P.V.C. INSULATED UNARMOURED COPPER CABLES

Similar documents
P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION

TECHNICAL SPECIFICATIONS

Single core conductor BETAtherm 145

INTERNATIONAL STANDARD

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +105 C, 1000 VOLTS, TYPE LSFSGU

TYPE TEST REPORT OF 11 KV 3 x 240 mm² CU/XLPE/SWA/PVC CABLE. Kinectrics International Inc. Report No.: K RC-0001-R00.

NPS/001/007 Technical Specification for Overhead Line Conductors

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

University of Kelaniya Dalugama, Kelaniya, Sri Lanka Tel , Fax ,

U.V resistance UL Sunlight Resistance. Flame retardant IEC

Technical Specification for Single Core 38/66kV TR-XLPE Insulated Underground Cable

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -

TECHNICAL SPECIFICATION FOR CONDUCTORS

Superastic Flex Cable 450 / 750V Exceeds all the specifications in its category.

TECHNICAL SPECIFICATIONS

DATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0

NPS/002/001 Technical Specification for Earthing Materials

XLPE CABLE (11KV - Aluminium)

INTERNATIONAL STANDARD

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS

Cables for Railway Signalling Applications General Requirements

SEAL & SIGNATURE OF THE TENDERER

Not Applicable DD/MM/YY Completed Forms to be submitted by 30/08/2013 : Hrs IST. Date of Opening for Technical Bids 30/08/2013 : 14.

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION

SARDAR VALLABHBHAI NATIONAL INSTITUTE OF TECHNOLOGY,SURAT

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

DEMOCRATIC SOCIALIST REPUBLIC OF SRI LANKA UVA WELLASSA UNIVERSITY BIDDING DOCUMENT

Heat-Shrinkable Tubing

Section - III Evaluation and Qualification Criteria

*** Supercedes: BECO E and COM , , & ***

Specifications: Ice point resistance: Fundamental interval (0 C to 100 C): 38.5Ω (nominal)

Construction guideline

Procurement of Digital Podium (For Contracts value estimated to cost less than Rs. 25 lakhs)

Technical Specification for LV ABC Fuse Switch Disconnectors

TECHNICAL SPECIFICATIONS FOR AERIAL BUNCHED CABLES FOR OVERHEAD DISTRIBUTION

ENGLISH Datasheet Platinum Resistance Pt100 & Pt1000 Thin Film Detectors Platinum Sensing Resistors Thin Film (Pt100 & Pt1000 Ohm)

Mineral Insulated Platinum Resistance Thermometer PT100 Sensor - Available in 3mm or 6mm diameter x 150mm or 250mm probe lengths

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS

ENGLISH. 1metre 7/.02mm Teflon insulated twin twisted lead

Ceramic Ceramic No. of Lead/Wire Lead Allied RS order Dia Ø Length Wires Type Length Code code

THERMOFIT RNF-100 TUBING Polyolefin, Flexible, Heat-Shrinkable

3. VALIDITY OF BID. The bid submitted under this tender must be valid for a period of 120 days from the date of closing of tender.

DOMESTIC ELECTRICAL INSTALLATION PERIODIC INSPECTION REPORT (FOR A SINGLE DWELLING) B ADDRESS AND DETAILS OF THE INSTALLATION Address: SPECIMEN

Datasheet Platinum Resistance Pt100 Dual Element Industrial Sensor Probe 6mm diameter x 150mm or 250mm probe lengths

Gujarat Council of Elementary Education Sarva Shiksha Abhiyan

Pakistan International Airlines

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols

INVITATION FOR QUOTATION. No:-TEQIP-II/2017/iiit/Shopping/8/3857

SECTION WIRES AND CABLES

Pakistan International Airlines Procurement Logistics Department Commercial Purchases Section Tel: , Fax:

Guide to Documentation and Marking Part 6 General Accessories and Components for Slings

MATERIAL SPECIFICATION RIGID FOAM; CLOSED CELL POLYMETHACRYLIMIDE (PMI)

BIS or used as Amendment to STANDARD comments is 15 Nov. 2008

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

Flat polyvinyl chloride sheathed flexible cables

7. EXTENSION LEADS AND COMPENSATING CABLE

ALUMINIUM CONDUCTORS FOR OVERHEAD TRANSMISSION PURPOSES

Armoured Instrumentation Cables to BS7917

TENDER DOCUMENT INFORMTION TECHNOLOGY PROJECTS AND SERVICES

QUOTATION ENQUIRY. Frequency Range Output AC Voltage Regulation (Batt. Mode) ±10% Frequency Range (Batt. Mode)

Technical Specification for Live Line Tap Connectors

2. TEST RECORDS: All records of tests and analysis shall be kept in suitable forms approved by the Bureau.

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.

INVITATION FOR QUOTATION. TEQIP-III/2018/seip/Shopping/7

Contents Foreword Scope Normative references Terms and definitions Dimensions and tolerances Designation Technical

Profile No.: 4 NIC Code: ELECTRICAL CABLES (SINGLE AND MULTICORE)

Standard of Practice - Campus Electrical Distribution System

Ministry of Defence Defence Standard 61-12(Part 26)

Heating elements shall not be used for FRP tank-containers including tank swap bodies.

TECHNICAL SPECIFICATION A.B. CABLE

SRI LANKA AIR FORCE DEMOCRATIC SOCIALIST REPUBLIC OF SRI LANKA BIDDING DOCUMENT [NATIONAL COMPETITIVE BIDDING]

Datasheet RS Pro RS Series Axial Carbon Resistor 1kΩ ±5% 2W ppm/ C RS Stock No:

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained.

TECHNICAL SPECIFICATION FOR MS BEAMS 116X100 11MTR LONG FOR SUB-STATIONS

PTFE BELLOWS POLY FLUORO LTD. POLY FLUORO LTD.260A. Bommasandra Industrial Area, Hosur Road, Bangalore TECHNICAL SPECIFICATION

Sl.NO. Particulars Unit EMD Amount 1 Supply & Installation of Automatic Milk Fat 120 No s 1,00,000-00

SUPPLY AND DELIVERY OF READYMADE TROUSERS QUOTATION NO:

DOMESTIC GAS REGULATORS

TECHNICAL SPECIFICATIONS for 100Ci Ir-192 source projector(exposure device /Camera )

REPUBLIC OF SEYCHELLES

3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series

SUPPLY AND DELIVERY OF 200KVA EARTHING TRANSFORMER TENDER DOCUMENTS: SARAWAK ENERGY REF. NO. PLS PART I TENDER PROCEDURES

Polyethylene for biogas plants

TENDER FOR SUPPLY, PROVIDING & FIXING HEAVY DUTY PVC FLOORING FOR M/S BALMER LAWRIE & CO LTD 21, NETAJI SUBHASH ROAD KOLKATA

UNAVCO, INC. INVITATION FOR BID/IFB (THIS IS NOT AN ORDER)

PHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-BIPV-SM-P125-36

1.1 All testing apparatus shall be periodically checked and calibrated. Records of such checks/calibration shall be maintained.

TEST REPORT IEC Information technology equipment Safety Part 22: Equipment to be installed outdoors

INDUSTRIAL ATTACK 800

Sika KAB combination joint waterbars waterstopping systems

COMPILED BY APPROVED BY FUNCTIONAL RESP AUTHORISED BY V SINGH. Date: 16/03/2009. Date: 16/03/2009. Date: 19/03/2009 Date: 26/03/2009

PT. KABELINDO MURNI Tbk SHIPBOARD CABLE WIRE AND CABLE MANUFACTURER. No. EMS No. OSH No. QCS 00152

15 kv EPR Insulated, Jacketed, URD Cable

Transcription:

083 : 2007 CEB SPECIFICATION P.V.C. INSULATED UNARMOURED COPPER CABLES CEYLON ELECTRICITY BOARD SRI LANKA

Specification for P.V.C. INSULATED UNARMOURED COPPER CABLES CEB Specification 083 : 2007 CEYLON ELECTRICITY BOARD No. 50, Sir Chittampalam A. Gardiner Mawatha, Colombo 2, Sri Lanka Telephone: 94-11 2324471 / 8 Facsimile: 94-11-2323935

CONTENTS Page 1. SCOPE... 2 2. SYSTEM PARAMETERS... 2 3. SERVICE CONDITIONS... 2 4. APPLICABLE STANDARDS... 2 5. TECHNICAL REQUIREMENTS... 3 5.1 Conductor... 3 5.2 Insulation...3 5.3 Sheath...3 5.4 Completed Cable... 3 6. BASIC FEATURES... 4 6.1 General...4 6.2 Manufacture... 4 6.3 Single Core Cables - Insulated and Sheathed...4 6.4 Single Core Insulated Cable for Earth Conductor...4 7. QUALITY ASSURANCE... 4 8. ADDITIONAL REQUIREMENTS... 4 8.1 Marking...4 8.2 Packing...5 9. INFORMATION TO BE FURNISHED WITH THE OFFER... 5 9.1 All information furnished shall be in English,...5 9.2 Type Test Certificates... 5 10. SAMPLE... 6 11. INSPECTION & TESTING... 6 11.1 Acceptance/Sample Tests... 6 11.2 Routine Tests... 6 12. ANNEXURE... 6 Annexure A: Schedule of Guaranteed Technical Particulars. 7 Annexure B: Price variation. 9 Annexure C: Non Compliance Schedule. 11 1

SPECIFICATION FOR P.V.C. INSULATED UNARMOURED COPPER CABLES 1. SCOPE This specification covers the general requirements of design, manufacture, testing, supply and delivery of following copper cables. (a) (b) PVC Insulated and sheathed single core 600/1000V unarmoured copper Cables. PVC insulated 450/750V, unarmoured copper cable for earth conductor. 2. SYSTEM PARAMETERS (a) Nominal System Voltage 400/230V 3ph & Neutral (b) System highest Voltage 440/250V 3ph & Neutral (c) System frequency 50 Hz. (d) Number of phases 03 (e) Method of earthing Solidly earthed neutral at substations (f) System fault level 16 ka 3. SERVICE CONDITIONS (a) Annual average ambient temperature 30 C (b) Maximum ambient temperature 40 C (c) Maximum relative humidity 90% (d) Environmental conditions Humid tropical climate with heavily polluted atmosphere. (e) Operational altitude From M.S.L. to 1900 m above M.S.L. 4. APPLICABLE STANDARDS The items and components supplied shall be in accordance with the latest edition of the standard specified below and amendments thereof. However CEB specification shall supersede these standards in the event there is a discrepancy. (a) BS 6346 (1997) Electric cables. PVC insulated armoured cables for voltage of 600/1000V and 1900/3300 V (b) BS 6004 (2000) Electric cables for PVC Insulated, non-armoured cables for voltages up to and including 450/750V, for electric power, lighting and internal wiring (c) BS 7655-3:1(1997) Specification for insulating & sheathing materials for cables. PVC insulating compounds. Harmonized Types. (d) BS 7655-4:1(1997) Specification for insulating & sheathing materials for cables. PVC sheathing compounds. Harmonized Types. (e) BS 6360 (1991) Conductors in insulated cables and cords. (f) BS EN/IEC 60811-1.1 (1995) (g) BS EN/IEC 60811-1.2 (1995) Insulating and sheathing materials of electric cables. Common test methods. General application. Measurement of thickness and overall dimensions. Test for determining the mechanical properties. Insulating and sheathing materials of electric cables. Common test methods. General application. Thermal ageing methods. (h) BS 5099: 1992 Specification for spark testing of electric cables. 2

5. TECHNICAL REQUIREMENTS 5.1 Conductor 5.2 Insulation a) Conductor material Annealed Copper b) Tensile Strength 155-195 N/mm² c) Minimum Elongation of wire after break(for wire diameter. 1.36mm & above) 22.5% d) Number of cores Single e) Wrapping Test No crack f) Nominal Cross Section area of the conductor (mm²) g) Number of Standards h) Max Conductor D.C. Resistance (ohm/km) 50 70 95 120 185 240 300 19/1.78 19/2.14 19/2.52 37/2.03 37/2.52 61/2.25 61/2.52 0.387 0.268 0.193 0.153 0.0991 0.0754 0.0601 a) Insulation Type PVC Type TI 1 as per BS 7655 3.1 1997 b) Minimum tensile strength as manufactured 12..5 N/mm² c) Minimum tensile strength after ageing 12..5 N/mm² d) Minimum elongation at break as manufactured 125 % e) Minimum elongation at break after ageing 125 % f) Maximum variation of tensile strength 20 % g) Maximum variation of elongation at break 20 % h) Nominal Cross Section area of the conductor (mm²) 50 70 95 120 185 240 300 i) Minimum insulation thickness (mm) 1.4 1.4 1.6 1.6 2.0 2.2 2.4 5.3 Sheath a) Sheath type PVC Type TM 1as per BS 7655 4.1 1997 b) Minimum Tensile Strength as of manufactured 12..5 N/mm² c) Minimum Tensile Strength after ageing 12..5 N/mm² d) Minimum elongation at break as manufactured 125 % e) Minimum elongation at break after ageing 125 % f) Maximum variation of tensile strength 20 % g) Maximum variation of elongation at break 20 % h) Nominal Cross Section area of the conductor (mm²) 50 70 95 120 185 240 300 i) Minimum thickness of the sheath (mm) 1.5 1.6 1.6 1.7 1.8 1.9 1.9 5.4 Completed Cable a) Minimum insulation resistance per km at 20 C 5 MΩ 3

6. BASIC FEATURES 6.1 General The cables stipulated in the schedule of prices shall be as follows. (a) (b) PVC insulated and PVC sheathed un-armoured cables for voltage 600/1000V as per BS 6346 :1997 in regard to thickness and formation of the Insulation and Sheath. PVC insulated unarmoured cable as per BS 6004 :2000 in regard to thickness and formation of the Insulation. 6.2 Manufacture (a) Conductor The core of the cable shall be stranded plain annealed copper conductor of class 2 as per BS 6360 The electrical and mechanical properties of the conductor shall be as stipulated in Clause 5.0 - Technical Requirements.. (b) Insulation The Insulation shall be of extruded PVC compound Type TI 1 confirming to BS 7655-3.1 /1997. The insulation shall be closely applied to the conductor. It shall be possible to remove insulation without damage to the insulation itself and the conductor. The mean value of the thickness of the insulation shall not be less than the value stipulated in the Clause 5.0 - Technical requirements. (c) Sheath The oversheath shall be an extruded layer of PVC material confirming to the requirements for Type TM 1 material specified in BS 7655-4.1 /1997. This homogeneous oversheath layer applies over the insulation and it shall be treated to prevent deterioration due to ultra violet radiation of sunlight. The sheath shall be capable of being removed without damage to the core insulation. The mean value of sheath thickness shall be as stipulated in Clause 5.0 - Technical requirements. 6.3 Single Core Cables - Insulated and Sheathed The single core copper cable conforming to BS 6346 is required for use as phase and neutral cables. The core insulation shall be Brown, Black, Grey or Blue colour (as stipulated in the schedule of prices) and the over sheath shall be Black colour. Cross sectional area of the core conductor shall be as indicated in the schedule of Prices. 6.4 Single Core Insulated Cable for Earth Conductor The single core copper cable (50mm 2 or sizes specified in the price schedule) conforming to BS 6004 is required for use as the earth conductor. The PVC insulation of the core shall be green and yellow colour. 7. QUALITY ASSURANCE The Manufacturer shall possess ISO 9001: 2000 Quality Assurance Certification valid throughout the delivery period of this tender, for the manufacture of PVC Cables for the plant where the PVC Cables is being manufactured. The Bidder shall furnish a copy of the ISO Certificate certified as true copy of the original by the Manufacturer, along with the offer. 8. ADDITIONAL REQUIREMENTS 8.1 Marking The outer sheath/insulation of the cables shall be embossed with letters " CEB " followed by the identifications marked legibly as per relevant BS standard at every 500mm or less along the length of the Cable as follows; 4

8.2 Packing a) Manufacturer s Identification b) Voltage designation 600/1000 V or 450/750V. c) British Standard Number. d) Cable Type & nominal cross section area of the Conductor The cable shall be delivered in 100 Metre Coils (unless specified otherwise in the price schedule) wrapped in polythene. Each coil shall bear a tag under the polythene wrappings showing the following particulars a) Manufacturer's Name or Trade Mark, b) Type of cable c) Core size d) Length of cable e) Colour of Insulation /sheath f) Net weight/gross weight. 9. INFORMATION TO BE FURNISHED WITH THE OFFER 9.1 All information furnished shall be in English, a) Catalogues describing cables offered. b) Completed schedule of guaranteed technical particulars (Annex A). c) The manufacturer shall have at least 10 years of experience in the manufacture of PVC cables and shall furnish sufficient documentary evidence along with the offer bid to prove his manufacturing experience. 9.2 Type Test Certificates (a) 600/1000V cables - Type Tests as per BS 6346 and BS 6360 The certified copies of the Type Tests Certificates for the following applicable tests as per relevant BS Standard shall be furnished with the offer. a) Insulation Material b) Oversheath physical properties c) Compatibility Test for completed cables d) Flame propagation test on complete cable e) Elongation test. (b) 450/750V cable - Type Tests as per BS 6004 and BS 6360 The certified copies of the Type Tests Certificates for the following applicable tests as per relevant BS Standard shall be furnished with the offer. a) Insulation Material b) Compatibility Test for completed cables c) Flame propagation test on complete cable d) Voltage test on core e) Elongation test. The type test certificates pertaining to the above single core copper cables offered shall be from an independent testing authority acceptable to the purchaser, 5

10. SAMPLE Sample pieces of 1.0m length of copper cable for each cable size indicated in the price schedule that manufactured according to this specification shall accompany with the offer. Bidder's identity shall be indelibly marked on the sample. 11. INSPECTION & TESTING 11.1 Acceptance/Sample Tests The Manufacturer shall make necessary arrangements for inspection by an Engineer appointed by the CEB during Manufacture and before dispatch and also to carry out in his presence the sample tests and routine tests (as per Clause 11.2 below) stated in relevant BS standards. These tests shall be witnessed by the Engineer on selected samples and the copies of the test certificates shall be supplied with the delivery of cables. (a) 600/1000V cables - Sample tests as per BS 6346 a) Conductor construction b) Insulation thickness c) Oversheath thickness (b) 450/750V cable - Sample tests as per BS 6004 11.2 Routine Tests a) Conductor construction b) Insulation thickness and application c) Conductor resistance d) Voltage test on completed cable e) Insulation resistance The original of the following routine test reports of cable shall be made available for the observation of the CEB engineer inspecting the cable. (a) 600/1000V cables - Routine tests as per BS 6346 a) Spark test on insulation b) Spark test on over sheath c) Conductor resistance d) Voltage test on completed cable e) Insulation resistance on completed cable f) Cable markings (b) 450/750V cable - Routine tests as per BS 6004 a) Cable markings b) Absence of faults in the insulation 12. ANNEXURE Annexure A - Schedule of Guaranteed Technical Particulars (To be duly filled by the Bidder) Annexure B - Price Variation Annexure C - Non Compliance Schedule 6

Annexure - A SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS (To be filled by the manufacturer for each type/size of cable) 1) General - a) Name of Manufacturer b) Type of cable c) Nominal cross sectional area d) Number & nominal diameter of wire e) Number of cores f) Colour of insulation g) Colour of sheath 2) Particulars of the Conductor a) Conductor material b) Conductor Diameter mm c) Conductor DC Resistance at 20 0 C ohm/km d) Tensile Strength of Conductor wire N/mm² e) Minimum elongation of wire after break % f) Wrapping Test 3) Particulars of the Insulation a) Insulation type b) Thickness mm c) Smallest measure of Thickness mm d) Minimum tensile strength as manufactured N/mm² e) Minimum tensile strength after ageing N/mm² f) Minimum elongation at break as manufactured % g) Minimum elongation at break after ageing % h) Maximum variation of tensile strength % I) Maximum variation of elongation at break % 7

4) Particulars of the Sheath a) Sheath type b) Thickness mm c) Smallest measure of Thickness mm d) Minimum tensile strength as manufactured N/mm² e) Minimum tensile strength after ageing N/mm² f) Minimum elongation at break as manufactured % g) Minimum elongation at break after ageing % h) Maximum variation of tensile strength % i) Maximum variation of elongation at break % j) Whether the sheath is UV stabilized type Yes/No 5) Particulars of the Completed Cable a) Insulation resistance per km M Ohm b) Withstand the fire conditions I/We do hereby certify that the above particulars are true and correct. Seal and Signature of the Manufacturer/Bidder Date: 8

Annexure-B PRICE VARIATION The Bidders shall forward their offers on the basis of the Price Variation stipulated below. 1. Basis of the Offer (a) (b) (c) (d) Suppliers of PVC Insulated single core Copper Cables are required to make their offers on the basis of a Base Price plus a Fixed Price Margin. The Base Price shall be the Cash Seller's Midday Official Average Price of Copper Grade A, at London Metal Exchange (LME) in US Dollars on the day of the closing of Bids or the previous working day if the day of closing of Bid is a non working day at the LME. The Fixed Price Margin (FP) shall be quoted in the currency of choice of the Bidder. Accordingly FOB Price of Copper Cables of foreign Bidders and ex-factory price of Copper Cables of local Bidders for the purpose of evaluation shall be computed as; Where ; {[ (B 0 x MT)) x US 0 ] + ( FP x CC )} x TL B 0 - Base Price which is the Cash seller's midday official average price of Copper Grade A, in US Dollars per Metric tone at the LME on the fixed date [Clause (1 b)]. FP - MT - TL - CC - US 0 - Fixed Price Margin per kilometre of Copper Cables in the currency allowed under Clause 1(c) above. Quantity of Copper Grade A required in Metric Ton for the manufacture of one kilometre of Copper Cable. Total Length in kilometres of Copper Cable offered. Currency Conversion rate from the currency of choice of the Bidder to Sri Lanka Rupees prevailing on the data of Bid opening. Currency Conversion rate from the US Dollars to Sri Lanka Rupees prevailing on the date of Bid opening. 2 Award Price The FOB award price of Copper Cables for Foreign Bidders and the ex-factory award price of Local Bidders shall be computed as Where ; B1 - TL - (B1 x MT) TL + FP x TL Base Price which is the Cash seller's midday official average price of Copper Grade A, in US Dollars per Metric tone at the LME on the first working day immediately after the date of award. Total Length in kilometres of Copper Cable awarded. 9

FP - Fixed Price Margin per kilometre of Copper Cables in the currency allowed under Clause 1(c) above Intimation of the award will be faxed to the successful Bidder and or to his agent in Sri Lanka on the same day of the award. 3. Conversion of Currency a) For the purpose of the evaluation the Prices B o in US Dollars and the Fixed Price Margin (FP) in the currency of choice of the Bidder will be converted to Sri Lanka Rupees at the official Selling Exchange Rate of the Central Bank of Sri Lanka prevailing on the day of opening of Bids. b) The payment for the supply will be made to the Supplier at the contract price in the currency quoted for the Fixed Price Margin (FP). The base price B 1 in US Dollars will be converted to the currency of the FP at the exchange rates indicated in the bulletin of the LME applicable on the first working day immediately after the date of the award of the offer; where such exchange rate is not available for the currency of the FP in the Bulletin the selling rate at the Central Bank of Sri Lanka shall be applicable. 4. Variation Figures. The Bidders shall furnish Fixed Price Margin and the Weight of Copper Grade A required to manufacture one kilometre of Copper Cables offered as indicated below. Offers of Bidders who fail to furnish these particulars will be rejected. Description of the Copper Cables offered; Voltage Rating (V) Cross sectional Area of the Cu Conductor (mm²) Fixed Price Margin (FP) for manufacture of one kilometre of Copper Cables in the currency allowed as per Clause 1(c) (../km) Weight in metric tones (MT) of Copper Grade A required for the manufacture of one Kilometre of Copper Cables (Metric Ton/km) ------------------------------------------------------------------ Seal and Signature of the Manufacturer/Bidder Date: 10

Annexure - C Non Compliance Schedule On this schedule the bidder shall provide a list of non compliances with this specification, documenting the effects that such non compliance is likely to have on the equipment's life and operating characteristics. Each non- compliance shall be referred to the relevant specification clause. Clause No. Non Compliance Seal & Signature of the Manufacturer/Bidder Date: 11