PART VII - WATER SYSTEM DESIGN CRITERIA

Similar documents
SECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES

SECTION WATER MAINS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA

SECTION 8 WATER SUPPLY SYSTEMS

Engineering Design Center. Standard Drawings. 1st Edition -January 2016

2. A preconstruction meeting with the TWA s staff is required prior to initiating construction.

Fire Protection Underground Piping. ASCE Meeting 12/17/14 Columbia, SC

This is only a general checklist; please refer to the CVWD Development Design Manual (DDM) for all requirements and regulations.

Section V WATER DISTRIBUTION SYSTEM DESIGN GUIDELINES

All service lines shall conform to the following requirements:

Underground Piping for Private Hydrants & Sprinkler Supply Line

Contact the Jurisdictional Engineer for materials allowed by each jurisdiction.

Section 5 Design Criteria Domestic Water Facilities

Construction Documents (CDs) Required Signature Blocks and Standard Notes

3.0 DESIGN CRITERIA FOR SANITARY SEWER FACILITIES

WATER DISTRIBUTION DESIGN GUIDELINES

Rural Servicing Guidelines

STANDARDS FOR WATER FACILITIES

SEWER SYSTEM DESIGN GUIDELINES

Section 5 - Planning Criteria. Section 5

CHAPTER 4 MINIMUM DESIGN CRITERIA

County of Sacramento Standard Construction Specifications January 1, 2008 TECHNICAL PROVISIONS

SERVICE LINES, METERS AND APPURTENANCES

CURRENT NORTH LAS VEGAS ADDENDA

INSPECTION AND ACCEPTANCE FOR MAINTENANCE

B. Subsurface data is available from the Owner. Contractor is urged to carefully analyze the site conditions.

POTABLE WATER MAINS. E. Section Water Distribution System Design Guidelines. F. Section Water Main Testing and Acceptance

SECTION 3.0 SPECIFICATIONS FOR DRINKING WATER DISTRIBUTION SYSTEMS DESIGN

1. B16.1 Cast Iron Pipe Flanges and Flanged Fittings, Class C 111 Rubber Gasket Joints for Ductile Iron Pressure Pipe and Fittings

GUIDELINE FOR PROVIDING WATER AND SEWER SERVICE TO DEVELOPER PROJECTS AND PUBLIC OR PRIVATE PROPERTIES

SECTION POLYVINYL CHLORIDE (PVC) WATERLINE

ADDENDUM NO. 1. Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities

PART I DESIGN STANDARDS AND PROCEDURES FOR WATER DISTRIBUTION AND SANITARY SEWER SYSTEMS PRINCE GEORGE COUNTY, VIRGINIA

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)

TOWN OF MOUNT PLEASANT WESTCHESTER COUNTY, NEW YORK

SECTION TRENCHING & BACKFILLING

SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS

Contact Clark Public Utilities Construction Services department at (360) to initiate a request for service.

SECTION DUCTILE IRON FITTINGS. A. This section includes materials, installation, and testing of ductile iron fittings 48 inches and smaller.

CHAPTER 3 - PRESSURE IRRIGATION

Pipe Replacement Strategies for Aging and Seismic Issues

CITY OF CAMDENTON OFFICE OF THE BUILDING OFFICIAL Commercial Building & Architectural Review Permit Application

SEISMIC DESIGN CRITERIA FOR SAN FRACISCO WATER SYSTEM IMPROVEMENT PROGRAM

SECTION WATER DISTRIBUTION

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS

Read Only Copy Not For Distribution. Chapter 17. Private Potable Water Supply Systems 17.1 GENERAL REGULATIONS 17.2 QUANTITY OF WATER REQUIRED

NOTICE OF DISCONTINUATION,

Engineering Plan Submittal Requirements. Revised: October 6, 2017

ARTICLE 29 SANITARY SEWER FORCE MAINS

CITY OF HUMBLE DESIGN CRITERIA MANUAL FOR WASTEWATER COLLECTION SYSTEMS, WATER LINES, STORM DRAINAGE, AND STREET PAVING

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

CITY OF ASTORIA PUBLIC WORKS ENGINEERING DIVISION ENGINEERING DESIGN STANDARDS FOR IN-FILL DEVELOPMENT

APPLICATION FOR PUBLIC INFRASTRUCTURE PERMIT

SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS

SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL

GRAY WATER SYSTEMS (Reference California Plumbing Code Chapter 16 and 16A) Revised: 6/11/14

Section 7 Hydraulic Model Development and Evaluation Criteria

DIVISION 3: SEWER. Improvement Design Standards City of Dundee Oregon. Division 3 : Sewer Page 1

City of Denton. Water and Wastewater Criteria Manual

CHAPTER 3 - PRESSURE IRRIGATION

TRENCHLESS CONSTRUCTION (BORING, JACKING, AND TUNNELING)

SPECIFICATION : BORING AND JACKING

UNIFIED FACILITIES GUIDE SPECIFICATIONS

PORT OF SAN FRANCISCO PLUMBING CODE. Based on the 2010 California Plumbing Codes

CITY OF MARTINEZ STANDARD SPECIFICATIONS FOR WATER LINE WORK

GRAY WATER RECYCLING SYSTEMS

RICHFIELD CITY CONSTRUCTION STANDARDS

TECHNICAL PROCEDURE TABLE OF CONTENTS

RULES AND REGULATIONS FOR WATER AND WASTEWATER SERVICE APPENDIX B WATER AND WASTEWATER SERVICE CONSTRUCTION SPECIFICATIONS

APPENDIX A - Seismic Terms, Tables and Figures:

3/18/2016. Operator Basics: Storage and Distribution. RCAC 2016 Online Training Series. Storage and Distribution Word Search

C900/RJ. CertainTeed. PVC Pipe. with CertainTeed s proven Certa-Lok restrained joint system. Directional Drilling

Innovation in Joint Restraint Systems for PVC Pressure Pipe and Fittings. Clean & Safe Drinking Water Workshop. Wednesday, March 25, 2015

GENERAL CONSTRUCTION

CHECKLIST FOR STREETS, INLETS, AND STORM SEWER DESIGN

Water Distribution Design and Construction Standards

THE KANSAS CITY SOUTHERN RAILWAY COMPANY 427 West 12 th Street Kansas City, Missouri

SECTION TAPPING SLEEVES AND VALVES

DENR Public Water Supply Section FIGURE 1(A): ALKALINITY VS PH

MATERIAL ALLOWANCES AND UNIT PRICES

CONSTRUCTION PROCEDURES. AWWA D110 Type I Prestressed Concrete Tanks

Short title. This chapter may be cited as the "Kern County Building Code."

SECTION PIPE & PIPE FITTINGS PART 1 GENERAL

SECTION WATER DISTRIBUTION SYSTEM

Fence, Wall & Column Information Packet

ENGINEERING DESIGN STANDARDS

Section , Article 4 of the Zoning Ordinance December 14, 2012 Page 1 of 8

DIVISION 31 EARTHWORK 2006 Edition, Published January 1, 2006; Division Revision Date: January 31, 2012

Engineer s Packet. Water and Sewer

Town of New Tecumseth Engineering Design Criteria and Standards for Subdivisions and Capital Works Projects

2017 Material and Construction Specifications

Water Pipeline Design Guidelines

STANDARD SPECIFICATIONS SECTION JACKED CASING

Series 2000PV Mechanical Joint Restraint for PVC Pipe

SUB WATER DEPARTMENT STANDARD CONSTRUCTION SPECIFICATIONS TABLE OF CONTENTS SECTION DUCTILE IRON PIPE, FITTINGS AND SPECIAL ITEMS

Storm. Section. B. General Design and Drawing Standards Design

C. Foundation stabilization for pipe and utility structures.

ERIE COUNTY WATER AUTHORITY DESIGN STANDARDS FOR WATERMAIN, PUMP STATION, AND TANK CONSTRUCTION

WATER SUPPLY AND DISTRIBUTION

Building Permit Submittal Requirements

SEWER FORCE MAIN HDPE PIPE

Transcription:

PART VII - WATER SYSTEM DESIGN CRITERIA A. Water Distribution, General 1. The water system layout shall be approved by the City Engineer. The fire hydrant layout shall be approved by the Redwood City Fire Department. 2. The developer shall provide easements as necessary and required by the Engineering Division for water lines and accessories. The minimum width of easement shall be 15' clear of any property line fences. 3. Minimum size water main shall be eight inches in diameter; otherwise, the pipes must be sized for the design flow. 4. Calculations or computer modeling may be required for sizing more complicated water systems and for evaluating the impact on the existing systems, as determined by the City Engineer. B. Water Demand Projection 1. The Average Day domestic Water Demand Projection for new buildings is calculated using the ATTACHMENT Q. 2. The Maximum Day Demand is equal to twice the Average Day Demand. 3. The Peak Hour Demand is equal to four times the Average Day Demand (Twice the Maximum Day Demand) for the Redwood Shores Area; 1.6 times the Maximum Day Demand for the Main City Zone; and 2.4 times the Maximum Day Demand for the Hillside Areas. C. Fire Flow Requirement 1. Estimate the fire flow requirement per the International Fire Code (IFC) Appendix B. 2. For other than single and two family dwellings, the required fire flow may be reduced up to 50% when a building is provided with an approved automatic fire sprinkler system. D. Water Storage and Transmission Facilities 1. Size storage tanks using one time the service zone s Maximum Day Demand plus Fire Flow Requirement. 2. Size pump station, piping, and appurtenances for the largest of: a Peak-Hour Demand, b Maximum-Day Demand plus fire flow, or c The tank replenishment flow. VII-1

3. Maximum allowable main line pressure is 120 psi measured at a fire hydrant. 4. Maximum allowable service pressure measured at a faucet is 80 psi; minimum service pressure shall be 35 psi. 5. Flow velocities shall be 4 fps under normal service conditions. Under fire flow conditions, the preferred flow velocity is 7 fps. The flow velocity shall never exceed 10 fps. 6. If the service pressure exceeds the maximum of 80 psi, an individual pressure regulator will be required on the service line. If the pressure does not meet the minimum of 35 psi, an individual pressure booster station will be required on the service line. 7. Fire flows shall have a minimum residual pressure of 20 psi. 8. For calculating pressures in high pressure zones, calculate the maximum pressure using the elevation of the reservoir at half full. E. Alignment 1. Minimum clearances shall be 5 feet horizontal and 1 foot vertical clearance from any other underground pipe, and 10 feet horizontal clearance to sanitary sewer lines. 2. Water mains shall be installed above sanitary sewers. Where this clearance is not practical, consult the California Administrative Code (Health Code) for separation standards and alternatives. 3. Minimum cover shall be 3' from finished grade to top of pipe, or 2' below subgrade, whichever is greater. 4. The system shall be 'looped' from the street main, as required to provide adequate fire flow. 5. Gate or butterfly valves shall be installed to isolate each branch run from main supply run. Valves 12 and larger shall be butterfly valves, and 10 and smaller shall be gate valves. 6. Air release valves will be installed at locations required by the Engineering Division. F. Materials 1. Pipeline materials for mains shall be PVC conforming to the requirements of the City's Standard Technical Specifications. 2. Valves, burys and fittings shall be cast iron and fusion epoxy coated and lined, conforming to City Standard Specifications. VII-2

3. Water mains shall be pressure tested and disinfected prior to connection to the City's system, conforming to City Standard Technical Specifications. G. Cathodic Protection 1. Water systems in areas east of El Camino Real shall, in addition to other coatings called for in the specifications, have cathodic protection using a Petrolatum Wax Tape System for isolated fittings and restraining devices. Otherwise, Cathodic Protection Anode shall be used as called for in the Engineering Standards Specification Section 02661 Cathodic Protection and in the Engineering Standard Detail W-14 Cathodic Protection at Fittings and Valves. 2. For water systems in areas west of El Camino Real, and east of the Alameda de las Pulgas the soils shall be tested for corrosivity using the procedures described in Appendix "A" of AWWA C-105. Any soil having a soil-test evaluation of 10 points or more shall require the use of cathodic protection. H. Water Services 1. Separate water services and meters shall be installed in separate trenches for each dwelling unit. 2. Minimum service size shall be one and a half (1.5) inch. 3. Meter boxes shall be located where they are easily accessible to the meter reader, in the sidewalk, 18" behind and set parallel with the curb. Meters may not be closer than three feet to a driveway to be out of the way of parked vehicles. 4. Services shall not be located closer than five feet from a sewer lateral, with a minimum of 24" of cover. 5. Water meters and fire detector check meters may be installed by the City upon payment of the appropriate fee. 6. Detector meters and detector check valves, where required by the City Engineer, are to be supplied, installed and maintained by the property owner. I. Fire Protection Systems 1. Fire hydrants come in four (4) different styles depending on location and water main size, and shall be provided as approved by the Engineer. a Type A At Emerald Lake Hills area, fire hydrants shall be Mueller A-423 dry barrel or approved equal fusion epoxy lined and coated; provided with two 2-1/2 and one 4-1/2 outlets, conforming to AWWA C502. b Type B At Redwood Shores, fire hydrants shall be Clow 92 low silhouette, wet barrel or approved equal fusion epoxy lined and coated; provided with two 2-1/2 and one 4-1/2 outlets, conforming to AWWA C503. VII-3

c Type C At all other locations, for water main size under 10, fire hydrants shall be Clow 76 wet barrel or approved equal fusion epoxy lined and coated; provided with two 2-1/2 and one 4-1/2 outlets, conforming to AWWA C503. d Type D Wherever the water main size is 10 or larger, fire hydrants shall be Clow 865 wet barrel or approved equal fusion epoxy lined and coated; provided with one 2-1/2 and two 4-1/2 outlets, conforming to AWWA C503. 2. Location of fire hydrants must be approved by the Fire Department. Use the following criteria as a reference: a. The minimum number of fire hydrants shall be in accordance with Appendix C of the International Fire Code. b. Fire Hydrants shall be installed along both sides of divided or arterial streets. c. A fire hydrant shall be located on the same side of the street at all Fire Department Connections (FDC) within 50 linear feet. d. Landscape materials shall be designed so that, when fully grown shall not obscure the FDC s and fire hydrants (three foot minimum clearance required on all sides). e. Fire Department Connections approved by the Fire Department, are required for each commercial building and shall be located as close as possible to the street frontage. f. FDC s shall be designed to provide one 2 ½ outlet for each 250 gpm of sprinkler system demand. 3. For buildings requiring a separate fire sprinkler system, the system layout shall be shown, including the complete fire service line to the first joint above finish grade on the automatic sprinkler riser; riser location by dimension to the building wall; a profile to the riser, which shows how thrust is restrained at its base and where cathodic protection (if applicable) is cut off by an insulating flange; location of Backflow Prevention Device, Fire Department Connection (even if it s on building wall); Fire Hydrant and Post Indicator Valve or Wall Indicator Valve. 4. Before combustible materials may be stored or constructed on site, the Fire Department must approve fire flow and access. Before a fire hydrant may be placed in service, a high velocity flush of the fire hydrant shall be witnessed and approved by the City Engineer. J. Thrust Blocks 5. Thrust blocks shall be designed for a minimum operating pressure of 225 psi, with soil bearing pressures of 2000 psf, unless smaller soil pressures are recommended by the project geotechnical engineer. VII-4

6. In Bay Mud conditions, thrust blocks shall be designed with spread footings so as not to exceed the allowable bearing pressure of the soft Bay Mud (approximately 600 psf See Part IX of this Volume for more requirements). Consult the project geotechnical engineer. K. Backflow Prevention Devices 1. All commercial private water supply pipelines shall be provided with an approved backflow prevention device. 2. Backflow prevention device shall be in the form of a Reduced Pressure Principle Backflow Preventer, per City Standard Details. 3. The type of Backflow preventer will be determined by the Engineer, depending on whether the location is deemed to be a low hazard potential, or whether dangerous or toxic substances are involved. 4. Backflow prevention devices shall be approved by the County of San Mateo, shall bear the stamp of Underwriters Laboratories (U.L.); and be listed by the University of Southern California at www.usc.edu/dept/fccchr/list.html. 5. Devices shall be installed on private property. L. Maintenance Requirements 1. The City will maintain water mains and domestic water services in both public and private streets up to and including the domestic meter and the detector meter; and the fire service lines from the watermain up to the property line. 2. Property owners shall maintain backflow prevention devices, meter boxes, domestic water service runs beyond the meter and fire service lines starting from the property line. M. Seismic Design for Water Pipelines 1. Special attentions and seismic design requirements shall be applied in areas of largest potential permanent ground movements (including settlements and lateral spreads) due to seismic-induced liquefaction or cyclic softening of soft clays. These areas are located within 200 feet of creeks, sloughs, culverts and San Francisco Bay (high water level), underlain by the Young Bay Mud or Liquefiable deposits. They are shown on the map in Attachment T as Area 1. 2. Special attentions and seismic design requirements shall also be applied to hilly service areas west of Alameda De Las Pulgas where there are high probabilities of earthquake-induced landslides. They are shown on the map in Attachment T as Area 2. 3. Special attentions and seismic design requirements shall be optional and required on a case-by-case basis for the remainder of the city service areas east of Alameda De Las Pulgas and west of US 101 mentioned in Paragraph 1 and 2 above. They are shown on the map in Attachment T as Area 3. VII-5

4. Pipelines require seismic designs shall be designed for seismic hazards in accordance to latest and applicable AWWA standards and the 2005 American Lifelines Alliance s Seismic Guidelines for Water Pipelines (ALA 2005) with reference to the City s Seismic Vulnerability Assessment Report (G&E September 2011 Chapter 3). ALA (2005) provides guidance for selection of pipeline importance factors, return periods for earthquakes, methods to estimate soil permanent ground deformations, allowing pipe stresses and strains. These may be refined by cognizant geologists, geotechnical, civil, structural engineers and professionals, as approved by the City. 5. Minimum seismic design requirements are: a. The design of new pipes in the mapped area requires that the pipe should be reliable to withstand the seismically-induced permanent soil movements. Lacking site-specific calculation, the pipe should be able to sustain a 1% change in pipe length. This can be done by using fullyrestrained pipe that can reliably stretch (yield) 1%; or have sufficient flexible joints to absorb the equivalent movement. b. Submit seismic design calculations to document the design and installation of pipes 16-inches in diameter (nominal) and larger, and of critical pipes regardless of size as determined by the City Engineer. The design procedure may follow guidelines in ALA (2005). c. Detailed seismic design calculations are optional for the remainder pipe sizes and classifications. Chart Method (ALA 2005) Design Approach for Pipe Category C (Restrained Joints) - may be used for these pipes instead. d. Acceptable alternatives to meet this 1 percent strain are: i. Fully restrained High Density Polyethylene (HDPE) pipe with full penetration welds. ii. Or approved equals. e. All pipes to be provided with suitable corrosion protection. f. All designs to meet AWWA requirements for all other loadings. g. Service laterals, blow offs, air and vacuum release and other appurtenances will be installed to resist the corresponding seismic loads, or installed in manner so that can be isolated (valved out) within 3 feet (1 meter) of the main. h. Alternative designs meeting the intent of ALA (2005) and the City Standards may be submitted. VII-6