DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES...

Similar documents
Electric Service Standards

Telecommunication Spaces

A/E Design Deliverable Checklist

Customer Requirements Customer-owned Transformer Vault Room

A/E Design Deliverable Checklist

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

Communications Page 1 of 9

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

For the 2008 Code, the minimum clear distances were revised to reflect an accurate metric conversion (also known as a soft conversion).

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 14 - CONVEYING EQUIPMENT DESIGN STANDARDS SECTION

Element Z General Design Requirements Existing Facilities Information

NASHVILLE ELECTRIC SERVICE NON NETWORK VAULT DESIGN GUIDE

REQUIREMENTS FOR INDOOR INSTALLATION OF PADMOUNTED TRANSFORMERS

B. Accept materials on site in original factory packaging, labeled with manufacturer s identification.

Standard of Practice - Campus Electrical Distribution System

UNDERGROUND SERVICES SECONDARY

FACILITY DESIGN PLAN FOR HARDING HALL RENOVATION AND ADDITION SOUTH DAKOTA STATE UNIVERSITY DATE: March 29, 2017

SECTION SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS REVISED PART 1 GENERAL 1.1 DESCRIPTION:

Revision 1 RAM ELEVATORS. Elevator Electrical Planning Guide. RAM Manufacturing Ltd

THOMAS JEFFERSON UNIVERSITY HOSPITAL STANDARD OPERATING PROCEDURE FOR THE BUILD OUT OF TELECOMMUNICATIONS ROOMS AND ASSOCIATED SPACES

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement

GV 001 Equipment Bases and Enclosures General Information

Power Electronics, Inc. Packaged Equipment Center Standard Construction and Design Features

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

ELVORON LU/LA ELEVATOR


2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

CHARLES COUNTY GOVERNMENT ITB NO WAKEFIELD PUMPING STATION UPGRADE

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study

Introduction. Disclaimer. Table of contents

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT

UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES

Typical Finished Basement Details

Agenda Item No. AGENDA ITEM BRIEFING

Basement Renovation Guide For Residential Dwellings

DESIGN DEVELOPMENT PHASE

Engineering Specifications for the CXI Room of the FEH LUSI Document # ESD SP

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

INSTALLATION INSTRUCTIONS FOR ELECTRICAL CONTRACTORS

MSC Guidelines for Review of Ventilation System Plans

SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM)

TABLE OF CONTENTS. Wire, Cable, and Terminations Guide Specification MV Wire, Cable and Terminations Medium Voltage Switchgear

Underground Service Requirements and Instructions

1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal.

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018)

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

Element D Services Heating, Ventilating, and Air Conditioning

KITCHEN REMODELS CITY OF MISSION VIEJO BUILDING SERVICES DIVISON 200 CIVIC CENTER, MISSION VIEJO, CA (949)

TYPICAL INSTALLATION INSTRUCTIONS

Contact Clark Public Utilities Construction Services department at (360) to initiate a request for service.

ELECTRICAL SAFETY FOLLOW UP INSPECTION REPORT (4th)

2007 Title 24 Accessibility Code Updates and ADA Issues

RESIDENTIAL BUILDING REQUIREMENTS

S E R I E S Series Design & Installation Guide. September 2014

Building & Fire Appeals Board

Outdoor + Switchgear, Walk-in Equipment Buildings Low & Medium Voltage NEMA 3R

GENERAL PLAN REVIEW REQUIREMENTS

ASHRAE 62.2: What s New in 2016

Natural Gas Service Installation and Meter Clearance Requirements

CONTACT LIST DOORS IN THE PATH OF EGRESS TRAVEL SHALL MEET THE REQUIREMENTS OF ICC / ANSI A117.1 : SECTION MANEUVERING CLEARANCES AT DOORS

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

SECTION GROUNDING AND BONDING

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O.

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

Power Zone Center. Your solution for power distribution and control systems

SECTION MEDIUM VOLTAGE TRANSFORMERS

Gerber M Series Site Requirements

SECTION HVAC INSTRUMENTATION AND CONTROLS INSTALLATION

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

Basic Service. This Section provides information regarding a. Introduction

B. System Design and Performance Requirements

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

FEMA P-1019 Emergency Power Systems for Critical Facilities. ASFPM May 4, 2017 David K Low, PE DK Low & Associates

Emergency, Legally Required, and Optional Standby Power Systems

SPACE TYPE: OUTSIDE PARKING (STRUCTURE)

MATERIAL ALLOWANCES AND UNIT PRICES

3D Home Improvement and Inspection Services, Inc

Radon Vent Pipe System. Labeling Performance Indicators

RESIDENTIAL NEW CONSTRUCTION PLAN REVIEW CHECKLIST

Fairfax County, Virginia

OFFICE OF EDUCATIONAL FACILITIES FLORIDA BUILDING CODE SECTION 423 APPLICATION MATRIX

Refer any questions, clarifications regarding Division 16 to UA Facilities Design & Construction.

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Delivering Reliability. Electrical Vaults. Power & Energy-Underground Structures

TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX

Temporary Wiring Practices And Guidelines For NECA. National Electrical Contractors Association Omaha, Nebraska

YOUR SPLASH PAD RESOURCE

COMMERCIAL CONDUIT RULES AND REGULATIONS

SEWER SYSTEM DESIGN GUIDELINES

MINIMUM SPECIFICATIONS

ELECTRICAL SAFETY INSPECTION REPORT

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Section 2: Underground

Transcription:

DIVISION 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN Contents 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION 13 00 60 LIST OF FIGURES... 6

13 00 60 - MEDIUM VOLTAGE VAULT DESIGN 1. General Requirements 1.1. The term electric vaults or medium voltage vaults shall be defined as any room containing electrical equipment operating above 600 volts. 1.2. Vaults shall be designed to comply with NEC 450, Part III, as a 3 hour rated structure and shall not be constructed with any flammable material. 1.3. 15 kv switching vaults shall not be installed in a building penthouse or any other floor above grade level because of the difficulty of pulling 500 kcmil, 15 kv cable up through a building. Transformer vaults are allowed in the penthouse provided that a 2 hour rated chase is installed vertically between the lower switching vault and the upper transformer vault. 1.4. Once energized, access to electrical vaults shall be by University Electric Utility employees only. If access to a vault by others is needed, a University Electric Utilities employee shall be present. 2. Architectural Requirements 2.1. PROHIBITED: Gypsum board for any application 2.2. PROHIBITED: Construction materials that requires spray-on fireproofing. 2.3. PROHIBITED: Standby generators, transfer switches, small secondary transformers and related panelboards, and fire alarm panels in electric vaults. 2.4. PROHIBITED: Use of pre-stressed or post stressed concrete walls, floors or ceilings. 2.5. Vault walls, floor, and ceiling shall be capable of supporting a 5,000 lb point load. Installation of 15kV cables requires the use of specialized pulling equipment. The equipment must be anchored to the vault wall, floor or ceiling, as field conditions require. The vault structure must be capable of supporting this equipment. Cable pulling can exert as much as 5,000 lbs. of pressure on this equipment. The use of stressed concrete in vaults is prohibited to allow the mounting of cable pulling equipment as required. 2.6. Shall not contain any foreign utilities that pass through the vault. No ductwork that does not directly serve the space shall be permitted in the vault. No electrical conduit may pass through the vault. Any and all equipment entering the vault must directly serve the space.

2.7. Shall have two means of egress on opposite ends of the space. 2.8. Vault doors shall be designed with the following features: 2.8.A. 2.8.B. 2.8.C. 2.8.D. 2.8.E. One of the two doors to the vault must be large enough to move the electrical equipment upright through the door. Removable transoms are acceptable. Alternate means of removing equipment from the vault must be submitted to the University electrical engineering staff for review and approval. Entrance to the vault shall be possible through both doors. Both vault doors must be provided with an ST-1 core lock. Both doors must be self-locking. Once the key is removed, the door stays locked. Include door sweeps and gaskets (seals) in architectural door schedules. 2.9. Walls of the vault shall be painted white. 2.10. The medium voltage vault shall have a minimum 12 clear from the finished floor. No architectural supports or appurtenances may occupy this space. Any exceptions must be approved by University of Minnesota Energy Management Electrical Engineering. 3. Fire Protection Systems 3.1. PROHIBITED: Fire protection sprinkler systems in electric vaults. The A/E shall design electric vault(s) to eliminate the need for a fire protection sprinkler system per the latest edition of NFPA 13 and/or any other applicable codes. 3.2. Vault smoke detection shall be an incipient detection system to avoid entrance of nonelectrical personnel into the vault for periodic smoke detector maintenance. 4. Mechanical Systems 4.1. Design space for a nominal 80 degrees Fahrenheit ambient. 4.2. Chilled water cooling is preferred. 4.3. Design heat load for a peak summer loading. Do NOT design for maximum transformer heat rejection. It is acceptable to allow the vault to get above 80 degrees ambient on the few hot and humid days of the year. 4.4. If the A/E chooses to ventilate the vault with 100 percent outside air instead of chilled water, the design concept must be reviewed and approved by the University electrical and mechanical engineering staff.

4.5. Install an OFF-AUTO switch mounted in the vault to allow personnel to shut the ventilation off during maintenance of the vault. In addition, if the switch is left in the OFF position for more than 4 hours, the ventilation system shall automatically restart. This is intended to allow University electricians to turn off vault ventilation during maintenance activities in which the airflow from fans can be problematic. 4.6. Supplemental heating must be provided, if necessary, for the vault to maintain a minimum ambient of 65 degrees Fahrenheit. 4.7. Maintain slightly positive room pressurization. 4.8. Exhaust only ventilation of high voltage vaults is prohibited. Supply air must be provided to the vault. Simply conditioning recirculated room air will not provide a positively pressurized space. Designers should note that the incipient smoke detection system would not function properly if the vault were at a lower pressure than the room containing the smoke detection equipment. 4.9. PROHIBITED: The vault shall not contain any mechanical equipment that requires access by unauthorized personnel for maintenance (e.g. motor starters, fans, louver operators, etc.). Ductwork and incipient smoke detection piping is acceptable. 4.10. Supply air to a vault must be filtered. 5. Electrical Requirements 5.1. Provide a ground grid under all electric vaults. 5.1.A. Reference 26 05 26 for ground grid requirements. 5.2. Vault lighting shall be switched with illuminated 3-way switches, and shall be on an emergency circuit. 5.3. Provide at least one vault duplex receptacle on an emergency circuit. Receptacle shall be colored red. 5.4. Contract documents shall note that housekeeping pads must be sealed prior to equipment being placed on them.

5.5. A 36 x36 x12 spare fuse cabinet shall be provided and mounted on the wall of the vault. 5.6. A minimum of 72 inches of clearance shall be maintained in front of 15 kv switchgear and in front of the primary termination compartment of the transformers. 5.7. To provide safe operating clearance for hot stick operation, a minimum of 6 feet of clearance is required in front of all electrical equipment doors. In addition, a minimum of 6 feet of clearance is required in front of any removable panels where grounding clusters may be applied or an exposed live part may exist. A minimum of 60 inches shall be maintained in the rear of the 15 kv switchgear for cable pulling purposes. 5.8. Minimum duct bank size into a building shall be 2 x 2 (total of 4 barrels). 5.9. If the 15 kv duct bank enters the vault from below the slab on grade, the vault shall be provided with a sump drain (not sanitary drain) to avoid flooding from the outside manhole. 5.10. If the 15 kv duct bank enters the vault through a wall, a water break must be used (e.g. a pullbox or cable tray) to avoid water from running into the switchgear. END OF SECTION

DIVISION 13 00 60 LIST OF FIGURES 1. Figure 1 Typical Electric Vault Layout Detail 2. Figure 2A Typical Electric Vault Elevation Detail 1 3. Figure 2B Typical Electric Vault Elevation Detail 2 4. Figure 2C Typical Electric Vault Elevation Detail 3 5. Figure 3 Typical Electric Vault Ventilation Details END OF SECTION

DIVISION 13 00 60 - FIGURE 1 TYPICAL ELECTRIC VAULT LAYOUT DETAIL NOTE: THIS DRAWING IS DIAGRAMATIC ONLY. FINAL EQUIPMENT LAYOUT TO BE DETERMINED BE A/E BASED ON AVAILABLE SPACE AND ACTUAL EQUIPMENT SIZES. 42" DOOR WITH PANIC HARDWARE. ALL DOORS SHALL BE PROVIDED WITH AN ST-1 CORE. ALL DOORS SHALL BE PROVIDED WITH SWEEPS AND GASKETS. DEDICATED DUPLEX RECEPTACLE ON GENERATOR BACKUP 36" MIN. $ 3 30" MIN. (36" TYPICAL) MAIN GROUND BUS DEDICATED SIMPLEX RECEPTACLE FOR SCADA RACK (ON GENERATOR BACKUP) PROVIDE 2 - ETHERNET JACKS FOR SCADA RACK SCADA RACK - PROVIDED BY U OF M ELECTRIC UTILITIES (36"H X 36"W X 12"D) PER N.E.C. L.V. SIDE XFMR A H.V. SIDE 6' MIN. (7 FT TYPICAL TO ACCOMMODATE EQUIPMENT REPLACEMENT) OUTGOING TO XFMR A INCOMING FEEDER #1 TIE SWITCH TIE SWITCH 5' MIN. SEAL EQUIPMENT PADS PRIOR TO SETTING EQUIPMENT INCOMING FEEDER #2 STRUCTURAL COLUMN ALL WALLS SHALL BE PAINTED WHITE L.V. SIDE XFMR B H.V. SIDE OUTGOING TO XFMR B SPARE FUSE CABINET ILLUMINATED 3-WAY SWITCH $ 3 30" MIN. (36" TYPICAL) DO NOT MOUNT LIGHTING ABOVE EQUIPMENT OR CABLE TRAY. ALL VAULT LIGHTING CIRCUITS SHALL BE SWITCHED. REVISION 4 09-07-17 'WALL PACK' - BATTERY BACKED UP LIGHT DOUBLE-DOOR WITH REMOVABLE MULLION AND PANIC HARDWARE (FOR EQUIPMENT REPLACEMENT) VAULT MUST BE ACCESSIBLE THROUGH ALL DOORS.

DIVISION 13 00 60 - FIGURE 2A TYPICAL ELECTRIC VAULT ELEVATION DETAIL 1 NOTE: THIS DRAWING IS DIAGRAMATIC ONLY. FINAL EQUIPMENT LAYOUT TO BE DETERMINED BE A/E BASED ON AVAILABLE SPACE AND ACTUAL EQUIPMENT SIZES. Ceiling Lowest Obstruction 12" Min. Cable Tray 'Waterfall' 24" Min. 15kV Air Insulated Switch 15kV Transformer 36" Min. 36" Min. 15kV Cable Connection Point 12' Min. S.A. 480V or 208V Termination 13.8kV Termination 3.5" Housekeeping Pad Finished Floor REVISION 2 6-5-17

NOTE: THIS DRAWING IS DIAGRAMATIC ONLY. FINAL EQUIPMENT LAYOUT TO BE DETERMINED BE A/E BASED ON AVAILABLE SPACE AND ACTUAL EQUIPMENT SIZES. DIVISION 13 00 60 - FIGURE 2B TYPICAL ELECTRIC VAULT ELEVATION DETAIL 2 Ceiling Lowest Obstruction 12" Min. Cable Tray 'Waterfall' Cable Tray 15kV Air Insulated Switch 36" Min. 36" Min. 12' Min. 5" RGS with Ground Bushing 3.5" Concrete Pad 6" Typ. (May be flush with pad) 3.5" Housekeeping Pad Finished Floor 15kV Conductors Entering from Below Finished Floor REVISION 3 6-19-17

DIVISION 13 00 60 - FIGURE 2C TYPICAL ELECTRIC VAULT ELEVATION DETAIL 3 NOTE: THIS DRAWING IS DIAGRAMATIC ONLY. FINAL EQUIPMENT LAYOUT TO BE DETERMINED BE A/E BASED ON AVAILABLE SPACE AND ACTUAL EQUIPMENT SIZES. 15kV Conductors Entering Through Side Wall Lowest Obstruction Ceiling 12" Min. 'Waterfall' 5" PVC With End-Bell 36" Min. 15kV Air Insulated Switch 36" Min. 12' Min. 3.5" Housekeeping Pad Finished Floor REVISION 2 06-05-17

DIVISION 13 00 60- FIGURE 3 TYPICAL ELECTRIC VAULT VENTILATION DETAILS ELECTRIC VAULTS MUST MAINTAIN A SLIGHTLY POSITIVE PRESSURE IN RELATION TO ADJACENT ROOMS/SPACES. ADDITIONAL AIR FROM OUTSIDE THE VAULT (UTILIZE TRANSFER AIR WHERE POSSIBLE, USE OF OUTSIDE AIR IS NOT PREFERRED) USE OF DUCTED RETURN IS PERMITTED BUT NOT REQUIRED. AIR HANDLER OR FAN COIL UNIT FD FD ALL FIRE DAMPERS MUST BE SERVICEABLE FROM OUTSIDE THE VAULT ELECTRIC VAULT GENERAL NOTES: 1. SUPPLY AIR TO VAULT MUST BE FILTERED FILTER SHALL BE LOCATED OUTSIDE OF VAULT 2. SYSTEM CAPACITY SHALL BE BASED ON PREDICTED ' TYPICAL' LOADS - DO NOT SIZE THE COOLING SYSTEM FOR FULL TRANSFORMER RATING OR EXPECTED ABSOLUTE PEAK DEMAND. 3. CHILLED WATER COOLING IS PREFERRED. COOLING A VAULT USING DIRECT OUTSIDE AIR MUST BE APPROVE BY ENERGY MANAGEMENT. T O/A SW THERMOSTAT - VAULT COOLING SET-POINT SHALL BE 80 DEGREES F. PROVIDE AN OFF/AUTO SWITCH TO CONTROL VAULT VENTILATION. WHEN TURNED TO OFF, FANS SHUT DOWN FOR 4 HOURS. AFTER 4 HOURS, SYSTEM AUTOMATICALLY RESUMES NORMAL OPERATION. 4. THE ENGINEER SHALL DESIGN A SYSTEM THAT PREVENTS WATER FROM A BROKEN COIL FROM ENTERING THE VAULT. IF NECESSARY, SPECIFY A WATER-BREAK IN THE DUCT WORK REVISION 2 06-05-17