Maintenance Bypass Breaker Cabinet Series Configuration 2. Installation and Operation Manual

Similar documents
Maintenance Bypass Breaker Cabinet Series Configuration 5. Installation and Operation Manual

Installation and Operation Manual

C60 Standby UPS. 800VA Models. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved.

XSTi Standby UPS. 400VA, 600VA, 800VA Models. User & Installation Manual

Installation Guide Document No Transaction Windows Copyright 2017 Terra Universal Inc. All rights reserved. Revised October 2017

Quick-Start Operating Guide Document No Process Gas Cooler Copyright 2010 Terra Universal Inc. All rights reserved. Revised October 2010

92831 TEL: (714) FAX:

NEUTRAL GROUNDING TRANSFORMERS INSTALLATION AND MAINTENANCE INSTRUCTIONS

Drag Chain Conveyor Installation and Operation Manual

Precision Automatic Vacuum Control (PAVC+)

DRYWALL DOLLY 900 LB. CAPACITY

4 rotary milling table

Owner s Manual & Safety Instructions

MD Power Supply -48Vdc +Bias Tee

Thermoelectric Coolers. All Models INSTRUCTION MANUAL. Rev. G 2016 Pentair Equipment Protection P/N

Thermoelectric Cooler

Symmetra PX kw 208 V. Receiving and Unpacking 08/2015.

HotSwap MBP Maintenance Bypass

Global Water Instrumentation, Inc.

78-RK VARIABLE SPEED HEAVY DUTY VIBRATOR OPERATING MANUAL

Owner s Manual & Safety Instructions

Sageon Site Monitor (SSM) Application Note

Owner s Manual & Safety Instructions

Owner s Manual Shelf Lip Accessory

1675 Locust Street Red Bud, IL Phone: Fax: WARRANTY & TERMS

OPERATION AND INSTALLATION MANUAL

Model # 158-P4. 12/12/2013 Page 1 of 11

Switch-Tek. LV41 & LV42 Series Manual. Sump Float Level Switches

Model # 922-S4. 12/18/2013 Page 1 of 8

Model # 238HS-P8. 4/27/2011 Page 1 of 11

Wash Down Duty Non-Contact Sensor

USER'S GUIDE TO OPERATION

! CAUTION: Read and follow these instructions.

Ecologix Environmental Systems, LLC

Model # 800SM-PS3. 8/3/2016 Page 1 of 8

Sby SR Instruments, Inc.

Field Economy Unit Instruction Manual

Low Voltage Switchgear Construction Checklist (under 500 kva)

GEK B Instructions. Test Cabinet. for Power/Vac Vacuum Circuit Breakers

LOAD RAMP 1000 LB. CAPACITY

Model # 338S-OP. 9/30/2011 Page 1 of 13

Installation, Operation & Maintenance Manual

SELF-REGULATING ROOF HEAT CABLE. Installation Guide WS-SRIM V2.0

Zehnder Carboline Radiant Heating and Cooling Ceiling Panels. Installation, Operation and Maintenance. Cooling Fresh Air Clean Air

WL Switchgear. Instruction and Installation Guide. 11-C Rev. 4. usa.siemens.com/switchgear

Lithonia Lighting Terms and Conditions of Sale

Installation. Basic Rack Power Distribution Units AP9560 AP9561

No part of this manual may be reproduced in any form or by any means, without prior written permission of Darrera.

Model # 358H-PR. 4/8/2011 Page 1 of 12

FTW 175 Wireless Monitoring System Reference Manual Part Number

1675 Locust Street Red Bud, IL Phone: Fax: WARRANTY & TERMS

Carbon Canister Vapor Polisher

INSTALLATION PROCEDURE

Imperial Series. Model IMP-425/525/625/825/1000AP IMD-425/525/625/825/1000AP IMP-1025/1200/1500/2000AP IMD-1025/1200/1500/2000AP

QA-ES Automation Bundle

Model # BARK-358-RDP

TM Wallbox Power Module HWI-WPM-6D VAC, 50/60Hz HWI-WPM-6D VAC, 50/60Hz

Gun Safe 6720F / 6740F. Operation & Installation Guide. FIRE 30minutes /1100ºF RATED THEFT. Manual # M

Aero Tec Models 700 & 750 (115 vac)

DJ Switch 10F V2 ORDERCODE 50365

Rack Power Distribution Unit AP7562, AP7563, AP7564 General Information

LIB System for UPS Installation Manual (136S)

FORM HEADWALL. FORM HEADWALL (floating) (floating) Installation Manual

Unit Substation Transformer Construction Checklist (under 500 kva)

Installation. Smart-UPS VT in Parallel kva 380/400/415 V 208/220 V 200/208 V

Car and Counterweight Frames

1 TON PORTABLE GANTRY CRANE Model LB. PORTABLE GANTRY CRANE Model 94831

POLICY AND PROCEDURE MANUAL

self level laser Model Set up And Operating Instructions

4300 WINDFERN RD #100 HOUSTON TX VOICE (713) FAX (713) web: twrlighting.com IMPORTANT!!!

Gerber M Series Site Requirements

7 PIECE TUBE FLARING KIT

DCL-Series Drum Carriers Instruction Manual

CDM Network Programmer for CCT100x

Daker DK kva. Parallel installation quick start. Part. LE08927AA-09/15-01 GF

END TRUCKS WHEEL SIZES: 9", 12", 15" & 18"

Product Specifications MRI Trench Duct

VISE MOUNTED. Model 97359

Bulk Bag Unloader Installation, Operation and Maintenance Manual

NVD-40 NEAR VERTICAL DRUM LIFTER INSTRUCTION MANUAL

Cutlass Fasteners, Inc. 83 Vermont Ave., Unit 6, Warwick, RI Tel: (401) Fax: (401) cutlass-studwelding.com

Bottom Hinged Flood Barrier Operation & Maintenance Manual

Adjustable Fused Power Supply

STEEL PIPE NIPPLES SEAMLESS Price Sheet PNS-9.16C Effective: September 5, 2016 Cancels Price Sheet PNS-10.15C of October 5, 2015

Stainless steel rolling cabinet

WheelTime Exchange Standard Terms and Conditions. ZF Services North America, LLC (ZFSNA) 9/1/2015 ZF SACHS Heavy Duty Clutch and Shocks

Product Manual (Revision A) Original Instructions. Digital Frequency Control. Installation and Operation Manual

Revision 1 RAM ELEVATORS. Elevator Electrical Planning Guide. RAM Manufacturing Ltd

RHE3 Dock Leveler Installation Manual

BESTMOVE STANDING TRANSFER AID

Model # 358-R48. 7/7/2011 Page 1 of 11

TeraFrame HD Cabinet System Supplemental Installation Guide

MICRO-INVERTER PIGRID W MICRO GRID TIED INVERTER 208, 220, 230, 240VAC

MASTER. Water Conditioning Corp. OPERATION MANUAL. PURO PRO 1200 SCP Series Modular Reverse Osmosis System. January 2012 Version

BESTMOVE STANDING TRANSFER AID

MASTER. Water Conditioning Corp. OPERATION MANUAL. PURO PRO 1200 SC Series Modular Reverse Osmosis System. January 2012 Version

a u t o b a h n price list january 2018

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists

Low-profile, 11U high cabinets hold networking equipment, servers, and phone equipment.

Transcription:

Maintenance Bypass Breaker Cabinet 90881 Series Configuration 2 Installation and Operation Manual

03/13/2012 2 755-00084-C2 R03

Copyright 2012 C&C Power, Inc. All rights reserved. C&C Power, Inc. 395 Mission Street Carol Stream, IL 60188 www.ccpower.com Technical Support: Phone: (630) 617-9022 Email: support@ccpower.com 03/13/2012 3 755-00084-C2 R03

03/13/2012 4 755-00084-C2 R03

TABLE OF CONTENTS 1. Important Information About This Manual... 6 1.1 Manual Symbols... 6 2. Introduction:... 7 3. Safety Precautions... 8 4. Inspection Upon Receipt of Goods... 9 4.1 General... 9 4.2 Visible Damage... 9 4.3 Concealed Damage... 9 4.4 Return of Damaged Goods... 9 5. System Overview... 10 6. System Specifications... 11 6.1 AC Input/Output... 11 6.2 General Specifications... 11 7. Installation... 12 7.1 Preparation... 12 7.1.1 Equipment Inspection... 12 7.1.2 Necessary Equipment and Tools... 12 7.1.3 Installation Safety Precautions... 12 7.2 Installation Steps... 13 7.2.1 Equipment Location... 13 7.2.2 Equipment Mounting... 13 7.2.3 Equipment Connections... 13 8. System Operation: Configuration 2 Interlocks... 14 9. Reference Materials... 15 10. Warranty... 19 03/13/2012 5 755-00084-C2 R03

1. IMPORTANT INFORMATION ABOUT THIS MANUAL SAVE THESE INSTRUCTIONS! This manual contains important information that is needed during the installation and maintenance of the system. 1.1 MANUAL SYMBOLS Warning: Indicates information provided to protect the user against personal injury and/or safety hazards. Caution: Indicates information provided to protect the user against safety hazards and/or possible equipment damage. Important: Indicates information provided as an installation or operating instruction or tip as well as general important installation and system information. 03/13/2012 6 755-00084-C2 R03

2. INTRODUCTION: The C&C Power family would like to thank you for choosing a C&C Power Inc. product for your equipment needs. We know there are a lot of choices in the industry and we appreciate the opportunity to supply each of our customers with the highest quality power products manufactured in the United States today. All of C&C Power s solutions are factory tested to some of the highest standards in the industry. Sales support for future equipment needs or upgrades is provided by our regional sales staff and qualified representatives. All technical questions and service issues should be directed to our main office by dialing the number listed below. This is a 24-hour, 7-day service number. After normal working hours, please leave a detailed message with your phone number on the voice mail system and a qualified service representative will contact you as quickly as possible. C&C Power, Inc. 395 Mission Street Carol Stream, IL 60188 www.ccpower.com Technical Support: Phone: (630) 617-9022 Email: support@ccpower.com 03/13/2012 7 755-00084-C2 R03

3. SAFETY PRECAUTIONS Before installing or maintaining this system, it is extremely important to read this manual and be sure that all system drawings and schematics are reviewed and clearly understood. If there are any questions concerning this manual or any of the installation or maintenance procedures and/or requirements please contact a C&C Power representative before proceeding. When installing this power system, follow all applicable federal, state and local regulations as well as industry guidelines to insure proper system installation. Only qualified electricians should attempt to install or service this equipment. System installation and maintenance should always be performed with heavily insulated tools. Always wear eye protection when installing or maintaining batteries and/or power equipment. Maintenance Bypass Breaker Cabinet systems can be very heavy. Use a minimum of two people when unloading and setting equipment in place. For the safety of others, never leave an open cabinet or panel unattended. To reduce the risk of fire, replace fuses with the same type and rating of fuses supplied with the system. Be sure to fully read and understand this manual and verify that all electrical connections are correct and properly torqued. Use extreme caution when installing and maintaining the system! To avoid personal injury including electrical shock, severe burns and possible death, all jewelry including bracelets, rings and watches must be removed prior to installing or servicing this system. 03/13/2012 8 755-00084-C2 R03

4. INSPECTION UPON RECEIPT OF GOODS 4.1 GENERAL Special precautions and care have been taken to ensure the system arrives safe and undamaged. However, upon receipt, you should inspect the entire shipment, including the crate and any boxes for evidence of damage that may have occurred during transit. 4.2 VISIBLE DAMAGE It is the responsibility of the person receiving the shipment to inventory and fully inspect all materials against the bill of lading or weigh bill IMMEDIATELY while the carrier representative is still present. Insure that all items are accounted for, including number of skids and quantity of boxes. Also note any visible external damage that may have occurred during transit. Make all applicable notations on the delivery receipt before signing and file a damage report with the carrier. 4.3 CONCEALED DAMAGE Within 3 to 30 days of receipt (depending on courier), unpack the system and check for any concealed damage. Check the materials received against the detailed packing list to verify the quantity and the condition as complete and satisfactory. Note any damage to the internal packaging, then request an inspection by the carrier and file a concealed damage claim. If there is a material shortage, contact a C&C Power representative at the main office to file a claim. Please contact your shipping company for all shipping damage. C&C Power is not responsible for any shipping damage. 4.4 RETURN OF DAMAGED GOODS Should equipment be damaged and require return to C&C Power for repair, a representative will provide instructions along with an RMA number to expedite the return. A RMA number must be obtained before returning equipment to C&C Power, Inc. 03/13/2012 9 755-00084-C2 R03

5. SYSTEM OVERVIEW The C&C Power 90881 Series Maintenance Bypass Breaker Cabinet (MBBC) is used in conjunction with a an Uninterruptable Power Supply (UPS) to maintain total continuity of power to connected load circuits when bypass of the UPS equipment is required for performance of regular service and maintenance. The 90881 Series MBBC s are available with current capacities ranging from 250 to 400 Amperes with multiple input voltage options available. The MBBC contains three Cutler Hammer Series C circuit breakers that are protected by a Kirk Key interlock system. 03/13/2012 10 755-00084-C2 R03

6. SYSTEM SPECIFICATIONS 6.1 AC INPUT/OUTPUT Voltage: Multiple options available. (See equipment label for configuration specific information) 208 VAC, 3-Phase, 4-Wire 480 VAC, 3-Phase, 4-Wire System Capacity: 250 to 400 Amperes (See equipment label for configuration specific information) Circuit Breakers: UL Listed, Multiple voltage rating options available, AIC ratings from 35kAIC to 65kAIC. (See equipment label for configuration specific information) AC Input/Output Terminations: Mechanical lugs are used for both terminations. Wire Size and Type: Per NEC and/or all applicable national and local codes. 6.2 GENERAL SPECIFICATIONS Cabinet Size: 30 W x 11 D x 42 H Operating Temperature: 0 C to 40 C (32 F to 104 F) Weight (approximate): 115 lbs. 03/13/2012 11 755-00084-C2 R03

7. INSTALLATION 7.1 PREPARATION 7.1.1 EQUIPMENT INSPECTION Remove the equipment from the packaging material and inspect for any shipping damage that may have been overlooked upon receipt of goods. Verify that the system includes all necessary hardware for installation. 7.1.2 NECESSARY EQUIPMENT AND TOOLS o Heavily insulated assortment of hand tools 7.1.3 INSTALLATION SAFETY PRECAUTIONS Before proceeding with system installation, be sure to review and understand all of the SAFETY PRECAUTIONS in this manual! AC VOLTAGE WARNING! The input/output voltage in this equipment can be up to 480 VAC. Be sure to fully read and understand this manual and verify that all AC connections are correct and properly torqued. Use extreme caution when installing and maintaining the system! 03/13/2012 12 755-00084-C2 R03

7.2 INSTALLATION STEPS Before installing or maintaining this system, it is extremely important to read this manual and be sure that all system drawings and schematics are reviewed and clearly understood. If there are any questions concerning this manual or any of the installation or maintenance procedures and/or requirements please contact a C&C Power representative before proceeding. 7.2.1 EQUIPMENT LOCATION This equipment is intended to be installed in a restricted access location. Prior to installation verify all applicable codes pertaining to the related equipment. Clearance around the equipment should be as suggested by NEC and/or all applicable national and local codes. 7.2.2 EQUIPMENT MOUNTING Place the Maintenance Bypass Breaker Cabinet in an upright position on the floor of the designated installation area with the rear of the cabinet abutting a rigid vertical structure (e.g. a wall). Secure the cabinet to the rigid vertical structure with appropriate anchoring hardware utilizing the four 0.375 inch diameter mounting holes located in the back panel of the cabinet (see drawings in Reference Materials section) to assure maintaining the cabinet in a stable upright position. 7.2.3 EQUIPMENT CONNECTIONS The Product Schematic Drawing for this specific MBBC configuration is included in the Reference Materials Section of this manual. Follow this schematic drawing for cable connections relative to 3-phase main lug input/output and feeds associated with UPS input and output. Cable ingress and egress can be facilitated through knockouts fabricated in either the top or bottom panels of the cabinet. 03/13/2012 13 755-00084-C2 R03

Do not operate the MBB circuit breaker unless the UPS is in BYPASS mode! Failure to follow the operating instructions for this equipment could result in equipment damage, fire, severe injury or death! 8. SYSTEM OPERATION: CONFIGURATION 2 INTERLOCKS The following User Instructions are for a three circuit breaker MBBC configured to be controlled by a 2-Interlock, 1-Key breaker interlock system: NORMAL OPERATION The UPS Input Breaker UIB is Closed/On. The Maintenance Bypass Breaker MBB is Locked Open/Off with the interlock locking bolt in the extended position and Key A1 held captive. The Maintenance Isolation Breaker MIB is Closed/On with the interlock locking bolt in the withdrawn position. TRANSFER TO MAINTENANCE BYPASS 1. Transfer the UPS to the Bypass mode. 2. Turn Key A1 in the interlock on the MBB breaker to unlock. 3. Close/Turn-On the MBB breaker. Key A1 is now free. 4. Open/Turn-Off the MIB breaker. 5. Insert Key A1 into the interlock on the MIB breaker and turn it to lock the MIB breaker in the Open/Off position. Key A1 is now held captive. 6. The UPS is now ready for routine maintenance. 7. If further maintenance requires a total shutdown of the UPS and isolation from the input, the UIB breaker must be Opened/Turned-Off and the battery supply to the UPS must be disconnected. Refer to your UPS manual for proper shutdown procedures. RETURN THE UPS AND BYPASS SWITCH TO NORMAL OPERATION 1. If the UIB breaker was Opened/Turned-Off for maintenance, then follow the UPS manual for proper startup procedures. To restore input power to the UPS, Close/Turn-On the UIB breaker. Make sure the UPS is in Bypass mode before proceeding! 2. Turn Key A1 in the interlock on the MIB breaker to unlock. 3. Close/Turn-On MIB Breaker. Key A1 is now free. 4. Open/Turn-Off MBB Breaker. 5. Insert Key A1 into the interlock on the MBB breaker and turn it to lock the MBB breaker in the Open/Off position. Key A1 is now held captive. 6. Transfer the UPS from bypass mode to normal mode. 03/13/2012 14 755-00084-C2 R03

9. REFERENCE MATERIALS 03/13/2012 15 755-00084-C2 R03

03/13/2012 16 755-00084-C2 R03

03/13/2012 17 755-00084-C2 R03

03/13/2012 18 755-00084-C2 R03

10. WARRANTY LIMITED WARRANTY AND EXCLUSIONS C&C Power, Inc. strives to produce quality products at reasonable prices. If you are not satisfied with our product because of a defect, we will repair or replace the defective part or parts free of charge for a period of one year from the date of purchase. In the event you claim that the product contains a defect, simply notify C&C Power, Inc. of the defect, and we will arrange for repair or replacement. The sole and exclusive remedy against C&C Power, Inc. relating in any way to a product defect shall be the repair or replacement of defective parts as provided for under this LIMITED WARRANTY. No other remedy, including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property, or any other incidental or consequential loss, is available. This LIMITED WARRANTY shall not be deemed to have failed of its essential purpose so long as C&C Power, Inc. is willing and able to repair or replace defective parts in the manner prescribed in this LIMITED WARRANTY. Certain integrated products, which are not manufactured by C&C Power; will be warranted by the applicable manufacturer. These warranties shall be between the manufacturer and the user. Terms and conditions may vary. These integrated products include, but may not be limited to, the following products: Batteries, Inverters and UPS Systems. Any action for breach relating to the sale of a C&C Power, Inc. product must be commenced within one year after the cause of action has accrued. THIS LIMITED WARRANTY IS IN LIEU OF ANY OTHER WARRANTY, EXPRESS OR IMPLIED, AND ALL SUCH WARRANTIES ARE EXCLUDED, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. 03/13/2012 19 755-00084-C2 R03

C&C Power, Inc. 395 Mission Street Carol Stream, IL 60188 Phone: 630.617.9022 www.ccpower.com