COMPILED BY APPROVED BY FUNCTIONAL RESP AUTHORISED BY V SINGH. Date: 16/03/2009. Date: 16/03/2009. Date: 19/03/2009 Date: 26/03/2009

Similar documents
BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

C&G 2382 BS7671: th Edition IEE Wiring Regulations. 25 Questions

ELECTRICAL SAFETY INSPECTION REPORT

(Condensed from National Electric Code)

CHAPTER 5 METERING REQUIREMENTS

2015 Code Rollout Meeting Q & A

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

UNDERGROUND SERVICES SECONDARY

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

Installation, Inspection and Maintenance of Dry Type Transformers

úê üßµö ÖãÆü ü ¾Ö³ÖÖÖ - III

MANUFACTURER'S RESPONSIBILITIES AND REQUIREMENTS FOR FACTORY TESTS

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O.

SOMFY SPECIFICATION March 2012 SECTION... ROLLER WINDOW SHADES SOMFY LS 40 MOTOR RANGE. Disclaimer for advice given to architects and engineers

SECTION GROUNDING AND BONDING

ELECTRICAL BULLETIN

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT

Installation Guide EcoFoot5D High Density 5-Degree Ballasted Racking System Document No. ES10560

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Technical Specification for LV ABC Fuse Switch Disconnectors

SPECIFICATION SHEET JUNCTION BOXES

Temporary Wiring Practices And Guidelines For NECA. National Electrical Contractors Association Omaha, Nebraska

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

COMPLEMENT. Switches for Electrical Fixed Installations for household and similar purposes

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS

An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application

ELECTRICAL BULLETIN

Glass Reinforced Polyester Enclosures BPG. Glass Reinforced Polyester Enclosures

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

ELECTRICAL SAFETY FOLLOW UP INSPECTION REPORT (4th)

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

Article 10 - ADMINISTRATIVE SECTION

UPS Electrical Design and. Installation. critica POWER SUPPLIES

Change-over and monitoring unit For medical locations acc. to DIN VDE 0100 Part 710

Hazards. Hazards. Hazards. Effects on the Body. GA Tech Electrical Safety Presentation

RC9 Poke-Thru Series INSTALLATION INSTRUCTIONS Installation Instruction No.: R3 Updated April 2005

ELECTRIC METERING GENERAL

Certificate of Compliance

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

Ensto Industrial Solutions. Enclosing solutions. for the solar energy industry

INSTALLATION INSTRUCTIONS FOR ELECTRICAL CONTRACTORS

Section 2: Underground

-SQA- SCOTTISH QUALIFICATIONS AUTHORITY. Hanover House 24 Douglas Street GLASGOW G2 7NQ NATIONAL CERTIFICATE MODULE DESCRIPTOR

HotSwap MBP Maintenance Bypass

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.

ComEd Customer Requirements for Proper Installation of Metering Equipment Residential and Commercial Customers

Basic Service. This Section provides information regarding a. Introduction

Mar11 Rev D

The University of Texas at Austin September 30, 2011

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

Flush mounting boxes. For masonry - TECHNICAL CHARACTERISTICS

Code of practice for protective earthing of electrical installations

WIRING RULES AND REGULATIONS OF TOMBIGBEE ELECTRIC POWER ASSOCIATION

ROOFTOP PV GUIDELINES FOR SAFE AND LEGAL INSTALLATIONS IN CAPE TOWN

PV Mounting System 2703 SERIES 200 UL GROUND MOUNT SYSTEM. SnapNrack Residential PV Mounting Systems Code Compliant Installation Manual

Low-profile, 11U high cabinets hold networking equipment, servers, and phone equipment.

Data Bus Connector and Terminator Requirements Document DB-1001-A. Revision C

RN Optical Termination Panel (RN OTP)

Guidance for installers when making connections in consumer units. electricalsafetyfirst.org.uk beama.org.uk

Basic Requirements for Residential Electrical Installations

Lightning Protection System for PC Buildings

GUIDELINES FOR SUB-SYSTEM COMPLETION CERTIFICATES AND TEST RECORDS FOR ELECTRICAL INSTALLATIONS IN POTENTIALLY EXPLOSIVE ATMOSPHERES

Feb12 Rev D

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

HILTI CP 657 Firestop Brick

Fixings, bonds and clamps

CHAPTER 11 CONDUITS AND FITTINGS

B. Accept materials on site in original factory packaging, labeled with manufacturer s identification.

1.1 All testing apparatus shall be periodically checked and calibrated. Records of such checks/calibration shall be maintained.

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

Certificate of Acceptance

HILTI CP 674 Cavity Closure For Rainscreen / Cladding Systems

MAR 17 Rev B1

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

4CS12 4CS-1/2 4X1-7/8D Handybox. Features. Dimensions and Weight. Long Description. Catalog Number

Solar PV System Code Compliance Best Practices, 2017 NEC Updates, and Opportunities for Improvement

WIRING METHODS CHAPTER 38

Revision 1 RAM ELEVATORS. Elevator Electrical Planning Guide. RAM Manufacturing Ltd

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.

Model BF 720 Incubators Avantgarde.Line with forced convection

MICRO-INVERTER PIGRID W MICRO GRID TIED INVERTER 208, 220, 230, 240VAC

Mar11 Rev C

ELECTRICAL SAFETY INSPECTION REPORT

NEUTRAL GROUNDING TRANSFORMERS INSTALLATION AND MAINTENANCE INSTRUCTIONS

Technical System Catalogue Modular PDU (PSM)

Thank you for purchasing the SC-CONVERSION System 500/600 Conversion Kit. This Kit is available in two different versions:

2-finger angular gripper SGB 32-50

International Standard Corresponding Indian Standard Degree of Equivalence

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained.

INSTALLATION AND OPERATING INSTRUCTIONS

ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200

ENERGY-DISTRIBUTION. TwinLine N 44 The new system of floor-standing cabinets in IP44

Thermocouples. Operating and Maintenance Manual English. Thermocouples

FLUE KIT INSTALLATION MANUAL

Diffused Aeration Piping Equipment

Shur-Shot X-Proof Hydrogen Fluoride Alarm Operations Manual

Transcription:

SPECIFICATION Document Classification: Controlled Disclosure Title: Distribution Specification: Part 8 Unique Identifier: 34-434 COMMON BASE AND STANDARD Document Type: PASSIVE UNITS FOR SINGLE- PHASE 230 V SERVICE Effective date: MARCH 2009 Total pages: 16 Revision date: MARCH 2014 COMPILED BY APPROVED BY FUNCTIONAL RESP AUTHORISED BY SIGNED _ SIGNED _ AJ MAUDU Senior Engineer B MCLAREN LV/MV Study Committee Chairman V SINGH for TESCOD MN BAILEY CMDT for MD (Dx) Date: 16/03/2009. Date: 16/03/2009. Date: 19/03/2009 Date: 26/03/2009 Content Introduction...4 1 Scope...4 2 Normative references...4 3 Definitions and abbreviations...5 3.1 Definitions...5 3.2 Abbreviations...5 4 Requirements...5 4.1 General...5 4.2 Standard configurations...6 4.3 Common base...8 5 4.4 Wall outlet box (where required)...10 Tests...11 5.1 General...11 5.2 Dimensions...11 5.3 Heating test...11 5.4 Short time overcurrent...12 5.5 Dielectric strength...12 5.6 Visual inspection...12 Annex A - List of drawings...13 Annex B - Impact assessment...14 Technical schedules A and B...1 Page JF Scholtz Mar 2009 Rev 1

Page: 2 of 16 Revision history DATE REV CLAUSE DESCRIPTION June 1996 0 First issue Oct. 1996 Jan. 1998 1 2 Changes: Connectors rated to carry 80A Clause 4.2.8 of SABS IEC 1036 added as a requirement tab thickness of base changed to 3mm thick. 2 additional mounting feet required for 4x4 wall box. Schedules A and B and Deviation Schedule added Compiled By: A Abrosie Aug. 1998 3 Label explaining the use of the ECU coding Tab included Compiled By: A Abrosie Nov. 2002 4 Conduit length increased to 500mm and flexible type stipulated Compiled By: T Gillard Title changed to Common bases and standard passive units for 230V service connections 2 References to standards updated. Compulsory standards added. Reference to SABS 1524 removed (a direct reference is now made to the relevant IEC spec referenced in SABS 1524, IEC 61036). SANS 60669-1 replaced SABS 163. SANS 1085-1 replaced by SANS 1085. D-DT-3171 sheets A-F relocated to D-DT-1017 2 Definitions and abbreviations extended. Term ED socket dropped. Terms Common base and Standard Passive Unit (SPU) adopted. 4.1 General requirements modified to list three types of standard configurations: Common base only, SPU with rails and SPU without rails these are the standard configurations used in the field. 4.2 Standard configurations added to describe the three standard configurations in detail. 4.3.1 Clarification added that the test only applies to the common base case (650 C). 4.3.1 (e) Test 5.1.7 from SANS 1619 applied to the wall outlet box only, so it was moved to the section on wall outlet boxes. 4.3.6 Sentence on tests from SANS 62052-11 moved to separate clause 4.3.7 and more detail given. Following clauses renumbered. 4.3.10 Removed. Only the SPU with rails is pre-wired and that is covered in the relevant section. Following point renumbered. 4.3.10 Labelling of line and load terminals corrected. 4.3.12 Common base now supplied with two M20 holes drilled into the base for new SPU installations (this speeds up installation). The drilling centres remain for the common base only configuration. This is because it is used for maintenance of existing installations where pre-drilled holes may be in the wrong place for the existing cable to fit. This means that additional holes have to be drilled and that the pre-drilled holes present a safety hazard because they provide access to the interior of the base. 4.3.16 Warning sticker text updated in accordance with 01TI-03. 4.4.1 The dimensions of the wall outlet box are now only given by D-DT- 1017 sheet 6. Previously SANS 1085-1 had dimensions for surface

Page: 3 of 16 DATE REV CLAUSE DESCRIPTION mounting boxes but they were dropped. The old D-DT-3171, which is the source of the new D-DT-1017 contradicted the old SANS 1085-1 overall dimensions anyway. The wall outlet box must now be constructed as a single piece. 4.4.2 A new 4.4.2 has been added to cover the spacing of the mounting lugs for the mounting of the double switched socket outlet assembly in the wall outlet box. 4.4.3 A new 4.4.3 has been added to cover the requirement that the double switched socket outlet assembly and cover plate be interchangeable with their off the shelf equivalents. 4.4.4 Compulsory standard and SABS mark requirement added. SABS 163 replaced by SANS 60669-1. Old 4.4.4 removed (conduit is no longer used and the length of cable between the common base and wall outlet box is specified in the relevant section). 4.4.8 Added. This clause references the plug extraction test from SANS 1619. It was moved from the common base section. 5.5 Dielectric test from SANS 62052-11 now replaces the old test from SABS 1524. The new SABS 1524 references the test in SANS 62052-11. Annex A Drawing list updated Annex B Technical schedules reworked completely. Dec 2006 0 Compiled By: J Maudu 2 Normative references revised. Sentences on tests from SANS 62052-11 updated in 4.3.7. SABS changed to SANS. Document re-formatted, new number issued, changed from SCSSCAAJ1 to 34-434. FEB 2009 0A Compiled By: J Maudu Clause 4.2.2: An abridged COC (installation certificate) shall be supplied in triplicate. The COC numbering shall comply with technical instruction 01TI-03 which will be updated when necessary. The COC number to be carbon printed on the abridged COC issued with the standard passive units and printed on the passive base itself in accordance with 01TI-03. The warning sticker affixed to the passive base shall be yellow with black text on it and shall comply with technical instruction 01TI-03. A warning flash (a black triangle with a black lightning flash symbol in it, on a yellow background) shall also be printed on the sticker Clause 4.2.3: The warning sticker affixed to the passive base shall be yellow with black text on it and shall comply with technical instruction 01TI-03. A warning flash (a black triangle with a black lightning flash symbol in it, on a yellow background) shall also be printed on the sticker. MAR 2009 1 Document published

Page: 4 of 16 Authorisation This document has been seen and accepted by: Name MN Bailey V Singh B McLaren Designation Corporate Manager Divisional Technology Power Plant Technologies Manager LV/MV Study Committee Chairman This standard shall apply throughout Eskom Distribution Division Development team J Maudu - IARC Introduction This section of the Distribution Standard has been prepared to establish and promote the use of standardized designs, structures and materials for LV public lighting services. Keywords Common base, passive unit, single-phase, service connections Bibliography Not Applicable 1 Scope This specification sets out Eskom s requirements for common bases and standard passive units for singlephase 230 V service connections. 2 Normative references Parties using this document shall apply the most recent edition of the documents listed below (list the references below): The following standards contain provisions that, through reference in the text, constitute requirements of this specification At the time of publication the revisions indicated were valid. All standards are subject to review and parties to agreements based on this specification are encouraged to investigate the possibility of applying the most recent revisions of the standards listed below. Information on currently valid national and international standards may be obtained from the Information Centre at Megawatt Park and Technology Standardization Department. SANS 60529: 2001, Degrees of protection provided by enclosures (IP Code). ANSI/UL 94:1991, UL standard for safety tests for flammability of plastic materials for parts in devices and appliances. SANS 62052-11: Alternating-current static watt-hour meters for active energy (classes 1 and 2). VC 8003:1998, Manually operated switches for fixed installations SANS 60669-1: 1998, Switches for household and similar fixed electrical installations

Page: 5 of 16 VC 8008: 1998, Plugs, socket-outlets and socket-outlet adaptors SANS 164-1:2006, Plugs and socket-outlets for household and similar purposes. Part 1: Conventional system (6 A and 16 A, 250 V). SANS 10142: 2001, Code of practice: The wiring of premises. Part 1: Low voltage installations SANS 1085:2004, Wall outlet boxes for the enclosure of electrical accessories. SANS 1619:2006, Small power distribution units (readyboards) for single-phase 230 V service connections. SANS 1507-1, Electric cables with extruded solid dielectric insulation for fixed installations (300/500 V to 1 900/3 300 V) Part 1: General DISSCAAC7, Specification for concentric cable. 34-312,, Specification for indoor arresters for the protection of electricity dispensers Eskom drawing D-DT-1017, Sheets 1, 2, 3, 4, 5, 6 and 7, Common base and standard passive unit. 3 Definitions and abbreviations 3.1 Definitions Common base A base with jaws to accommodate the terminals of a plug-in ED or ECU. The base also has terminals for the connection of the supply and load conductors. Electricity control unit (ECU): A single-phase prepayment meter with a maximum current rating of 20 A and integrated overcurrent and earth fault protection functionality. This meter is designed to be connected to the supply and the load by plugging it in to a common base. Electricity dispenser (ED): A single phase prepayment meter with a maximum current rating of 60 A. This meter is designed to be connected to the supply and the load by plugging it in to a common base. Standard passive unit (SPU): An assembly consisting of a common base and a wall outlet box with two socket outlets. The common base and wall outlet box can be mounted on rails as an option. 3.2 Abbreviations COC: Certificate of compliance 4 Requirements 4.1 General Common bases for prepayment meters shall be supplied in one of three standard configurations, as stipulated by the purchaser in schedule A. The three standard configurations are: a) Common base only (D-DT-1017 sheet 1). This configuration is used for accommodating an ED or ECU and consists of a common base only. This configuration shall be used for new installations where an ED is to be installed or for existing installations where either an ED or ECU has been installed. This configuration is used for maintenance where an ECU is installed (as part of a SPU) because the wall outlet box and the cable between the common base and the wall outlet box become the customer s property after the installation is commissioned. This means that Eskom will only maintain the common base itself, not the wall outlet box. The common base shall be supplied without any holes drilled in it in this configuration, in order to ensure that the box can be used for maintenance in installations where the cables do not enter the common base from the bottom, which is the current norm.

Page: 6 of 16 b) SPU with rails (D-DT-1017 sheet 8). This configuration is used for accommodating an ECU and caters for mounting the common base and wall outlet box together side by side inside an installation on rails. This configuration is only used for new installations because if either a customer s wall outlet box or cable that connects the wall outlet box to the common base fail he is responsible for replacing it as mentioned in (a) above. The common base shall be supplied with the mounting holes and cable entry holes drilled when it is supplied in this configuration. This is to save time on site when this item is installed in new installations, since it is a high usage item. c) SPU without rails (D-DT-1017 sheet 7). This configuration is used for accommodating an ECU and caters for mounting the common base in a meter box outside the installation and the wall outlet box inside the installation. This configuration is only used for new installations because if either a customer s wall outlet box or cable that connects the wall outlet box to the common base fail he is responsible for replacing it as mentioned in (a) above. The common base shall be supplied with the mounting holes and cable entry holes drilled when it is supplied in this configuration. This is to save time on site when this item is installed in new installations since it is a high usage item. More detailed requirements for the three standard configurations are given in clause 4.2 below. 4.2 Standard configurations 4.2.1 Common base only a) The common base shall comply with clause 4.3 and D-DT-1017 sheet 1. b) No mounting holes or cable entry holes shall be drilled into the common base by the manufacturer. Drilling centres shall however be provided as indicated on D-DT-1017 sheet 1. 4.2.2 SPU with rails a) The common base shall comply with clause 4.3 and D-DT-1017 sheet 2. b) The wall outlet box shall comply with clause 4.4 and D-DT-1017 sheet 6. c) The SPU shall be assembled in accordance with D-DT-1017 sheet 8. d) The common base shall be supplied with mounting holes drilled in three of the four mounting bosses, as shown on D-DT-1017 sheet 8. e) The common base shall be supplied with M20 holes drilled in the base for cable entry, as shown on D-DT-1017 sheet 8. f) An abridged COC (installation certificate) shall be supplied in triplicate. The COC numbering shall comply with technical instruction 01TI-03 which will be updated when necessary. g) The COC number to be carbon printed on the abridged COC issued with the standard passive units and printed on the passive base itself in accordance with 01TI-03. h) The warning sticker affixed to the passive base shall be yellow with black text on it and shall comply with technical instruction 01TI-03. A warning flash (a black triangle with a black lightning flash symbol in it, on a yellow background) shall also be printed on the sticker.

Page: 7 of 16 i) The cable used to connect the wall outlet box to the common base shall comply with SANS 1507. The type of cable used shall be 600/ 1000 V, 2.5mm 2, copper, two core and earth cable. SANS 1507 refers to these cables as Circular sheathed multicore cables with bare earth continuity conductors with aluminium/ PVC or aluminium/ PE laminate. j) The cable used to connect the wall outlet box to the common base shall be just long enough to make the connection. k) The cable used to connect the wall outlet box to the common base shall be UV stable. l) No. 1 compression glands shall be used to terminate the cable between the wall outlet box and the common base on both ends. These compression glands shall be removable with a tool without damaging the gland, the cable, the common base or the wall outlet box. Glands shall not be glued on to the common base or wall outlet box. m) The SPU shall be supplied with the cable used to connect the wall outlet box to the common base terminated securely into the fully wired wall outlet box on one end and to the common base on the other end. The compression glands shall be tightened to the torque to be used in service. It shall be possible to install and commission the SPU without making any further connections. n) The rails used to mount the common base and the wall outlet box shall be spaced 153mm apart, the same distance as the mounting holes for the wall outlet box. 4.2.3 SPU without rails a) The common base shall comply with clause 4.3 and D-DT-1017 sheet 2. b) The wall outlet box shall comply with clause 4.4 and D-DT-1017 sheet 6. c) The SPU shall be assembled in accordance with D-DT-1017 sheet 7. d) The common base shall be supplied with mounting holes drilled in three of the four mounting bosses, as shown on D-DT-1017 sheet 7. e) The common base shall be supplied with M20 holes drilled in the base for cable entry, as shown on D-DT-1017 sheet 7. f) No abridged COC is to be supplied. An accredited person shall issue a full COC on site. g) The warning sticker affixed to the passive base shall be yellow with black text on it and shall comply with technical instruction 01TI-03. A warning flash (a black triangle with a black lightning flash symbol in it, on a yellow background) shall also be printed on the sticker. h) The cable used to connect the wall outlet box to the common base shall comply with SANS 1507. The type of cable used shall be 600/ 1000 V, 2.5mm 2, copper, two-core and earth cable. SANS 1507 refers to these cables as Circular sheathed multicore cables with bare earth continuity conductors with aluminium/ PVC or aluminium/ PE laminate. i) The cable used to connect the wall outlet box to the common base shall be 1000mm long. j) The cable used to connect the wall outlet box to the common base shall be UV stable. k) No. 1 compression glands shall be used to terminate the cable between the wall outlet box and the common base on both ends. These compression glands shall be removable with a tool without damaging the gland, the cable, the common base or the wall outlet box. Glands shall not be glued on to the common base or wall outlet box.

Page: 8 of 16 l) The SPU shall be supplied with the cable used to connect the wall outlet box to the common base terminated securely into the fully wired wall outlet box. The compression gland on the wall outlet box end shall be tightened to the torque to be used in service. The common base end of the cable shall be prepared for termination so that it can be connected to the load side field wiring terminals in the common base without further preparation. It shall not however be connected on to the load terminals in the common base. The compression gland on the common base shall be supplied fitted on to the common base (hand tight). It is not necessary to terminate the common base side of the cable between the common base and the wall outlet box because the cable would then have to be disconnected at this point in order to install the wall outlet box inside an installation and the common base outside the installation. 4.3 Common base 4.3.1 All common bases shall comply with the following requirements of SANS 1619: a) Clause 4.1 Construction Paragraph 4.1.1.7 Paragraph 4.1.1.9 b) Clause 4.2 Fire resistance (The entire clause) This test is carried out on the case of the common base (a 650 C test). c) Clause 4.3 Resistance to impact (The entire clause) d) Clause 4.4 Resistance to solvents (The entire clause) e) Clause 5 Tests Paragraph 5.1.2 Paragraph 5.1.3 Paragraph 5.1.4 NOTE: Compliance is indicated if there is no damage to the common base. f) Clause 6 Marking/labelling Paragraph 6.1 a), b) and c) Paragraph 6.2 Paragraph 6.3 4.3.2 The common base shall be manufactured in accordance with drawing D-DT-1017 sheet 1 or 2, depending on the configuration specified. 4.3.3 The common base mounting bosses shall be of the size and in the positions shown in D-DT-1017 sheet 1 and 2. The mounting holes in the mounting bosses shall only be drilled if called for by the configuration specified. 4.3.4 The common base dimensions shall be tested in accordance with 5.2.

Page: 9 of 16 4.3.5 A surge arrester complying with the requirements of 34-312, shall be mounted in the common base. It shall be connected between the LINE LIVE and NEUTRAL terminals. The arrester shall be mounted in one of the volumes reserved for this purpose as shown in D-DT-1017 sheet 3. 4.3.6 The four connectors shall be rated to carry 80 A continuously. The test of 5.3 shall be performed to verify the reliability of the contacts. 4.3.7 Paragraphs 5.4, 5.6 and 5.8 of SANS 62052-11 shall apply to the terminal blocks in the common base. In clause 5.6 of SANS 62052-11 the outdoor meter clearances and creepage distances from table 3a shall apply. The voltage category shall be taken as 600V. In clause 5.8 the 960 C test shall be performed on the terminal block. 4.3.8 The incoming supply cable will be concentric service cable complying with SCSSCAAC7. The cable sizes used may vary from 4 mm2 to 16 mm2 (phase conductor area). It shall be possible to terminate these cables using caged clamps. Innovative methods of terminating concentric cable will be considered. 4.3.9 The common base shall have an earth terminal, connected to the NEUTRAL LINE terminal, and shall allow a separate earth conductor connection at the EARTH LOAD side. This termination shall be a caged clamp. 4.3.10 In addition to the markings required by SANS 1619, the following shall be clearly and indelibly marked: LINE LIVE, LOAD LIVE, LINE NEUTRAL:, LOAD NEUTRAL and LOAD EARTH or similar. 4.3.11 The common base shall be designed for a 25 year life. 4.3.12 The common base shall be supplied with two M20 cable entry holes drilled in the base if required by the configuration specified. 4.3.13 The common base shall comply with ANSI/UL 94, classification V1. 4.3.14 The common base shall be UV-stabilized. 4.3.15 It shall not be possible to access any current carrying points using the standard test finger described in IEC 60529. 4.3.16 A label indicating the use of the coding tab shall be included in the common base with the layout and wording as shown below. The sticker shall be yellow with black text on it. A warning flash (a black triangle with a black lightning flash symbol in it, on a yellow background) shall also be printed on the sticker. WARNING Do NOT install ED if no Earth Leakage present. -Cut tab for ED -Do not cut tab for ECU 4.3.17 The short time overcurrent test described in clause 5.4 shall be carried out. 4.3.18 The dielectric test described in clause 7.4 of SANS 62052-11 shall be carried out.

Page: 10 of 16 4.4 Wall outlet box (where required) 4.4.1 The wall box shall comply with all the requirements of SANS 1085. The wall box shall be a surface-mounting box in accordance with SANS 1085. The wall box is intended for indoor use only. The internal depth of the wall box shall be 36 mm. The dimensions of the wall outlet box shall be in accordance with D-DT-1017 sheet 6. The base, sides and mounting lugs of the wall outlet box shall be constructed as a single piece. A top plate to ensure that the cover plate fits onto the wall outlet box properly, without any gaps, may be provided as a separate piece if required. 4.4.2 The wall box shall have lugs on which an assembly consisting of the two socket outlets and two switches shall be mounted. The mounting centres for the assembly shall be in accordance with the mounting centres for a 105.5 x 105.5 mm flush mounting wall outlet box as specified in SANS 1085 (as shown on D-DT-1017 sheet 6). The width of the lugs shall comply with SANS 1085 (10 mm). The holes in the lugs shall be suitable for a 4mm diameter fixing screw. 4.4.3 The wall outlet box shall be constructed so that it is only necessary to attach a double switched socket assembly to the mounting lugs and then attach a matching cover plate from the same manufacturer to the assembly to complete the unit. Replacement parts for the assembly and cover plate used shall be available off the shelf. There shall be no gaps between the wall outlet box and the cover plate when it is fitted. The cover plate may vary in width between 123mm and 125mm and in length between 123mm and 125mm. The construction of the wall outlet box shall be such that any assembly and cover plate designed for a 105.5 x 105.5 mm flush mounting wall outlet box in accordance with SANS 1085 could be used to replace the one originally installed. If the assembly purchased has a different manufacturer to the original it will be necessary to purchase a matching cover plate for it. 4.4.4 The wall box, shall have 4 mm diameter mounting holes on its base, as shown on D-DT-1017 sheet 6 and shall be mounted on a box plate or on mounting feet such that: a) The wall box is removeably secured to the base plate or mounting feet using the 4mm mounting holes; b) The centre of the cable entry of the wall box is 25 mm above the bottom of the base plate or mounting feet as shown in D-DT-1017, sheet 6. This is to ensure that the cable entry of the wall box is at the same distance from the wall surface as the common base cable entry; and c) The base plate or mounting feet shall have 10 mm diameter mounting holes in the configuration shown in D-DT-1017, sheet 6. 4.4.5 The wall outlet box shall be supplied with a double switched socket-outlet assembly and cover plate fitted. The 16A socket-outlets shall comply with VC 8008 and SANS 164-1 and shall bear the SABS mark. The switches shall comply with VC 8003 and SANS 60669-1 and shall bear the SABS mark. 4.4.6 The wall box shall be designed for a 25 year life. 4.4.7 The wall box components shall comply with the requirements of SANS 10142. A SANS 10142 authorisation committee certificate shall be provided. 4.4.8 The test outlined in paragraph 5.1.7 of SANS 1619 shall be carried out on the wall outlet box. Compliance is indicated if there is no damage to the wall outlet box.

Page: 11 of 16 5 Tests 5.1 General All tests in clause 4.2 shall be performed on the common base. All tests required by SANS 1085 and by clause 4.3 shall be performed on the wall outlet box. 5.2 Dimensions Insert a test insert, (see D-DT-1017, sheet 5) into the common base. With the insert fitted in to the common base, test the common base interior for compliance with classification IP51, in accordance with IEC 60529. 5.3 Heating test This test is taken from ANSI/UL 414, clause 15. 5.3.1 Insert a test insert in accordance with D-DT-1017, sheet 5, into the common base. Current carrying load circuit parts shall be capable of carrying specified test currents without any part attaining a temperature rise greater than specified in 5.3.3 at any constant ambient temperature in the range of 25 C ± 5 C when tested as described in 5.3.2 and 5.3.3. All cables used for connection shall be 16 mm2 copper. 5.3.2 The following sequence of tests shall be performed: a) five insertions and withdrawals shall be made with a test insert; b) a temperature test shall be conducted at 100 % of the continuous ampere rating. Measure the temperature after 1 h of current injection; d) immediately following the temperature test, the meter shall be removed and reinserted 13 times while it is thermally hot; e) the common base shall be allowed to cool for 2 h or to room temperature and shall then be removed and reinserted 12 times; f) following the final insertion operation, a cycling test shall be conducted consisting of 16 cycles with current on for 2 h and off for 1 h at 120 % of the continuous ampere rating; and g) the temperature test shall then be repeated at 100 % of the continuous rating. Measure the temperature after 1 h of current injection. 5.3.3 The temperature rise observed in the common base shall not exceed the following: a) 65 C at a jaw or at a field wiring terminal when tested in accordance with items (b) and (f) of 5.3.2; b) 55 C within 3,2 mm from the opening for wire in a field wiring terminal when tested in accordance with items (b) and (f) of 5.3.2; and c) 7 C maximum increase at a jaw or a field wiring terminal when tested in accordance with item (f) of 5.3.2 when compared to the rise recorded when tested in accordance with item (b) of 5.3.2.

Page: 12 of 16 5.4 Short time overcurrent Insert a test insert into the common base. Connect the LIVE LOAD terminal to the NEUTRAL LOAD terminal using a 16 mm 2 copper conductor. Inject a 2,5 ka 50 Hz current for one half cycle. Confirm by visual inspection, that no damage was done to the common base. 5.5 Dielectric strength Test the common base in accordance with clause 7.4 of SANS 62052-11 (protective class I). 5.6 Visual inspection After completion of all tests, confirm by visual inspection, that no damage was done to the common base or wall outlet box.

Page: 13 of 16 Annex A - List of drawings (Normative) The following drawings form part of this specification and are attached. D-DT-1017 Common base and Standard Passive Unit. D-DT-1017 Sheet 1 Common base detail (for new ED installations and all maintenance). D-DT-1017 Sheet 2 Common base detail (for new ECU installations as part of SPU). D-DT-1017 Sheet 3 Standard active unit insert. D-DT-1017 Sheet 4 Common base reserved volumes. D-DT-1017 Sheet 5 Common base current test setup. D-DT-1017 Sheet 6 Wall outlet box dimensions and mounting requirements. D-DT-1017 Sheet 7 Standard passive unit (SPU) without rails D-DT-1017 Sheet 8 Standard passive unit (SPU) with rails

Page: 14 of 16 Annex B - Impact assessment Impact assessment form to be completed for all documents. 1 Guidelines o All comments must be completed. o Motivate why items are (not applicable) o Indicate actions to be taken, persons or organisations responsible for actions and deadline for action. o Change control committees to discuss the impact assessment, and if necessary give feedback to the compiler of any omissions or errors. 2 Critical points 2.1 Importance of this document. E.g. is implementation required due to safety deficiencies, statutory requirements, technology changes, document revisions, improved service quality, improved service performance, optimised costs. Document revision and improve service quality. 2.2 If the document to be released impacts on statutory or legal compliance - this need to be very clearly stated and so highlighted. 2.3 Impact on stock holding and depletion of existing stock prior to switch over. All new in accordance with this specification. 2.4 When will new stock be available? 2.5 Has the interchangeability of the product or item been verified - i.e. when it fails is a straight swop possible with a competitor's product? Straight swop. 2.6 Identify and provide details of other critical (items required for the successful implementation of this document) points to be considered in the implementation of this document. 2.7 Provide details of any comments made by the Regions regarding the implementation of this document. None 3 Implementation timeframe 3.1 Time period for implementation of requirements. 3.2 Deadline for changeover to new item and personnel to be informed of DX wide change-over. No deadline

Page: 15 of 16 4 Buyers Guide and Power Office Annex B (continued) 4.1 Does the Buyers Guide or Buyers List need updating? No. 4.2 What Buyer s Guides or items have been created? 4.3 List all assembly drawing changes that have been revised in conjunction with this document. 4.4 If the implementation of this document requires assessment by CAP, provide details under 5 4.5 Which Power Office packages have been created, modified or removed? None. 5 CAP / LAP Pre-Qualification Process related impacts 5.1 Is an ad-hoc re-evaluation of all currently accepted suppliers required as a result of implementation of this document? No. 5.2 If NO, provide motivation for issuing this specification before Acceptance Cycle Expiry date. Revision to be done in 3 years 5.3 Are ALL suppliers (currently accepted per LAP), aware of the nature of changes contained in this document? 5.4 Is implementation of the provisions of this document required during the current supplier qualification period? No. 5.5 If to 5.4, what date has been set for all currently accepted suppliers to comply fully? 5.6 If to 5.4, have all currently accepted suppliers been sent a prior formal notification informing them of Eskom s expectations, including the implementation date deadline? 5.7 Can the changes made, potentially impact upon the purchase price of the material/equipment? No 5.8 Material group(s) affected by specification: (Refer to Pre-Qualification invitation schedule for list of material groups)

Page: 16 of 16 6 Training or communication Annex B (continued) 6.1 State the level of training or communication required to implement this document. (E.g. none, communiqués, awareness training, practical / on job, module, etc.) Comment: 6.2 State designations of personnel that will require training. No Training. 6.3 Is the training material available? Identify person responsible for the development of training material. 6.4 If applicable, provide details of training that will take place. (E.G. sponsor, costs, trainer, schedule of training, course material availability, training in erection / use of new equipment, maintenance training, etc). 6.5 Was Training & Development Section consulted w.r.t training requirements? 7 Special tools, equipment, software 7.1 What special tools, equipment, software, etc will need to be purchased by the Region to effectively implement? None 7.2 Are there stock numbers available for the new equipment? 7.3 What will be the costs of these special tools, equipment, software? 8 Finances 8.1 What total costs would the Regions be required to incur in implementing this document? Identify all cost activities associated with implementation, e.g. labour, training, tooling, stock, obsolescence Comment:... Impact assessment completed by: Name: A J Maudu Designation: Senior Engineer, Power Plant, IARC

ESKOM DISTRIBUTION Specification reference number: 34-434 Page 1 Enquiry No.:. Tenderer s name: Project name: Date: Technical schedules A and B Standard passive units for single-phase 230 V service connections Schedule A: Purchaser's specific requirements Schedule B: Particulars of equipment to be supplied 1 2 3 4 5 Item Clause Description Schedule A Schedule B 1 4.1 Common base configuration required (common base only, SPU with rail, SPU without rail)? For common base only configuration: 2 4.2.1 (a) Does the common base comply with the dimensions on D-DT-1017 sheet 1? 3 4.2.1 (b) Has the common base been supplied without any pre-drilled mounting holes or cable entry holes? For SPU with rails configuration: 4 4.2.2 (a) Does the common base comply with the dimensions on D-DT-1017 sheet 2? 5 4.2.2 (b) Does the wall outlet box comply with the overall dimensions and mounting dimensions of D-DT- 1017 sheet 6? 6 4.2.2 (c) Is the overall layout of the SPU on rails in accordance with D-DT-1017 sheet 8? 7 4.2.2 (d) Have the three M6 mounting holes indicated on D- DT-1017 sheet 8 been drilled (the bottom two and the one 153mm above them)? 8 4.2.2 (e) Have M20 cable entry holes been drilled in the base of the common base as indicated on D-DT- 1017 sheet 8? 9 4.2.2 (f) Has an abridged COC been supplied (in triplicate)? Does the COC numbering system comply with 01TI-03? 10 4.2.2 (g) and (h) Has a suitable length of 2.5mm 2 copper two core and earth cable been used to connect the wall outlet box to the common base? 11 4.2.2 (i) Is the cable used UV stable? 12 4.2.2 (j) Has the cable been terminated at both ends, using no. 1 compression glands (not glued)? 13 4.2.2 (k) Is the SPU supplied ready for commissioning with all wiring in accordance with SANS 10142? Has a SANS 10142 authorization committee certificate been provided with the tender? 14 4.2.2 (l) Have the rails been spaced 153mm apart? For SPU without rails configuration: 15 4.2.3 (a) Does the common base comply with the dimensions on D-DT-1017 sheet 2? 16 4.2.3 (b) Does the wall outlet box comply with the overall dimensions and mounting dimensions of D-DT- 1017 sheet 6? 17 4.2.3 (c) Is the overall layout of the SPU without rails in accordance with D-DT-1017 sheet 7? 18 4.2.3 (d) Have the three M6 mounting holes indicated on D- DT-1017 sheet 7 been drilled (the bottom two and the one 195mm above them)?

ESKOM DISTRIBUTION Specification reference number: 34-434 Page 2 Enquiry No.:. Tenderer s name: Project name: Date: 1 2 3 4 5 Item Clause Description Schedule A Schedule B 19 4.2.3 (e) Have M20 cable entry holes been drilled in the base of the common base as indicated on D-DT- 1017 sheet 7? 20 4.2.3 (g) and (h) Has a 1000mm length of 2.5mm 2 copper two core and earth cable been used to connect the wall outlet box to the common base? 21 4.2.3 (i) Is the cable used UV stable? 22 4.2.3 (j) Has the cable been terminated at the wall outlet box end, using a no. 1 compression gland (not glued)? 23 4.2.2 (k) Has the cable been terminated at the wall outlet box end and prepared for termination but left unattached at the common base end? Has a no. 1 compression gland been hand-tightened onto the common base? 5.6.1.1.1 All configurations common base details 24 4.3.1 Has a type test certificate from an independent accredited test authority that proves compliance with the relevant clauses of SANS 1619 been provided with the tender? 25 4.3.5 Has a surge arrester that complies with 34-312 been supplied with the common base? 26 4.3.5 Has a letter from the surge arrester manufacturer stating that it complies with 34-312 been provided with the tender? 27 4.3.6 Has a type test certificate from an independent accredited test authority that proves compliance with test 5.3 been provided with the tender? 28 4.3.7 Has a type test certificate from an independent accredited test authority that proves compliance with clauses 5.4, 5.6 and 5.8 of SANS 62052-11 been provided with the tender? 29 4.3.8 Have caged clamps been provided to terminate the concentric cable? 30 4.3.9 Has an earth terminal, connected to the Neutral line terminal, been supplied? 31 4.3.10 Have the terminals been labeled? 32 4.3.14 Is the common base UV stabilized? 33 4.3.15 Does the common base comply with clause 4.3.15 when the test insert has been inserted? 34 4.3.16 Has the sticker been included and worded correctly? 35 4.3.17 Has a type test certificate from an independent accredited test authority that proves that the common base complies with clause 5.4 been provided with the tender? 36 4.3.18 Has a type test certificate from an independent accredited test authority that proves that the common base complies with clause 5.5 and therefore clause 5.4.6.3 of SANS 62052-11 been provided with the tender?

ESKOM DISTRIBUTION Specification reference number: 34-434 Page 3 Enquiry No.:. Tenderer s name: Project name: Date: 1 2 3 4 5 Item Clause Description Schedule A Schedule B Wall outlet box details (complete for SPU configurations but not for common base only configuration) 37 4.4.1 Has a type test certificate from an independent accredited test authority that proves that the wall outlet box complies with SANS 1085 been provided with the tender? 38 4.4.1 Is the internal depth of the wall outlet box 36mm? 39 4.4.1 and 4.4.2 Are the overall dimensions and mounting dimensions of the wall outlet box in accordance with D-DT-1017 sheet 6? 40 4.4.3 Can off the shelf double switched socket outlet assemblies and cover plates be fitted to the wall outlet box without modifying it? 41 4.4.4 Has the wall outlet box been removably secured to the base plate/ mounting feet? 42 4.4.5 Have two switched socket outlets been supplied? 43 4.4.5 Has a type test certificate from an independent accredited test authority that proves that the socket outlets comply with VC 8008 and SANS 164-1 been provided with the tender OR has a currently valid letter granting the manufacturer of the socket outlets the right to apply the SABS mark been provided? 44 4.4.5 Has a type test certificate from an independent accredited test authority that proves that the switches comply with VC 8003 and SANS 60669-1 been provided with the tender OR has a currently valid letter granting the manufacturer of the socket outlets the right to apply the SABS mark been provided?? 45 4.4.7 Does the wall outlet box comply to SANS 10142 and has an authorization certificate been supplied? 46 4.4.8 Has a type test certificate from an independent accredited test authority that proves that the wall outlet box complies with the test in clause 5.1.7 of SANS 1619 been provided with the tender? Additional information (all configurations) 47 Colour of SPU XXXXX 48 Material of label XXXXX 49 SPU manufacturer s name XXXXX 50 SPU manufacturer s type or code XXXXX 51 Does SPU comply with requirement V1 of XXXXX UL94-91? - attach documents 52 Does SPU comply with 34-434? Attach XXXXX documentation showing compliance for all requirements. List each point of non-conformance.

ESKOM DISTRIBUTION Specification reference number: 34-434 Page 4 Enquiry No.:. Tenderer s name: Project name: Date: Technical Schedules A and B Deviation schedule Any deviations offered to this specification shall be listed below with reasons for deviation. In addition, evidence shall be provided that the proposed deviation will at least be more cost-effective that that specified by Eskom. Item Clause Proposed deviation