This report is subject to renewal February 1, 2015.

SECTION WOOD FLOORING

Evidence of Performance Joint sound reduction of filling material

1. Interior gypsum wallboard. 2. Exterior gypsum board panels for ceilings and soffits. 3. Tile backing panels.

SECTION GYPSUM WALLBOARD SYSTEMS. A. Gypsum board at new wall partitions or where indicated on drawings. B. ASTM C442 - Gypsum Backing Board

Specialists in Acoustic Flooring and House to Flat Conversions

Shaftwall & Stairwell Systems Fire protection & sound isolation for shafts & stairwells

-Letter - Tables 1 and 2 - Figure 1 - Exhibits 1 through 6

Product Test Summaries

SOUND INSULATION TESTING IN DWELLINGS

Loadbearing timber joist floors

SECTION WOOD FLOORING. 1. Section Above-Grade Vapor Retarders. 2. Section Below-Grade Vapor Retarders

Installation Guide and Safety Manual

Build higher and faster with FIRM-FILL CMD (corrugated steel deck) from Hacker Industries, Inc., the leader in pourable floor underlayments.

BENEFITS OF GREEN GLUE IN STANDARD WALL CONSTRUCTION

Embassy Suites Hotel Springfield, Virginia. Dominick Lovallo Structural Option AE Senior Thesis Thesis Advisor: Dr.

Section HIGH-TENSION Stretched-Fabric Wall Systems SoftWalls, Inc.

Optimizing Ceiling Systems and Lightweight Plenum Barriers

RIVERBANK ACOUSTICAL LABORATORIES

Part E robustdetails. robustdetails. January 2017 Update Pack. Dear Colleague,

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

NRCC Guarded Hot Box Testing (ASTM C ) for Energy Efficiency of a Total Roof Assembly

KINETICS. Roll-Out Floor Isolation System CREATE QUIET

ENGINEERED SOLUTIONS VERSA-DEK COMPOSITE 3.5LS COMPOSITE LONG SPAN FLOOR DECK.

Model 4010 Individual Panels / Curve & Diverter

2000 POCKET DOOR TECHNICAL DATA

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: CITADEL ARCHITECTURAL PRODUCTS, INC.

1.2 Reference Standard: NOFMA - National Oak Flooring Manufacturers Association Grading Standards.

MOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall

C06. S02. P02 P22 CasoLine mf

VALIDATION REPORT No

ACCESSORIES TAPES ALUMINUM FRAMING CLEANERS & SEALERS NOSING, TRANSITIONS & LEVELERS

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015.

MODEL KWIK-WALL... One Source for Wall Systems. SOUND CONTROL

ASTM C 1363 Thermal Performance Test Report

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

LABORATORY MEASUREMENTS OF THE SOUND REDUCTION INDEX ROCKWOOL ABLATIVE COATED BATTS

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS

CONTRACT NUMBER: W912DQ-08-C % CORRECTED DESIGN 28 JULY 2008

QuietRock 530 RF Application Notes

FLOORING FOR FLOOD-PRONE AREAS. Vinyl Flooring. Pros of Vinyl Flooring for Flood-Prone Areas

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

STEEL STUD, TRIMS AND ACCESSORIES FOR DRYWALL CONSTRUCTION MONTREAL TORONTO CALGARY EDMONTON VANCOUVER THE STRENGTH WITHIN

Transcription:

ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to AMORIM CORK COMPOSITES Series/Model: AcoustiCORK ECOx2 Sound Reduction Underlayment for LVT Plank Flooring Specimen Type: 152 mm (6") Concrete Slab with Drop Ceiling Overall Size: 3023 mm by 3632 mm (119" by 143") STC 62 IIC 66 Test Specimen Identification: Floor Topping: 3 mm (0.12") Flexco Premium Wood Vinyl Plank Floor Underlayment: 1.9 mm (0.07") AcoustiCORK ECOx2 Sound Reduction Underlayment for LVT Plank Flooring Floor Slab: 152.4 mm (6") 5000 PSI Concrete Slab Main Beams: 43 mm (1.69") Armstrong HD8906 Drywall Main Beam Cross Tees: 37.3 mm (1.47") Armstrong XL8945P Cross Tee Insulation: 88.9 mm (3.5") Johns Manville Kraft Faced R-13 Fiberglass Insulation Ceiling: 15.9 mm (0.63") National Gypsum Gold Bond Fire-Shield Type X Gypsum Panel Reference should be made to Intertek-ATI Report H1810.12-113-11 for complete test specimen description. This page alone is not a complete report. 130 Derry Courtaa York, PA 17406aa www.archtest.com www.intertek.com/building p. 717.764.7700 f. 717.764.4129

Page 1 of 5 Acoustical Performance Test Report AMORIM CORK COMPOSITES 26112 110th Street Trevor, Wisconsin 53179 Report H1810.12-113-11 Test Date 05/19/17 Report Date 10/13/17 Project Scope Architectural Testing, Inc., an Intertek company (Intertek-ATI), was contracted to conduct airborne sound transmission loss and impact sound transmission tests. This report is a reissue in the name of Amorim Cork Composites through written authorization from the original report holder. The complete test data is included as attachments to this report. The full test specimen was assembled on the day of testing by Intertek-ATI. All materials provided by the client were installed on an existing Intertek-ATI assembly (152 mm (6") Concrete Slab with Drop Ceiling) utilizing Intertek-ATI-supplied materials. Test Methods The acoustical tests were conducted in accordance with the following standards. The equipment listed in the attachments meets the requirements of the following standards. ASTM E 90-09 (2016), Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions ASTM E 413-16, Classification for Rating Sound Insulation ASTM E 492-09(2016)e1, Standard Test Method for Laboratory Measurement of Impact Sound Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine ASTM E 989-06 (2012), Classification for Determination of Impact Insulation Class (IIC) ASTM E 2235-04 (2012) Standard Test Method for Determination of Decay Rates for Use in Sound Insulation Test Methods Test Procedure All testing was conducted in the VT test chambers at Intertek-ATI located in York, Pennsylvania. The microphones were calibrated before conducting the tests. The airborne transmission loss test was conducted in accordance with the ASTM E 90 test method using the single direction method. Two background noise sound pressure level and five sound absorption measurements were conducted at each of five microphone positions. Four sound pressure level measurements were made simultaneously in both rooms, at each of five microphone positions. 130 Derry Courtaa York, PA 17406aa www.archtest.com www.intertek.com/building p. 717.764.7700 f. 717.764.4129

Page 2 of 5 Test Procedure (Continued) The impact sound transmission test was conducted in accordance with the ASTM E 492 test method. Two background noise sound pressure level, two sound pressure level measurements with the tapping machine operating at each position specified by ASTM E 492, and five sound absorption measurements were conducted at each of five microphone positions. The air temperature and relative humidity conditions were monitored and recorded during all measurements. Test Conditions Source Room Maximium Temperature 21.8 C (71.2 F) Maximium Temperature Receive Room Minimum Temperature 21.6 C (70.9 F) Minimum Temperature 22.8 C (73 F) Minimum Relative Humidity 57% 22.8 C (73.1 F) Minimum Relative Humidity 47% Maxmimum Relative Humidity 57% Maxmimum Relative Humidity 48% Test Calculations The STC (Sound Transmission Class) and IIC (Impact Insulation Class) ratings were calculated in accordance with ASTM E 413 and ASTM E 989, respectively. Test Specimen Materials and Installation Details Material Premium Wood Vinyl Plank Sound Reduction Underlayment for LVT Plank Flooring Concrete Slab Drywall Main Beam Dimensions (mm/inch) Thickness (mm/inch) Manufacturer and Series Quantity Average Weight 914.4 by 101.6 10.98 m² 4.51 kg/m² 3 / 0.12 Flexco 36 by 4 118.19 ft² 0.92 lb/ft² Note: Adhered to the underlayment with Excelsior MS 700 Modified Silane Wet Set Resilient Flooring Adhesive using a 0.79 mm by 1.59 mm by 0.79 mm (1/32" by 1/16" by 1/32") trowel. Adhesive was allowed to cure per manufacturer's specifications. 3023 by 1041 119 by 41 1.9 / 0.07 AcoustiCORK ECOx2 10.98 m² 118.19 ft² 0.69 kg/m² 0.14 lb/ft² Note: A sheet of 2 mil polyethylene plastic sheeting was adhered to the floor slab with 3M Super 77 spray adhesive. The underlayment was adhered to the sheeting with Excelsior MS 700 Modified Silane Wet Set Resilient Flooring Adhesive using a 0.79 mm by 1.59 mm by 0.79 mm (1/32" by 1/16" by 1/32") trowel. Adhesive was allowed to cure per manufacturer's specifications. 3023 by 3632 10.98 m² 366.18 kg/m² 152.4 / 6 5000 PSI 119 by 143 118.19 ft² 75 lb/ft² Note: Installed in a test frame flush to the source room. Mats of #5 reinforcing bars were placed 25.4 mm from both the top and bottom of the slab, with bars spaced on 305 mm centers in both 38.1 by 2870 10.9 lin m 0.45 kg/m 43 / 1.69 Armstrong HD8906 1.5 by 113 35.76 lin ft 0.3 lb/ft Note: Twelve gauge hanger wires were attached to the bottom side of the concrete at twelve locations and then to the main beams. The hanger wire was twisted around itself a minimum of three times within 76 mm creating a 305 mm plenum. The measured steel thickness is 0.5 mm.

Page 3 of 5 Test Specimen Materials and Installation Details (Continued) Material Cross Tee Fiberglass Insulation Gypsum Panel Dimensions (mm/inch) 38.3 by 1219 1.5 by 48 Thickness (mm/inch) Manufacturer and Series Quantity Average Weight 37.3 / 1.47 Armstrong XL8945P 27.2 lin m 89.24 lin ft 0.45 kg/m 0.3 lb/ft Note: Inserted into the main beams on 610 mm centers. The measured steel thickness is 0.5 mm. 2962 by 584 116.6 by 23 88.9 / 3.5 Johns Manville Kraft Faced R-13 Note: Loose laid onto the ceiling grid system 10.98 m² 118.19 ft² 1.33 kg/m² 0.27 lb/ft² 3023 by 1219 National Gypsum Gold Bond Fire- 10.56 m² 11.23 kg/m² 15.9 / 0.63 119 by 48 Shield Type X 113.67 ft² 2.3 lb/ft² Note: Fastened with 25.4 mm fine thread drywall screws on 305 mm centers. Seams and perimeter sealed with Pecora AC-20 Acoustical Sealant and covered with pressure-sensitive tape. Comments The total weight of the floor/ceiling assembly was 4228.1 kg / 9320.3 lbs. Intertek-ATI will store samples of the test specimen for four years. Photographs of the test specimen are included in the attachments. A drawing of the test specimen is included in the attachments.

H1810.12-113-11-R0 Page 4 of 5 This report is reissued in the name of Amorim Cork Composites through written authorization from the original report holder. The original Report No. is H1810.04-113-11. Intertek-ATI will service this report for the entire test record retention period. Test records, such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation, will be retained by Intertek-ATI for the entire test record retention period. The test record retention period ends four years after the test date. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen tested. This report is intended to help in the client s quality assurance program, but it does not represent a continuous or exhaustive evaluation of the specimen tested or of other products or materials that were not evaluated. The statements and data provided herein do not constitute approval, disapproval, certification, or acceptance of performance or materials. This report may not be reproduced, except in full, without the written approval of IntertekATI. FOR INTERTEK-ATI: Daniel B. Mohler Project Lead - Acoustical Testing Jordan Strybos Project Manager - Acoustical Testing Attachments (7 pages): This report is complete only when all attachments listed are included. Instrumentation (1) Airborne Sound Transmission Loss Data (2) Impact Sound Transmission Data (2) Photographs (1) Drawings (1) * Stated by Client/Manufacturer N/A - Non Applicable

Page 5 of 5 Revision Log Revision Date Page(s) Description R0 10/13/17 N/A Original Report Issue - Reissue of Report No. H1810.04-113-11 in the name of Amorim Cork Composites. This report produced from controlled document template ATI 00629(d), Revised: 01/11/17.

Attachments Instrumentation Instrument Manufacturer Model ATI Number Date of Calibration Data Acquisition Unit National Instruments PXI-4462 65124 06/16 * Microphone Calibrator Norsonic 1251 INT00127 03/17 Receive Room Microphone PCB Piezotronics 378C20 65617 05/17 Receive Room Microphone PCB Piezotronics 378B20 63744 05/17 Receive Room Microphone PCB Piezotronics 378B20 63745 05/17 Receive Room Microphone PCB Piezotronics 378B20 63746 09/16 Receive Room Microphone PCB Piezotronics 378B20 63747 05/17 Receive Room Environmental Indicator Comet T7510 63810 63811 10/16 10/16 Source Room Microphone PCB Piezotronics 378B20 63738 04/17 Source Room Microphone PCB Piezotronics 378B20 63739 04/17 Source Room Microphone PCB Piezotronics 378B20 63740 04/17 Source Room Microphone PCB Piezotronics 378B20 63742 04/17 Source Room Microphone PCB Electronics 378B20 63741 04/17 Source Room Environmental Indicator Comet T7510 63812 11/16 Tapping Machine Look Line s.r.l. EM50 (TM50) 65351 02/17 * The calibration frequency for this equipment is every two years per the manufacturer's recommendation. Test Chambers VT Receive Room Volume VT Source Room Volume 155.77 m³ (5500.85 ft³) 190 m³ (6709.79 ft³)

AIRBORNE SOUND TRANSMISSION LOSS ASTM E 90 Test Date 05/19/17 Data File No. H1810.04 Client Amorim Cork Composites Description 3 mm (0.12") Flexco Premium Wood Vinyl Plank, 1.9 mm (0.07") AcoustiCORK ECOx2 Sound Reduction Underlayment for LVT Plank Flooring, 152.4 mm (6") 5000 PSI Concrete Slab, 43 mm (1.69") Armstrong HD8906 Drywall Main Beam, 37.3 mm (1.47") Armstrong XL8945P Cross Tee, 88.9 mm (3.5") Johns Manville Kraft Faced R-13 Fiberglass Insulation, 15.9 mm (0.63") National Gypsum Gold Bond Fire-Shield Type X Specimen Area 10.98 m² Technician Freq Daniel B. Mohler Background Source Receive Specimen 95% Number Absorption SPL SPL SPL TL Confidence of (Hz) (db) (m²) (db) (db) (db) Limit Deficiencies 50 37.5 33.9 104 62 37 4.30-63 37.2 23.5 102 63 36 4.40-80 41.8 16.7 109 67 40 5.10-100 33.9 11.8 107 68 39 2.00-125 34.0 10.2 104 63 41 1.30 5 160 33.1 9.6 107 63 44 1.30 5 200 28.4 10.6 104 57 48 1.00 4 250 29.4 9.8 103 53 51 0.80 4 315 25.5 9.7 106 53 54 0.70 4 400 24.4 8.4 104 48 58 0.70 3 500 23.2 8.2 103 43 61 0.40 1 630 25.0 7.6 102 39 65 0.40 0 800 23.1 8.0 102 38 66 0.70 0 1000 19.0 7.8 102 37 67 0.40 0 1250 18.7 8.1 100 35 67 0.30 0 1600 15.8 8.0 100 33 68 0.40 0 2000 12.3 8.7 101 34 68 0.40 0 2500 9.6 10.0 96 30 67 0.40 0 3150 8.5 10.4 98 28 70 0.40 0 4000 7.4 11.7 98 27 71 0.30 0 5000 6.5 13.4 95 23 72 0.40-6300 6.7 16.2 93 16 75 0.60-8000 7.0 20.9 93 14 77 0.70-10000 7.2 25.2 92 9 79 0.60 - STC Rating Deficiencies 62 26 (Sound Transmission Class) (Sum of Deficiencies) Notes: 1) Receive Room levels less than 5 db above the Background levels are highlighted in yellow. 2) Specimen TL levels listed in red are potentially limited by the laboratory flanking limit. 3) Specimen TL levels listed in blue indicate the lower limit of the transmission loss. 4) Specimen TL levels listed in green indicate that there has been a filler wall correction applied ATI 00614, Revised: 01/11/17 Page 1 of 2

AIRBORNE SOUND TRANSMISSION LOSS ASTM E 90 Test Date 05/19/17 Data File No. H1810.04 Client Amorim Cork Composites Description 3 mm (0.12") Flexco Premium Wood Vinyl Plank, 1.9 mm (0.07") AcoustiCORK ECOx2 Sound Reduction Underlayment for LVT Plank Flooring, 152.4 mm (6") 5000 PSI Concrete Slab, 43 mm (1.69") Armstrong HD8906 Drywall Main Beam, 37.3 mm (1.47") Armstrong XL8945P Cross Tee, 88.9 mm (3.5") Johns Manville Kraft Faced R-13 Fiberglass Insulation, 15.9 mm (0.63") National Gypsum Gold Bond Fire-Shield Type X Specimen Area 10.98 m² Technician Daniel B. Mohler 100 Airborne Sound Transmission Loss 90 Sound Transmission Loss (db re: 20 mpa) 80 70 60 50 40 30 20 10 Specimen TL Contour Curve 0 63 125 250 500 1000 2000 4000 8000 Frequency (Hz) ATI 00614, Revised: 01/11/17 Page 2 of 2

IMPACT SOUND TRANSMISSION ASTM E 492 Test Date 05/19/17 Data File No. H1810.04 Client Amorim Cork Composites Description 3 mm (0.12") Flexco Premium Wood Vinyl Plank, 1.9 mm (0.07") AcoustiCORK ECOx2 Sound Reduction Underlayment for LVT Plank Flooring, 152.4 mm (6") 5000 PSI Concrete Slab, 43 mm (1.69") Armstrong HD8906 Drywall Main Beam, 37.3 mm (1.47") Armstrong XL8945P Cross Tee, 88.9 mm (3.5") Johns Manville Kraft Faced R-13 Fiberglass Insulation, 15.9 mm (0.63") National Gypsum Gold Bond Fire-Shield Type X Specimen Area 10.98 m² Technician Daniel B. Mohler Freq Background SPL Absorption Normalized Impact SPL 95% Number Confidence (Hz) (db) (m²) (db) Limit Deficiencies 50 37.1 35.4 59 3.1-63 37.6 23.3 53 3.4-80 41.4 18.0 47 1.5-100 34.1 11.3 52 0.9 6 125 34.1 10.3 48 1.2 2 160 32.4 9.7 48 1.1 2 200 28.6 10.5 47 0.7 1 250 29.6 10.4 50 0.8 4 315 25.5 9.6 50 0.7 4 400 24.4 8.3 48 0.5 3 500 23.1 8.0 45 0.6 1 630 24.7 7.7 45 0.4 2 800 23.3 8.0 42 0.5 0 1000 19.6 7.8 35 0.5 0 1250 18.7 8.0 28 0.7 0 1600 16.0 8.0 21 0.8 0 2000 12.4 8.8 17 1.1 0 2500 9.7 10.0 13 1.0 0 3150 8.6 10.4 14 0.8 0 4000 7.4 11.7 10 0.6-5000 6.6 13.3 7 0.5-6300 6.7 16.2 7 0.3-8000 7.0 21.0 8 0.2-10000 7.1 25.1 9 0.2 - of IIC Rating Deficiencies 66 25 (Impact Insulation Class) (Sum of Deficiencies) Note: Receive Room levels less than 5 db above the Background levels are highlighted in yellow. ATI 00615, Revised: 01/11/17 Page 1 of 2

IMPACT SOUND TRANSMISSION ASTM E 492 Test Date 05/19/17 Data File No. H1810.04 Client Amorim Cork Composites Description 3 mm (0.12") Flexco Premium Wood Vinyl Plank, 1.9 mm (0.07") AcoustiCORK ECOx2 Sound Reduction Underlayment for LVT Plank Flooring, 152.4 mm (6") 5000 PSI Concrete Slab, 43 mm (1.69") Armstrong HD8906 Drywall Main Beam, 37.3 mm (1.47") Armstrong XL8945P Cross Tee, 88.9 mm (3.5") Johns Manville Kraft Faced R-13 Fiberglass Insulation, 15.9 mm (0.63") National Gypsum Gold Bond Fire-Shield Type X Specimen Area 10.98 m² Technician Daniel B. Mohler 100 Impact Sound Transmission 10 90 20 80 30 70 40 Sound Pressure Level (db re: 20 mpa) 60 50 40 30 50 60 70 80 Impact Insulation Class (IIC) 20 90 10 Normalized Impact SPL 100 0 110 63 125 250 500 1000 2000 4000 8000 Contour Curve Frequency (Hz) ATI 00615, Revised: 01/11/17 Page 2 of 2

Photographs Source Room View of Test Specimen Installation Receive Room View of Test Specimen Installation

Drawing 1-Floor Topping 2-Underlayment 3-Concrete Slab 4-Hanger Wire 5-Insulation 6-Ceiling Grid 7-Ceiling