SECTION HVAC GRAVITY VENTILATORS

Similar documents
Wall Louvers (10200)

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

MASTERSPEC - SHORT FORM. B. See Division 5 Section "Metal Stairs" for steel tube railings associated with metal stairs.

SECTION ALUMINUM WINDOWS

GUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM

SECTION TURBINE VENTILATORS

PIPE AND TUBE RAILINGS

SECTION EXPANSION CONTROL

A. This Section includes ceiling- and wall-mounted diffusers, registers, grilles and louvers.

A. Access doors and frames are part of an access door and frame allowance.

SECTION ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS PART 1 - GENERAL 1.1 SUMMARY. A. Section Includes:

ST. JOHNS COUNTY ARCH. PROJ. NO SECTION PREFABRICATED ALUMINUM CANOPIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

Aluminum Flush Doors and Frames SPECIFICATIONS. Section [8120] PART 1 GENERAL

SECTION MANUFACTURED ROOF EXPANSION JOINTS

Signature Series 5 Lap SECTION ALUMINUM WINDOWS

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

SECTION ALUMINUM RAILINGS

SECTION PIPE AND TUBE RAILINGS PART 1- GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY 1.3 PERFORMANCE REQUIREMENTS

Specifiers: Click on the icon in the WORD toolbar to reveal detailed instructions

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work.

SECTION GLASS BALUSTRADE RAILING SYSTEMS

A. The extent of extruded aluminum walkway covers is shown on the Drawings and as specified herein.

Walkway Covers and Canopies. Architectural & Engineering Catalog. Version 2.0

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

SECTION IMPACT RESISTANT WALL PROTECTION

Louvers Selection, Design Considerations and Details Written by Matt Trentham, R.L. Craig Company, Inc.

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

Specifications for FL-100 Soffit Panel

Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION


GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM

SECTION EXTERIOR GRILLS AND SCREENS

SECTION ALUMINUM STORM WINDOWS

B. Samples for Initial Selection: For each type of impact-resistant wall protection unit indicated.

SPECIFICATION SECTION PART 1 GENERAL

PROJECT LOCATION SECTION COPPER METAL PLATE WALL PANELS

SECTION METAL BUILDING SYSTEMS

by Rollfab Metal Products

Aluminum-Framed Entrances and Storefronts

CASEMENT PROJECT OUT SERIES 6400 AAMA/WDMA/CSA 101/I.S.2/A Structural Performance: Thermal Break: Main Frame Depth: 3 1/4

SECTION COMPOSITE METAL WALL PANEL SYSTEM (Accu-Trac Low Profile DS)

EME6325D WIND-DRIVEN RAIN RESISTANT STATIONARY LOUVER

SECTION AIR DUCT CLEANING

SECTION PANEL AND POST AND PYLON SIGNAGE. 1. Non-illuminated Panel and Post signs. 2. Internal illumination Pylon (Cabinet and Post) signs.

A. This Section includes automatic entrance door systems operating as follows: 1. Swinging operation.

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

ELM6375DX DRAINABLE ADJUSTABLE LOUVER EXTRUDED ALUMINUM

HORIZONTAL SLIDER SERIES 900 ANSI/AAMA/NWWDA 101/I.S Structural Performance: Thermal Break: C.R.F.: 50. Thermal U Value:.66. Main Frame Depth: 4

HORIZONTAL SLIDER SERIES 910 ANSI/AAMA/NWWDA 101/I.S Structural Performance: Thermal Break: C.R.F.: 50. Thermal U Value:.66. Main Frame Depth: 4

SPECIFICATIONS: Architectural Aluminum Railings

CASEMENT PROJECT OUT SERIES 4400 AAMA/WDMA/CSA 101/I.S.2/A Structural Performance: Thermal Break: Main Frame Depth: 4

Attachment A-Flagpole(s) Specifications

Aluminum Component Pipe Railings

Metal Roof Panels

SECTION ACOUSTICAL PANEL CEILINGS

A. Product Data: For each type of deck, accessory, and product indicated.

Corium Brick Rainscreen System Specifications

Specifiers: Click on the icon in the WORD toolbar to reveal detailed instructions

SECTION PERSONNEL DUTY LOCKERS. 1. FPPL Series Police Personnel Duty Lockers, including the following:

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION WATERTIGHT FLOOD PLANKS. A. ASTM A 36 - Standard Specification for Carbon Structural Steel.

DOUBLE HUNG SERIES 860 AAMA/WDMA/CSA 101/I.S.2/A Structural Performance: Thermal Break: C.R.F. 50. Thermal U Value:.61. Main Frame Depth: 4

SECTION Structured Polycarbonate Panel Assemblies. Series 3500 BPC System with 40mm Tongue and Groove

ALUMINIUM SAND TRAP LOUVER : CONSTRUCTION

SINGLE HUNG SERIES 810 AAMA/WDMA/CSA 101/I.S.2/A Structural Performance: Thermal Break: C.R.F.: 50. Thermal U Value:.61. Main Frame Depth: 4

SECTION PLATE CONNECTED WOOD TRUSSES

SECTION DECORATIVE METAL AND GLASS RAILING

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

BEARING METAL STUD FRAMING

1.2.1 Section Cold-Formed Metal Framing: Metal framing for support of aluminum soffits.

PROJECT LOCATION SECTION ZINC ALLOY METAL PLATE WALL PANELS

SECTION ENTRANCE FLOOR GRILLES STAINLESS STEEL GRATING

HORIZONTAL SLIDER SERIES 600 AAMA/WDMA/CSA 101/I.S.2/A Structural Performance: Thermal Break: C.R.F.: 50. Thermal U Value:.

SECTION A. AAMA/NWWDA Voluntary Specifications for Aluminum, Vinyl (PVC) and Wood Windows and Glass Doors.

PW251 21/2 x7 GUIDE SPECIFICATION. Curtain Wall

SECTION GUTTERS AND DOWNSPOUTS

MODERNFOLD GWS 100SR-G MOVEABLE GLASS WALLS

SP Standard Profile. Flanged to Duct Install Type THERMAL BREAKS OPPOSED ACTION PARALLEL ACTION. T.A. Morrison & Co. Inc.

A. Pre-engineered, pre-finished extruded aluminum Pavilions.

SECTION SLIDING ALUMINUM-FRAMED GLASS DOORS Panda Windows and Doors, Thermally Broken Multi-Slide Door Systems

PROJECT LOCATION SECTION TEXTURED METAL PLATE WALL PANELS

SECTION DIRECTORIES

ACOUSTICAL WALL TREATMENT SECTION 09840

CENTRIA EcoScreen Perforated Screen Wall Panels

WESTECK WINDOWS and DOORS

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

ALL-ALUMINUM DOOR & WINDOW FRAMING

HIR 1 ACOUSTICAL, IMPACT RESISTANT, TACKABLE WALL PANEL SPECIFICATION

A. Section includes extruded aluminum windows with operating sash, operating hardware, and insect screens.

SECTION ALUMINUM HANDRAILS AND RAILINGS

Series - 1

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System

SL150 Guide Specification

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS

T700 SERIES(AW50)-Impact (Formerly 8050 series) SINGLE HUNG 3 1/4 FRAME DEPTH (SIDE LOAD)

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

DBI-SALA Uni 8 Overhead Horizontal Lifeline Cable System SECTION HORIZONTAL FALL PROTECTION - OVERHEAD CABLE

Transcription:

SECTION 23 37 23 HVAC GRAVITY VENTILATORS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the following types of roof-mounting intake and relief ventilators: 1. Louver penthouses. 2. Roof hoods. 3. Goosenecks. B. Related Sections include the following: 1. Division 23 Section "HVAC Power Ventilators" for roof-mounting exhaust fans. 1.3 PERFORMANCE REQUIREMENTS A. All roof top equipment shall bare the Miami Dade Notice of Acceptance Label. B. Each piece of rooftop equipment covered in this section shall bare the Miami Dade Notice of Acceptance (N.O.A.) seal and be listed by Miami-Dade as having passed each of the following tests. The passage of fewer test standards will not be accepted. C. TAS-201: Large and Small Missile Impact Test 1. TAS-202: Uniform Structural Load Test 2. TAS-203: Uniform Cyclic Pressure Test 3. Tests shall be based on a minimum 150 mile per hour wind standard. D. Water Entrainment: Limit water penetration through unit to comply with ASHRAE 62.1-2007. 1.4 SUBMITTALS A. Product Data: For each type of product indicated. For louvers specified to bear AMCA seal, include printed catalog pages showing specified models with appropriate AMCA Certified Ratings Seals. Matrix Proj. No. 13-0170 HVAC Gravity Ventilators 23 37 23-1

B. LEED Submittal: 1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1-2004, Section 5 - "Systems and Equipment." C. Shop Drawings: For intake and relief ventilators. Include plans, elevations, sections, details, and ventilator attachments to curbs and curb attachments to roof structure. D. Coordination Drawings: Roof framing plans and other details, drawn to scale, on which the following items are shown and coordinated with each other, based on input from installers of the items involved: 1. Structural members to which roof curbs and ventilators will be attached. 2. Sizes and locations of roof openings. E. Samples for Verification: For each type of exposed finish required for intake and relief ventilators. F. Welding certificates. 1.5 QUALITY ASSURANCE A. Source Limitations: Obtain ventilators through one source from a single manufacturer where indicated to be of same type, design, or factory-applied color finish. B. Product Options: Drawings indicate size, profiles, and dimensional requirements of intake and relief ventilators and are based on the specific equipment indicated. Refer to Division 01 Section "Product Requirements." 1.6 COORDINATION 1. Do not modify intended aesthetic effects, as judged solely by Architect, except with Architect's approval. If modifications are proposed, submit comprehensive explanatory data to Architect for review. A. Coordinate installation of roof curbs and roof penetrations. These items are specified in Division 07 Section "Roof Accessories." PART 2 PRODUCTS 2.1 MANUFACTURERS A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection: 1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified. 2. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified. Matrix Proj. No. 13-0170 HVAC Gravity Ventilators 23 37 23-2

2.2 MATERIALS A. Aluminum Extrusions: ASTM B 221, Alloy 6063-T5 or T-52. B. Aluminum Sheet: ASTM B 209, Alloy 3003 or 5005 with temper as required for forming or as otherwise recommended by metal producer for required finish. C. Galvanized-Steel Sheet: ASTM A 653/A 653M, G90 zinc coating, mill phosphatized. D. Stainless-Steel Sheet: ASTM A 666, Type 304, with No. 4 finish. E. Fasteners: Same basic metal and alloy as fastened metal or 300 Series stainless steel, unless otherwise indicated. Do not use metals that are incompatible with joined materials. 1. Use types and sizes to suit unit installation conditions. 2. Use hex-head or Phillips pan-head screws for exposed fasteners, unless otherwise indicated. F. Post-Installed Fasteners for Concrete and Masonry: Torque-controlled expansion anchors, made from stainless-steel components, with capability to sustain, without failure, a load equal to 4 times the loads imposed, for concrete, or 6 times the load imposed, for masonry, as determined by testing per ASTM E 488, conducted by a qualified independent testing agency. G. Bituminous Paint: Cold-applied asphalt emulsion complying with ASTM D 1187. 2.3 FABRICATION, GENERAL A. Factory or shop fabricate intake and relief ventilators to minimize field splicing and assembly. Disassemble units to the minimum extent as necessary for shipping and handling. Clearly mark units for reassembly and coordinated installation. B. Fabricate frames, including integral bases, to fit in openings of sizes indicated, with allowances made for fabrication and installation tolerances, adjoining material tolerances, and perimeter sealant joints. C. Fabricate units with closely fitted joints and exposed connections accurately located and secured. D. Fabricate supports, anchorages, and accessories required for complete assembly. E. Perform shop welding by AWS-certified procedures and personnel. 2.4 LOUVER PENTHOUSES A. Manufacturers: 1. Greenheck. 2. Loren Cook Company. 3. Penn Ventilation. Matrix Proj. No. 13-0170 HVAC Gravity Ventilators 23 37 23-3

B. Construction: All-welded assembly with 6-inch-deep louvers, mitered corners, and sheet roof. C. Frame and Blade Material and Nominal Thickness: Extruded aluminum, of thickness required to comply with structural performance requirements, but not less than 0.080 inch for frames and 0.080 inch for blades. D. Frame and Blade Material and Nominal Thickness: Galvanized-steel sheet, of thickness required to comply with structural performance requirements, but not less than 0.052 inch for frames and 0.064 inch for blades. E. Frame and Blade Material and Nominal Thickness: Stainless-steel sheet, of thickness required to comply with structural performance requirements, but not less than 0.062 inch with grain running parallel to length of blades and frame members. 1. AMCA Seal: Mark units with the AMCA Certified Ratings Seal. F. Roof Curbs: Galvanized-steel sheet; with mitered and welded corners; 1-1/2-inch thick, rigid fiberglass insulation adhered to inside walls; and 1-1/2-inch wood nailer. Size as required to fit roof opening and ventilator base. 1. Configuration: Coordinate flashing cant strip and slope of curb with actual roof conditions. Refer to Architectural plans for slope requirements. 2. Overall Height Above the Roof Level: 12 inches minimum. 3. Pitch Mounting: Manufacture curb for roof slope. 4. Metal Liner: Galvanized steel. G. Bird Screening: Galvanized-steel, 1/2-inch-square mesh. H. Galvanized-Steel Sheet Finish: 2.5 ROOF HOODS 1. Surface Preparation: Clean surfaces of dirt, grease, and other contaminants. Clean welds, mechanical connections, and abraded areas and repair galvanizing according to ASTM A 780. Apply a conversion coating suited to the organic coating to be applied over it. A. Manufacturers: 1. Greenheck. 2. Loren Cook Company. 3. Penn Ventilation. B. Factory or shop fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figures 5-6 and 5-7. C. Materials: Aluminum sheet, minimum 0.063-inch thick base and 0.050-inch thick hood; suitably reinforced. Matrix Proj. No. 13-0170 HVAC Gravity Ventilators 23 37 23-4

D. Roof Curbs: Galvanized-steel sheet; with mitered and welded corners; 1-1/2-inch thick, rigid fiberglass insulation adhered to inside walls; and 1-1/2-inch wood nailer. Size as required to fit roof opening and ventilator base. 1. Configuration: Coordinate flashing cant strip and slope of curb with actual roof conditions. Refer to Architectural plans for slope requirements. 2. Overall Height Above the Roof Level: 12 inches minimum. 3. Pitch Mounting: Manufacture curb for roof slope. 4. Metal Liner: Galvanized steel. E. Bird Screening: Galvanized-steel, 1/2-inch-square mesh. F. Galvanized-Steel Sheet Finish: 2.6 GOOSENECKS 1. Surface Preparation: Clean surfaces of dirt, grease, and other contaminants. Clean welds, mechanical connections, and abraded areas and repair galvanizing according to ASTM A 780. Apply a conversion coating suited to the organic coating to be applied over it. A. Factory or shop fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 5-5; with a minimum of 0.052-inch-thick, galvanized-steel sheet. B. Roof Curbs: Galvanized-steel sheet; with mitered and welded corners; 1-1/2-inch thick, rigid fiberglass insulation adhered to inside walls; and 1-1/2-inch wood nailer. Size as required to fit roof opening and ventilator base. 1. Configuration: Coordinate flashing cant strip and slope of curb with actual roof conditions. Refer to Architectural plans for slope requirements. 2. Overall Height Above the Roof Level: 12 inches minimum. 3. Pitch Mounting: Manufacture curb for roof slope. 4. Metal Liner: Galvanized steel. C. Bird Screening: Galvanized-steel, 1/2-inch-square mesh. D. Galvanized-Steel Sheet Finish: 1. Surface Preparation: Clean surfaces of dirt, grease, and other contaminants. Clean welds, mechanical connections, and abraded areas and repair galvanizing according to ASTM A 780. Apply a conversion coating suited to the organic coating to be applied over it. 2. Factory Priming for Field-Painted Finish: Where field painting after installation is indicated, apply an air-dried primer immediately after cleaning and pretreating. a. Color and Gloss: As selected by Architect from manufacturer's full range. Matrix Proj. No. 13-0170 HVAC Gravity Ventilators 23 37 23-5

PART 3 EXECUTION 3.1 INSTALLATION A. Install intake and relief ventilators level, plumb, and at indicated alignment with adjacent work. B. Secure intake and relief ventilators to roof curbs with cadmium-plated hardware. Use concealed anchorages where possible. Refer to Division 07 Section "Roof Accessories" for installation of roof curbs.] C. Install goosenecks on curb base where throat size exceeds 6 by 6 inches. D. Install intake and relief ventilators with clearances for service and maintenance. E. Install perimeter reveals and openings of uniform width for sealants and joint fillers, as indicated. F. Install concealed gaskets, flashings, joint fillers, and insulation as installation progresses. Comply with Division 07 Section "Joint Sealants" for sealants applied during installation. G. Label intake and relief ventilators according to requirements specified in Division 23 Section "Identification for HVAC Piping and Equipment." H. Protect galvanized and nonferrous-metal surfaces from corrosion or galvanic action by applying a heavy coating of bituminous paint on surfaces that will be in contact with concrete, masonry, or dissimilar metals. I. Repair finishes damaged by cutting, welding, soldering, and grinding. Restore finishes so no evidence remains of corrective work. Return items that cannot be refinished in the field to the factory, make required alterations, and refinish entire unit or provide new units. 3.2 CONNECTIONS A. Duct installation and connection requirements are specified in other Division 23 Sections. Drawings indicate general arrangement of ducts and duct accessories. 3.3 ADJUSTING A. Adjust damper linkages for proper damper operation. *** END OF SECTION 23 37 23 *** Matrix Proj. No. 13-0170 HVAC Gravity Ventilators 23 37 23-6