SECTION SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION

Similar documents
Acceptable Floor Substrates: Concrete, cured mortar bed, plywood, and backer board.

SECTION LATEX-MODIFIED MEDIUM BED MORTAR

SECTION CERAMIC TILE. B. Ceramic tile wall finishes including standard and custom designs.

INSTALLATION INSTRUCTIONS

STEAM SHOWER / ROOM; WOOD OR METAL STUDS Wood or Metal Studs Cement Backer Board Walls, Mortar Bed Floor Ceramic Tile

SECTION WOOD FLOORING. 1. Section Above-Grade Vapor Retarders. 2. Section Below-Grade Vapor Retarders

Assembly Instruction. wedi Fundo Primo Steam Shower System

SECTION WOOD FLOORING

SECTION CEMENT BOARD SUPPORTED ADHERED MASONRY VENEER. 2. Installation materials including adhesives, mortars, and pointing mortars.

DIVISION 9 - SECTION QTscu Re-bonded Recycled Rubber Impact Sound Insulation Patent No. RE 41,945

CSI GUIDE Countertops

Kolorines Glass Mosaic Tiles Project Specification

COOK COUNTY ILLINOIS CONTRACT FOR WORK DOCUMENT NO Countywide Warehouse and Records Storage Center Hawthorne Project TKB No.

Installation Guide LVP Glue Down

AquaDefense. Mapelastic. Premium Waterproofing and Crack-Isolation Membrane DESCRIPTION FEATURES AND BENEFITS WHERE TO USE

TECH TALK Sponsored by

A. Section includes hydraulic-cement-based, polymer-modified, self-leveling underlayment for application below interior floor coverings.

1.3 Work shall include all reinforcement and accessories necessary to complete installation.

SECTION EPOXY TERRAZZO

8245 Remmet Ave Canoga Park, CA (888) Installation Instructions - AVM System 700 Under Tile Waterproofing and Anti-Fracture Membrane

A. Source Limitations: Obtain each type of building insulation through one source.

SECTION CONCRETE PAVING SLABS SET IN MORTAR

FLUID APPLIED WATERPROOFING

Assembly Instruction. wedi Fundo Primo Shower System

SECTION HYDRAULIC CEMENT UNDERLAYMENT

Union County Vocational - Technical Schools Scotch Plains, New Jersey

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.

Fiber Reinforced Tile and Stone Mortar

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS REPORT HOLDER: PAREX USA, INC.

Schluter -KERDI-DRAIN

CONTRACT NUMBER: W912DQ-08-C % CORRECTED DESIGN 28 JULY 2008

EDGEWATER, FLORIDA JUNE 14, 2010

KOSTER AMERICAN CORPORATION

Suggested Specification for Tri-Patch Versatile Concrete Patching Compound

Magnum Board Section Digicon Information Inc. Page 1

TECH TALK Sponsored by

ARDEX X 90 OUTDOOR TM

ARDEX X 32 MICROTEC Universal Rapid Setting and Drying Thin-to-Thick Bed Mortar

B. Related Sections: 1. Division 07 Section "Joint Sealants" for sealing of expansion, contraction, control, and isolation joints in tile surfaces.

Sections Paver Tiling Guide Specification; for installation of Marion Ceramics, Thin Brick Tiles; Flooring, Veneer

AVM System 500. Aussie Membrane 500

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

EXTERIOR ROOF / DECK FLOORS Roof Deck or Balcony over Occupied Space, Drainage Mat, Mortar Bed Ceramic Tile

ARDEX GUIDE SPECIFICATION ARDEX MRF Moisture-Resistant, Rapid-Drying, Skimcoat Patching Underlayment

Union County Vocational - Technical Schools Scotch Plains, New Jersey

SECTION MANUFACTURED ROOF EXPANSION JOINTS

Application Specification:

Colphene BSW Training and Application Guide. Colphene BSW Waterproofing Membrane. 1. Prepare substrate

ARCHITECTURAL GUIDE SPECIFICATIONS - DESCRIPTIVE

SECTION RESINOUS FLOORING or SECTION QUARTZ FLOORING

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

HYDRATHANE INTERIOR WATERPROOFING MEMBRANE. Product. Scope. Building Regulations. Appraisal No. 959 [2017] Appraisal No. 959 (2017) BRANZ Appraisals

Installation of Large Format Tile & Stone

Gold Bond BRAND Gypsum Sheathing

SIKALASTIC-152 EXTERIOR WATERPROOFING MEMBRANE. Product. Scope. Appraisal No. 811 [2013] Appraisal No. 811 (2013) Amended 28 August 2017

SECTION TILING

CTIOA Field Report

Specification and Installation

TILE TILE

SPECIFICATION GUIDELINE

prospec.com Concrete Repair & Restoration

USG DUROCK BRAND SHOWER SYSTEM A SUPERIOR SHOWER SYSTEM FROM A NAME YOU TRUST

When I started tiling, we didn t do our own shower pans that BATHS

1.1 Related Work Specified in Other Sections (Delete if Not Applicable):

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

Chevy Chase Club June 30, 2008 Bowie Gridley Architects SECTION GYPSUM BOARD SHAFT WALL ASSEMBLIES

Dural Durabase WP Installation Instructions For showers and general waterproofing (800)

REPORT HOLDER: COREV AMERICA BRITTMOORE PARK DRIVE HOUSTON, TEXAS EVALUATION SUBJECT:

Tensile ASTM D1970 MD = 939 psi / CD = 1252 psi Self Sealability / water penetration resistance around nails. ASTM D1970 Section 7.

SECTION SPRAY APPLIED FLOOR ADHESIVE

POOLS AND WATER FEATURES Concrete Tank Cementitious Waterproofing Bonded Mortar Bed Concrete, Ceramic Tile

Schluter -Shower System Installation Handbook Bonded Waterproofing System for Tiled Showers, Steam Showers, and Bathtub Surrounds

SECTION RESILIENT SHEET FLOORING

Perimeter Relief and Control Joints in Fire-Rated Gypsum Board

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

SECTION ULTRACOMPACT WALL FINISHES - THIN SET

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

SECTION mil thickness COLD FLUID-APPLIED WATERPROOFING

Floor Insulation Underlayment Section Sound Control Matting

HARO SPORTS FLOOR C.S.I. GUIDE SPECIFICATION Helsinki-Gymnasium Floor System 10/2010 SECTION WOOD ATHLETIC FLOORING

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

ENKASONIC FLOOR UNDERLAYMENT 9110

Daytona Beach Pier Building Renovation Jun 2010

Editing notes to assist users are separated from specification text by rows of asterisks. Delete these notes prior to final printing.

SECTION SPRAY APPLIED WALL COVERING ADHESIVE

INSTALLATION BASICS FOR TUFTED BROADLOOM BACKING

GUIDE SPECIFICATION

Pacific Polymers Elasto-Deck BT Guide Specification

Combustible Exterior Wall Cladding Systems: An ICC Perspective

Mapeguard. Premium Crack-Isolation and Sound-Reduction Sheet Membrane DESCRIPTION INDUSTRY STANDARDS AND APPROVALS FEATURES AND BENEFITS WHERE TO USE

May 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building

INSTALLATION BASICS FOR TUFTED BROADLOOM BACKING

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

GUIDE SPECIFICATION

SECTION SELF-ADHERING SHEET WATERPROOFING

GOWANDA, NEW YORK SEPTEMBER 18, 2008 ARCH PROJECT NO

CSI SECTION

Schluter -DITRA Installation Handbook The Universal Underlayment for Ceramic and Stone Tile. Introducing Schluter -DITRA-XL. New detail included

PLATON RUGGED, DIMPLED HIGH-DENSITY POLYETHYLENE (HDPE) MEMBRANE THAT KEEPS FOUNDATIONS AND FLOORING DRY ADVANCED TECHNOLOGY EASY INSTALLATION

Transcription:

SECTION 093000 - SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION PART 1 - GENERAL This specification includes the sheet membrane used as waterproofing, vapor retarder, and crack isolation in conjunction with tile and dimension stone installations. The content of this section should be combined with the specification for the tile and stone finishes including the setting materials required to complete the sheet membrane installation. 1.1 SUMMARY Typical Floors and Walls: NobleSeal TS sheet membrane may be installed for waterproofing and crack isolation on floor and wall substrates for tile and dimension stone installation. Steam Room Walls and Ceilings: NobleSeal TS may be installed as a bonded water/vapor barrier on walls and ceilings. Acceptable Floor Substrates: Concrete and cured mortar bed, plywood, backer board. Acceptable Wall Substrates: Concrete, masonry, backer board, mortar. Acceptable Backer Boards: Cementitious backer board, glass mat, water-resistant gypsum backer board, fiber-cement backer board, fiber-reinforced water-resistant gypsum backer board, cementitious coated extruded foam backer board in accordance with TCNA Handbook. Note: Some backer boards are not suitable for steam rooms. Consult manufacturer s specifications. A. Section Includes: 1. Sheet membrane waterproofing for [tile] [and] [dimension stone] installations. The next three paragraphs describe NobleSeal TS used as waterproofing for floors and walls in showers, tub surrounds, and other wet areas. a. Sheet membrane bonded to tile substrate with NobleBond EXT or latex Portland cement mortar, thin-set mortar for shower floors [and walls]. b. Sheet membrane bonded to tile substrate with NobleBond EXT or latex Portland cement mortar, thin-set mortar for walls at tub surrounds. c. Sheet membrane loose-laid under thickset tile substrate for shower floors. 2. Sheet membrane waterproofing and water vapor retarder for [tile] [and] [dimension stone] installations. The next paragraph describes NobleSeal TS used as waterproofing and vapor retarder for steam room floors, walls, and ceilings. SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION 093000-1

a. Sheet membrane bonded to tile substrate with latex Portland cement mortar for steam room floors [and walls]. 3. Sheet membrane crack isolation for [tile] [and] [dimension stone] installations. The next two paragraphs describe NobleSeal TS used as crack isolation for floors. Select the required installation method. 1.2 REFERENCES a. Sheet membrane bonded to tile substrate with latex Portland cement mortar for floors. b. Sheet membrane bonded to tile substrate with adhesive for floors. A. ANSI A108.13 - Installation of Load Bearing, Bonded, Waterproof Membranes for Thin-Set Ceramic Tile and Dimension Stone. B. ANSI A108.17 - Installation of Crack Isolation Membranes. C. ANSI A118.10 - American National Standard Specifications for Load Bearing, Bonded, Waterproof Membranes for Thin-Set Ceramic Tile and Dimension Stone Installation. D. ANSI A118.12 - American National Standard Specifications for Crack Isolation Membranes for Thin-Set Ceramic Tile and Dimension Stone Installation. E. ASTM E96/E96M - Standard Test Methods for Water Vapor Transmission of Materials. F. ASTM F1869 - Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride. G. ASTM F2170 - Standard Test Method for Determining Relative Humidity in Concrete Floor Slabs Using in situ Probes. H. TCNA Handbook - TCNA Handbook for Ceramic, Glass, and Stone Tile Installation. 1.3 ACTION SUBMITTALS A. Product Data: For each specified product. B. LEED Submittals: Include the next paragraph for LEED NC, LEED CS, and LEED for Schools. 1. Certificates for Credit MR 5: For regional materials indicating location of manufacturer and point of extraction, harvest, or recovery. Include distance to Project, cost, and fraction by weight for regional components. Include the next paragraph for LEED CI, only. SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION 093000-2

2. Certificates for Credit MR 5: For regionally manufactured [and regionally extracted and manufactured] materials indicating location of manufacturer [and point of extraction, harvest, or recovery]. Include distance to Project, cost, [and fraction by weight] for regional components. Include the next paragraph for LEED NC, LEED CI, and LEED CS. 3. Data for Credit IEQ 4.1: For [adhesives] [and] [sealants], statement of VOC content. C. Shop Drawings: 1. Include details of sheet membrane waterproofing installation with flashings and terminations. 1.4 INFORMATIONAL SUBMITTALS A. Field quality-control reports. PART 2 - PRODUCTS 2.1 SHEET MEMBRANE [WATERPROOFING] [AND] [CRACK ISOLATION] NobleSeal TS is rated "Extra Heavy Duty" when tested with ceramic tile to ASTM C627, Standard Test Method for Evaluating Ceramic Floor Tile Installation Systems Using the Robinson-Type Floor Tester. A. Sheet Membrane: ANSI A118.10; composite sheet membrane made from an alloy of non-plasticized Chlorinated Polyethylene (CPE) with non-woven fiber laminated to both sides. 1. Basis of Design Manufacturer: Noble Company. 2. Basis of Design Product: NobleSeal TS. B. Performance: Include water vapor permeance for steam room applications. ASTM E96/E96M, Procedure E uses the desiccant method at high temperature 100 deg F (37.8 deg C). 1. Water Vapor Permeance: ASTM E96/E96M, Procedure E; maximum 0.15 perms (28.6 ng/pa s m 2 ). Include crack isolation for flooring applications. Available ratings are Standard performance and High performance based on crack bridging capability. 2. Crack Isolation: "High performance" rating when tested to the "System Crack Resistance" portion of ANSI A118.12. SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION 093000-3

2.2 ACCESSORIES A. Bonding Mortar: 1. Latex-Portland Cement Mortar (Thin Set): ANSI A118.4. B. Bonding Adhesive: Type recommended by sheet membrane manufacturer to suit application [with VOC less than LEED allowable limits]. Include NobleBond EXT for interior and exterior locations used in horizontal and vertical applications excluding steam room. 1. Basis of Design Product: NobleBond EXT. Include NobleBond 21 for interior locations used in horizontal applications, only. 2. Basis of Design Product: NobleBond 21. C. Mortar Bed: 1. Portland Cement Mortar (Thickset): ANSI A108.02. D. Seam Sealant: Type recommended by sheet membrane manufacturer [with VOC less than LEED allowable limits]. For projects required to meet LEED VOC limits, include NobleSealant 150, only. 1. Basis of Design Product: NobleSealant 150. 2. Basis of Design Product: NobleWeld 100. E. Perimeter Sealant: Type recommended by sheet membrane manufacturer [with VOC less than LEED allowable limits]. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine [tile] [and] [stone] substrates, including [walls,] [floors,] [ceilings,] [and] [framing] for unacceptable conditions affecting sheet membrane installation. B. Examine roughing-in for plumbing piping to verify actual locations of piping connections before sheet membrane installation. C. Correct unacceptable conditions before installing sheet membrane. 3.2 PREPARATION SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION 093000-4

Floor slab moisture content may be measured by moisture emission test or by relative humidity test, or both. A. Examine, prepare, and test concrete floors for finish flooring installation in accordance with ASTM F710. Perform one [moisture emission test in accordance with ASTM F1869] [relative humidity test in accordance with ASTM F2170] and one alkalinity test for every 2,000 sf (185 sq m). Obtain instructions for corrective measures from flooring and adhesive manufacturers when test results are not within specified limits. Use more restrictive substrate tolerances when installing large format tile. Verify acceptable limits with tile manufacturer. 1. Surface Tolerance: Maximum variation from plane of 3/16 inch (4.5 mm) in 10 feet (3000 mm). a. Floor systems over which tile will be installed shall be in conformance with [IRC] [IBC] [applicable building codes]. Include moisture emission rate or relative humidity requirements, or both. When using NobleBond EXT use the following requirements. Coordinate with tests specified above. 2. Moisture Emission Rate: Maximum 4 lb. per 1000 sq ft (1.4 kg 100 sq m) per 24 hours when tested using calcium chloride moisture test kit for 72 hours. 3. Relative Humidity: Maximum 85 percent. 4. Alkalinity Range: ph of 7.0 to 9.0. B. When tested moisture emission rate exceeds specified maximum, consult membrane manufacturer, thin-set manufacturer, and tile manufacturer for acceptable mitigation methods and materials. 3.3 INSTALLATION - SHEET MEMBRANE WATERPROOFING [AND VAPOR RETARDER] Include this article when sheet membrane is installed on solid substrates including floors and tile backer boards. Include option above only when sheet membrane is installed in steam rooms. A. Comply with ANSI A108.13, TCNA Handbook, and the manufacturer s instructions for installation of sheet membrane waterproofing. Include the next paragraph for thin-set floor and wall applications. B. Bonded Installation for Thin-Set Applications: 1. Apply bonding [mortar] [adhesive] for full coverage of substrate. 2. Install sheet membrane and fully embed into bonding material. SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION 093000-5

a. A carpet type roller may be used to embed sheet membrane on horizontal surfaces. b. Hand roller or flat side of trowel can be used to embed sheet membrane on vertical surfaces. Include the next paragraph for mortar bed floor applications only. C. Loose Laid Installation for Mortar Bed Applications: 1. Loose lay sheet membrane on floor substrate. D. If membrane is not wide enough, seam by overlapping sheets minimum 2 inches (50 mm), shingle fashion in direction of water drainage. Seal joints watertight. E. Turn sheet membrane installed on floors up vertical surfaces minimum 2 inches (50 mm) higher than flood plane and bond to substrate. 1. Shower Walls: When sheet membrane is turned up and terminated behind backer board, extend minimum 3 inches (75 mm) above finished dam or high point and fasten to substrate with no penetrations less than 2 inches (50 mm) above finished dam. F. Extend sheet membrane over floor drains. Cut drain opening in sheet membrane and seal to drain body. Secure membrane with floor drain clamping ring. G. Seal sheet membrane watertight to items penetrating sheet membrane. 3.4 INSTALLATION - SHEET MEMBRANE WATERPROOFING AND VAPOR RETARDER Include this article when sheet membrane is installed on framing before installation of solid substrates for use at steam room walls and ceilings only. A. Comply with TCNA Handbook and the manufacturer s instructions for installation of sheet membrane waterproofing. B. Apply continuous bead of seam sealant to framing flanges. C. Overlap sheets minimum 2 inches (50 mm) shingle fashion in direction of water drainage. Seal joints watertight. D. Seal sheet membrane watertight to items penetrating sheet membrane. E. Install sheet membrane over framing and mechanically fasten to retain sheet membrane in place. F. Install tile backer board and mechanically fasten to framing. G. Seal fastener penetrations. SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION 093000-6

3.5 INSTALLATION - SHEET MEMBRANE CRACK ISOLATION Show locations of sealant (soft) joints on Drawings to place the joints in the vicinity of the slab-on-grade control joints. A. Comply with ANSI A108.17, TCNA Handbook, and the manufacturer s instructions for installation of sheet membrane waterproofing. B. Apply bonding [mortar] [adhesive] for full coverage of substrate. C. Install sheet membrane and fully embed into bonding material. 3.6 FIELD QUALITY CONTROL Include this article for flood testing floor waterproofing installations only. A. Upon completion of sheet membrane waterproofing installation, plug drains, dam perimeter of waterproofing, and fill with water minimum 2 inches (50 mm) deep and maintain for 24 hours. 1. Inspect waterproofing for leaks. 2. Repair leaks and re-test until watertight. B. Prepare test and inspection reports. Indicate corrective measures required to make installation watertight. 3.7 PROTECTION A. Protect sheet membrane from pedestrian and vehicular traffic and prolonged exposure to sunlight. B. Keep sheet membrane clean until [tile] [and] [stone] finishes are installed. END OF SECTION 093000 P.O. Box 350 Grand Haven, MI 49417-0350 800-878-5788 Fax: 231-799-8850 www.noblecompany.com Registered Trademark of Noble Company, Grand Haven, MI. Trademark of Noble Company, Grand Haven, MI. SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION 093000-7