CERTIFICATE OF FIRE APPROVAL

Similar documents
TYPE APPROVAL CERTIFICATE

EC TYPE EXAMINATION (MODULE B) CERTIFICATE

CERTIFICATE OF TYPE APPROVAL ISSUED ON BEHALF OF TRANSPORT CANADA

Materials and Qualification Procedures for Ships

Materials and Qualification Procedures for Ships

LR SOFTWARE CONFORMITY ASSESSMENT SYSTEM. Assessment Module GENPMS Software Products for Planned Maintenance Schemes

PROCEDURE. GTT (GAZ TRANSPORT & TECHNIGAZ) Mk III, Mk V & NO96 MEMBRANE CONTAINMENT SYSTEMS GENERAL APPROVAL AND SUPPLY OF MATERIALS AND COMPONENTS

Materials and Qualification Procedures for Ships

Certificate of Conformity of Factory Production Control

Insulation in decks and bulkheads PYROLIQ sealing compound system

Marine Fire Wrap General Installation Instructions Cable Penetrations through A0-A60 and B0-B30 Bulkheads and Decks

Marine & Offshore Fire Divisions. bulkhead, deck & floor systems

HILTI CP 643N Firestop collar

Guidance Notes for Flettner Rotor Approval

Maritime Safety Committee s 89 th Session

INFORMATION BULLETIN No. 51

MED 2014/90/EU QUALITY SYSTEM MODULE D CERTIFICATE

Property of Cooks Plumbing Supplies

MSC Guidelines for Review of IMO High-Speed Craft Code General Arrangements, Structural Fire Protection, and Means of Escape

BRE Global Assessment Report

Fire Protection and Applications

INTERNATIONAL CONVENTION FOR THE CONTROL AND MANAGEMENT OF SHIPS' BALLAST WATER AND SEDIMENTS, 2004

pproval of rvc upplrsno. 2.9 APRIL 2013

HILTI CP 657 Firestop Brick

Stowage of Explosives on Vessels and issues noted with Small Ships

INDIAN REGISTER OF SHIPPING CLASSIFICATION NOTES. Type Approval of Mechanical Joints used in Piping

Understanding EN 10204:2004 Type 3.2 Certification. Working together for a safer world

BRE Global Test Report

Tehnical Data Sheet Astro HS FM Compound. UIC of product-type: HSFMC CPR-JA5013 ETA-14/0047. ETAG 026-Part 1 ETAG 026-Part 2

MOBILE OFFSHORE DRILLING UNITS 2017

B-02 THERMAL OIL HEATERS

The world s first commercial LNG fuel tank made of high manganese austenitic steel

PACIFIC MARINE SERVICES

ST. VINCENT AND THE GRENADINES

ANNEX 5 DRAFT MSC CIRCULAR DUE DILIGENCE CHECKLIST IN IDENTIFYING PROVIDERS OF CTU-RELATED SERVICES

FIREPRO FIRESTOP PIPE COLLARS. Firestop solution for plastic pipework penetrations

HILTI CP 606 Flexible Firestop Sealant

Loss Prevention Standard

Intermaritime Certification Services (ICS) QUALITY MANAGEMENT SYSTEM INSTRUCTIVE FOR ISM-CODE

Project Address: Name of Person Completing Form:

Retroshield XL TM. Insulation THERMO REFLECTIVE INSULATION

This electronic edition is licensed to for 1 copy. International Maritime Organization

HILTI CP 617 Intumescent acoustic putty pad

ANNEX 1. RESOLUTION MSC.325(90) (adopted on 24 May 2012)

BRE Global Test Report

(Acts whose publication is obligatory)

Title: The Fire Resistance Performance of PRT and PRC, Side and Centre-Opening, Vandal Resistant, Lift Landing Doorsets. WF Assessment Report No:

Class III Pipes Fittings (Dy 500 mm)

HILTI CP 601S Elastomeric Firestop Sealant

CERTIFICATION SCHEME FOR TYPE APPROVAL OF PRODUCTS

Marine & Offshore Fire Divisions bulkhead & deck systems. U-FW/GMM EN Rev: 1 Sept 17

Carriage of Dangerous Goods and Harmful Substances

Peer Reviewer (Same as team members - see section 2.1)

HILTI CP 674 Cavity Closure For Rainscreen / Cladding Systems

Flooring and Acoustic Damping Sikafloor Marine

Hull Surveys for Liquefied Gas Carriers

Stainless Metal Craft (Aust) Pty Ltd

Guide to Documentation and Marking Part 6 General Accessories and Components for Slings

Information Paper on Oil Tanker In-Service Structural Survey Regimes

This classification report consists of five pages and may only be used or reproduced in its entirety.

Insulwhite. Insulation WHITE-FACED THERMO REFLECTIVE INSULATION

Title: The Fire Resistance Performance of PRT and PRC, Side and Centre-Opening Lift Landing Doorsets. WF Assessment Report No: Prepared for: Klefer SA

International requirements and approval of marine fuel cell applications

U L - E U C E R T I F I C A T E

Qualification scheme for welders of aluminium alloys

(ii) Existing ship means a ship which is not a new ship. (iii) "Sewage" means: (a) drainage and other wastes from any form of toilets and urinals; (b)

Finestone Stucco System

European Technical Approval No. ETA-12/0056

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

IMO. RESOLUTION A.753(18) adopted on 4 November 1993 GUIDELINES FOR THE APPLICATION OF PLASTIC PIPES ON SHIPS

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Qualification scheme for welders of hull structural steels

New Lloyd s Register Rules for Natural Gas Fuelled Ships

CLASSIFICATION SOCIETIES WITHIN MARINE REGULATORY ENVIRONMENT OF THE EUROPEAN UNION AND NATIONAL PERSPECTIVE OF THE REPUBLIC OF CROATIA

RESOLUTION MSC.269(85) (adopted on 4 December 2008)

Factory Inspection Report

Duro-Last Roofing, Inc. 525 Morley Drive Saginaw, MI 48601

SINTEF Building and Infrastructure confirms that. Guardian Fastening System

EcoTouch Insulation with PureFiber Technology

SOLAS Chapter VI / 2. Verified Gross Mass of loaded shipping containers A broker s guide. RSA Marine Risk Management - June 2016

SUITABILITY: SMARTPLY OSB3 - ZERO ADDED FORMALDEHYDE

Part E robustdetails. robustdetails. January 2017 Update Pack. Dear Colleague,

MANAGEMENT OF ASBESTOS FREE MATERIALS AND SPARES ON COMPANY SHIPS

GUIDELINES FOR DEVELOPING AND APPROVING PROCEDURES FOR SAMPLING, TESTING AND CONTROLLING THE MOISTURE CONTENT FOR SOLID BULK CARGOES WHICH MAY LIQUEFY

GE/GN8640. Risk Evaluation and Assessment. Guidance on Planning an Application of the Common Safety Method on. Rail Industry Guidance Note

Guidelines on Corrosion Resistant Steel for COT

Monolithic Isolation Fittings

RISK COMMITTEE BYLAW OF THE SUPERVISORY BOARD OF ING BANK ŚLĄSKI S.A.

INSULATED JOINTS. Monolithic Joints for Electrically Isolating Pipelines

BRE Global Classification Report

Section 906. STRUCTURAL STEEL

CERTIFICATE OF APPROVAL No CF 663 HILTI AG

MANUFACTURING TOLERANCES FOR PROFILED METAL ROOF AND WALL CLADDING

Date of Authorization June 29, 2006 BMEC Authorization Authorization Report - Camino Modular Floor System: SC Series

IMPLEMENTATION OF INSTRUMENTS AND RELATED MATTERS. Consistency of In Water Survey (IWS) provisions for passenger and cargo ships

6. In case BOE not submitted at the time of Direct Import Payment, BOE to be submitted within 15 days from the date of transaction.

FOR FURTHER INFORMATION ON THE KOOLTHERM RANGE OF PRODUCTS PLEASE TELEPHONE THE KINGSPAN TECHNICAL SERVICES DEPARTMENT (01457)

AS/NZS 2280:2012 AS/NZS

Subj: Installation and Operation of ECDIS on board Greek Vessels

EN DK NA:2007

Transcription:

Examined Office LR427..206.09 CERTIFICATE OF FIRE APPROVAL This is to certify that The product detailed below will be accepted for compliance with the applicable Lloyd s Register Rules and Regulations and with the International Convention for the Safety of Life at Sea, (SOLAS), 974, as amended, for use on ships and offshore installations classed with Lloyd s Register, and for use on ships and offshore installations when authorised by contracting governments to issue the relevant certificates, licences, permits etc. Manufacturer Roxtec International AB Address Box 540 S-37 23 Karlskrona Sweden Type Description CABLE PENETRATION (STANDARD FIRE TEST) Fire Resisting Single/Multiple Cable and Pipe Circular Penetrations Type: R- Series for use in steel bulkheads and decks. Specified Standard IMO Res. MSC.6 (67)- (FTP Code) Annex Part 3 IMO MSC/Circ.20 IMO Res. MSC.307 (88)-(200 FTP Code) Section 8 The attached Design Appraisal Document forms part of this certificate. This certificate remains valid unless cancelled or revoked, provided the conditions in the attached Design Appraisal Document are complied with and the equipment remains satisfactory in service. of issue 7 May 207 Expiry date 27 May 2020 Certificate No. SAS F5054/M Signed Lloyd's Register EMEA Sheet No of 5 Name S. Abraham Surveyor to Lloyd s Register EMEA A Member of the Lloyd s Register Group Note: This certificate is not valid for equipment, the design or manufacture of which has been varied or modified from the specimen tested. The manufacturer should notify Lloyd s Register of any modification or changes to the equipment in order to obtain a valid Certificate. Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as the 'Lloyd's Register'. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

7 Fenchurch Street, London, EC3M 4BS Telephone 020 7423 246 Fax 020 7423 2053 2 of 5 SAS F5054/M 7 May 207 SOUTSO/SFS/TA/SA/WP25746023&WP2385944 ATTACHMENT TO CERTIFICATE OF TYPE APPROVAL No. SAS F5054/M This Design Appraisal Document forms part of the Certificate. APPROVAL DOCUMENTATION Tests in accordance with IMO Res. MSC.6(67)-(FTP Code) Annex Part 3: Norwegian Fire Research Laboratory (SINTEF), Trondheim, Norway, Test Reports No: 03070.0A, dated 7 December 200, 03070.23A and 03070.23B both dated December 2002 and 03070.29A, dated 28 October 2003. SP Technical Research Institute, Boras, Sweden, Test report No: P602999 dated 23 January 2007. Tests in accordance with IMO Res. MSC.307 (88)-(200 FTP Code) Annex, Part 3: Danish Institute of Fire and Security Technology, Hvidovre, Denmark; Fire Test Report No: PGA065 dated 03 July 205 and PGA0723A dated 4 February 206 Manufacturer s drawings (for reference purposes only): Roxtec drawing no: S00390 CONDITIONS OF CERTIFICATION Cable penetrations. For use in A-60 Class steel bulkheads and decks, with the cable penetrations fitted to the insulated side of steel bulkheads and top side of steel decks in all cases (restricted applications); the insulation arrangements for A-60 Class bulkhead and deck cable penetrations are to be as described in Roxtec drawing no: S00390 2. For use in A-0, A-5, A-30 Class steel bulkheads and decks, all cable penetrations tested only in A- 60 Class divisions, but not separately in A-0 Class divisions as required by IMO Res. MSC.307(88)- (200 FTP Code) Annex, Part 3 Appendix 2. A.IV.2.2.., are to be fitted with the same or equivalent A-60 Class insulation arrangements as those used in the fire tests (including any insulation fitted on the penetration itself) for a minimum distance of 200mm around the penetration, on all fire risk sides in bulkheads (as identified at the design stage by the Plan Approval Authority for the specific project) and on the underside in decks and insulation should be extended to cover the full side(s) and the end face(s) of the steel frame, with an overlap of at least 20mm from the steel edges. The above mentioned A-60 Class insulation arrangements should be additional to any thermal or acoustic insulation, but may include any fire rated insulation (e.g. A-5, or A-30) already fitted on the bulkhead or deck and/or on the penetration itself, such that the total fire rating is A-60 3. The following penetrations in Table below were tested separately in A-0 Class decks and therefore they may be accepted in A-0 Class decks with as-tested arrangements in lieu of the requirements in Condition 2. For use in A-5 and A-30 decks, these penetrations need not be fitted with a 200mm A-60 insulation collar around the penetrations (as described in Condition 2), however any A-60 insulation that was applied on these penetrations in the A-60 fire tests (as described in condition above) shall be fitted for these applications, however the A-60 insulation may be replaced with A-5 or A-30 insulation respectively

7 Fenchurch Street, London, EC3M 4BS Telephone 020 7423 246 Fax 020 7423 2053 3 of 5 SAS F5054/M 7 May 207 SOUTSO/SFS/TA/SA/WP25746023&WP2385944 Penetration type/size (a) R50 R200 ATTACHMENT TO CERTIFICATE OF TYPE APPROVAL No. SAS F5054/M Table : Approved arrangements for cable penetrations in A-0 Class steel decks Position of tested penetration in Approximat Maximu Applicatio division/general n (b) or e Cable fill m cable Restricted (c) ratio Steel decks only Steel decks only Symmetrically/Genera l Symmetrically/Genera l 40% 0.5 40% 39 Minimum Insulation arrangements required for A-0 divisions Insulation not required on or around the penetration Insulation not required on or around the penetration (b) General applications refer to installation arrangements where the penetrations are fitted either symmetrically or non-symmetrically to the fire exposed side or fire unexposed side of the deck (c) Restricted applications refer to installation arrangements where the penetrations are fitted non-symmetrically to the topside of the deck in all cases 4. Penetration seals consist of: Roxtec mild steel sleeves 55mm deep, filled with R seal frames which hold the 60mm thick RM modules. The steel sleeves (5.6mm to 8.8mm thick) may be welded or bolted to the division 5. Tested Roxtec seal frame types: R and R EMC 6. Tested steel sleeve/frame sizes: SLR 70 up to SLR 200 7. Production items are to be manufactured in accordance with a quality control system which shall be maintained to ensure that items are of the same standard as the approved prototype Pipe penetrations. For use in A-60 Class steel bulkheads and decks with approved arrangements as described in Tables 2 and 3 below 2. For applications in A-0, A-5, A-30 Class steel bulkheads and decks, all pipe penetrations tested only in A-60 Class divisions, but not separately in A-0 Class divisions as required by IMO Res. MSC.307(88)-(200 FTP Code) Annex, Part 3 Appendix 2. A.III.2.2.., are to be fitted with the same or equivalent A-60 Class insulation arrangements as those used in the fire tests (including any insulation fitted on the penetration itself in the tests) for a minimum distance of 200mm around the penetration, on all fire risk sides in bulkheads (as identified at the design stage by the Plan Approval Authority for the specific project) and on the underside in decks and insulation should be extended to cover the full side(s) and the end face(s) of the steel frame, with an overlap of at least 20mm from the steel edges. The above mentioned A-60 Class insulation arrangements should be additional to any thermal or acoustic insulation, but may include any fire rated insulation (e.g. A-5, or A-30) already fitted on the bulkhead or deck and/or on the penetration itself, such that the total fire rating is A-60.

7 Fenchurch Street, London, EC3M 4BS Telephone 020 7423 246 Fax 020 7423 2053 4 of 5 SAS F5054/M 7 May 207 SOUTSO/SFS/TA/SA/WP25746023&WP2385944 ATTACHMENT TO CERTIFICATE OF TYPE APPROVAL No. SAS F5054/M Table 2: Approved arrangements in A-60 Class Steel Bulkheads: Penetration Maximum Pipe Maximum Position of tested Minimum Minimum total length of type/size (a) Nominal Outside Fire rating penetration in of A-60 approved A-60 insulation to Diameter(mm) division/general (b) or Insulation Collar be fitted along the pipe, when Restricted (c) required around measured from the the penetration Penetration insulation collar (mm). (if applicable) or bulkhead insulation (in mm). R70 Single steel pipe of A-60 Restricted 50 Not required 0mm R200 2 steel pipes of A60 Restricted 50 Not required 8mm and 50mm R70 2 copper pipes, A-60 General Not required 500 each of 0mm R200 3 copper pipes of A60 General Not required 500 0mm, 28mm and 54mm (b) General applications refer to installation arrangements where the penetrations may be fitted either symmetrically or non-symmetrically to the fire exposed side or fire unexposed side of the bulkhead (c) Restricted applications refer to installation arrangements where the penetrations are to be fitted nonsymmetrically to the fire unexposed side of the bulkhead in all cases Table 3: Approved arrangements in A-60 Class Steel Decks Penetration type/size (a) R70 R200 Maximum Pipe Nominal Outside Diameter (in mm) Single steel pipe of 0mm 2 steel pipes of 8mm and 50mm Maximum Fire rating Position of SPM seal in decks/ General (a) or Restricted (b) Minimum of A-60 Insulation Collar required around the penetration, on the underside of the deck (in mm). Minimum length of approved A-60 insulation to be fitted along the pipe on single side or both sides of bulkhead as applicable, when measured from the Penetration insulation collar (if applicable) or bulkhead insulation (in mm). A-60 General 50 Not required A-30 General 50 Not Required (b) General applications refer to installation arrangements where the penetrations may be fitted either symmetrically or non-symmetrically to the fire exposed side or fire unexposed side of the deck (c) Restricted applications refer to installation arrangements where the penetrations are to be fitted nonsymmetrically to the fire unexposed side/topside of the deck in all cases

LR427..206.09 Lloyd s Register EMEA 7 Fenchurch Street, London, EC3M 4BS Telephone 020 7423 246 Fax 020 7423 2053 5 of 5 SAS F5054/M 7 May 207 SOUTSO/SFS/TA/SA/WP25746023&WP2385944 ATTACHMENT TO CERTIFICATE OF TYPE APPROVAL No. SAS F5054/M PLACE OF PRODUCTION Roxtec International AB Box 540 S-37 23 Karlskrona Sweden Examined Office Lloyd's Register EMEA Saji Abraham Senior Specialist Statutory Fire & Safety Southampton Technical Support Office Marine & Offshore Lloyd s Register Supplementary Type Approval Terms and Conditions This certificate and Design Appraisal Document relates to type approval, it certifies that the prototype(s) of the product(s) referred to herein has/have been found to meet the applicable design criteria for the use specified herein, it does not mean or imply approval for any other use, nor approval of any products designed or manufactured otherwise than in strict conformity with the said prototype(s).