TECHNICAL NOTE. Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC. On Cold-Formed Steel Construction INTRODUCTION

Similar documents
VERTICAL AND HORIZONTAL LATERAL LOAD SYSTEMS

MECHANICAL BRIDGING AND BRIDGING ANCHORAGE OF LOAD BEARING COLD-FORMED STEEL STUDS. Paul E. Lackey, EIT Nabil A. Rahman, Ph.D.

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)

Structural vs Nonstructural Members. Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures

TECHNICAL NOTE. On Cold-Formed Steel Construction DESIGN CONSIDERATIONS FOR FLEXURAL AND LATERAL-TORSIONAL BRACING

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

AC R1 # Triangle Parkway Suite 100 Norcross, Ga Phone: Fax: AC R1. September 11, 2012

ANALYSIS AND DESIGN OF MOMENT RESISTING MIDWALL BY THE STEEL NETWORK, INC.

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS

Originally Issued: 05/20/2013 Revised: 07/07/2017 Valid Through: 05/31/ Design

Lateral load basics Code acceptance of Standard. Standard Overview 2008 Wind & Seismic Standard. Wind. Wind Load Path. IBC Section 1604.

Product Designation As specified in the AISI standard for cold formed steel framing General provisions A5.2.

LATERAL DRIFT DESIGN IN COLD FORMED STEEL WALL SYSTEMS

Tables with Allowable ASD Seismic Values For Design at R = 6.5. Special Moment Frame MF1-12

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

Lateral Design of Mid- Rise Wood Structures

Originally Issued: 02/11/2011 Revised: 02/23/2018 Valid Through: 02/28/2019

SECTION PLATE CONNECTED WOOD TRUSSES

AISI S E1 AISI STANDARD. Errata to North American Specification. for the Design of Cold-Formed. Steel Structural Members.

Nabil A. Rahman, Ph.D., P.E.

Single & Back-to-Back StiffWall Column Product Profile

22. DESIGN OF STEEL BRACED FRAMES Eccentrically Braced Steel Frames

Light Steel Framing Members. Table of Contents

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS

Council on Tall Buildings

Design Example 2 Reinforced Concrete Wall with Coupling Beams

INNOVATIVE DESIGN AND TESTING OF A SEISMIC RETROFITTED STEEL DECK TRUSS BRIDGE

Guide to Attaching Exterior Wall Coverings through Foam Sheathing to Wood or Steel Wall Framing

Interpretation of SECTION 12 DESIGN AND DETAILING FOR EARTHQUAKE LOADS IS

ctbuh.org/papers Proposed Methodology To Determine Seismic Performance Factors For Steel Diagrid Framed Systems

SEAU 5 th Annual Education Conference 1. ASCE Concrete Provisions. Concrete Provisions. Concrete Strengths. Robert Pekelnicky, PE, SE

Copyright. magazine. CFS Load Bearing Construction

HSS section calculations are based on the AISC Steel Construction Manual, 13 th edition (ASD only).

Suspension Systems for Acoustical Lay-in Ceilings Seismic Design Categories D, E & F

CVEN 483. Structural System Overview

QUALITY CONTROL TESTING OF PLASTERBOARD FOR BRACING APPLICATIONS. Y L Liew Vicroads Victoria, Australia

On Improved Performance Of Eccentrically Braced Frames With Replaceable Shear Link

AISI Standard for Cold-Formed Steel Framing - Truss Design

4.2 Tier 2 Analysis General Analysis Procedures for LSP & LDP

The New SDI Diaphragm Design Manual

ACCEPTANCE CRITERIA FOR HELICAL PILE SYSTEMS AND DEVICES PREFACE

EVALUATION OF COLLECTOR DESIGN FOR CONCRETE DIAPHRAGMS

Wood Solutions Fair, 2014, Toronto

Seismic Rehabilitation of Selby Condominium Complex, Montreal (Quebec), Canada

Collective Chord Behavior in Large Flexible Diaphragms

W. Mark McGinley March 3, 2016 ISEA MEETINGS 1

Seismic design of braced frame gusset plate connections

3.5 Tier 1 Analysis Overview Seismic Shear Forces

Overview of the Standard for Seismic Design of Cold-formed Steel Structural Systems - Special Bolted Moment Frames

SEISMIC PERFORMANCE OF CONCRETE TILT-UP BUILDINGS: CURRENT WALL-TO-SLAB CONNECTIONS

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

An Update on AISI Standards for Cold-Formed Steel Framing

Originally Issued: 12/18/2015 Revised: 04/14/2017 Valid Through: 12/31/2017

The System Slotted Deflection Track (pat# 5,913,788)

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

Cyclic Tests of Long Shear Walls with Openings

Standard for Cold-Formed Steel Framing - Header Design

April 2, 2012 PARTIES INTERESTED IN EXPANSION ANCHORS IN MASONRY ELEMENTS

INHERENT DUCTILITY OF REINFORCED CONCRETE SHEAR WALLS WITH NON-SEISMIC DETAILING

Evaluation of Full-Scale House Testing Under Lateral Loading

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS 9050 CENTRE POINTE DRIVE, SUITE 400 WEST CHESTER, OHIO EVALUATION SUBJECT:

Performance-Based Design of Wood Shearwalls Considering Performance of the Overall Structure

DESIGN OF HIGH-RISE CORE-WALL BUILDINGS: A CANADIAN PERSPECTIVE

Tech Tips SidePlate Connections FAQ 09/30/2017

Considerations for Outof-Plane. Design

PR-L274 Nordic Structures Revised April 16, 2017

PORTAL FRAMES 1.0 INTRODUCTION

A Guide for the Interpretation of Structural Design Options for Residential Concrete Structures

LATERAL LOAD BEHAVIOR OF UNBONDED POST-TENSIONED HYBRID COUPLED WALLS. Qiang SHEN Graduate Research Assistant. Yahya C. KURAMA Assistant Professor

ACCEPTANCE CRITERIA FOR HELICAL FOUNDATION SYSTEMS AND DEVICES PREFACE

Bijan Khaleghi, Ph, D. P.E., S.E.

REPORT HOLDER: CALIFORNIA EXPANDED METAL PRODUCTS COMPANY (CEMCO) CROSSROADS PARKWAY NORTH, SUITE 325 CITY OF INDUSTRY, CALIFORNIA 91746

Structural Glossary. ARCH 631 Structural Glossary F2014abn

DESIGN CALCULATIONS INSTA-FOOTING LOAD BEARING CAPACITIES ON CONCRETE SLAB. January 14, 2017 Rev -

CIVIL BREADTH Exam Specifications

HYBRID MOMENT RESISTING STEEL FRAMES

Performance based Displacement Limits for Reinforced Concrete Columns under Flexure

USING WOOD STRUCTURAL PANELS FOR SHEAR AND WIND UPLIFT APPLICATIONS

In-plane testing of precast concrete wall panels with grouted sleeve

Learning Objectives. Copyright Materials. This presentation is protected by US and International Copyright laws. Reproduction,

Experimental study on seismic behavior of composite concrete and

Individual Truss Marking Is it a Building Code Requirement?

Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS

DESIGN AND CONSTRUCTION OF STEEL PLATE SHEAR WALLS. Matthew Eatherton 1 ABSTRACT

Bjorhovde, R. Stub Girder Floor Systems Structural Engineering Handbook Ed. Chen Wai-Fah Boca Raton: CRC Press LLC, 1999

ECCENTRICALLY BRACED FRAME DESIGN FOR MODERATE SEISMIC REGIONS

Special Inspections for Wood Construction BCD710 Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council

GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION REROOFING ADJUSTABLE FRAMING SYSTEM

THE AISC SEISMIC PROVISIONS: PAST, PRESENT AND FUTURE

CURTAINWALL DEFLECTION SOLUTIONS

For Best Non-Structural Steel Stud Specifications, Stay Apprised of Industry Standard Requirements

CALIFORNIA BUILDING CODE

Sabah Shawkat Cabinet of Structural Engineering 2017

ESR-2269 Reissued November 1, 2008 This report is subject to re-examination in one year.

Limit States Design in Structural Steel

Cold-Formed Steel Special Bolted Moment Frames: Capacity Design Requirements

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

Transcription:

TECHNICAL NOTE On Cold-Formed Steel Construction 1201 15th Street, NW, Suite 320 W ashington, DC 20005 (202) 785-2022 $5.00 Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC Summary: This Technical Note is intended to discuss some of the design requirements, detailing and practical limitations of diagonal strap bracing design. Diagonal flat strap bracing is a commonly used type of lateral force resisting system in residential and low rise commercial cold-formed steel applications. Disclaimer: Designs cited herein are not intended to preclude the use of other materials, assemblies, structures or designs when these other designs and materials demonstrate equivalent performance for the intended use; CFSEI documents are not intended to exclude the use and implementation of any other design or construction technique. INTRODUCTION Structures require a resisting system to transfer lateral loads imposed on them. Typically these loads are from wind or seismic forces. A commonly used type of lateral force resisting system in residential and low rise commercial cold-formed steel applications is diagonal flat strap bracing. When designing this type of force resisting system there are a number of design and serviceability considerations that should be investigated. These include loads, strap size, fastener quantity, connection detailing, and construction practices. GENERAL BRACING REQUIREMENTS The International Building Code (IBC) and the Uniform Building Code (UBC) contain limited information on requirements for designing diagonal strap bracing lateral force resisting systems. The designer is required to design diagonal straps and their connections in accordance with the design standard referenced in the model code. The 2006 IBC references the North American Specification for the Design of Cold-formed Steel Structural Members (AISI NAS-01), including 2004 Supplement (AISI NASPEC-SUP04) and the 1997 UBC references the AISI Specification for Design of Cold-Formed Steel Structural Members, 1986 (with December 1989 Addendum). In the AISI Standard for Cold-Formed Steel Framing - Lateral Design (Lateral-04) the design of diagonal strap bracing is to be done in accordance to the provisions of NAS-01. TYPES OF DIAGONAL STRAP BRACING Diagonal strap bracing can be detailed in a variety of different styles. Commonly diagonal strap bracing is used on the outside flange of perimeter load bearing studs (Figure 1). Another option is to use double sided diagonal strap bracing where there are straps on both the inside and outside flange of the studs. With either of these styles the strap may either be a wide strap connecting directly to the stud and track (Figure 2), or a narrower strap where a gusset plate is used to make the connection between the strap and the stud and track (Figure 3). Wide straps that connect directly to the stud and track may be preferred over straps with gusset plates for a couple of reasons. First the gusset plates and associated fasteners add thickness to the wall which may be difficult to conceal with siding or exterior finish. Second, wider straps connecting directly to the stud and track will ultimately require fewer fasteners which will reduce installation time. Cold-Formed Steel Engineers Institute 1 TECH NOTE L001-10 September 2010

FIGURE 1 FIGURE 2 TECH NOTE L001-10 September 2010 2 Cold-Formed Steel Engineers Institute

FIGURE 3 DESIGN CONSIDERATIONS When designing diagonal strap bracing there are a number of items to be investigated which are influenced by the type and geometry of the diagonal strap bracing. The provisions of the NAS-01 can be used to design these elements. The width of the brace will be primarily dependent on two things. First, it must be properly sized to resist the imposed tensile forces in the member. Second, if it is not desirable to use a gusset plate at each end of the strap a wider strap may be required to allow the strap to connect to both the stud and track. Connections and members must also be adequately sized to transfer loads. Where the studs are load bearing the effects of gravity loads in resisting and adding to overturning loads must be considered. Other potential design checks include induced eccentricity in the wall from a single sided strap, material over strength, and axial capacity of the chord studs. Finally, it will be necessary to properly design overturning restraints (holdowns), collectors and boundary elements. These items are not included in the scope of this Technical Note. It should be noted that because diagonal strap braces are tension only members the bottom track may be in compression between the diagonal strap and in tension outside of the brace. Often an anchor bolt is used to transfer shear loads from the bottom track to the foundation. If anchor bolts are in a compression area of the track, compressive axial capacity should be investigated. To resolve this anchor bolts may be placed in a tension area of the bottom track, or outside of the brace. Naturally this becomes an issue if the brace is located at a corner or end of a wall segment. Regardless of the anchor bolt location, bolt bearing on the web of the track and shear transfer shall be checked. During construction it is important that the strap is installed taut. This is contained in section C5.5 of the AISI Standard for Cold-Formed Steel Framing - Lateral Design, 2004 Edition. A taut strap will ensure that the strapping immediately engages when a lateral load is applied. Section 2211.4.6 of the 2003 IBC suggests pre-tensioning as a means to guard against loose straps. It is important, however, to ensure the strap is not overly pre-tensioned. Doing so can potentially reduce the load carrying capacity of the strap. The IBC uses response modification factors, or R-Factors, to provide an appropriate level of strength design load based on the type of lateral system. The IBC and ASCE 7 assign an R-Factor of 4 to ordinary steel concentrically braced frames. It should be recognized that there is a great deal of research available regarding the code assigned R-Factors and it may be beneficial to investigate this before using strap diagonal strap bracing, particularly in high seismic areas. This research is briefly discussed later. Cold-Formed Steel Engineers Institute 3 TECH NOTE L001-10 September 2010

The 2004 North American Standard for Cold-Formed Steel Framing - Lateral Design discusses the use of diagonal strap bracing and contains additional specific requirements for use in seismic areas. These special seismic requirements are contained in section C5 of the document and are included to ensure properly controlled ductility in the system. Specifically, the document gives additional requirements for connections, straps, studs and boundary members. EXISTING RESEARCH The Shear Wall Design Guide published by the Steel Framing Alliance in 1998 (Publication RG-9804) included diagonal strap bracing as one of the lateral systems investigated. This document highlights two important issues the designer must consider. 1. Straps are often constructed with material having yield strength higher than specified; therefore it is important to consider this in the design of the end connection. Ideally, to ensure ductile behavior the controlling design value should be the capacity of the strap. An over-strength strap will naturally be capable of transferring higher loads before reaching its yield point. This may result in a less ductile failure mode if the end connections are not sufficiently sized. 2. Diagonal strap bracing on one side of a wall will introduce eccentric loading on the end chord and tracks. Other research available includes McGill University s strap braced wall research program (2006) where the objective was to evaluate the ductility of diagonal strap bracing through monotonic and cyclic testing. This research discusses the difficulty in ensuring ductile behavior for diagonal strap bracing because of potential material over strength. In addition, the research suggests the ductility the system is also influenced by the stiffness of the holdown, anchor bolt and track detail. Also, the use of gusset plates will likely increase the wall stiffness compared to what flat straps alone would provide. The paper concludes that capacity based performance, where strap bracing would be selected as the fuse element, would improve the performance of the system. Additional design steps are required to achieve this. is a no rational basis for the establishment of these values. As was stated in FEMA 303, section 5.2 the R values, contained in the current Provisions, are largely based on engineering judgment of the performance of the various materials and systems in past earthquakes. The values of R must be chosen and used with careful judgment. Wilcoski also points out that when straps yield during a cyclic event the slack developed will influence the response of the system. As the system cycles between each tension strap it is not providing any resistance until a strap become taut again. The acceleration developed in the system during the slack time will cause shock loading of the members and connections. During cyclic testing this is represented as a pinched hysteretic envelope. With this research in mind, it is important for the designer to recognize the potential limitations of diagonal strap bracing, particularly if used in seismic areas. Specifically, it is important that the capacity of the system is controlled by the yielding of the strap while the rest of the system remains elastic. Similarly, the potential for material overstrength should be considered. Depending on the specific application the design may find the use of shear panels to be more appropriate. The 2007 edition of the AISI Standard for Cold-Formed Steel Framing - Lateral Design (S213-07) has added new special seismic requirements and commentary for diagonal strap bracing. Included in this are expected yield and tensile strength factors (R y and R t ) which should be used in the absence of verified physical properties. In his paper R-Factor Project Validation Test Plan author Jim Wilcoski suggests the following regarding R-Factors: These values are intended to represent the degree of ductility, overstrength, redundancy and energy dissipation capacity of the structural system. These factors have a tremendous impact on the design of buildings, yet there TECH NOTE L001-10 September 2010 4 Cold-Formed Steel Engineers Institute

DESIGN EXAMPLE Following is a design example for diagonal strap bracing using gusset plates to resist wind loads. The dimensions and load are shown in the drawing below. The flanges of the wall studs are considered to be braced and gravity loads are ignored. Design Data Loads: Material Properties: Wall Dimensions: Horizontal wind load at top of wall from diaphragm = 3500 lb ASTM A653 SS 33 (F y = 33 ksi; F u = 45 ksi) 8 ft. (length) by 9 ft. (height) Member Sizes: Wall Studs: 600S162-43 Track: 600T125-43 Straps: 43 mil (0.0451 design thickness) ASD Design Resolution of forces considering a tension only strap: Post load = 3938 lb Track load = 3500 lb Strap load = 5268 lb Equations and code references shown are for the AISI NAS-01. Cold-Formed Steel Engineers Institute 5 TECH NOTE L001-10 September 2010

DESIGN EXAMPLE (CONT.) Compression Post (Chord Stud) Assume flexural buckling in the plane of the wall is prevented by bridging at 1/3 points and does not control. P = 3938 lb From Table III-5 of the 2002 AISI Manual, for 600S162-43, where KL x = 9: P n = 7100 lb For Ω = 1.80 P a = 3944 lb Number of studs required = 3938/3944 = 1.0 Use two studs Check the studs for combined axial load and bending: P = 1969 lb each stud M x = 1969 6 /2 = 5907 in lb (due to straps on one side of 6 wall) Ω c P / P n = 0.50 > 0.15 Check eq. C5.2.1-1 and C5.2.1-2 (not eq. C5.2.1-3) Ω c P / P n = 0.50 (C5.2.1-1) Ω b C mx M x / M nx α x = 0.38 0.50 + 0.38 < 1.0 o.k. Ω c P / P no = 0.23 (C5.2.1-2) Ω b M x / M nx = 0.36 0.23 + 0.36 < 1.0 o.k. Two studs o.k. Flat Tension Strap For strap yielding: = A g F y (Eq. C2-1) Where: T a (req'd) = 5268 lb Ω = 1.67 = 5268 1.67 = 8798 lb Solve for w (strap width) = (w t) (F y ) 8798 = w 0.0451 33,000 ksi w = 5.91 in. Use 6 in. wide strap For fracture away from connection: = A n F u (Eq. C2-2) Where: A n = A g T a (req d) = 5268 lb Ω = 2.0 = 5268 2.0 = 10,536 lb TECH NOTE L001-10 September 2010 6 Cold-Formed Steel Engineers Institute

DESIGN EXAMPLE (CONT.) Solve for w = (w t) (F u ) 10536 = w 0.0451 45,000 ksi w = 5.91 in. Strap to Gusset plate Connection Use 6 in. wide strap Assume: For Ω = 3.0 #10 screws d = 0.190 in P ns = 735 lb P a = 245 lb Number of screws required = 5268/245 = 21.5 Use 22 #10 screws Gusset to Post Connection Number of screws required = 3938/245 = 16.1 Use 17 #10 screws Gusset to Track Connection Number of screws required = 3500/245 = 14.3 Use 15 #10 screws For guidance on the design and detailing of diagonal strap bracings with gusset plates please reference the article Detailing Help for Gusseted Flat Strap X-Braces written by John Lyons in the September 2004 LGSEA Newsletter. Once the gusset plate has been dimensioned and the screw spacing determined, fracture at the connection can be checked with section E5.3. Bottom Track For bearing strength of the bottom track: P n = m f C d t F u Where: m f = 1.0 (Table E3.3.1-2) C = 2.6 (Table E3.3.1-1) d = 0.625; t = 0.0451" 5/8 in. anchor bolts; 43 mil track Ω = 2.5 P n = 3297 lb P a = 1319 lb Number of 5/8 in anchor bolts req. = 3500/1319 = 2.65 Use 3 anchor bolts Note: The capacity of the embedded anchor bolts also needs to be checked For track yielding (assuming tensile loads): = A g F y (Eq. C2-1) Where: A g = 0.383 in 2 Ω = 1.67 = 0.383 33,000 = 12,639 lb T a = 12,639 lb > 3500 lb Track yielding is ok Cold-Formed Steel Engineers Institute 7 TECH NOTE L001-10 September 2010

DESIGN EXAMPLE (CONT.) For track fracture at anchor bolt: = A e F u (Eq. E3.2-8) Where: A e = A n U A n = 0.383 - (0.043 0.66) = 0.355 in 2 U = 1.0 Ω = 2.22 = 0.355 45,000 = 15,968 lb T a = 7188 lb Track fracture is ok Depending on anchor bolt locations relative to the gusset plate compression of the bottom track may need to be checked instead. Holdown Anchors Holdown anchors must be either designed or selected from a manufacturers catalog to resist the uplift forces at the tension post of the resisting system. For this example the holdown would need an allowable capacity of 3938 lb. The anchor bolt used with the holdown will be in addition to the anchor bolts required for shear. Also, the deflection of the holdown device and its influence on the overall rotation of the system shall be checked. References 1. International Building Code, 2006 Edition. International Code Council, Falls Church, Virginia. 2. Standard for Cold-Formed Steel Framing - General Provisions, American Iron and Steel Institute, Washington, DC, 2004. 3. Standard for Cold-Formed Steel Framing - Lateral Design, American Iron and Steel Institute, Washington, DC, 2004. 4. North American Specification for the Design of Cold-Formed Steel Structural Members (AISI-NASPEC), American Iron and Steel Institute, Washington, DC, 2001. 5. Uniform Building Code (UBC), International Council of Building Officials, Whittier, California, 1997. 6. Shear Wall Design Guide, Steel Framing Alliance, Washington, DC, 1998. 7. Wilcoski, J.,2004, R-Factor Project Validation Test Plan 8. Al-Kharat, M., Rogers, C. A., (2005) Testing of Light Gauge Steel Strap Braced Walls, Department of Civil Engineering and Applied Mechanics, McGill University, Montreal, Quebec, Canada 9. International Building Code, 2003 Edition. International Code Council, Falls Church, Virginia. 10. 2004 Supplement to the North American Specification for the Design of Cold-Formed Steel Structural Members, American Iron and Steel Institute, Washington, DC. 11. AISI Manual - Cold-Formed Steel Design. American Iron and Steel Institute, Washington, DC, 2002. 12. Lyons, John C. Detailing Help for Gusseted Flat Strap X-Braces, article in the Newsletter of the Light Gauge Steel Engineers Association (LGSEA). September, 2004. 13. North American Standard for Cold-Formed Steel Framing - Lateral Design (S213-07). American Iron and Steel Institute, Washington, DC, 2007. Primary Author of this Technical Note: Greg Greenlee, P.E., USP Structural Connectors CFSEI Technical Review Committee: Rob Madsen, P.E., Devco Engineering, Inc., chairman. This Technical Note on Cold-Formed Steel Construction is published by the Cold-Formed Steel Engineers Institute ( CFSEI ). The information provided in this publication shall not constitute any representation or warranty, express or implied, on the part of CFSEI or any individual that the information is suitable for any general or specific purpose, and should not be used without consulting with a qualified engineer, architect, or building designer. ANY INDIVIDUAL OR ENTITY MAKING USE OF THE INFORMATION PROVIDED IN THIS PUBLICATION ASSUMES ALL RISKS AND LIABILITIES ARISING OR RESULTING FROM SUCH USE. CFSEI believes that the information contained within this publication is in conformance with prevailing engineering standards of practice. However, none of the information provided in this publication is intended to represent any official position of the CFSEI or to exclude the use and implementation of any other design or construction technique. TECH NOTE L001-10 September 2010 8 Cold-Formed Steel Engineers Institute