FM APPROVED. FIRE PERFORMANCE Differences Between Elastomeric and Polyethylene/Polyolefin Insulations

Similar documents
Tube Insulation. Fiber Free

PRODUCT SELECTION GUIDE

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION

Alply CLASSIC WALL Architectural Insulated Panel Wall System

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION

Design & Construction Standards, Revised January

June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

Report on First Revision June 2014 NFPA 5000

DIVISION: THERMAL AND MOISTURE SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

european fire standards and national legislation

First Revision No NFPA [ Section No ]

NEW! THE FLEXIBLE PROFESSIONAL INSULATION WITH REVOLUTIONARY CHARACTERISTICS. even easier to use

INTERIOR FINISHES CHAPTER 8

October 12, Yours very truly, Gary G. Nichols, P.E., SECB Vice President. GGN/md Enclosure Evaluation Committee

AC R2 8. ECO-Block, LLC. May 23, ICC Evaluation Service, Inc Workman Mill Road Whittier, California 90601

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: NATURAL POLYMERS, LLC

Combustible Exterior Wall Cladding Systems: An ICC Perspective

ISOPA. Prüfungsanstalt (MFPA), Leipzig, on a polyurethane. rigid foam insulated roof construction.

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION

June 25, 2012 PARTIES INTERESTED IN SPRAY-APPLIED FOAM PLASTIC INSULATION

FIRE ISSUES IN ENGINEERED WOOD COMPOSITES FOR NAVAL WATERFRONT FACILITIES 1

Owens Corning PinkWrap Housewrap, the brand trusted to protect your home from moisture and the elements.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: RHINO LININGS CORPORATION

INTERIOR FINISHES CHAPTER 8

Application Specification:

Trusted DIVISION: 07 SYSTEM. Conformity! ICC-ES Evaluation. not specifically. Copyright 2014

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CHEMICAL BROTHERS INTERNATIONAL, LLC

THERMAL BARRIERS AND IGNITION BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY

ESR-1655 Reissued April 2014 This report is subject to renewal April 1, 2016.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

INTERIOR FINISHES CHAPTER 8

Comparison of the life safety elements of the 1997 UBC and the IBC 2000.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) LLC

EVALUATION SUBJECT: UPONOR/WIRSBO hepex TUBING, UPONOR AQUAPEX TUBING AND FITTINGS

ESR-2072 Reissued September 1, 2013 This report is subject to renewal September 1, 2015.

Smoke and Fiberglass Reinforced Plastic Components

SECTION and/or Resilient Sheet Flooring and/or Resilient Tile Flooring

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER:

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

SECTION Structured Polycarbonate Panel Assemblies. Series 3500 BPC System with 40mm Tongue and Groove

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE Specification for Underground Enclosure Integrity

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

SECTION PIPING INSULATION

Understanding new Acceptance Criteria of Alternative Assemblies Thermal and Ignition Barriers over SPF

SECTION STAY-IN-PLACE INSULATED CONCRETE FORMING SYSTEM

(Specifier Note: Aristech Surfaces LLC is the manufacturer of the Avonite brand

Chapter 2: Foundation

ROXUL Roof and Deck Insulation Section Master Guide Specification Page 1 April 2016

Material Safety Data Sheet

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

A. Source Limitations: Obtain each type of building insulation through one source.

Fire Inspection and Code Enforcement, 7 th Edition. Chapter 6 Building Construction: Components Inspector II

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: THE SPRAY MARKET, INC.

Originally Issued: 05/03/2013 Revised: 06/06/2016 Valid Through: 05/31/2017

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

CHAPTER 26 PLASTIC SECTION 2601 SECTION 2603 GENERAL FOAM PLASTIC INSULATION

B. Samples for Initial Selection: For each type of impact-resistant wall protection unit indicated.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

Reflective Insulation Specification & Application Guide for Post Frame and Metal Building Construction

CELCORE CELLULAR INSULATING CONCRETE SPECIFICATION FOR RETROFIT PLACEMENT OVER EXISTING ROOF MEMBRANES

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: BASF CORPORATION (RIGID PU SYSTEMS)

Code Review for Theaters and Props

Heat Release Rate of Wood-Plastic Composites

Page 1 of 5

3M Fire Barrier Moldable Putty Pads MPP+ Product Data Sheet

Trusted ICC ES DIVISION: ATLANTA, CGF PRO, ENERGYS. Look. Conformity! Evaluation. ICC-ES Evaluation

NEW THE FLEXIBLE INSULATION WITH ANTIMICROBIAL PROTECTION

ESR-1826 Reissued February 1, 2013 This report is subject to renewal February 1, 2015.

Quality Inspection 8618 London Heights San Antonio, TX Phone: (210)

NRCC Guarded Hot Box Testing (ASTM C ) for Energy Efficiency of a Total Roof Assembly

EcoTouch Insulation with PureFiber Technology

CHECKLIST Inspecting a Garage

Section BUILDINGS, SHELTERS, ENCLOSURES

AVM System 500. Aussie Membrane 500

FLAME RETARDANT POLYPROPYLENE SHEET

Intumescent Coatings and Spray Polyurethane Foam

PMG-1039 Effective Date: April 1, 2014 This listing is subject to re-examination in one year.

HIGH PILED COMBUSTIBLE STORAGE CITY OF NOVI SUBMITTAL CHECKLIST In Accordance with Chapter 23 of the 2006 International Fire Code

TENTS AND OTHER MEMBRANE STRUCTURES

EVALUATION SUBJECT: WATTS RADIANTPEX, WATTS RADIANTPEX+, WATTS HEATINGPEX, AND RADIANTFLOW

THERMOFIT RNF-100 TUBING Polyolefin, Flexible, Heat-Shrinkable

INSTALLATION STANDARD FOR ABS BUILDING DRAIN, WASTE, AND VENT PIPE AND FITTINGS IAPMO IS

INSULATION OWENS CORNING INSULATION PRODUCTS IN THIS SECTION:

Ammonia. Product performance for insulation of ammonia piping

Radon Vent Pipe System. Labeling Performance Indicators

Ecore Athletic Elevate BOUNCE 2 GUIDE SPECIFICATIONS Ecore

ACFoam-II HCFC Free "Green" Polyiso Specification

Transcription:

FIRE PERFORMANCE Differences Between Elastomeric and Polyethylene/Polyolefin Insulations Why a 5/50 rating alone does not assure fire safety FM APPROVED

FIRE PERFORMANCE: A 5/50 RATING DOES NOT ASSURE FIRE SAFETY. The Meaning of a 5/50 Rating for Pipe Insulation. For mechanical insulation, a common fire performance specification is 5/50. This reflects a flame spread rating of 5 or less and a smoke developed rating of 50 or less, according to the ASTM E 84 test which is specified by all building codes for the testing of materials to be used in building construction. The numbers are indexes, established to allow the comparison of one material to another. However, the numbers alone may not tell the whole story. In the case of polyethylene/polyolefin insulations, the flame-spread index gives no indication of the effects of melting and dripping of the material during the combustion process. Because they change form, polyethylene/polyolefin materials may burn quite differently from other flexible insulations in their end-use applications. Long an accepted test method for pipe insulation fire performance, ASTM E 84 and the resulting indexes alone may not assure fire safety in some applications.. What Is Polyethylene/Polyolefin Insulation? Polyolefin materials are polymers that are similar in character to high molecular weight wax. Polyethylenes are a type of polyolefin, comprising a specific chain of carbon-based monomers. As closed-cell materials, polyethylene/polyolefins are used as insulation because of their low water vapor transmission characteristic.. Aren t All Flexible Insulations the Same? Two distinct types of flexible insulation are available in the market today. These are: a) Elastomeric rubber-based, closed-cell products such as AP Armaflex b) Polyethylene/Polyolefin thermoplastic closed-cell products such as Tubolit Contrasting the two types of flexible insulations are significant differences in fire performance. These differences are not reflected in the 5/50 rating commonly required for mechanical system insulation, but they can be readily identified through simulated end-use testing. The ASTM E 84 Tunnel Test Compared with Simulated End-Use Tests These alternative tests are considered to be more predictive of real fire performance 4. Where Is Fire Performance a Concern? In commercial construction, insulation fire performance is of concern to code officials and others in areas where the insulation may contribute to a fire and may pose potential danger to life and property. Examples of these areas include long vertical runs or chases and plenum areas. Because of their fire performance characteristics, polyolefin insulations often are not an appropriate choice. 5. ASTM E 84 Tunnel Test Strengths and Weaknesses in Testing Polyethylene/Polyolefin Pipe Insulation. The ASTM E 84 Tunnel Test is specified by all US building codes to determine the surface burning characteristics of building materials. In the test, the material to be tested is applied to the ceiling of the apparatus. Intense flame is applied to one end of the specimen and the effects are measured for a period of ten minutes (Figure ). Invented in the 90s, the ASTM E 84 test is not always a reliable predictor of end-use performance. Fire testing professionals caution that the test can yield flame-spread indexes of 5 or less for materials that may perform poorly in simulated-use fire tests. They point out that the ASTM E 84 test makes no allowance for materials that melt and drip when exposed to heat or flame. However, melting and dripping may directly influence the performance of a material. In fact, when polyethylene/polyolefin insulations are tested, they may literally fall from the ceiling of the E 84 test in a matter of seconds long before they can be assigned a flame-spread index. Polyethylene/polyolefin materials that have fallen to the floor of the test apparatus burn in molten pools until extinguished. Because it tests all materials in a horizontal orientation, ASTM E 84 does not always yield results that reflect material performance in a vertical orientation. 6. ASTM Warnings Concerning Polyethylene/Polyolefin Insulation Test Results. This test method may not be appropriate for obtaining comparative surface burning behavior of some cellular plastic materials. Source: ASTM E 84-00, Section.4 Testing of materials that melt, drip or delaminate to such a degree that the continuity of the flame front is destroyed results in low flame spread indices that do not relate directly to indices obtained by testing materials that remain in place. Source: ASTM E 84-00, Section.5 Figure. ASTM E 84 Test. Test specimens are applied to the ceiling of the test in a flat configuration. Effects are measured for a period of ten minutes. Induced Draft Removable Top Vision Panel Test Sample Gas Air Figure. Armacell Vertical Pipe Chase Test. A simulated end-use test in which specimens are applied to actual pipes in a vertical chase configuration. Materials that pass the test do not support flames that extend beyond the top of the chase. 004 Armacell, LLC

7. Vertical Pipe Chase Test (TM ). The Vertical Pipe Chase Test is a simulated-use fire test that employs a vertical chase 8 x 4 x 8 high. Developed by Armstrong World Industries, the test simulates one of the most severe conditions that could be found in a building: a fire involving multiple insulated pipes in a confined vertical configuration (Figure ). The test utilizes a metal enclosure, protected internally with millboard and connected to a horizontal chase. Three iron pipes covered with test insulation are positioned within the vertical chase for testing. A four-pound wood crib acts as a flame source and is positioned two inches beneath the short horizontal run of the pipe assembly to engulf the elbows in flames. The flame source is directed to attack the pipe elbows, and the flame is transmitted vertically. The Vertical Pipe Chase Test demonstrates that the fire performance of pipe insulations with the same flame-spread index of 5 or less can differ in a simulated-use test. These differences in performance are not predicted by an ASTM E 84 Tunnel Test. The Vertical Pipe Chase Test is not intended to suggest the elimination of recognized fire-protection features normally found in vertical pipe chases and required by building codes. As with any fire test, the results may differ if the wall thickness and specific formulation of the materials selected are varied. 8. Failure Criteria for Vertical Pipe Chase Test. Pipe insulations that permit flame spread to the top of the chase are considered to have failed the test. The criteria used are: a) full involvement of the material b) transmission of flame over a distance equivalent to a commercial building story 9. Recognized Simulated End-Use Tests for Fire Performance. The Factory Mutual Research Corporation (FMRC) Full-Scale Horizontal Simulated Pipe Chase is a full-scale fire test conducted as a mock-up of a pipe chase containing three NPS pipes covered with a one inch thickness of insulation. If fire does not spread 4 feet in ten minutes, the insulation is considered acceptable (Figure ). The FMRC Flammability Test is a piloted ignition test conducted in normal air flow conditions. A 4 x 4 x /4 sample of insulation is blackened with wood charcoal and then subjected to a radiant heat source. Fire properties such as chemical heat release rate, mass loss rate and optical density of smoke are then measured as a function of time. The UBC (Uniform Building Code) 6- Room Fire Test is a test method consisting of an 8 x room with an eight-foot ceiling. Test samples consist of two 8 x 8 sections of insulation material forming a corner in which a wood crib ignition source is located. If char does not extend to the outer extremities of the sample within a fifteen-minute period, and smoke levels are not considered excessive, the insulation is considered acceptable (Figure 4). 0. FMRC Continuing Supervision of Armaflex Insulations. Each of the FMRC test methods mentioned in item 9. above are used in the continuing supervision of AP Armaflex. FMRC is the testing arm of Factory Mutual, the largest industrial insurance company in the United States. FMRC evaluates products by examinations and inspections to determine if they satisfy the criteria for approval by FMRC. The examinations and inspections are performed by FMRC engineers and technicians according to FMRC requirements or recognized national or international requirements. AP Armaflex is the first elastomeric insulation to be approved through continuing supervision by FMRC. The approval covers key insulation performance properties that AP Armaflex must meet or exceed: Thermal conductivity 0.7 Water vapor permeability 0.08 Fire performance Will not contribute significantly to fire AP Armaflex insulation carries the Factory Mutual seal of approval. FM APPROVED. Long-Term Polyethylene/Polyolefin Performance in Critical Applications. Beyond fire performance, there are other concerns when using polyethylene/polyolefin materials. For example, in refrigeration applications, they can melt or deform from heat generated during the defrost cycle. In chilled water and dual temperature systems, they may pull apart because of thermal expansion and contraction. Polyethylene/polyolefin insulations do not have the elastic properties required for these critical applications.. Appropriate Uses for Polyethylene/Polyolefin Insulation. Polyethylenes/polyolefins are an appropriate choice for some domestic plumbing applications. In such construction, it is assumed that the building materials surrounding the insulation will be a greater contributor to fire and smoke in total than the insulation. Figure. FMRC Full-Scale Horizontal Simulated Pipe Chase Test. This horizontal test subjects a specimen to an intense flame twice the size of the ASTM E 84 tunnel test. If the fire 6 From center of Pipe to Top of Box does not spread the full distance of 4 feet in a ten-minute period, the insulation is accepted. One of Three Insulated Pipes One Foot Square Pan of Heplane FMRC - Full-Scale Horizontal Simulated Pipe Chase 4 5 Figure 4. UBC 6- Room Fire Test used by FMRC. Two adjacent walls are covered with insulation material; a fire is set in a 0-lb. wood crib where the walls join. If char does not extend to the extremities of the sample within a fifteen-minute period, the insulation is accepted. 8 0 8 0 Ignition Source: 0-Pound Wood Crib AP Armaflex Insulation Door 9 6 9 (Door: 6 Wide by 7 0 High) 0 996 U.B.C. Standards 6- Room Test Configuration Room Fire Test

ARMACELL VERTICAL PIPE CHASE TEST How two different 5/50-rated insulations perform in simulated end-use testing. AP/ARMAFLEX ELASTOMERIC (5/50) TUBOLIT POLYETHYLENE (5/50) BOTTOM OF CHASE BOTTOM OF CHASE - 00:00 minutes wood crib positioned beneath insulated pipes: AP/Armaflex: elastomeric insulation applied to three IPS pipes. Tubolit: polyethylene/polyolefin insulation applied to three IPS pipes. TOP OF CHASE - 0:0 minutes full flame exposure: AP/Armaflex: The insulation is charred. Flames reach approximately one foot up the vertical chase. TOP OF CHASE Tubolit: The horizontal section is melting. A pool of liquid polyethylene/polyolefin burns on the floor of the chase. Flames are approximately two feet up vertical chase. - 04:08 minutes flames reach maximum: AP/Armaflex: The horizontal insulation sections are charred, with vertical flames approximately one foot high in the chase. Tubolit: The polyethylene has fully ignited, with flames two feet above the eight-foot chase. Failure of the test has occurred. 4 4-6:00 minutes flames recede: AP/Armaflex: Flames have reached a maximum and are now receding. 4 Tubolit: Test has been stopped to prevent flame spread through test ventilation unit. The high heat release rates of polyethylene/polyolefin insulations can lead to a flashover situation in which all combustible material near the fire would spontaneously ignite. 5 5- :00 minutes test concludes: AP/Armaflex: The insulation is charred approximately two feet up vertical chase. Even with this severe exposure to fire, the pipe insulation remains in place, protecting the pipe. The material is generally intact, and has added only minimal amounts of fuel to the fire. 5 Tubolit: The polyethylene is melted or burned away. Traces of flaming liquid polyethylene/polyolefin remain beneath the bare pipes., 4, 5 CONCLUSIONS. The Vertical Pipe Chase Test demonstrates that pipe insulations with the same 5/50 rating can differ in simulated end-use performance.. The test further illustrates the anticipated fire performance characteristics of elastomeric and polyethylene/polyolefin insulations in a real fire situation.. Finally, the test shows that polyethylene/polyolefin insulations may not be appropriate in commercial construction areas where fire performance is a concern, including vertical chases and plenums. 4

OBSERVATIONS ON FIRE TESTING OF POLYETHYLENE/POLYOLEFIN INSULATIONS J esse Beitel Jesse J. Beitel Senior Scientist Hughes Associates, Inc. Fire Science and Engineering Chair NFPA Technical Committee on Fire Tests Past Subcomittee Chair ASTM E 5., Protection of Openings Member Society of Fire Protection Engineers Member of All US Model Building Code Agencies: BOCA, ICBO, SBCCI Polyethylenes and Polyolefins Tend to fool the ASTM E 84 Tunnel Test There are two things to keep in mind relative to building codes. First, all building codes are minimum standards a base level of performance for building materials. Second, they are primarily concerned with providing an index or value for building code officials to follow. Not all cellular materials perform in the same way in all situations. Specifically, not all pipe insulation, although it may be the same color and have a 5/50 rating, may perform in the same way under similar circumstances. Some materials, such as AP Armaflex insulation, develop a char layer that provides an insulating surface to reduce the contribution to fire. Other materials, such as polyethylene, are thermoplastics that tend to melt and drip and particularly to change form quickly, from a solid when it begins to undergo fire exposure to a combustible pool fire much like a flammable liquid. As such, the material will burn very differently from what it would have if it had retained its original form. ASTM E 84 Is an Accepted Test, But May Not Reflect Performance in Real Fire Conditions For many years, the ASTM E 84 test has been our primary tool for evaluating the flammability of materials and products used inside commercial buildings. As such, the test has performed very well. However, for some types of materials, the values and performance we see in the ASTM E 84 test may not reflect their performance in certain real fire conditions. In real fires, orientation, ignition source and other factors can influence the flammability performance of the materials. The 5/50 rating that polyolefin and polyethylene insulation may attain may not tell the whole story in terms of actual performance. These materials are what we call thermoplastic, which means that when they come in contact with heat, they can potentially melt and drip. In the ASTM E 84 test, if a material melts and drips, it falls out of the exposing flame zone and may not give appropriate results. Because they melt and drip, polyethylenes and polyolefins tend to fool the ASTM E 84 test and can provide misleading results. Armstrong World Industries developed the Vertical Pipe Chase Test after it appeared that, within the cellular plastics industry, some inappropriate tests were specified that gave misleading results. One of these tests was the ASTM E 84 Tunnel Test. When exposed to real fires, these thermal plastic materials were shown to behave much differently from what one would have expected based on fire test results. As a result, the Federal Trade Commission took action to develop realistic end-use tests where cellular materials were concerned, and the Vertical Pipe Chase was our answer to addressing this need. We have tested a number of polyethylene and polyolefin formulations, including Tubolit, and have not found any great difference between the performance of one polyethylene versus another. The ASTM test standard has several caveats to try to provide guidance to people in the application of the test and the interpretation of the results. One caveat states that if the materials do melt and drip or delaminate during the test, then the results may not accurately reflect the material s flammability properties. Specifiers and owners need to be aware of the potential limitations that exist with the ASTM E 84 test, because it is still the primary test used for construction materials, whether the materials are typically used in horizontal or vertical orientations. There are several large scale tests that are used to evaluate the performance of pipe insulations especially in their end-use configurations and with more realistic ignition scenarios. One of these is Armstrong s Vertical Pipe Chase Test, and another is the Factory Mutual Large Scale Horizontal Pipe Chase Test. If specifiers or owners feel the material or its orientation may not be appropriately tested under ATSTM E 84, they should ask for additional information from the manufacturer in terms of other types of tests that have been performed to provide a more real life configuration and a more real life evaluation of that product or material. Thomas W. Fritz Manager, Product Fire Performance Armstrong World Industries, Inc. Subcomittee Chair ASTM E 5.5, Furnishings and Contents Assigned Expert ISO TC 9, Subcomittee, Reaction to Fire Member NFPA Committee on Fire Tests Member of All US Model Building Code Agencies: BOCA, ICBO, SBCCI To m Fritz 5

These and other materials on mechanical system insulation are available from the Armacell Technical Library. For more information, call 800 866-568. Or visit our website, at http://www.armacell.com. TECHNICAL INFO-SERVICE concise technical bulletins on insulation system performance. No. 005 No. 006 No. 007 No. 008 No. 009 No. 00 No. 0 No. 0 Thermal Conductivity of Polyethylene/Polyolefin Pipe Insulation. Water Vapor Permeability and Polyethylene/Polyolefin Pipe Insulation. Direct Burial of Polyethylene/Polyolefin Pipe Insulation. Fire and Smoke Properties of Polyethylene/Polyolefin Foams. What Is the MIL Spec MIL-P-580J? Temperature Limits of Polyethylene/Polyolefin Foams. Weathering of Polyethylene/Polyolefin Foam Insulation. Know the Facts About Polyethylene/Polyolefin Insulations. ARMACELL LLC 7600 Oakwood Street Extension P. O.Box 08 Mebane, NC 70 TEL. 99 04-846 FAX 99 04-847 E-MAIL info.us@armacell.com INTERNET www.armacell.com Armaflex and Tubolit are registered trademarks of Armacell International. 07 00 04 NA NA 004 Armacell LLC Printed in United States of America