SECTION COLD-FORMED METAL FRAMING

Similar documents
Retain "Preinstallation Conference" Paragraph below if Work of this Section is extensive or complex enough to justify a conference.

A. Product Data: For each type of deck, accessory, and product indicated.

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

BEARING METAL STUD FRAMING

UNIFIED FACILITIES GUIDE SPECIFICATIONS

PROJECT LOCATION SECTION COPPER METAL PLATE WALL PANELS

SECTION PLATE CONNECTED WOOD TRUSSES

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

ONE SCHOOL STREET SEPTEMBER 18, 2008 GOWANDA, NEW YORK ARCH PROJECT NO

PIPE AND TUBE RAILINGS

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

Your full service light gauge steel manufacturer

Page 1 of 5

SPECIFICATION GUIDELINE

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

SECTION PIPE AND TUBE RAILINGS PART 1- GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY 1.3 PERFORMANCE REQUIREMENTS

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

SECTION EXTERIOR GRILLS AND SCREENS

Division 11 - Equipment Section 11401

SECTION GYPSUM BOARD

CONTRACT NUMBER: W912DQ-08-C % CORRECTED DESIGN 28 JULY 2008

SECTION GYPSUM BOARD ASSEMBLIES

SECTION METAL BUILDING SYSTEMS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION ACOUSTICAL PANEL CEILINGS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

ST. JOHNS COUNTY ARCH. PROJ. NO SECTION PREFABRICATED ALUMINUM CANOPIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION REROOFING ADJUSTABLE FRAMING SYSTEM


B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work.

PROJECT LOCATION SECTION ZINC ALLOY METAL PLATE WALL PANELS

Structural vs Nonstructural Members. Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures

A. Section Metal Decking. (05300 in MF95) B. Section Cold Formed Metal Framing. (05400 in MF95)

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Product Designation As specified in the AISI standard for cold formed steel framing General provisions A5.2.

SECTION MANUFACTURED ROOF EXPANSION JOINTS

I-STUD Shaftwall System

SECTION ALUMINUM COMPOSITE MATERIAL WALL PANELS. A. Section includes aluminum composite material wall panels.

SECTION ALUMINUM RAILINGS

NOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION. MASTERFORMAT SECTION (Mortarless Concrete Brick Veneer)

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SECTION PRE-ENGINEERED ALUMINUM STAIRS AND RAILINGS

Chevy Chase Club June 30, 2008 Bowie Gridley Architects SECTION GYPSUM BOARD SHAFT WALL ASSEMBLIES

A. Access doors and frames are part of an access door and frame allowance.

1. Interior gypsum wallboard. 2. Exterior gypsum board panels for ceilings and soffits. 3. Tile backing panels.

Project Address: Name of Person Completing Form:

SECTION TURBINE VENTILATORS

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

EDGEWATER, FLORIDA JUNE 14, 2010

SECTION COMPOSITE METAL WALL PANEL SYSTEM (Accu-Trac Low Profile DS)

SECTION EXPANSION CONTROL

Prospective Construction Systems for Mass Housing

Houston Community College 3200 Main Parking Garage November 15, 2010 Houston Community College

SECTION MASONRY ACCESSORIES

SECTION SOUND ISOLATION

SECTION GYPSUM WALLBOARD SYSTEMS. A. Gypsum board at new wall partitions or where indicated on drawings. B. ASTM C442 - Gypsum Backing Board

COOK COUNTY ILLINOIS CONTRACT FOR WORK DOCUMENT NO Countywide Warehouse and Records Storage Center Hawthorne Project TKB No.

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

LAGUARDIA COMMUNITY COLLEGE - CUNY August 3, 2009

GUIDE SPECIFICATIONS For STRUCTURAL PRECAST HOLLOW CORE SLABS SECTION 03410

For Best Non-Structural Steel Stud Specifications, Stay Apprised of Industry Standard Requirements

SECTION COPPER WALL PANELS. ***This section has been updated to IBC. Verify for specific project conditions.***

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE

SECTION STRUCTURAL PRECAST HOLLOW CORE SLABS

Table of Contents. List of Drawings

Central Dartmouth Section Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Dartmouth, NS

Specifiers: Click on the icon in the WORD toolbar to reveal detailed instructions

Corium Brick Rainscreen System Specifications

The System Slotted Deflection Track (pat# 5,913,788)

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

A. This Section includes automatic entrance door systems operating as follows: 1. Swinging operation.

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Union County Vocational - Technical Schools Scotch Plains, New Jersey

POST FRAME BUILDING STANDARDS

JC Code & Construction Consultants, Inc. Advanced Training: The FBC & ASTM C 1063

A. This Section includes acoustical panel ceilings installed with exposed suspension systems.

DIVISION: FINISHES SECTION: GYPSUM BOARD ACCESSORIES REPORT HOLDER: CONLAB, INC. dba PREST ON CO.

A. Source Limitations: Obtain each type of building insulation through one source.

SECTION SECTIONAL OVERHEAD DOORS

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION GYPSUM WALLBOARD. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

SECTION ALUMINUM WINDOWS

DBI-SALA Uni 8 Overhead Horizontal Lifeline Cable System SECTION HORIZONTAL FALL PROTECTION - OVERHEAD CABLE

CURTAINWALL DEFLECTION SOLUTIONS

1. Cast-in-place concrete is specified in Section

Specifications for FL-100 Soffit Panel

GYPSUM BOARD SECTION GYPSUM BOARD PART 1 - GENERAL

A. Coordinate concrete unit masonry (also termed CMU and block ) work with work before and after, especially:

MASTERSPEC - SHORT FORM. B. See Division 5 Section "Metal Stairs" for steel tube railings associated with metal stairs.

***************************************************************************************************************

SECTION GLASS BALUSTRADE RAILING SYSTEMS

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS

LUX Specifications. Section S - Preformed Steel Siding

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)

Administrative Changes

Transcription:

SECTION 05400 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work of this Section shall include all materials and installation necessary to provide all cold formed metal framing. B. This Section includes: (sheetmetal) as shown and detailed: (**CONSULTANT TO SELECT APPLICABLE ITEMS FROM LIST**) 1. Exterior load-bearing wall framing 2. Interior load-bearing wall framing 3. Exterior non-load-bearing curtain-wall framing 4. Floor joist framing 5. Roof trusses 6. Roof rafter framing 7. Ceiling joist framing As shown and detailed on the Drawings and specified herein. C. Related Sections include the following: 1.02 DEFINITIONS 1. Division 5 (**Consultant to Specify**)for masonry shelf angles and connections. 2. Division 6 Section "Rough Carpentry" for subflooring, wall sheathing, or roof sheathing using wood-based structural-use panels, particleboard, fibrous-felted board, and foam-plastic sheathing. 3. Division 9 (**Consultant to Specify**) for interior non-load-bearing metal-stud framing and ceiling-suspension assemblies. 4. Division 9 (**Consultant to Specify**) for interior non-load-bearing, metal-studframed, shaft-wall assemblies. A. Minimum Uncoated Steel Thickness: Minimum uncoated thickness of cold-formed framing delivered to the Project site shall be not less than 95% of the thickness used in the cold-formed framing design. Lesser thicknesses shall be permitted at bends due to cold forming. B. Producer: Entity that produces steel sheet coil fabricated into cold-formed members. 05400-1

1.03 SUBMITTALS A. Product Data: For each type of cold-formed metal framing product and accessory indicated. B. Shop Drawings: Show layout, spacings, sizes, thicknesses, and types of cold-formed metal framing; fabrication; and fastening and anchorage details, including mechanical fasteners. Show reinforcing channels, opening framing, supplemental framing, strapping, bracing, bridging, splices, accessories, connection details, and attachment to adjoining Work. C. Mill certificates signed by steel sheet producer [or test reports from a qualified independent testing agency] indicating steel sheet complies with requirements. D. Welding Certificates: Copies of certificates for welding procedures and personnel. E. Product Test/Evaluation Reports: From a qualified testing agency, such as the International Code Council (ICC), indicating that each of the following complies with requirements, based on comprehensive testing of current products in accordance with the current building code: 1. Expansion anchors. 2. Power-actuated anchors. 3. Mechanical fasteners. 4. Vertical deflection clips. 1.04 QUALITY ASSURANCE 5. Miscellaneous structural clips and accessories. A. Mill certificates signed by steel sheet producer [or test reports from a qualified independent testing agency] indicating steel sheet complies with requirements, including uncoated steel thickness, yield strength, tensile strength, total elongation, chemical requirements, [ductility,] and galvanized-coating thickness. B. Testing Agency Qualifications: An independent testing agency, acceptable to authorities having jurisdiction, qualified according to ASTM E 329 to conduct the testing indicated, as documented according to ASTM E 548. C. Welding: Qualify procedures and personnel according to AWS D1.1, "Structural Welding Code Steel," and AWS D1.3, "Structural Welding Code Sheet Steel." D. Fire-Test-Response Characteristics: Where metal framing is part of a fire-resistancerated assembly, provide framing identical to that of assemblies tested for fire resistance per ASTM E 119 by a testing and inspecting agency acceptable to authorities having jurisdiction. 1. Fire-Resistance Ratings: Indicated by GA File Numbers in GA-600, "Fire Resistance Design Manual," or by design designations from UL's "Fire Resistance Directory" or from the listings of another testing and inspecting agency. 05400-2

E. AISI Specifications: Comply with AISI's "Specification for the Design of Cold-Formed Steel Structural Members" [or "Load and Resistance Factor Design Specification for Cold-Formed Steel Structural Members" and the following] for calculating structural characteristics of cold-formed metal framing. 1. CCFSS Technical Bulletin: "AISI Specification Provisions for Screw Connections." F. VOC compliance certificate signed by manufacturers certifying compliance of their products with regulations of authorities having jurisdiction over volatile organic compounds (VOCs). 1.05 DELIVERY, STORAGE, AND HANDLING A. Protect cold-formed metal framing from corrosion, deformation, and other damage during delivery, storage, and handling. B. Store cold-formed metal framing, protect with a waterproof covering, and ventilate to avoid condensation. PART II - PRODUCTS 2.01 MANUFACTURERS A. Manufacturers shall be certified Steel Stud Manufacturers Association (SSMA) members. 2.02 MATERIALS A. Steel Sheet: ASTM A 653/A 653M, structural steel, zinc coated, of grade and coating as follows: 1. Grade: [33 (230]. 2. Coating: [G60 (Z180)]. 3. Grade: [33 (230) or C, Type 1 or 2]. 2.03 ANCHORS, CLIPS, AND FASTENERS A. Steel Shapes and Clips: ASTM A 36/A 36M, zinc coated by hot-dip process according to ASTM A 123. B. Anchor Bolts: ASTM F 1554, Grade [36] [55], threaded carbon-steel [hex-headed] [headless, hooked] [headless, with encased end threaded,] bolts and carbon-steel nuts; and flat, hardened-steel washers; zinc coated by [hot-dip process according to ASTM A 153/A 153M, Class C] [mechanically deposition according to ASTM B 695, Class 50]. C. Expansion Anchors: Hilti KB-TZ, Simpson Strong-Bolt, or equal with current ICC ES report. D. Power-Actuated Anchors: Fastener system of type suitable for application indicated with current ICC ES report. 05400-3

E. Mechanical Fasteners: Corrosion-resistant-coated, self-drilling, self-threading steel drill screws. 1. Head Type: Low-profile head beneath sheathing, manufacturer's standard elsewhere. F. Welding Electrodes: Comply with AWS standards. 2.04 MISCELLANEOUS MATERIALS A. Galvanizing Repair Paint: SSPC-Paint 20. B. Nonmetallic, Nonshrink Grout: Premixed, nonmetallic, noncorrosive, nonstaining grout containing selected silica sands, portland cement, shrinkage-compensating agents, and plasticizing and water-reducing agents, complying with ASTM C 1107, with fluid consistency and 30-minute working time. 2.05 GYPSUM SHEATHING A. Sheathing: Comply with requirements in Division 9 Section (**Consultant to Specify**) 2.06 FABRICATION A. Fabricate cold-formed metal framing and accessories plumb, square, and true to line, and with connections securely fastened, according to manufacturer's written recommendations and requirements in this Section. 1. Fabricate framing assemblies using jigs or templates. 2. Cut framing members by sawing or shearing; do not torch cut. 3. Fasten cold-formed metal framing members by welding or screw fastening, as standard with fabricator. Wire tying of framing members is not permitted. a. Comply with AWS D1.3 requirements and procedures for welding, appearance and quality of welds, and methods used in correcting welding work. b. Locate mechanical fasteners and install according to Shop Drawings, with screw penetrating joined members by not less than three exposed screw threads. 4. Fasten other materials to cold-formed metal framing by welding, bolting, or screw fastening, according to Shop Drawings. B. Reinforce, stiffen, and brace framing assemblies to withstand handling, delivery, and erection stresses. Lift fabricated assemblies to prevent damage or permanent distortion. C. Fabrication Tolerances: Fabricate assemblies level, plumb, and true to line to a maximum allowable tolerance variation of ⅛ in 10 (1:960) and as follows: 1. Spacing: Space individual framing members no more than plus or minus ⅛ (3 mm) from plan location. Cumulative error shall not exceed minimum fastening requirements of sheathing or other finishing materials. 05400-4

PART III - EXECUTION 3.01 EXAMINATION PROJECT NO. ####### 2. Squareness: Fabricate each cold-formed metal framing assembly to a maximum out-of-square tolerance of ⅛ (3 mm). A. Examine supporting substrates and abutting structural framing for compliance with requirements for installation tolerances and other conditions affecting performance. Proceed with installation only after unsatisfactory conditions have been corrected. 3.02 PREPARATION A. Before sprayed fire-resistive materials are applied, attach continuous angles, supplementary framing, or tracks to structural members indicated to receive sprayed fireresistive materials. B. After applying sprayed fire-resistive materials, remove only as much of these materials as needed to complete installation of cold-formed framing without reducing thickness of fireresistive materials below that are required to obtain fire-resistance rating indicated. Protect remaining fire-resistive materials from damage. 3.03 INSTALLATION, GENERAL A. Cold-formed metal framing may be shop or field fabricated for installation, or it may be field assembled. B. Install cold-formed metal framing according to ASTM C 1007, unless more stringent requirements are indicated. C. Install cold-formed metal framing and accessories plumb, square, and true to line, and with connections securely fastened, according to manufacturer's written recommendations and requirements in this Section. 1. Cut framing members by sawing or shearing; do not torch cut. 2. Fasten cold-formed metal framing members by welding or screw fastening, as standard with fabricator. Wire tying of framing members is not permitted. a. Comply with AWS D1.3 requirements and procedures for welding, appearance and quality of welds, and methods used in correcting welding work. b. Locate mechanical fasteners and install according to Shop Drawings, with screw penetrating joined members by not less than three exposed screw threads. D. Install framing members in one-piece lengths, unless splice connections are indicated for track or tension members. E. Install temporary bracing and supports to secure framing and support loads comparable in intensity to those for which structure was designed. Maintain braces and supports in place, undisturbed, until entire integrated supporting structure has been completed and permanent connections to framing are secured. 05400-5

F. Do not bridge building expansion and control joints with cold-formed metal framing. Independently frame both sides of joints. G. Install insulation in built-up exterior framing members, such as headers, sills, boxed joists, and multiple studs at openings that are inaccessible on completion of framing work. H. Fasten hole reinforcing plate over web penetrations that exceed size of manufacturer's standard punched openings. I. Erection Tolerances: Install cold-formed metal framing level, plumb, and true to line to a maximum allowable tolerance variation of ⅛ in 10 (1:960) and as follows: 1. Space individual framing members no more than plus or minus ⅛ (3 mm) from plan location. Cumulative error shall not exceed minimum fastening requirements of sheathing or other finishing materials. 3.04 NON-LOAD-BEARING CURTAIN-WALL INSTALLATION A. Install continuous tracks sized to match studs. Align tracks accurately and securely anchor to supporting structure as indicated. B. Fasten both flanges of studs to top and bottom track, unless otherwise indicated. Space studs as follows: 1. Stud Spacing: As indicated. C. Set studs plumb, except as needed for diagonal bracing or required for nonplumb walls or warped surfaces and similar requirements. D. Isolate non-load-bearing steel framing from building structure to prevent transfer of vertical loads while providing lateral support. E. Install horizontal bridging in curtain-wall studs, spaced in rows indicated on Shop Drawings but not more than 54 (1370 mm) apart. Fasten at each stud intersection. F. Install miscellaneous framing and connections, including stud kickers, web stiffeners, clip angles, continuous angles, anchors, fasteners, and stud girts, to provide a complete and stable curtain-wall-framing system. 3.05 JOIST INSTALLATION A. Install perimeter joist track sized to match joists. Align and securely anchor or fasten track to supporting structure at corners, ends, and spacings indicated on Shop Drawings. B. Install joists bearing on supporting frame, level, straight, and plumb; adjust to final position, brace, and reinforce. Fasten joists to both flanges of joist track. 1. Install joists over supporting frame with a minimum end bearing of 1-½ (38 mm). 2. Reinforce ends and bearing points of joists with web stiffeners, end clips, joist hangers, steel clip angles, or steel-stud sections as indicated on Shop Drawings. 05400-6

C. Space joists not more than 2 (51 mm) from abutting walls, and as follows: 1. Joist Spacing: As indicated. PROJECT NO. ####### D. Frame openings with built-up joist headers consisting of joist and joist track, nesting joists, or another combination of connected joists if indicated. E. Install joist reinforcement at interior supports with single, short length of joist section located directly over interior support, with lapped joists of equal length to joist reinforcement, or as indicated. 1. Install web stiffeners to transfer axial loads of walls above. F. Install bridging at each end of joists and at intervals indicated. G. Secure joists to load-bearing interior walls to prevent lateral movement of bottom flange. H. Install miscellaneous joist framing and connections, including web stiffeners, closure pieces, clip angles, continuous angles, hold-down angles, anchors, and fasteners, to provide a complete and stable joist-framing assembly. 3.06 FIELD QUALITY CONTROL A. Testing: University shall engage a qualified independent testing agency to perform field quality-control testing. B. Field and shop welds shall be subject to inspection and testing. C. Testing agency shall report test results promptly and in writing to Contractor and University's Representative. D. Remove and replace Work that does not comply with specified requirements. E. Additional testing and inspecting, at Contractor's expense, shall be performed to determine compliance of corrected Work with specified requirements. 3.07 REPAIRS AND PROTECTION A. Galvanizing Repairs: Prepare and repair damaged galvanized coatings on fabricated and installed cold-formed metal framing with galvanized repair paint according to ASTM A 780 and manufacturer's written instructions. B. Touchup Painting: Wire brush, clean, and paint scarred areas, welds, and rust spots on fabricated and installed prime-painted, cold-formed metal framing. Paint framing surfaces with same type of shop paint used on adjacent surfaces. C. Protect paper-surfaced gypsum sheathing that will be exposed to weather for more than 30 days by covering exposed exterior surface of sheathing with a securely fastened airinfiltration barrier. Apply covering immediately after sheathing is installed. D. Protect cutouts, corners, and joints in sheathing by filling with a flexible sealant or by applying tape recommended by sheathing manufacturer at time sheathing is applied. 05400-7

E. Provide final protection and maintain conditions, in a manner acceptable to manufacturer and installer, that ensure cold-formed metal framing is without damage or deterioration at time of Substantial Completion. END OF SECTION 05400 05400-8