HST2 Expansion anchor Everyday standard expansion anchor for cracked concrete

Similar documents
HUS-HR / HUS-CR Screw anchor

Hilti HIT-HY 200 A (R) mortar with HIT-V rods

Hilti HST3 Metal Expansion Anchor

Hilti HIT-RE 500 V3 mortar with HIT-V rod

Anchor HSA Fastening. Technology Manual HSA. Stud anchor. Version /

Anchor Fastening Technology Manual. HIT-HY 170 mortar with rebar (as anchor) Hilti HIT-HY 170 mortar with rebar (as anchor) Version

HST Carbon steel. HST-R Stainless steel HST-HCR High corrosion resistance steel. Fire resistance

HKD Push-in anchor, Single anchor application

HVU with HAS/HAS-E rod adhesive anchor system

English translation prepared by CSTB - Original version in French language. Throughbolt PTB-ETA7-PRO

HUS3-H 8 / 10 / 14 Carbon steel concrete screw with hexagonal head. HUS3-C 8 / 10 Carbon steel concrete screw with countersunk head

Anchor Fastening. Technology Manual HUS3. Screw Anchor HUS3-H 6/8/10/14 HUS3-C 6/8/10 HUS3-HF 8/10/14 HUS3-A 6 HUS3-I 6 HUS3-P 6 HUS3-PS 6 HUS3

(English language translation, the original version is in French language) DeWalt PB-SS-PRO 01/02/ /06/2017. Plant 1 & 2

Hilti-HY 110 available in 330ml and 500ml foil packs. Static mixer HIT M1. Rebar BSt 500 S

English translation prepared by CSTB - Original version in French language. Injection system Hilti HIT-RE 500 V3

Hilti HVU-TZ foil capsule. HAS-TZ HAS-R-TZ HAS-HCR-TZ rod. Shock

European Technical Assessment ETA-15/0288 of 17/06/2015

HRD-U 10 / - S 10 / -U 14 Frame anchor

European Technical Approval ETA-08/0058

European Technical Assessment. ETA-17/0237 of 15/05/2017. General Part. Technical Assessment Body issuing the. Instytut Techniki Budowlanej

High-performance anchoring adhesive. n Styrene-free n Low odour n Low wastage n No transportation restrictions

Injection Adhesive VM-PY

Concrete screw BSZ Steel/steel zinc flake coated

European Technical Assessment ETA-14/0454 of 11/12/2014

Hilti HDA Submission Folder


English translation prepared by CSTB - Original version in French language. MULTIEXPANSION Nylon Frame Anchor

General Information. Installation Information Design Information Material Information Ordering Information

VF22PRO Chemical Injection System STYRENE-FREE INJECTION SYSTEM - VINYLESTER

(English language translation, the original version is in French language) FM 753 A4

European Technical Approval ETA-98/0001

English translation prepared by CSTB - Original version in French language POWERS PB-PRO-S

European Technical Assessment. ETA-12/0398 of 29/12/2017. General Part. Instytut Techniki Budowlanej. Technical Assessment Body issuing the

R-RBP Rawlbolt - Bolt Projecting for use in cracked and non-cracked concrete.

System Components. Grades. General Information Installation Information

HSV Carbon steel with DIN 125 washer. HSV-BW Carbon steel with DIN 9021 washer and DIN 127b spring washer

HSV. with DIN 125 washer HSV-BW. Carbon steel. with DIN 9021 washer and DIN 127b spring washer

(English language translation, the original version is in French language) 07/05/ /05/2018. Plant 1 & 2

Anchor Fastening Technology Manual. HIT-HY 170 mortar with rebar. Hilti HIT-HY 170 mortar with rebar (as post-installed conn.

European Technical Approval ETA- 10/0273

Trutek TCM380 PRO. Trutek Fasteners Polska Al. Krakowska 55 Sekocin nowy Rasxyn Poland T:

English translation prepared by CSTB - Original version in French language

European Technical Approval ETA-11/0344

General Construction Supervisory Authority Approval

MULTI-MONTI Technical Manual

(English language translation, the original version is in French language) SPIT FIX3. Société Spit Route de Lyon F BOURG-LES-VALENCE France

Sormat ITH-Pe PRODUCT DATA SHEET. ITH-Pe - POLYESTER BASED RESIN STYRENE FREE. Polyester based injection resin, styrene free. ITH 165 Pe art.

European Technical Approval

European Technical Approval

AC200+ Acrylic Injection Adhesive Anchoring System

APPENDIX A: Strength Design Performance Values

European Technical ETA-04/0023 Assessment of 17 October 2017 General Part

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

(English language translation, the original version is in Czech language) DEWALT BSC-PBZ-PRO. DeWalt Black & Decker Str Idstein Germany

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Hilti HIT-RE 500 post-installed rebars

European Technical Assessment ETA-14/0453 of 11/12/2014

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code.

(English language translation, the original version is in French language) Société SPIT Route de Lyon - B.P BOURG-LES-VALENCE FRANCE

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

AC50 Silver Adhesive Anchoring System

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.

Hilti, Inc South 122 nd East Avenue Tulsa, OK

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

HILTI HY 150 REBAR DESIGN GUIDE

European Technical Approval

E TA TECHNICAL REPORT. Design of Metal Anchors For Use In Concrete Under Seismic Actions. TR 45 Edition February 2013

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

SEISMIC QUALIFICATION TESTING OF CONCRETE EXPANSION ANCHORS TO NUCLEAR STANDARDS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 17.

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

ETA-11/0093. hollow core slabs. fischerwerke GmbH & Co. KG. Klaus-Fischer-Straße Waldachtal DEUTSCHLAND. fischerwerke. of this assessment

CHEMICAL /4" 3/8" to 5/8" /8" 3/4" to 1-1/4" 1 10

European Technical Approval

Construction. Universal anchoring adhesive. Product Description. Tests. Product Data Sheet Edition _1. 1 Sika AnchorFix S 1/6

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

European Technical Approval ETA-07/0025

European Technical Approval

EUROPEAN TECHNICAL ASSESSMENT ETA-17/0336

(English language translation, the original version is in French language) Upat UKA 3 with anchor rod C

European Technical Assessment ETA-16/0865 of 08/11/2016

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

European Technical Approval

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

HVAC Ductwork and Strut Channels Suspended Ceilings

European Technical Assessment ETA-10/0422 of 08/01/2016

European Technical Approval

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

Dock Bumpers and Support Ledgers Racking and Railing Attachments

ETA-07/0291 of 30/06/2014. European Technical Assessment. Draft. General Part. Technical Assessment Body issuing the. Instytut Techniki Budowlanej

European Technical Assessment ETA 14/0075 of 14/04/2014

EPCON C8. Cracked Concrete - Anchor Studs 43.1 CRACKED CONCRETE - CHEMICAL INJECTION 43.1 GENERAL INFORMATION

hors Anc Eaton's B-Line series fasteners 183

Trusted ICC ES HILTI, INC. SYSTEM E ANCHOR. Conformity! Look. Evaluation. ICC-ES Evaluation

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

(English language translation, the original version is in French language) AT-HP Stainless Steel

High Strength Epoxy tested in accordance to ICC-ES AC308

Transcription:

HST2 Expansion anchor Everyday standard expansion anchor for cracked Anchor version HST2 HST2-R (M8-M16) Benefits - Optimized expansion cone and wedge design combined with special steel and coatings. - Suitable for non-cracked and cracked - Product and length identification mark facilitates quality control and inspection HST2-BW HST2-R-BW (M8-M16) Base material Load conditions Concrete (non-cracked) Concrete (cracked) Static/ quasi-static Fire resistance Installation conditions Other information Hammer drilled holes Diamond drilled holes Hollow drillbit drilling European Technical Assessment CE conformity PROFIS Anchor design Software FM approved Approvals / certificates Description Authority / Laboratory No. / date of issue European technical assessment a) DIBt, Berlin ETA-15/0435 / 2017-08-07 Fire test report DIBt, Berlin ETA-15/0435 / 2017-08-07 a) All data given in this section according to ETA-15/0435, issue 2017-08-07. 1 Nov-17

Static and quasi-static loading (for a single anchor) All data in this section applies to: - Correct setting (See setting instruction) - No edge distance and spacing influence - Steel failure - Minimum base material thickness - Concrete C 20/25, fck,cube = 25 N/mm² Effective anchorage depth for static Eff. Anchorage depth hef [mm] 47 60 70 82 Mean ultimate resistance Non-cracked NRu,m VRu,m 11,9 21,2 26,6 46,5 HST2-R/HST2-R-BW 11,9 21,2 26,6 46,5 12,0 22,7 33,0 58,1 HST2-R/HST2-R-BW 16,5 26,6 38,5 66,8 Cracked NRu,m VRu,m 6,6 11,9 15,9 26,6 HST2-R/HST2-R-BW 6,6 11,9 15,9 33,2 12,0 22,7 33,0 58,1 HST2-R/HST2-R-BW 16,5 26,6 38,5 66,8 Characteristic resistance Non-cracked NRk VRk 9,0 16,0 20,0 35,0 HST2-R/HST2-R-BW 9,0 16,0 20,0 35,0 11,4 21,6 31,4 55,3 HST2-R/HST2-R-BW 15,7 25,3 36,7 63,6 Cracked NRk VRk 5,0 9,0 12,0 20,0 HST2-R/HST2-R-BW 5,0 9,0 12,0 25,0 11,4 21,6 31,4 55,3 HST2-R/HST2-R-BW 15,7 25,3 36,7 63,6 Nov-17 2

Design resistance Non-cracked NRd VRd 6,0 10,7 13,3 23,3 HST2-R/HST2-R-BW 6,0 10,7 13,3 23,3 9,1 17,3 25,1 44,2 HST2-R/HST2-R-BW 12,6 20,2 29,4 50,9 Cracked NRd VRd 3,3 6,0 8,0 13,3 HST2-R/HST2-R-BW 3,3 6,0 8,0 16,7 9,1 17,3 25,1 44,2 HST2-R/HST2-R-BW 12,6 20,2 29,4 44,6 Recommended loads a) Non-cracked Nrec Vrec 4,3 7,6 9,5 16,7 HST2-R/HST2-R-BW 4,3 7,6 9,5 16,7 6,5 12,3 17,9 31,6 HST2-R/HST2-R-BW 9,0 14,5 21,0 35,7 Cracked Nrec Vrec 2,4 4,3 5,7 9,5 HST2-R/HST2-R-BW 2,4 4,3 5,7 11,9 6,5 12,3 17,9 31,6 HST2-R/HST2-R-BW 9,0 14,5 21,0 31,8 a) With overall partial safety factor for action = 1,4, The partial safety factors for action depend on the type of loading and shall be taken from national regulations, Fire resistance All data in this section applies to: - Correct setting (See setting instruction) - No edge distance and spacing influence - Steel failure - Minimum base material thickness - Concrete C 20/25, fck,cube = 25 N/mm² - Hilti technical data for strength class C55/67 to C80/95: for a structural element that fullfills the requirements according to DIN EN 1992-1-2 the fire resistance of C20/25 could be assumed. - partial safety factor for resistance under fire exposure M,fi=1,0 (in absence of other national regulations) Effective anchorage depth for static Eff. Anchorage depth hef [mm] 47 60 70 82 3 Nov-17

Characteristic resistance Fire Exposure R30 NRk,fi VRk,fi 0,9 2,3 3,0 5,0 HST2-R/HST2-R-BW 0,9 2,3 3,0 5,0 0,9 2,5 5,0 9,0 HST2-R/HST2-R-BW 0,9 2,5 5,0 9,0 Fire Exposure R120 NRk,fi VRk,fi 0,5 0,7 1,0 2,0 HST2-R/HST2-R-BW 0,5 0,7 1,0 2,0 0,5 0,7 1,0 2,0 HST2-R/HST2-R-BW 0,5 0,7 1,0 2,0 Design resistance Fire Exposure R30 NRd,fi VRd,fi 0,9 2,3 3,0 5,0 HST2-R/HST2-R-BW 0,9 2,3 3,0 5,0 0,9 2,5 5,0 9,0 HST2-R/HST2-R-BW 0,9 2,5 5,0 9,0 Fire Exposure R120 NRd,fi VRd,fi 0,5 0,7 1,0 2,0 HST2-R/HST2-R-BW 0,5 0,7 1,0 2,0 0,5 0,7 1,0 2,0 HST2-R/HST2-R-BW 0,5 0,7 1,0 2,0 Materials Mechanical properties Nominal tensile strength fuk,thread Yield strength fyk,thread 660 730 710 720 [N/mm²] HST2-R/HST2-R-BW 720 710 710 650 528 584 568 576 [N/mm²] HST2-R/HST2-R-BW 576 568 568 520 Stressed cross-section As [mm²] 36,6 58,0 84,3 157 Moment of resistance W [mm³] 31,2 62,3 109 277 Char, bending resistance M 0 Rk,s 25 55 93 240 [Nm] HST2-R/HST2-R-BW 27 53 93 216 Nov-17 4

Material quality Part Bolt HST2-R/HST2-R-BW Material Carbon steel, galvanized Stainless steel Anchor dimensions Minimum thickness of fixture tfix,min [mm] 2 2 2 2 Maximum thickness of fixture tfix,max [mm] 195 200 200 235 Shaft diameter at the cone dr [mm] 5,5 7,2 8,5 11,6 Maximum length of anchor l1,max [mm] 75 90 105 140 Minimum length of anchor l1,min [mm] 260 280 295 350 Length of expansion sleeve l2 [mm] 14,8 18,2 22,7 24,3 Setting information Setting details Nominal diameter of drill bit do [mm] 8 10 12 16 Cutting diameter of drill bit dcut [mm] 8,45 10,45 12,50 16,50 Drill hole depth 1) h1,1 [mm] 60 74 88 103 h1,2 [mm] 65 75 90 105 Diameter of clearance hole in the fixture df [mm] 9 12 14 18 Torque moment Tinst [Nm] 20 45 60 110 Width across SW [mm] 13 17 19 24 1) h1,1 valid for hammer drilled holes and h1,2 valid for diamond drilled holes. 5 Nov-17

Installation equipment Rotary hammer TE2 TE16 Diamond coring tool DD 30W, DD EC1 Hollow drill bit - - TE CD, TE YD Other tools hammer, torque wrench, blow ut pump Setting parameters Anchor Size M8 M10 M12 M16 Effective anchorage depth hef [mm] 47 60 70 82 Minimum base material thickness hmin [mm] 100 800 120 100 140 120 160 140 Minimum smin [mm] 60 60 55 55 60 60 70 80 spacing in for c [mm] 50 75 80 115 85 100 110 140 noncracked smin [mm] 60 60 55 55 60 60 70 80 for c [mm] 60 75 70 115 80 100 110 140 Minimum spacing in cracked smin [mm] 40 50 55 55 60 60 70 80 for c [mm] 50 60 70 110 75 100 100 140 smin [mm] 40 50 55 55 60 60 70 80 for c [mm] 50 60 65 110 75 100 100 140 Minimum cmin [mm] 50 70 55 70 55 70 85 80 edge for s [mm] 60 80 115 110 145 130 160 180 distance in cmin [mm] 60 70 50 70 55 70 70 80 non-cracked for c [mm] 60 80 115 110 145 130 160 180 Minimum cmin [mm] 45 55 55 70 55 70 70 80 edge for s [mm] 50 60 90 100 120 130 150 180 distance in cmin [mm] 45 55 50 70 55 70 60 80 cracked for c [mm] 50 60 90 100 110 130 160 180 Critical spacing for splitting failure and scr,sp [mm] cone failure scr,n [mm] 141 180 210 246 Critical spacing for splitting failure and ccr,sp [mm] cone failure ccr,n [mm] 71 90 105 123 For spacing (edge distance) smaller than critical spacing (critical edge distance) the design loads have to be reduced. Nov-17 6

Setting instructions *For detailed information on installation see instruction for use given with the package of the product Setting instruction Hammer drilling 1. Drill the hole 2. Clean the hole 3. Insert the anchor 4. Use a setting tool HS-SC 5. Checking 6. Attach the belonging washer Hollow Drill Bit, no cleaning required 1. Drill the hole with the Hollow drill bit 2. Insert the anchor 3. Use a setting tool HS-SC 4. Checking 5. Attach the belonging washer 7 Nov-17

Diamond coring 1. Core the hole 2. Flushing 3. Clean the hole 4. Insert the anchor 5. Use a setting tool HS-SC 6. Checking 7. Attach the belonging washer Nov-17 8