Performance of a Solar LiBr - Water Absorption Refrigerating Systems

Similar documents
Revue des Energies Renouvelables Spécial ICT3-MENA Bou Ismail (2015) Numerical study of a single effect ejector-absorption cooling system

Exergy analysis of a flat plate solar collector

Investigation of Separator Parameters in Kalina Cycle Systems

Improvement of distillation column efficiency by integration with organic Rankine power generation cycle. Introduction

Solar Absorption Aqua-Ammonia Absorption system simulation base on Climate of Malaysia

Conceptual Design of Nuclear CCHP Using Absorption Cycle

K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India

Effect of Distance between Double Glazing on the Performance of a Solar Thermal Collector Control

OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT

THERMODYNAMIC ANALYSIS OF R134A DMAC VAPOR ABSORPTION REFRIGERATION (VAR) SYSTEM

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K.

Low-Grade Waste Heat Recovery for Power Production using an Absorption-Rankine Cycle

and Exergy Analysis of a Typical LiBr/H 2 O VAR

Investigations of N 2 O Transcritical Refrigeration Cycle Using Dedicated Mechanical Subcooling. Sanjeev Kumar 1 and Dr. D.K.

Thermal Analysis of Solar Flat Plate Collector

ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE

Refrigeration Cycle. Definitions , , 11-46, 11-49,

Heat Exchangers. Introduction. Classification of heat Exchangers

Heat Pump Efficiencies simulated in Aspen HYSYS and Aspen Plus

LECTURE-15. Ideal Reverse Brayton Cycle. Figure (6) Schematic of a closed reverse Brayton cycle

ANALYSIS OF ABSORPTION REFRIGERATION SYSTEM WITH AMMONIA-WATER

PERFORMANCE OF SOLAR COLLECTORS UNDER LOW TEMPERATURE CONDITIONS: Measurements and simulations results

NOVEL CYCLES FOR POWER AND REFRIGERATION

Feedwater Heaters (FWH)

EXPERIMENTAL STUDY ON THE REPLACEMENT OF HFC-R134A BY HYDROCARBONS MIXTURE IN AUTOMOTIVE AIR CONDITIONER. Skudai, Johor, Malaysia 81310

Thermodynamic analysis on post combustion CO 2 capture of natural gas fired power plant

Experimental investigation of single-phase and twophase closed thermosyphon solar water heater systems

Design of Experiment for Solar Water Heater Performance Analysis

Pinch Analysis for Power Plant: A Novel Approach for Increase in Efficiency

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS

Estimation of Boil-off-Gas BOG from Refrigerated Vessels in Liquefied Natural Gas Plant

Optimisation and Cost Analysis of a Lithium Bromide Absorption Solar Cooling System

Héctor Rubio Plana Gas Natural, SDG S.A. 18th. June 2009

R442A (RS-50) Features and uses of the R442A (RS-50) Lubricants TECHNICAL DATA SHEET. Barcelona Girona Madrid Zaragoza

Performance Assessment of Large Vapor Absorption System

Grand Composite Curve Module 04 Lecture 12


A Software for Performance Simulation of Solar Water Heating Systems

Low temperature cogeneration using waste heat from research reactor as a source for heat pump

Exergy Analysis of Absorption Power Cycle Depending on Source Temperatures

ENERGY EFFICIENT SYSTEMS Recover & recycle your waste heat

Development of an Innovative 2.5 kw Water- Silica Gel Adsorption Chiller

Lecture No.3. The Ideal Reheat Rankine Cycle

Waste Heat Recovery of IC Engine Using VAR System

Cool Producing Systems Based on Burning and Gasification of Biomass

Modeling and analyzing solar cooling systems in Polysun

Energy and Buildings

Review Questions for the FE Examination

Exergy analysis of transcritical carbon dioxide refrigeration cycle with an expander

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

Exergetic Optimization of Absorption Chiller Single Stage H 2 O-NH 3 by Experiments Design Method

AN EXERGY COST ANALYSIS OF A COGENERATION PLANT

Available online at ScienceDirect. Energy Procedia 49 (2014 ) SolarPACES 2013

A Study on Automobile Air-Conditioning Based on Absorption Refrigeration System Using Exhaust Heat of a Vehicle

Evaluation of efficiency and collector time constant of a solar flat plate collector

Chapter 6 THE SECOND LAW OF THERMODYNAMICS

EVALUATION OF SOLAR SORPTION REFRIGERATION SYSTEM PERFORMANCE IN LATVIA

Investigation of New Low-GWP Refrigerants for Use in Two-Phase Evaporative Cooling of Electronics

ABSTRACT. Christopher Somers, Masters of Science, Dr. Reinhard Radermacher, Mechanical Engineering

DESIGN AND MODELING THE Φ-F

Comparison of Different Gas Turbine Inlet Air Cooling Methods

Comparison of combined heat and power systems using an organic Rankine cycle and a low-temperature heat source

DESIGN ANALYSIS OF A REFRIGERATED WAREHOUSE USING LNG COLD ENERGY

Gas Turbine Inlet Air Cooling System

ELECTROTECHNOLOGIES FOR ENERGY END-USES: APPLICATION OF MVR TO FOOD INDUSTRIES

SOLAR ENGINEERING OF THERMAL PROCESSES

Refrigeration Kylteknik

Experimental analysis of heat-pump integrated with solar energy

CO 2. transcritical refrigeration cycles: potential for exploiting waste heat recovery with variable operating conditions

We will incorporate life cycle strategic partnering to achieve operational efficiency and economically effective programs. Low-Carbon, Low-Cost Energy

A Study on the Integration of a Novel Absorption Chiller into a Microscale Combined Cooling, Heating, and Power (Micro-CCHP) System

IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS

EFFECT OF AMBIENT TEMPERATURE, GAS TURBINE INLET TEMPERATURE AND COMPRESSOR PRESSURE RATIO ON PERFORMANCE OF COMBINED CYCLE POWER PLANT

Multi-Variable Optimisation Of Wet Vapour Organic Rankine Cycles With Twin-Screw Expanders

Hydrogen oxygen steam generator integrating with renewable energy resource for electricity generation

A Simplified Thermal Model for a CO2 Compressor

Electrical/thermal performance of hybrid PV/T system in Sharjah, UAE

DUBAL Energy Optimization Absorption Chiller Pilot Project

CHAPTER 3 PERFORMANCE CRITERIA FOR CHP

Performance evaluation of a solar ejector-vapour compression cycle for cooling application

ScienceDirect. Compact hot water storage systems combining copper tube with high conductivity graphite and phase change materials

Researcher, 1(2), 2009, Energy Integration Of Crude Distillation Unit Using Pinch Analysis

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 03 Issue: 08 Aug p-issn:

Thermodynamic simulation of a solar absorption refrigeration cycle in transient mode using a concentrator as heat source

A Design of the Organic Rankine Cycle for the Low Temperature Waste Heat

Thermodynamic Modeling of Binary Cycles Looking for Best Case Scenarios

An Absorption Chiller in a Micro BCHP Application: Model based Design and Performance Analysis

Computational Study of Hybrid Water Heater with Evacuated Glass Tube Solar Collector and Rice Husk Combustion

Thermodynamic analysis of a regenerative gas turbine cogeneration plant

PERFORMANCE ANALYSIS OF ORGANIC RANKINE CYCLES USING DIFFERENT WORKING FLUIDS

Solar Tower Receivers. The Power to Change the World

SOLAR DESALINATION TECHNOLOGY BRIEF

Thermodynamic Data. CO (g, 0 C, 1 atm) CO (g,100 C, 1 atm):

Energy and Exergy Analysis of M.P.C Absorption Chiller

CPC EVACUATED TUBE COLLECTOR SYSTEMS FOR PROCESS HEAT UP TO 160 C

Design Optimization of a Non-evacuated CPC Collector

Solutions to TUTORIAL-6 (10/03/2017) Thermodynamics for Aerospace Engineers (AS1300) Second Law of Thermodynamics

MCG THERMODYNAMICS II. 22 April 2008 Page 1 of 7 Prof. W. Hallett

MULTI-OBJECTIVE OPTIMIZATION ON SUPERCRITICAL CO 2 RECOMPRESSION BRAYTON CYCLE USING KRIGING SURROGATE MODEL

LIFE CYCLE COST ANALYSIS OF WASTE HEAT OPERATED ABSORPTION COOLING SYSTEMS FOR BUILDING HVAC APPLICATIONS

Transcription:

Rev. Energ. Ren. : Journées de Thermiue (2001) 73-78 Performance of a Solar LiBr - Water Absorption Refrigerating Systems R. Fathi et S. Ouaskit Laboratoire de Physiue de la Matière Condensée, Faculté des Sciences Ben M'Sik, Casablanca, B.P. 7955, Maroc Abstract - Up to now, the production of the cold is undertaking mainly by the classical way of compression refrigerator cycle. The cycle need an electrical power or mechanics expense for the training of the compressor and the C.F.C for their functioning. Most of the C.F.C impoverish the layer of ozone and participate with a considerable manner, to the increase of the sere effect, then to climatic changes. To contribute to the rational utilisation of energy and the protection of the environment, the research undertaken in the area of the cold has been mainly oriented to a new process adaptation in many fields like the food product conservation and climatisation. This can be obtained by the utilisation of process and sources of not conventional energy like the combined absorption process and solar energy. Besides the environmental aspect, these refrigerator systems are of great interest in the far rural zones which are not served by the electrical network, particularly for food product conservation and the air conditioning of tourist infrastructures and hotels in distant rural zones. Absorption cycles are autonomous systems which can provide a solution to this problem. After modelisation of the absorption refrigerator machine functioning with LiBr-H 2 O, by determining energy and mass statements of each cycle element supposed in the permanent regime. We have determined the COP of the solar single-stage absorption refrigerator as a function of the temperature in the different components of the cycle. Therefore, we have changed the dimension of the cycle by introducing double-line heat exchanger (between generator-condenser and between evaporator-generator). In this study, we present the variation of the COP and the heat-transfer rate with different temperature of the cycle, the obtained values are compared with an improved configuration using a double- line heat exchanger. Keywords: Refrigeration cycle - Absorption refrigeration - Solar energy - COP. 1. INTRODUCTION Solar cooling is a very attractive topic for researches of the solar thermal system field. The reason is that the cooling load usually reaches its peak value when solar energy is mostly available. Most of the research works in this field are carried out employing either a vapour compression cooling cycle or an absorption cooling cycle. The absorption cooling cycle is usually a preferable alternative since it uses thermal energy collected from the sun without the need to convert this energy into mechanical energy as reuired by the vapour compression cycle. In addition the absorption cycle uses thermal energy at a lower temperature than that dictated by the vapour compression cycle. Most of the absorption cooling cycles use either LiBr-H 2 O or NH 3 -H 2 O solutions. In solar applications the LiBr-H 2 O system is superior to the NH 3 -H 2 O system for several reason. Among these reasons are that the LiBr- H 2 O system is simpler in design and operation, and cheaper in cost as compared to the NH 3 -H 2 O system. Also, the LiBr-H 2 O system can operate at a low generator temperature and this range of temperature the system has a COP (Coefficient of Performance) higher than that of the NH 3 -H 2 O system. The LiBr-H 2 O can be operated by the simple flat plate collectors while the NH 3 -H 2 O systems operates with evacuated tubes collectors or solar concentrators. The NH 3 -H 2 O system is restricted in building applications because of the hazards associated with the use NH 3 whereas LiBr-H 2 O systems are safe. A part from the many advantages of the LiBr-H 2 O system mentioned above, the system ails to function if the ambient (heat sink) temperature is increased. At high ambient temperature the system may either suffer from crystallisation at the absorber inlet for the strong solution, or from having water vapour in the suction line of the solution circulating. Considerable research has been carried out to develop an efficient and a economic coupling between solar energy collection and the absorption unit [1]. The performance of absorption cycles has been studied extensively in the recent past using computer simulation [2-4]. The aim of the present study is to perform a direct analysis of the solar LiBr-H 2 O absorption refrigerating cycle. The variation of the different heat and flow of the poor solution with generator temperature is obtained. The COPs (Solar Coefficient of Performance) of the cycle is obtained as a function of the different temperature of the cycle and concentration, more we have studied the effect of using a heat exchanger to recover part of the condenser load to heat LiBr-H 2 O solution going to the generator. 73

74 R. Fathi et al. 2. DESCRIPTION OF THE SOLAR SINGLE-STAGE ABSORPTION CYCLE A schematic representation of the solar single-stage absorption cycle is shown in Fig. 1. The cycle consists of generator, absorber, a condenser, an evaporator, two heat exchanger, circulating pumps and solar collector. The cycle working between two pressure levels : low pressure at the evaporator-absorber and high pressure at condenser-generator. The emitted vapours in the generator are constituted by pure water when in LiBr salt remain in the solution. In the evaporator, heat input of the cold bath to T e is used in the boiling the liuid water. The produced vapours are absorbed in the absorber by the rich concentration X r LiBr solution (kg of LiBr/kg of the solution). This latter becomes poor X p << 1 LiBr solution before reaching the generator. Once in the generator the solution receives the heat which allows to take the water to its boiling point. The solution enriched in LiBr returns to the absorber via a detender. The vapours of refrigerant fluid (H 2 O) to high pressure are sent in the condenser while the liuid leaving it returns to the evaporator. The presentation of the cycle in P-T-X diagram is given in the figure 2, where numbers refer to corresponding state points in the figure 1. The super stars of the numbers in the figure 2 indicate the corresponding euilibrium temperatures for a given pressure and concentration. The continuous lines in the figures 1 and 2 refer to pure H 2 O (i.e. refrigerant). Fig. 1: Schematic of the single-stage absorption cycle Fig. 2: The presentation of the single-stage absorption cycle on the P-T-X diagram 3. SIMULATION OF THE SOLAR SINGLE-STAGE ABSORPTION CYCLE The simulation is based on mass and energy balances for each element of the cycle, supposed in permanent regime. The euilibrium pressure of the vapour phase or liuid P s (kpa) is determined according to the water saturation temperature T s ( C) by using the euation proposed by ASHRAE [5].

J. I. TH. 2001 : Performance of a Solar LiBr-Water Absorption 75 1596.49 104095.5 Ln P = 7.05 (1) (T 2 s + 273.15) (Ts + 273.15) The vapour emitted at the generator level, which circulates through the condenser and the evaporator, is formed by pure water. Then Y (kg of LiBr/kg of the solution H 2 O-LiBr) is eual to zero. Hence, we only need to calculate the title X (kg of LiBr/kg of the liuid solution H 2 O-LiBr) of the H 2 O-LiBr liuid solution circulating between the generator and the absorber. The title is given by the following euation [6]: 3 3 T = T A X + B X (2) s n n n= 0 n= 0 n n where T ( C) is the euilibrium temperature of H 2 O-LiBr solution at a given concentration X and at a pressure P corresponding to T s ( C). The A n and B n coefficient are given as follows: i- For 0 X 0.45; 0 Ts 20 C and 0 T 144 C N A n B n 0 1.00 0.0 1-0.4427 34.108 2 2.64478-193.02 3-2.7419 414.90 ii- For 0.45 0.7; 0 T s 120 C and 5 T 174 C N A n B n 0-2.00755 124.94 1 16.976-771.649 2-31.33362 1522.858 3 19.7668-795.09 The specific enthalpy of the liuid water h l (kj/kg) and the vapour water h v (kj/kg) are determined as follow [7]: h l = 4.199 T (3) h v = 1.73 T + 2501.6 (4) In the case of the solution, the specific enthalpy h (kj/kg) can be calculated according to the solution temperature T ( C) and the mass fraction X of the solution H 2 O-LiBr by [8] : h(t,x) 4 4 4 = Cn Xn + T Dn Xn + T2 En Xn (5) n= 0 n= 0 n= 0 The various calorific powers are as follows : g X = h 9 l h9 + (h10 h9) (6) X X 10 9 ml c ml X = h 12 12 h6 + (h7 h12) (7) X X 2 1 12 7 = h h (8) e ml 5 4 = (h h ) (9) Neglecting the pumping work, the COP (Coefficient of Performance) of the cycle is estimated as follows :

76 R. Fathi et al. COP = e (10) g The efficiency of a collector depends on its temperature. The higher the temperature of a given collector, the greater its heat loss. In designing a solar absorption refrigerator, the collector efficiency (η s ), which is defined as the ratio of the output ( g ) to the incident solar power (I s ), is very important : g η s = (11) i Taking into account the temperatures reached by solar collectors, we have selected the flat plate solar collectors. The efficiency of which is given by Hottel - Whilier [9]: U(Tg Tc ) ηs = F b η0 (12) Is where : 1 1 exp( β) U F b = Fr (1 Fr β), Fr =, β = β mcp with the following characteristics: η 0 = 0.7 is the optical efficiency, U = 2 W/m 2 K is the coefficient of thermal losses, m = 50 kg/hm 2 is the flow rate by surface unit, I s = 800 W/m 2 is the global irradiation of an inclined plane, C p = 4186 J/kgK is the specific heat of working fluid (water), T g is the temperature of heat source and T c is the condenser temperature. The overall COPs of the solar absorption refrigerator is eual to the product of the efficiency of the solar collector (η s ) and the COP of the absorption refrigerator given by euation [10]. COPs = COP (13) ηs 4. THE DOUBLE - LINE HEAT EXCHANGER Heat exchangers, usually known as economisers, are used in the absorption cycle to recover the heat from the strong solution leaving the generator and thus improving the COP of the absorption cycle. The heat carried out by the refrigerant leaving the generator is not recovered by this means. As the generator temperature is increased the amount of heat carried by the refrigerant, and available for recovery, is also increased. It is now suggested to recover this heat in the heat exchanger to preheat the weak solution going to the generator. This is done as shown in the figure 3 where H.E. no.2 is integrated with the condenser to reduce the cost. The extra cost involved in including the refrigerant line to the heat exchanger is compensated by the reduction in the cost of the condenser since its thermal load is reduced. The previous analysis for the cycle with single-line heat exchanger (Fig. 1) is also applied for the cycle with double- line heat exchanger except the following changes : c ml 1a 2 = (h h ) (14) T = (15) 1a T11 Fig. 3: Schematic of the single-stage absorption cycle using double line heat exchanger

J. I. TH. 2001 : Performance of a Solar LiBr-Water Absorption 77 5. RESULTS AND DISCUSSION The temperature T m of the average source has a considerable influence on the threshold of cycle functioning (T g ). The figure 4 illustrates the evolution of the COPs according to T g for different values of T m and for T e = 10 C. One notices that the functioning temperature limits T g, that corresponds to a null COPs, grow when T m increases. Contrarily to the NH 3 -H 2 O absorption refrigerating cycle [10], the COPs depends slightly on the generator temperature T g due to the fact that the refrigerant is pure. One observes a diminution of the COPs according to T m. More this figure represents flows of heat exchanged by the different elements of the absorption cycle for T e = 10 C, T m = 20 C and ml = 1 kg/s. One observes that the refrigerator effect e remains practically constant when the temperature T g increases. In presenting the results, one temperature is changed while the others are held constant. To study the effect of using a double-line heat exchanger on the performance of the solar single-stag cycle, the COPs of both cycle are calculated at various values of the parameters design. The results are plotted in Figs 5 and 6. The use of a double line heat exchanger improves the COP by about 4 % as compared to its value using a single-line heat exchanger, for both cycles. The figure 7 depict the variation of g and c with T g. The at the generator and the condenser are decreased in comparison with its value using heat-transfer a single-line heat exchanger. Fig. 4: Variation of the COP and exchanged heat of the different organs of the solar single-stage absorption cycle with T g (single-line H.E.) Fig. 5: Variation of the COP of the solar single-stage absorption cycle with T g (---- double-line H.E., single-line H.E.) Fig. 6: Variation of the COP of the solar single-stage absorption cycle with T e (---- double-line H.E., single-line H.E.)

78 R. Fathi et al. Fig. 7: Variation of the g and c of the solar single-stage absorption cycle with T g (---- double-line H.E., single-line H.E.) 6. CONCLUSION In this paper, we have developed a method of calculation that is based on simple analytic data which relate the thermodynamic variable of the H 2 O-LiBr fluid couple. Thus, we were able to describe perfectly the thermodynamic mixture state of H 2 O-LiBr fluid, in different steps of the absorption cycle without having to use data or diagram tables. The simulation results have revealed that there is a temperature limit "underhand/to the over" of which the cycle can not working. Moreover, the temperature of the cold source T m has an influence on the threshold of functioning of the cycle. The COP reaches maximal values for T m =20 C or 25 C and T e = 10 C. The use of a double line heat exchanger to recover a part of the condenser load improves the COP of both cycles by about 4 % Actually we develop new approaches based an thermodynamic irreversible model [11]. The most important point in the study is the application non-euilibrium phenomenological theory of mass and heat transfer, with special emphasis few case including physical binary gas liuid interaction in non-ideal mixtures [12, 13]. REFERENCES [1] M.S. Audi, 'Estimation of Solar Energy Flux in Jordan', Dirasat, 6 (2), pp. 121-134, 1979. [2] K. Gommed and G. Grossman, 'Performance Analysis of Staged Absorption Heat Pumps : Water - Lithium Bromide Systems', ASHARE Trans., 96 (1), pp. 1590-1598, 1990. [3] G. Grossman, K. Gommed and D. Gadith, 'A Computer Model for Simulation of Absorption Systems in Flexible and Modular Form', ASHARE Trans., 93 (1), pp. 2389-2428, 1987. [4] M.O Mc Linden and S.A. Klein, 'Steady State Modeling of Absorption Heat Pumps with a Comparison to Experiments', ASHARE Trans., 91 (2B), pp. 1793-1807, 1985. [5] ASHARE, 'Handbook of Fundamentals', 1985. [6] ASHARE, 'Handbook and Product Directory, Tabulation of the Enthalpy-Composition-Temperature Data and Vapour Pressure Chart for Aueous LiBr Solutions', 1977. [7] J.H. Keenan, F.G. Keyes, P.G. Hill and J.G. Moore, 'Steam Tables, Thermodynamic Properties of Water including Vapour, Liuid and Solid Phases', John Wiley, New-York, 1969. [8] D.A. Kouremenos, K.A. Antonopoulos and E. Rogdakis, 'Hour Simulation of Solar H 2 O-LiBr Absorption Heat Transformers in Athens', Solar and Wind Technology, Vol. 7, N 2/3, pp. 111-118, 19, 1990. [9] J. Bougard and A. Pilatte, 'Système de Chauffage Solaire Utilisant des Collecteurs à Eau', Internal Report, Service Thermodynamiue, Faculté Polytechniue de Mons, Belgium, 1983. [10] M. Charia, 'Contribution à l Etude des Cycles Frigorifiues à Absorption Monoétagées et biétagées', Thèse de Doctorat d Etat Es- Sciences Physiues, Fac. des Sciences, Rabat, 1990. [11] N.E. Wijeysundera, 'An Irreversible Thermodynamic Model for Solar-Powered Absorption Cooling Systems', Solar Energy, 68 (1), pp. 69-75, 2000. [12] M.D. Staicovici, 'A Non-Euilibrium Phenomenological Theory of the Mass and Heat Transfer in Physical and Chemical Interactions, Part I - Application to NH 3 :H 2 O and other Working Systems', Int. Journal of Heat and Mass Transfer, 43, pp. 4153-4173, 2000. [13] M.D. Staicovici, 'A Non-Euilibrium Phenomenological Theory of the Mass and Heat Transfer in Physical and Chemical Interactions, Part II - Modelling of the NH 3 :H 2 O Bubble Absorption, Analytical Study of Absorption and Experiments', Int. Journal of Heat and Mass Transfer, 43, pp. 4175-4188, 2000.