Tolerances for Concrete Construction. Tolerances for Concrete Construction. Tolerance 6/16/2015

Similar documents
CHAPTER 9 STAIR CASES 9.1 GENERAL FEATURES 9.2 TYPES OF STAIR CASES

HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT

A Guide for the Interpretation of Structural Design Options for Residential Concrete Structures

Tips For Designing Constructable Concrete Buildings

SECTION REINFORCING STEEL

SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC Permit Requirements

See the IRC for additional information. See CPD-DS Information Bulletin 100 for Requirements for 1 & 2 Family Dwelling plan submittals.

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Special Reinforced Concrete Structural Walls

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Project Address: Name of Person Completing Form:

DIVISION 03 CONCRETE SPECIFICATION : FORMS AND FORMWORK

1. Cast-in-place concrete is specified in Section

Lintel Tables Design Notes and Limitations

2003 International Residential Building Code

WORK BELOW LOWEST FLOOR FINISH 1/7 230, , , FRAME 2/6 96, , ,056.00

Strength Design of Reinforced Concrete Structures

ARCH 614 Note Set 12.1 S2014abn

1 Exam Prep Placing Reinforcing Bars Tabs and Highlights

FACT SHEET #2 DECK INFORMATION

The following excerpt are pages from the Hilti North America Post- Installed Reinforcing Bar Guide.

CHAPTER 19 CONCRETE. Italics are used for text within Sections 1903 through 1905 of this code to indicate provisions that differ from ACI 318.

STRUCTURAL MASONRY SPECIAL INSPECTOR. Study Guide

BRIDGE DESIGN MANUAL UPDATES. Jamie F. Farris, P.E.

Administrative Changes

VTU EDUSAT PROGRAMME Lecture Notes on Design of Stair cases

Bijan Khaleghi, Ph, D. P.E., S.E.


The designer shall also submit additional information required by the University as described and underlined below.

CITY OF BRISTOL DECK CONSTRUCTION GUIDE ACCORDING TO THE 2012 IRC WITH THE 2016 CT AMMENDMENTS

Bonner Bridge Replacement Update:

Hollowcore Floors. The ideal structural floor solution for all building types in all sectors.

SECTION STAY-IN-PLACE INSULATED CONCRETE FORMING SYSTEM

SECTION STRUCTURAL PRECAST HOLLOW CORE SLABS

1. Section , Concrete Reinforcement and Embedded Assemblies. B. ACI 530/ASCE 5 - Building Code Requirements for Masonry Structures

Concrete Block Machines Typical Fixed Block Machine

Phase IIIA Education Building

SECTION CAST-IN-PLACE CONCRETE

REINFORCING TABLES INSTALLATION MANUAL

JULY 2014 LRFD BRIDGE DESIGN 5-1

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

JULY 2016 LRFD BRIDGE DESIGN 11-1

Sabah Shawkat Cabinet of Structural Engineering 2017

> 0. 1 f, they are treated as beam-columns.

11/07/2017. Tolerances & The Intolerant World of Structural BIM Coordination. Dave Merrifield. BIM and Tolerances. Speaker Twitter Handle.

A. SYSTEM DETAILS A.1 Product Range

PRECAST CONCRETE PRODUCTS

Copyright. magazine. CFS Load Bearing Construction

Smarter. Safer. Leaner.

RESIDENTIAL CONSTRUCTION New Dwellings and Additions

Revise Sections through of Part 1 of the 2009 Provisions as follows:

STANDARD SPECIFICATION FOR CRIBLOCK CONCRETE CRIBWALL

Section A A: Slab & Beam Elevation

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses

Steps And Stairs Installation Option 1 - Steps In Wall Option 2 - Steps With Plant Space Option 3 - Steps In Front of Walls Option 4 - Steps Along

Table of Contents. July

Schöck Isokorb type CV

USE OF 500 GRADE STEEL IN THE DESIGN OF REINFORCED CONCRETE SLAB. Prof. M. Shafiul Bari, Ph.D Department of Civil Engg., BUET

Reinforced Concrete Design. A Fundamental Approach - Fifth Edition

In-plane testing of precast concrete wall panels with grouted sleeve

DIRECT DESIGN METHOD DDM

PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION

Steps And Stairs Installation Steps In Wall - Option 1 Steps In Front of Walls - Option 2 Steps In Wall; 10 (25cm) Tread - Option 3 Step Parallel to

A. Coordinate concrete unit masonry (also termed CMU and block ) work with work before and after, especially:

CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT. Submittal Requirements

SLAB ON GRADE Insul-Joint or Expansion Joint Material as Required by A/E Specifications AquaCheck Liquid Coating 400 (Waterproofing Membrane) with Aqu

SEAU 5 th Annual Education Conference 1. ASCE Concrete Provisions. Concrete Provisions. Concrete Strengths. Robert Pekelnicky, PE, SE

Seismic Installation Manual

R CODE CHANGE PROPOSAL FORM (See instructions on page 2)

CONSTRUCTION SURVEY. Construction survey includes personnel, equipment, and supplies required for, but not limited to, the following:

HOT ROLLED STEEL FLAT PRODUCTS FOR STRUCTURAL FORMING AND FLANGING PURPOSES SPECIFICATION (Third Revision of IS 5986)

SPECIFICATIONS: Architectural Aluminum Railings

TECHNICAL SPECIFICATIONS

Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report

A. The scope of this standard includes recommendations for the specification of cast-in-place concrete.

Flat Slabs. d 2. A typical flat slab (without drop and column head)

Design and Construction of the SH58 Ramp A Flyover Bridge over IH70. Gregg A. Reese, PE, CE, Summit Engineering Group, Inc.

CONCRETE STEPS, HANDRAILS, AND SAFETY RAIL

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)

ITEM 6 CONCRETE CURBS, GUTTERS, AND SIDEWALKS

Wall Panels. Structural wall panel. Architectural wall panel. Cladding wall panel. Sandwich wall panel

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

DESIGN OF WALLS FOR SHEAR

Design and Estimation of Reinforced Building: A Case Study

Seismic Detailing of RC Structures (IS: )

SPECIFICATION FOR REINFORCED SOIL WALL

PT Slab Deflections. What is acceptable? By Douglas Sarkkinen, PE,SE Senior Structural Engineer Otak, Inc PTI Annual Conference, Kansas City, MO

DIVISION 04 MASONRY CAST STONE. A. Design Considerations. 1. Cast stone shall comply with ASTM C1364, Standard Specification for Cast Stone.

DETAIL DRAWINGS. RASTRA is a stay-in-place insulated concrete. form that is structurally strong, energy-efficient,

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs

SECTION CAST-IN-PLACE CONCRETE

14.1 PCI Standard Design Practice

CANTILEVER RACK SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE

Minimum slab thickness of RC slab to prevent undesirable floor vibration. Technology, Dhaka-1000, Bangladesh. 2.

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE

2012 IBC/2011 MSJC MASONRY CODE COMPILATION

KINETICS Pipe & Duct Seismic Application Manual

Transcription:

Tolerances for Concrete Construction Thomas J Downs P.E., FACI President Forensic Experts Minneapolis, MN What is it? Tolerances for Concrete Construction When did we start this anyway? Who said we needed tolerances? Now that we have them, how do we use them? Tolerance It s the elephant in the living room. Everybody knows It s there. If you ignore It, maybe It will go away. 1

Tolerances should be: Considered in design Controlled during construction Enforced by inspection Tolerance - Defined Sympathy or indulgence for practices differing from or conflicting with one s own. The permissible deviation from a specified value History of ACI 117 Tolerance 1962 ACI 117 was formed. Committee purpose was to gather and summarize all the of tolerances that existing committees were publishing. 2

History of ACI 117 Tolerance 1980 - Proposed ACI Standard published in Concrete International 1981 Concrete International published reviews praising and bashing the Proposed Standard. 1981 - The Standard was adopted by ACI History of ACI 117 Tolerance 1990 ACI adopts Standard Specification for Tolerances for Concrete Construction 2006 ACI 117-06 document was published. 2010 ACI 117-10 document was published. 2014 ACI 117.1R-14 Tolerance Compatibility Who Said We Need Tolerances If you ask an Engineer, all things are to be built exactly as specified. If you ask a Contractor, the tolerance limits just slow down construction. If you ask an Owner, they don t care as long as the building works and things fit! 3

Who Said We Need Tolerances No structure is exactly level, plumb, straight or true. Tolerances are a means to establish permissible variations from the values specified. Tolerances are based on: Normal Needs Common Construction Practices How do we use them? Tolerances should be used to provide the owner with a tangible benefit. Tolerances should convey to the contractor a performance expectation. Tolerances should be selected based on necessity rather than desirability. 4

Tolerances Overly constrictive tolerances are not impossible to achieve, just costly to produce. Tolerances should always be based on, normal needs and common construction practices Tolerances Most problems with tolerances arise from unrealized expectations. The degree of accuracy depends on the interrelationship of the parts. Tolerance Chapter 1 1.2.2 Tolerances shall not extend the structure beyond legal boundaries. Tolerances are measured from the points, lines, and surfaces defined in the Contract Documents. If application of tolerances causes the extension of the structure beyond legal boundaries, the tolerance must be reduced. 1.2.3 Tolerances are not cumulative. The most restrictive tolerance controls. 5

Tolerances Chapter 1 6 6 In this region, the face of the wall may deviate horizontally ±6 from the location shown on the drawings. Within the envelope established by Section 4.1.2, the wall face may slope with respect to the specified plane at a rate established by Section 4.8.2. 500-0 In this region, the face of the wall may deviate horizontally from the location shown on the drawings by an amount ±0.1% of the height above the top of foundation as shown on drawings. Within the envelope established by Section 4.1.2, the wall face may slope with respect to the specified plane at a rate established by Section 4.8.2. 83-4 Face of wall as shown on drawings In this region, the face of the wall may deviate horizontally ±1 from the location shown on the drawings. Within the envelope established by Sections 4.1.1 and 4.2.1, the wall face may slope with respect to the specified plane at a rate established by Section 4.8.2. 1 1 Top of foundations as shown on drawings 2.2.1 Placement of nonprestressed reinforcement, measured from form surface When member depth (or thickness) is 4 in. or less ±1/4 in. When member depth is over 4 in. to12 in. ± 3/8 in. When member depth is over 12 in. ± 1/2 in. Unformed Surface A B Formed Surfaces 6

2.2.2 Concrete cover measured perpendicular to concrete surface When member depth (or thickness) is 12 in. or less - 3/8 in. When member depth is over 12 in. -1/2 in. Reduction in cover shall not exceed one-third the specified concrete cover. Reduction in cover to formed soffits shall not exceed -1/4 in. Unfinished Surface Specified Cover Tolerance 2.2.3 Vertical deviation for slab-onground reinforcement ± 3/4 in. 7

2.2.5 Spacing of nonprestressed reinforcement, measured along a line parallel to the specified spacing Except as noted below ± 3 in. Stirrups the lesser of ± 3 or ± 1 in. per ft. of beam depth Ties the lesser of ± 3 or ± 1 in. per ft. of least column width The total number of bars shall not be less than that specified. 2.2.6 Placement of prestressing reinforcement or prestressing ducts 2.2.6.1 Horizontal deviation Element depth (or thickness) 24 in. or less ± 1/2 in. Element depth (or thickness) over 24 in. ± 1 in. Unformed Surface Vertical Deviation Tolerance Horizontal Deviation Tolerance Formed Surfaces Member Depth Vertical Deviation Tolerance 8

2.2.6.2 Vertical deviation Element depth 8 in. or less Element depth over 8 in. to 24 in. Element depth more than 24 in. ± 1/4 in. ± 3/8 in. ± 1/2 in. 2.2.7 Longitudinal location of bends in bars and ends of bars. At discontinuous ends of corbels and brackets ± 1/2 in. At discontinuous ends of others At other locations ± 1 in. ± 2 in. 2.2.8 Embedded length of bars and length of bar laps # 3 - # 11 bar sizes -1 in. # 14 - #18 bar sizes -2 in. 9

2.2.9 Bearing plate for prestressing tendons, deviation from specified plane. ± 1/4 in. per ft., but not less than ± 1/8 in. 2.2.10 Placement of smooth rod or plate dowels in slab on ground. 2.2.10.1 Centerline of dowel, vertical deviation slab depth 8 in. or less ± 1/2 in. When slab depth greater than 8 in. 2.2.10.2 Spacing of dowels ± 3 in. ± 1 in. 2.2.10.3 Centerline dowel location ± 1/2 in. 2.3 Placement of embedded items, excluding dowels in slabs on ground 2.3.1 Clear distance to nearest reinforcement shall be the greater of the bar diameter or 1 in. 10

Bar Diameter = D b 1 in. (25 mm) D b 2.3.4 Anchor bolts in concrete 2.3.4.1Top of anchor bolt from specified elevation Vertical deviation ±1/2 in. 2.3.4.2Centerline of individual anchor bolts from specified location Horizontal deviation 3/4 in. and 7/8 in. bolts ±1/4 in. 1 in., 1-1/4 in., and 1 1/2 in. bolts ±3/8 in. for 1 3/4 in., 2 in., and 2 1/2 in. bolts ±1/2 in. Chapter 3 - Foundations 3.1 Deviation from plumb 3.1.1 Category A For unreinforced piers extending through materials offering no or minimal lateral restraint (for example, water, normally consolidated organic soils, and soils that might liquefy during an earthquake) ±12.5% of shaft diameter 3.1.2 Category B For unreinforced piers extending through materials offering lateral restraint (soils other than those indicated in Category A) ±1.5% of shaft length 3.1.3 Category C For reinforced concrete piers ±2.0% of shaft length 11

Tolerances Chapter 3 3.2 Deviation from location 3.2.1 Foundations, unless noted otherwise in this section Horizontal deviation of the as-cast edge with a width of less than 8 ft. ± 2% of the foundation s width or ± 1/2 in. Horizontal deviation of the as-cast edge 8 ft. or greater ± 2 in. 3.2.2 Foundations supporting masonry Horizontal deviation of the as-cast edge shall be the lesser of ± 2% of the foundation s width or ± 1/2 in. 3.2.3 Top of drilled piers Horizontal deviation of the as-cast center shall be the lesser of 4.2% of the shaft diameter or ±3 in. Tolerances Chapter 3 3.3 Deviation from elevation 3.3.1 Top surface of foundations Vertical deviation +1/2 in. -2 in. 3.3.2 Top surface of drilled piers Vertical deviation +1 in. -3 in. Tolerances Chapter 3 3.5 Deviation from cross-sectional dimensions of foundations 3.5.1 Formed footings Horizontal deviation +2 in. -1/2 in. 3.5.2 Unformed footings cast against soil Horizontal deviation from plan dimension Where dimension is 2 ft. or less +3 in. -1/2 in. Where dimension is more than 2 ft. +6 in. -1/2 in. 3.5.3 Deviation from footing thickness -5% 12

Chapter 4 Cast In Place For Buildings 4.1 Deviation from plumb 4.1.1 For heights less than or equal to 83 ft 4 in. For lines, surfaces, corners, arises and elements: the lesser of 0.3% times the height above the top of foundations as shown on structural drawings or ±1 in. For the outside corner of an exposed corner column and control joint grooves in concrete exposed to view: the lesser of 0.2% times the height above the top of foundations as shown on structural drawings or ±1/2 in. 4.1.2 For heights greater than 83 ft 4 in. For lines, surfaces corners, arises and elements: the lesser of 0.1% times the height above the top of foundations as shown on structural drawings or ± 6 in. For the outside corner of an exposed corner columns and control joint grooves in concrete exposed to view: the lesser of 0.05% times the height above the top of foundations as shown on structural drawings or ± 3 in. 4.2 Deviation from location 4.2.1 Horizontal deviation Vertical Elements, measured at the top of element foundation ±1 in. Other Elements ±1 in. Edge location of all openings ±1/2 in. Sawcuts, joints, and weakened plane embedments in slabs ±3/4 in. 13

4.2.2 Vertical deviation Elements ±1 in. Edge location of all openings ±1/2 in. Tolerance = ±1 in. (25 mm) Vertical Deviation Elevation View 4.4 Deviation from elevation 4.4.1 Top surface of slabs Slabs-on-ground ±3/4 in. Formed suspended slabs, before removal of supporting shores ±3/4 in. Slabs on structural steel or precast concrete. no requirement 4.4.2 Formed surfaces before removal of shores ±3/4 in. 4.4.3Lintels, sills, parapets, horizontal grooves, and other lines exposed to view ±1/2 in. 4.4.4 Top of walls ±3/4 in. 4.4.5 Fine grade for slabs-on-ground ±3/4 in. 14

4.5 Deviation from cross-sectional dimensions 4.5.1 Thickness of elements, except slabs, where specified dimension is 12 in. (305 mm) or less +3/8 in. -1/4 in. More than 12 in. not more than 36 in. +1/2 in. -3/8 in. Over 36 in. +1 in. -3/4 in. 4.5.2 Unformed beams and walls cast against soil Horizontal deviation from plan dimension: Where dimension is 2 ft. or less +3 in. 1/2 in. Where dimension is more than 2 ft. +6 in. 1/2 in. 4.5.3 Thickness of suspended slabs -1/4 in. 4.5.4 Thickness of slabs-on-ground Average of all samples Individual sample -3/8 in. -3/4 in. 4.5.4.1Minimum number of samples shall be four per 5,000 sq. ft. or part thereof. 4.5.4.2 Samples shall be taken within 7 days of placement. 15

4.6 Deviation from formed opening width or height 1/2 in. + 1 in. 4.7 Deviation from relative elevations or widths 4.7.1Stairs, measured along a line parallel to the stair axis Difference between largest and smallest tread or riser in any flight shall not exceed 3/8 in. Difference in height of adjacent risers measured at the nose shall not exceed 3/16 in. Difference in depth of adjacent treads shall not exceed 3/16 in. 4.8 Deviation from slope or plane 4.8.1 Stair tread from back to nosing ±1/4 in. 4.8.2Formed surfaces over distances of 10 ft. All conditions, unless noted otherwise in this section ±0.3% Outside corner of exposed corner column ±0.2% Contraction joint grooves in concrete exposed to view ±0.2% 16

4.8.3 Formed surface irregularities (gradual or abrupt) Abrupt irregularities shall be measured within 1 in. of the irregularity. Gradual surface irregularities shall be measured by determining the gap between concrete and near surface of a 5 ft straightedge, measured between contact points. Class A Surface... +1/8 in. Class B Surface... +1/4 in. Class C Surface... +1/2 in. Class D Surface... +1 in. 4.8.4 Random traffic floor surface finish tolerances shall meet the requirements of Section 4.8.5 or 4.8.6. 4.8.4.4 Floor test surfaces shall be measured and reported within 72 hr. after completion of slab concrete finishing operations and before removal of any supporting shores. 4.8.4.6 Floor surface test measurements shall not cross planned changes in floor surface slope. 4.8.4.7 Test results shall be reported in a manner that will allow the data to be verified or the tests to be replicated. 17

4.8.5.1 Specified overall values for flatness (SOFF) and levelness (SOFL) shall conform to one of the following floor surface classifications, unless noted otherwise. Floor SurfaceClassification: Specified OverallFlatness Specified OverallLevelness Conventional 20 15 Moderately flat 25 20 Flat 35 25 Very flat 45 35 Super flat 60 40 4.8.6 Random traffic floor finish tolerances as measured by manually placing a freestanding (unleveled) 10 ft (3 m) straightedge anywhere on the slab and allowing it to rest naturally upon the test surface shall conform to the following requirements: 4.8.6.1 The gap under the straightedge and between the support points shall not exceed one of the following: Floor SurfaceClassification Maximum Gap90% Maximum Gap100% Conventional 1/2 in. (13 mm) 3/4 in. (19 mm) Moderately flat 3/8 in. (10 mm) 5/8 in. (16 mm) Flat 1/4 in. (6 mm) 3/8 in. (10 mm) Very flat N/A N/A Super flat N/A N/A 18

4.9 Sawcut depth in slab-on-ground 4.9.1 Depth of sawcut joint ±1/4 in. Tolerances Questions? 19