DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

Similar documents
NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

U.V resistance UL Sunlight Resistance. Flame retardant IEC

Construction guideline

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

Technical Specification for Single Core 38/66kV TR-XLPE Insulated Underground Cable

Armoured Instrumentation Cables to BS7917

Cables for Railway Signalling Applications General Requirements

XLPE CABLE (11KV - Aluminium)

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

*** Supercedes: BECO E and COM , , & ***

UNIFIED FACILITIES GUIDE SPECIFICATIONS

PT. KABELINDO MURNI Tbk SHIPBOARD CABLE WIRE AND CABLE MANUFACTURER. No. EMS No. OSH No. QCS 00152

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR

C&G 2382 BS7671: th Edition IEE Wiring Regulations. 25 Questions

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. ANSI/SCTE (Formerly IPS SP 100)

DATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0

Engineering Data for Copper and Aluminum Conductor Electrical Cables

SECTION INSULATED WIRE AND CABLE

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +105 C, 1000 VOLTS, TYPE LSFSGU

3.0) TRANSMISSION LINES MINIMUM REQUIRED STANDARDS LINES

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS

ENERGY PROTOLON(SMK) LWL. (N)TSKCGEWOEU Medium Voltage Reeling Cable with integrated Fibre Optics

THE PERFORMANCE OF XLPE WATER TREE RESISTANT INSULATION SYSTEMS AGAINST THE REQUIREMENTS OF DIN VDE /A3

Superastic Flex Cable 450 / 750V Exceeds all the specifications in its category.

7. EXTENSION LEADS AND COMPENSATING CABLE

History of Cable Systems HISTORICAL OVERVIEW OF MEDIUM & HIGH VOLTAGE CABLES. Nigel Hampton

Electrical Insulating Tapes

C900/RJ. CertainTeed. PVC Pipe. with CertainTeed s proven Certa-Lok restrained joint system. Directional Drilling

Large plastic pipe technology. Large diameter pressure pipe. up to DN/ID 5000 mm

Profile No.: 4 NIC Code: ELECTRICAL CABLES (SINGLE AND MULTICORE)

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS

TECHNICAL SPECIFICATIONS

FINOLEX FLAME RETARDANT (FR) PVC INSULATED INDUSTRIAL CABLES FINOLEX FLAME RETARDANT (FR) PVC INSULATED INDUSTRIAL CABLES - PROJECT PACKING

PTFE BELLOWS POLY FLUORO LTD. POLY FLUORO LTD.260A. Bommasandra Industrial Area, Hosur Road, Bangalore TECHNICAL SPECIFICATION

PHOTOVOLTAIC CABLES. Energy and Fiber Optical Cables for Solar Energy Systems.

catalog Copper Wires

Pig s Tail. protective wrapping. use pig s Tail for:

ORDINANCE ON TECHNICAL REQUIREMENTS FOR CABLE DUCTS

Cable Jointing Manual. Jointing Procedures. Module 18. Concentric Cables

CONDUITS AND FITTINGS

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

Specifications for Concrete Embedment Liner

Mineral Insulated Platinum Resistance Thermometer PT100 Sensor - Available in 3mm or 6mm diameter x 150mm or 250mm probe lengths

TESTING PTE EARTHING

HEKAPLAST. PE-HD twin wall cable ducts and cable protection pipes for underground installation. Corrugated and Twin Wall Pipes of Plastics

PHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-P156-60

supply, Installation, testing & commissioning of panel gas flooding system with NOVEC 1230 at Mandi House/L-3 & GTBN Underground station of DMRC

Distribution System Design General Requirements

ELECTRICAL SAFETY INSPECTION REPORT

«CABLE T 92» WORKSHOP BALI, INDONESIA JUNE, 1992 POWER CABLES IN TROPICAL ENVIRONMENTS : SYNTHESIS. By L. DESCHAMPS SEE / EDF (France)

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

Cable Management Systems

GUIDE SPECIFICATIONS IN CSI FORMAT: RESILIENT FLOORING

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less)

Una e mpre sa Vi akab l e GLOSSARY.

ELECTRICAL BULLETIN

OSNALINE. Tubes and tube bundles. Member of the KME Group. KME Germany AG & Co. KG [GB] OSNALINE

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

Fixing of PVC Net, Self Fusing High Voltage Insulation Tape & Catenary Sleeve (MVLC) on Main line in Delhi. Metro Rail Corporation Ltd.

Technical Specification for LV ABC Fuse Switch Disconnectors

Industrial LSZH Loose Tube, Gel-Free, Double-Jacket Cable

Cables for Drag Chains

WIRING METHODS CHAPTER 38

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION

ROLINX Laminated Busbar. Design Rules Version 01 (12/2015)

This section applies to the design and installation relating to wire and cable systems and terminations. 16G Figure 1 16G Figure 2

U.S. Department of Transportation Pipeline and Hazardous Materials Safety Administration Plastic Pipe

SECTION POLYVINYL CHLORIDE (PVC) WATERLINE

THERMOFIT RNF-100 TUBING Polyolefin, Flexible, Heat-Shrinkable

2015 Code Rollout Meeting Q & A

General Requirements. Technical Specifications for Insulators of Transmission Lines

EXPANDED POLYSTYRENE (EPS GEOFOAM) EMBANKMENT DIVISION 31 EARTHWORK

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

SEAL & SIGNATURE OF THE TENDERER

Heat-Shrinkable Tubing

Factors Affecting Current Ratings for Underground and Air Cables

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)

ARCHITECTURAL GUIDE SPECIFICATIONS - DESCRIPTIVE

SPECIFICATION DIVISION 7 NUMBER SECTION DESCRIPTION DIVISION 07 THERMAL AND MOISTURE PROTECTION SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

ANSI/NEMA WC 71 ICEA S Nonshielded Cables Rated V for Use in the Distribution of Electric Energy

1. B16.1 Cast Iron Pipe Flanges and Flanged Fittings, Class C 111 Rubber Gasket Joints for Ductile Iron Pressure Pipe and Fittings

(Condensed from National Electric Code)

Single-Jacketed Tubing

Underground Service Requirements and Instructions

PMG LISTING CRITERIA FOR MULTILAYER PIPE AND FITTINGS ASSEMBLY FOR REFRIGERANT APPLICATIONS LC1036

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE

Permicav XV TM NEXT GENERATION OF VAPOUR-PERMEABLE INSULATION FOR WALLS WITH CAVITIES

Exolit Flame Retardants for Plastics

PHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-BIPV-SM-P125-36

ENGLISH. 1metre 7/.02mm Teflon insulated twin twisted lead

ICEA STANDARD FOR DISTRIBUTION FRAME-WIRE TECHNICAL REQUIREMENTS. Published By INSULATED CABLE ENGINEERS ASSOCIATION, INC. Post Office Box 1568

Custom-Designed Clamps. Machined Versions. Online Configurator for Custom-Designed Clamps A56.

THE ADVANTAGES HDPE MANHOLES

Ceramic Ceramic No. of Lead/Wire Lead Allied RS order Dia Ø Length Wires Type Length Code code

Transcription:

DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- T/0018/ DMRC-E-TR-CABLE-2 SPECIFICATIONS FOR 33 kv CABLES FOR ELEVATED AND Issued on: Date Stage 20 th Aug 2014 DELHI METRO RAIL CORPORATION LTD. 7 th Floor, B-Wing, Metro Bhawan, Fire Brigade Lane, Barakhamba Road, New Delhi 110 001 Page 1 of 14

Previous Record of specification Stage Date Draft -1 20/08/2014 Page 2 of 14

Contents 1. Detailed description of the equipment and its application in DMRC - MV cables... 4 2. Governing Specifications... 5 2.1 Standards...5 2.2 Abbreviations...6 3. Technical Requirement... 6 3.1 ConductingCore...6 3.2 Conductor:...6 3.3 Conductor Screen:...7 3.4 Insulation:...7 3.5 Insulation Screen:...7 3.6 Water Barrier:...7 3.7 Metallic Screen:...8 3.8 Inner Sheath:...8 3.9 Armouring:...8 3.10 Short Circuit Ratingof Metallic Sheath/Screen...8 3.11 Outer Sheath...8 4. Additional Requirement... 9 4.1 Outer Sheath should have following features:...9 5. Maintenance & Life... 10 6. Special Condition... 10 7. TESTING... 11 8. DATA SHEET - 33 kv CABLES... 12 Page 3 of 14

1. DETAILED DESCRIPTION OF THE EQUIPMENT AND ITS APPLICATION IN DMRC - MEDIUM VOLTAGE CABLES These specifications are applicable to 33 kv cables in various corridors, constituting the 33 kv distribution network. 33 kv Cables are required to be used in the Auxiliary Network, for supply of power at 33 kv to various ASSs located at Stations and in the Depot. The Auxiliary Network consists of duplicate 33 kv feeders, each feeder consisting of 3 Single core cables, assembled in twisted or cloverleaf pattern. The Cross section of the conducting core generally used is as follows for various connections: Page 4 of 14 Conducting Core From AMS/RSS to ASS 400 sq. mm Copper 33 kv Ring Main (Underground section) 400 sq. mm Copper 33 kv Ring Main (elevated section) 300 sq. mm Aluminum From ASS to ASS 300 sq. mm Aluminum 33 kv CB to Transformer (33 kv/415 V) 95 sq mm Copper (less than and up to 3 MVA) Station ASS Panel to PD ASS 95 sq mm Copper The electro technical characteristics required to be guaranteed for medium voltage cable for the above cable sizes, are shown in the technical sheet enclosed as an Annexure with this specification. The elevated corridor ASSs shall be supplied from a 33 kv cables Network, which shall consist of two cables (cable 1 and cable 2) normally independent from one another. The network is divided into loops, as necessary, as shown in the relevant Auxiliary Power Supply scheme. The 33 kv distribution cables in the elevated sections shall be laid inside cable path/channels provided on the viaduct along the tracks. Current rating for cables shall be determined taking into consideration the following installation methods as applicable: In the tunnels In cast in pipes Trenches On brackets Ducts And on the following as per design data: temperature correction thermal resistivity laying depth cable distance cable grouping factor etc

2. GOVERNING SPECIFICATIONS The 33 kv Cables shall conform to IEC 60502 and shall be of 18/30 kv (36 kv). The cables shall be of dry-insulated, radial-field cable, based on proven technology. They shall be constituted by assembly of three single core cables in twisted or cloverleaf pattern, annealed circular stranded Copper conductor or stranded Al Conductor for the cables as specified. The cable shall be XLPE insulated with semi-conducting screen over conducting core. The cable shall also be Tape armoured. It shall conform to IEC 60502 Part 2 latest for construction and for testing. 2.1 Standards The 33 kv Cables shall satisfy the following requirements and shall also comply with standards in force when the cables are manufactured, particularly which are in the following table (Unless otherwise stipulated in the specifications, the latest version of the following Standards shall be applicable): - Standard # IEC 60502 IEC 60228 IEC 60840 IEC 60332 IEC 60811 IEC 60754 ASTM D 2843 ASTM D 2863 IS 7098 Part 2 Description Power cables with extruded insulation and their accessories for rated voltages from 1 kv (Um = 1,2 kv) up to 30 kv (Um = 36 kv) Part 2: Cables for rated voltages from 6 kv (Um = 7,2 kv) up to 30 kv (Um = 36 kv)" Conductors of insulated cables Power cables with extruded insulation and their accessories for rated voltages above 30 kv (Um = 36 kv) up to 150 kv (Um = 170 kv) - Test methods and requirements Part 1 : Tests on electric and optical fibre cables under fire conditions Part 3 : Tests on electric cables under fire conditions Electric and optical fibre cables - Test methods for non-metallic materials Test on gases evolved during combustion of materials from cables - Part 1: Determination of the halogen acid gas content Standard Test Method for Density of Smoke from the Burning or Decomposition of Plastics Test Method for Measuring the Minimum Oxygen Concentration to Support Candle-Like Combustion of Plastics (Oxygen Index) Cross linked polyethylene insulated thermoplastic sheathed cables, Part 2: for working voltages from 3.3 KV up to & Including 33 KV. Page 5 of 14

2.2 Abbreviations IEC International Electro technical Council ASTM - American Society for Testing and Materials AMS Auxiliary Main Substation ASS Auxiliary Sub Station RSS Receiving Sub Station XLPE Cross Linked Poly Ethylene FRLS Fire Retardant Low Smoke FRLSZH Fir Retardant Low Smoke Zero Halogen CB Circuit Breaker PD Property Development IS Indian Standard 3. TECHNICAL REQUIREMENT The cables shall be insulated with chemically cross-linked polyethylene (XLPE), with semi-conducting screen over a copper conducting core, insulating envelope AIuminium Tape armouring and suitable protective sheath. operating voltage: 33 kv rms between phases, specified voltage: 18/30 kv rms (according to IEC 60502) Conductors as specified The Contractor shall calculate and inform current rating to verify cross-sectional area of 33 kv cables, according to the latest arrangement of the ASSs along each 33 kv cable. All cables whether Fire Retardant Low Smoke (FRLS) to be used in elevated sections or Fire Retardant Low Smoke Zero Halogen (FRLSZH) to be used in the Underground Sections shall conform to IEC 60502 or equivalent. The cables, in addition, shall be nonfire propagating, non-toxic and low-smoke producing type. The various constructional features required for the 33 kv cables are as under: 3.1 Conducting Core The conducting core shall be made of bare annealed copper or aluminium, as the case may be according to Class 2 as per publication IEC 60228; Latest Version. 3.2 Conductor: The conductor shall be formed from annealed circular stranded Copper conductor (or stranded Aluminum Conductor as the case may be) complied with IEC latest publications 60228. The conductor shall be compact circular stranded. Page 6 of 14

3.3 Conductor Screen: The conductor screen to be provided as per Clause 7.1 IEC 60502-2:2005 or equivalent clause in latest version of IEC 60502-2. The conductor screen shall consist of suitable thickness and volume resistivity. It shall be easily removable from conductor during jointing. Nominal thickness of conductor screen shall be 0.7mm. 3.4 Insulation: The Insulation shall be XLPE complying with IEC 60502 and IEC 60811. The insulation shall have a higher degree of Cross- Linking, free from contaminants and air voids, heat resistant and shall be applied by the extrusion process. The XLPE insulation shall be suitable for use on power cable in wet and dry locations at conductor temperature as per IEC 60502-2.For this purpose, short circuit current in conductor is to be considered as 7 ka. The conductor with screening shall be provided with cross-linked polyethylene (XLPE) insulation applied by extrusion. The nominal thickness of insulation shall not be less than 8 mm as per IEC 60502-2 and subject to tolerance as per IEC 60840, clause 10.6.2. Alternatively higher thickness of insulation as per IS 7098 with specified eccentricity in IS 7098 will also be accepted. The insulation compound shall be of high quality, and shall be heat, moisture, ozone and corona resistant. XLPE compound should be from reputed manufacturer e.g. Borealis Sweden or NUC Japan or equivalent with satisfactory service experience of more than 5 years. The Insulation shall be applied by triple extrusion and vulcanized using dry curing process to form a compact homogenous body free from micro voids and contaminants. 3.5 Insulation Screen: The Insulation screening shall be applied direct upon the insulation as per IEC 60502-2. The screen shall be tightly fitted to the insulation to exclude all air voids and still it could be easily stripped on site. Semiconducting compound should be from a reputed manufacturere.g. Borealis, Sweden or NUC Japan or equivalent with satisfactory service experience of more than 5 years. Nominal thickness of insulation screen shall be 0.7mm. The conductor screen, insulation & insulation screen shall be extruded in a single process (triple extrusion). 3.6 Water Barrier: Longitudinal: Page 7 of 14

The water barrier shall be semi-conducting water swellable tape to be applied over the extruded insulation screening to block and prevent moisture propagation in a longitudinal direction. The semi-conducting tape shall be suitable for the operating temperature of the cable and compatible with the insulation. 3.7 Metallic Screen: The metallic screen shall be plain copper round wire and copper tape applied helically over the semi-conductor bedding tape(s). An annealed plain copper binder tape shall be applied in the form of an open helix, over the copper wire screen. The area of the copper wire /copper tape should be able to withstand specified earth fault current (minimum 1 ka for 3 sec). Bidder to submit the calculations giving details of the area of copper wire/ copper tape screen. The three-phase short-circuit current capacity of metallic screen is to be considered, 1 ka (for the cables to be fed by substations where Neutral Grounding Resistor (NGR) is installed). The sheath shall be impervious to moisture, reasonably close fitting and free from defects and impurities such as oxide, which give rise to failure under working conditions. 3.8 Inner Sheath: A polypropylene tape shall be applied over the metallic screen. For FRLSZH cables an inner layer of FRLSZH tape shall be applied over metallic screen followed by Polyethylene laminated Aluminium tape. 3.9 Armouring: Double Tape Aluminium armouring should be applied over the inner sheath and the thickness of the same should be as per IEC 60502. 3.10 Short Circuit Rating of Metallic Sheath/Screen The area of copper wires/copper tape shall be designed to meet the requirement of the system short circuit rating of 1 ka for 3 Seconds. 3.11 Outer Sheath The outer sheath to be provided as per IEC 60502-2. Page 8 of 14

4. ADDITIONAL REQUIREMENT Cables laid on viaduct & ramps shall be exposed to sun, therefore such cables shall be capable of withstanding ultraviolet radiation. They shall be black in colour with identification for Red, Yellow & Blue phases which can be clearly seen without efforts throughout the run. 4.1 Outer Sheath should have following features: A. Cables laid in elevated sections shall be exposed to sun. The outer sheath shall be extruded in black colour with UV Protection, FRLS PVC conforming to the requirement of IEC specifications and extruded continuously. Such cables shall have phase identification after interval of 10 meters. Colour coding shall be done at manufacturer s works. The details of compound used for outer sheath shall be submitted. B. For Underground cables the outer sheath shall be extruded Red/ Yellow/ Blue colour halogen free flame retardant polyolefin conforming to the requirement of IEC specifications and extruded continuously. Outer sheath shall be treated with Anti Termite/ Anti pest/ Anti rodent & corrosion Resistant Compound. The sheath shall be resistant to water, ultraviolet radiation, fungus attacks, conforming to the requirement of IEC specifications and extruded continuously. The details of compound used for outer sheath shall be submitted. 4.2 The Contractor shall confirm the cross section of the cables in as regard to: - the route installation, - the thermal conditions in service, - the climatic conditions, - the energy and currents flowing through these cables, taking into account the worst electrical conditions, - operation under permissible overload conditions, - operation under permissible overload conditions when all 33 kv distribution are supplied by only one transformer, and on only one 33 kv cable. 4.3 The protective sheath shall carry the indications listed below, in letters and digits at least 6 mm high: - Designation of ownership, - Nature and cross-sectional area of conductors, - Specified cable voltage, - phase numbering, - Manufacturer s name - Length of cable shall be marked at 1 m interval. - Year and month of manufacturing Page 9 of 14

4.4 The cable shall be manufactured by a company having ISO accreditation for quality. 4.5 The manufacturing process of XLPE cable shall consist of conductor screen, insulation & insulation screen which shall be extruded in a single process. (Triple extrusion) and cross linked by a standard Process of dry curing technology to ensure homogeneity and absence of micro voids. The cables shall be manufactured by Dry Curing Process. 4.6 The Contractor shall provide trefoil clamps of non metallic sturdy type at every 5 meters with cable ties at every meter. 4.7 The Employer may decide to visit the works of cable manufacturer to verify the manufacturing process mentioned. 4.8 The Bidder along with the Bid, shall submit the details regarding cable construction, bill of material the manufacturing process proposed to be adopted for the manufacturing of 33 kv cables to be used in the project, along with Quality control measures adopted by the Manufacturer, to ensure :- The values and tolerances are strictly as per IEC. The cable manufacturer exercises strict quality control measures, including stage inspections, routine inspections etc. to ensure conformity to standards. Periodical inspections of the Manufacturer works, manufacturing processes, Internal Quality control records of the manufacturer etc shall be carried out by the User (DMRC/Nominated agency), to ensure compliance to Quality standards. 5. MAINTENANCE & LIFE The cable should be designed for maintenance free service of minimum 35 years for all types of installation & under prescribed environmental conditions. 6. SPECIAL CONDITION 6.1 All type of Cables to be used in Underground Sections shall be Fire Retardant Low Smoke Zero halogen Type (FRLSZH) and cables to be used in elevated and at grade sections shall be FRLS Type. Cables from AMS to ASS shall also be FRLS type excluding portion laid in underground section (station and tunnel) which shall be FRLSZH type. The interconnections between the elevated & underground section shall be dealt accordingly with minimum number of joints. 6.2 The manufacturer shall have laid down in-house selection process of the raw material used and shall submit all details, if equivalent raw material (as referred in clause 3.4, 3.5 above) is used whenever specified. Page 10 of 14

7. TESTING 7.1 All type tests to be conducted as per IEC 60502-2 The 33 kv cable shall comply with following Test Standards in addition to test standards of IEC 60502: a. IEC 60332 Part 1 and 3, category A, test on single and bunched cables under fire condition. b. Limiting Oxygen Index at least 30 tested as per ASTM D-2863. c. Temperature index of minimum 250 deg C as per IS 7098 (Part-2). d. Smoke density Test (on sheathing material), when tested in accordance to ASTM D- 2843, maximum smoke density rating shall be 60 as per IS 7098 Part 2. This will be applicable for FRLS Cable. e. All Insulation is to be moisture and heat resistant, with temperature rating appropriate to the application conditions and in no case lower than 90 deg C. f. In addition to the above FRLSZH cables used in U/G section shall also comply with following test standards :- Determination of the amount of halogen Acid Gases as per IEC 60754 Part 1 (Maximum HCL gas shall not exceed 0.5%) and IEC 60754 Part II Smoke density Test (on sheathing material), when tested in accordance to ASTM D-2843, maximum smoke density rating shall be 30 as per IS 7098 Part 2. This will be applicable for FRLSZH Cable. 7.2 The user may ask repetition of the following type tests - Bending Test - Tan δ measurement for cables - Impulse test followed by a voltage test for 4 hrs. 7.3 The manufacturer shall not change the Bill of Material used in the manufacturing of samples for routine and Type testing as repeated above and in cables intended to supply against the contract Page 11 of 14

8. DATA SHEET - 33 KV CABLES S. No. Description Unit Values 1 Manufacturer 2 Cable Size Sq mm 400 300 95 3 Cable type Copper/XLPE Aluminium/ XLPE/PVC Copper/ XLPE/PVC 4 Voltage Grade (U 0 /U (U 2 ) kv 18/30 (36) 18/30 (36) 18/30 (36) 5 Reference Standard IEC 60502 IEC 60502 IEC 60502 6 No. and cross sectional area of conductor 3 x1c x 400 sq mm 3 x1c x 300 sq mm 3 x1c x 95 sq mm 7 Conductor Material Copper Aluminium Copper 8 Shape Circular compact stranded Circular compact stranded Circular compact stranded 9 Class/Standard Class 2/ IEC 60228 Class 2/ IEC 60228 Class 2/ IEC 60228 10 Nominal Diameter of Conductor mm * * * 11 Conductor Screen materials Extruded semiconducting com'd Extruded semiconducting com'd Extruded semiconducting com'd 12 Nominal thickness of conductor screen mm * * * 13 Insulation material XLPE XLPE XLPE 14 15 Nominal thickness of insulation Nominal diameter over insulation mm * * * mm * * * Page 12 of 14

16 Insulation screen material (Non-metallic) Extruded semiconducting com'd Extruded semiconducting com'd Extruded semiconducting com'd 17 Nominal thickness of insulation screen mm * * * 18 Nominal thickness of tape mm * * * 19 No. and Diameter of wires No. /mm * * * 20 Cross sectional area Sq mm * * * 21 Outer sheath material Flame retardant Flame retardant polyvinyl chloride Flame retardant polyvinyl chloride 22 Nominal thickness of outer sheath mm * * * 23 Nominal overall diameter (± 2mm) mm * * * 24 Minimum bending radius mm * * * 25 26 Max. D. C. Conductor resistance at 20 o C Star reactance per phase at 50 Hz Ω/km * * * Ω/km * * * 27 Capacitance per phase µf/km * * * 28 Charging current per phase at U 0, 50 Hz A/km * * * 29 Max. Current rating in air A * * * 30 31 Max. Current rating in Ground Max. Conductor temperature on continuous A * * * 90 90 90 Page 13 of 14

32 33 Max. conductor temperature in short circuit Max. short Circuit current rating 250 250 250 * * * t = 0.1 sec ka * * * t = 0.2 sec ka * * * t = 0.5 sec ka * * * t = 1.0 sec ka * * * Length marking: Length shall be marked with number at one meter intervals on the sheath. *Bidder to furnish the data Page 14 of 14