REFLECTIT. Reflectit Application Instructions Spray and Roller DS % Acrylic Coating Providing a Pearlescent Appearance

Similar documents
CUSTOM BRICK. Custom Brick Finish Polymer System Application Instructions For Use On Vertical Walls DS154

AquaFlash System Installation Guide DS196

MANUFACTURER S (SHORT FORM) SPECIFICATION / SECTION

Technical Service. INSTALLATION INSTRUCTIONS FOR TARAFLEX SPORT PRODUCTS over Gypsum base Products. This document refers to the following products:

FIVE STAR PRODUCTS, INC. (800)

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150

Metallic Color Coat. Factory-mixed, 100% acrylic polymer coating

3M Fast Tack Water Based Adhesive 1000NF

Refer to Substrates & Surface Preparation.

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

Carboguard 890 PRODUCT DATA SHEET SELECTION & SPECIFICATION DATA. Generic Type. Cycloaliphatic Amine Epoxy

Aliphatic Acrylic-Polyester Polyurethane

ARDEX GUIDE SPECIFICATION ARDEX CD Concrete Dressing and ARDEX CD FINE Concrete Dressing Polymer-Modified, Portland Cement-Based, Resurfacing Compound

Application Instructions for Keystone Kool Deck on Existing Concrete

ELASTOFLEX ELASTOMERIC TEXTURED ACRYLIC WALL COATING SPECIFICATION

Installation Instructions

Caparol System PRO Data sheet

TECHNICAL DATA SHEET

TEX COTE 600 TEXTURED COATING MASONRY PROTECTIVE COATING

BEP Blue Barrier Installation and Application Guide

Technical Data Sheet

BEP Blue Barrier Installation and Application Guide

CAULKING INSTRUCTIONS GRABBERGARD EFC & IFC

DSC602NC. Outsulation PD / Outsulation PD (NC) Non-Combustible System Application Instructions

Corlar 2.1 PR-P High Solids Productive Epoxy Primer

Corlar 2.1 PR-P High Solids Productive Epoxy Primer For Use With FG-040, FG-041 or FG-042 Activators

Guideline Specification ACRYMAX ARS-1-C Reinforced Composite Elastomeric Membrane System for Concrete Roofs Fluid-Applied Roofing

SIDER-POOL. Product Data. Features and Uses

TECHNICAL ADVICE. PREPARATION Levels of finish for plasterboard and their decoration

Stop and Read Before Installing Material

PAYING ATTENTION TO DETAIL by Bob Cusumano

Ash Brook Golf Course Scotch Plains, New Jersey

REPORT HOLDER: GREENMAKER INDUSTRIES, LLC 697 OAKWOOD AVENUE WEST HARTFORD, CONNECTICUT EVALUATION SUBJECT: DECOPLAST DDARS NOTCHED

Section COATING RESTORATION

MDF WALL PANELS INSTALLATION INSTRUCTIONS

POWERBASE ICF / SIDER PROOF FF-PR

INFINITY SYSTEM. Infinity System Application Instructions DS145

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS REPORT HOLDER: PAREX USA, INC.

For detailed product information, visit our DeckOver, Textured DeckOver or Extra Textured Deckover product pages.

COMMERCIAL MAINTENANCE & REPAIR GUIDE

Signature Seal 100 Medium-to-High Sheen Sealer VOC Characteristics and Applications

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FLUID APPLIED ROOFING REPORT HOLDER: METACRYLICS

Product Information CHEMGLAZE B 9942 A/B. Coating for Casting Pits. Easy Application Chemglaze B 9942 A/B will bond to damp and wet surfaces.

ITEM 458 WATERPROOFING FOR STRUCTURES

DIVISION 9 FINISHES Section Floor Finishes

OLD BRICK ORIGINALS KILN-FIRED THIN BRICK VENEER Installation Guide. RobinsonBrick.com

Part of the Sikaplan WT Membrane System

DuPont ChromaClear G2-4700S (Hyper Cure - Air Dry and Express Bake)

General Applications Before applying, mix the pre-measured catalyst* into Liquid Roof by following label directions.

GigaCrete Specification PlasterMax. PlasterMax : Fire Rated Plaster for Direct Application over Cement Masonry Units (CMU) Interior Walls

Canadian Construction Materials Center # R

DURA 500 THERMOPLASTIC FLAT ROOF COATING SYSTEM BY SUPERIOR POLYMERS INC.

Corlar LV PR 178 Series Epoxy Primer

1. Rapid Set Cement. 2. Methods of preparation. 3. How to stage a job site. 4. Installation Mix, place, finish. 5. Coloring the TRU.

SECTION CONCRETE AND MASONRY COATINGS

SECTION SIMULATED STONE MASONRY

Blue Barrier Liquid Wrap 2300

A. Section includes surface preparation and the application of high-performance coating systems on the following substrates:

CROMAX PRO WB9908 SUPER JET BLACK BASECOAT

INSTALLATION MANUAL. METAL INSULATED PANELS -ROXUL -Expanded Polystyrene

Encore Countertop Instructions

Scotch-Weld Metal Bonder Acrylic Adhesive DP8407NS Gray

TREAT RISING DAMP AND REDECORATE IN UNDER 24HRS

Vulkem EWS with PUMA Technology (Heavy Duty) APPLICATION INSTRUCTIONS

PRODUCT GUIDE: ZINC-RICH COATINGS. Version:

Construction. Pulastic Coating-221 W. 2 Component Polyurethane

Dynamic Bonding Systems B.V. A division of Dutch Bonding Group B.V.

HYDRAULIC GATE SEALS. Industrial Rubber Supply (1995) Ltd.

GENERAL SHALE NATURAL THIN ROCK VENEER Installation Guide. GeneralShale.com

ASTEC ANTI-GRAFFITI CLEAR COATING POLYURETHANE SILICONE MODIFIED TYPE. Aliphatic 2 Pack Polyurethane Anti-graffiti coating. PRODUCT DESCRIPTION

Soft Grip. WATERBASED Anti-Slip Coatings

1.5 SUBMITTALS A. General: Submit samples, product data, shop drawings, warranties and certificates in accordance with

OUTSULATION SMD SYSTEM

TRANSPORT II " 10.5" MOUNTING POSTS FENCE LINE POST. Classic gate shown GATE OPENING CANTILEVER GATE SAFETY WARNING

APPLICATION INSTRUCTIONS.

REPORT HOLDER: COREV AMERICA BRITTMOORE PARK DRIVE HOUSTON, TEXAS EVALUATION SUBJECT:

32 Sq ft Kit Technical Data Sheet

2. Drying and curing of concrete shall be 28 days 2. Wind-lock B-Ml mixing blade or equivalent

DESIGN GUIDELINE FLUID-APPLIED WATERPROOFING

General Guidelines Solutions for Facades Application of Sikasil Weather Sealants. January 2010 / Version 1

64C1-2-A High Temperature Resistant Insulative Coating

PALISADE PD 40 SECTION SOLAR CONTROL FILMS. A. Optically clear Titanium Nitride ceramic sputtered polyester film for solar control.

QUALITY ASSURANCE MANUAL FOR APPLICATORS OF ELASTOMERIC SHEET LININGS

SECTION IMPACT RESISTANT WALL PROTECTION

COMPOSITE (WPC) ENGINEERED VINYL FLOORING INSTALLATION

INSTALLATION INSTRUCTIONS FOR GERFLOR TARASAFE ULTRA VINYL SHEETGOODS

Associated Spec Consultants, Inc. February 27, 2014 SECTION ARCHITECTURAL COATINGS

Freedom One-Piece Barrier Free Showers Installation Instructions

Paint to Protect TM International Fireproof Technology, Inc Von Karman Ave. Irvine, CA 92614

1.2 Reference Standard: NOFMA - National Oak Flooring Manufacturers Association Grading Standards.

SECTION 1045 PAINT FOR STRUCTURAL STEEL

Application Guide AC- 130 Metal Alloy Surface Preparation For Bonding

Section Fluid Applied Waterproofing

Corlar 2.8 HG High Solids Epoxy

GEOGARD LO Base Coat / GEOGARD Finish Coat

SECTION WINDOW FILM. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved

STORAGE AND TRANSPORTION

HEAD OFFICE 22 Park Drive Dandenong VIC Phone: (03) Fax (03)

Low cost because floor renovation can be completed the same day

Transcription:

REFLECTIT 100% Acrylic Coating Providing a Pearlescent Appearance Reflectit Application Instructions Spray and Roller

Tools Required for Application of Reflectit Spray Application 1. Stainless Steel Trowel 2. Palm Sander or Foam Sanding Block 3. Fine or Very Fine Sandpaper 4. Air Compressor capable of maintaining 12 CFM (5.66 L/s) or above 5. Wind-lock B-M1 Mixing Paddle or equivalent 6. High-torque 1/2 in (12.7 mm) Variable Speed Drill 7. Nylon Stocking or Fine Mesh Paint Screen (Trimaco Standard Paint Strainer 11583/12FF or equivalent) 8. Delmhorst Moisture Meter Model #BD-2100 9. Nursery Shade Cloth 10. Binks 2001 or 2100 Stainless Steel Spray Gun 11. 66SS Fluid Nozzle 12. 66SD Air Nozzle 13. 12 ft (3.7 m) Air and Fluid Hoses 14. Binks dual regulated pressure tank Tools Required for Application of Reflectit Roller or Brush Application 1. Wind-lock B-M1 Mixing Paddle or equivalent 2. High-torque 1/2 in (12.7 mm) Variable Speed Drill 3. Delmhorst Moisture Meter Model #BD-2100 4. Nursery Shade Cloth 5. 1 in (25 mm) Nap Polyester or Polyester Blend with Nylon or Lamb s Wool Roller Cover with Beveled Ends and Phenolic Core 6. 18 in (460 mm) Wide, Double Pressure Roller Frame with 2 1/4 in (57 mm) inside diameter 7. 4 in ((102 mm) Wide Roller for cutting in 8. 100 % Nylon Bristle Brush (very small areas only) Training: The contractor applying Reflectit shall be experienced in spraying or rolling high gloss coatings and shall have been trained by Dryvit Systems, Inc. Field Service personnel in the proper application of SkimIt, Color Prime and Reflectit. Dryvit Systems, Inc. does not guarantee the workmanship of trained contractors. 2

I. Spray Application Instructions A. General Instructions. The following instructions apply to using Binks pressure pot spray equipment. B. Mock-up 1. It is strongly recommended that a minimum 8 ft x 8 ft (2.4 m x 2.4 m) area of actual project or mock-up wall be sprayed with Reflectit for the approval of the color and overall appearance by the owner/architect. This area should include individual panels of a minimum 2 ft x 2 ft (0.61 m x 0.61 m) to a maximum 5 ft x 5 ft (1.5 m x 1.5 m) [or 25 sq ft (2.3 m 2 ) with the vertical height not being more than 5 ft (1.5 m)]. The mock-up serves as the basis for approval for the project done under actual project conditions using the tools and materials that will be used on the job. In addition, it allows the applicator to refine any necessary techniques specific to the project. C. Material Preparation 1. Reflectit a. Order enough Reflectit in order to complete the project with a single batch whenever possible. If more than one batch is needed, material should be boxed to minimize color differences from batch to batch. b. There will be some separation in the Reflectit and soft settling. This is normal and the material can be easily mixed to uniformity. Just prior to application, mix Reflectit for 1 minute to ensure uniformity using a Windlock B-M1 mixing paddle or equivalent driven by a high-torque 1/2 in (12.7 mm) variable speed drill, at maximum 400-500 RPM, just enough to maintain a vortex. Mix all the pails the same length of time. DO NOT OVERMIX. Water addition is not necessary. c. Strain the Reflectit using a nylon stocking or fine mesh paint screen. A Trimaco standard paint strainer 11583/12FF or equivalent is recommended and available at local paint stores. 2. Color Prime a. Color Prime is required where the substrate has been coated with Dryvit SkimIt (see SkimIt data sheet DS847 for application instructions). Color Prime is not required where the substrate is a new Dryvit finish, but is recommended to even out absorption of the Reflectit into the finish and improve uniformity of appearance. Just prior to application, mix Color Prime for 1 minute to ensure uniformity using a Wind-lock B-M1 mixing paddle or equivalent driven by a high-torque 1/2 in (12.7 mm) variable speed drill, at maximum 400-500 RPM, just enough to maintain a vortex. DO NOT OVERMIX. b. Add approximately one-half gallon (1.9 liters) water per 5 gallon (19 L) pail of Color Prime. Mix all the pails the same length of time and make the same water-add to each pail for a particular batch. DO NOT OVERMIX. D. Surface Preparation 1. A spray applied finish will accentuate surface imperfections. When attempting to replicate smooth glossy panels it is necessary to skim out the base coat a second time with the Dryvit Primus, Genesis, Primus DM, Genesis DM or Genesis DMS mixtures to obtain a flat and level surface. It is critical that the base coat surface be smooth, flat, and free of imperfections prior to application of SkimIt or smooth finish. Refer to appropriate Dryvit product data sheet for mixing instructions and application. 2. Apply Dryvit finish as specified to the properly prepared clean and dry base coat. When attempting to replicate smooth glossy panels, apply a finely textured Dryvit finish such as Lymestone or Freestyle in two tight passes minimizing trowel marks. Apply on controlled panel area, of a minimum 2 ft x 2 ft (0.61 m x 0.61 m) to a maximum 5 ft x 5 ft (1.5 m x 1.5 m) [or 25 sq ft (2.3 m 2 ) with the vertical height not being more than 5 ft (1.5 m)]. Due to the reflective nature of Reflectit, larger smooth areas will be more difficult to finish and achieve acceptable aesthetics especially during critical light conditions. ~OR~ 3. Apply SkimIt in accordance with SkimIt application instructions on product data sheet DS847 to a properly prepared base coat. Completely and carefully remove any dust from sanding of the SkimIt before applying Color Prime. Apply on controlled panel area, of a minimum 2 ft x 2 ft (0.61 m x 0.61 m) to a maximum 5 ft x 5 ft (1.5 m x 1.5 m) [or 25 sq ft (2.3 m 2 ) with the vertical height not being more than 5 ft (1.5 m)] to ensure aesthetics will not be compromised. 4. The SkimIt or finish must be completely dry before applying Color Prime and/or Reflectit. Test the SkimIt or finish for dryness with a moisture meter. The meter reads zero when the probe is inserted into a dry finish. The Delmhorst Moisture Meter model #BD-2100 is recommended. Contact Delmhorst at 1-877-335-6467 or www.delmhorst.com. Do not apply SkimIt over Color Prime or Reflectit. 5. Apply a uniform coat of the specified color-coordinated Color Prime by spray using the same equipment, procedures and techniques as for the Reflectit as described below. Allow Color Prime to dry at least twelve (12) hours or until completely dry. 3

E. Application Conditions 1. Air and surface temperatures for application of Reflectit must be between 50 F (10 C) and 90 F (32 C) and must remain so for a minimum of 24 hours. Avoid spraying on windy days or airborne Reflectit material will mist unprotected surfaces and also result in a non-uniform appearance. To prevent cratering of the finish, avoid positioning the spray gun closer than 16 in (0.4 m) from the wall. Spray in the shade. When spraying on sunny days, shade the wall using nursery shade cloth or other appropriate method. Avoid spraying onto a wall surface that is over 90 F (32 C). Spray application over warm, hot surfaces will cause the Reflectit to dry too quickly affecting gloss and appearance compared to Reflectit spray applied over cooler surfaces. F. Equipment The following illustrations are provided by Binks. 1. A Binks 2001 or 2100 stainless steel spray gun is required for spray application of both the Reflectit and the Color Prime. A 66SS fluid nozzle and a 66SD air nozzle, (which is an external mix air cap) are required. 2. The Binks spray gun is to be used in conjunction with a Binks dual regulation (air and fluid) pressure tank. 3. A compressor capable of maintaining 12 cubic feet per minute (CFM) (5.66 L/s) at 80 psi (552 kpa) or above working pressure is needed. A four horsepower compressor is usually adequate. G. Spray Techniques 1. Attach air line from compressor to tank. Make sure both air and fluid pressures are set to zero. 2. Turn up the fluid pressure to approximately 10 psi (69 kpa) 3. Pull the trigger on the spray gun until a stream of Reflectit begins to flow (use a clean container to collect the Reflectit material). The stream should flow out approximately 7 1/2 in (19 cm) before it begins to fall off. Adjust the fluid pressure until this happens. The resulting fluid pressure should be in the range of 10-15 psi (69-103 kpa). 4

4. With the fluid pressure at the appropriate setting, turn up the air pressure to approximately 40 psi (276 kpa). Spray apply on a scrap piece of uniformly colored sheathing or other similar surface in a vertical orientation while adjusting the air pressure to achieve proper atomization of the Reflectit. The resulting air pressure should be 35-45 psi (241-311 kpa). Hold the gun about 16 in (40 cm) from the surface and spray for several seconds. The atomized Reflectit should appear in a uniform oval pattern approximately 20 in (51 cm) long by 4 in (10 cm) wide. See the section below, provided by Binks, to adjust if this is not the case. FAULTY PATTERNS AND HOW TO CORRECT THEM PATTERN CAUSE CORRECTION Dried material in side-port A restricts passage of air. Greater flow of air from cleaner side-port B forces fan pattern in direction of clogged side. Dissolve material in side-ports with thinner, then blow gun clean. Do not poke into openings with metal instruments. Dried material around the outside of the fluid nozzle tip at position C restricts the passage of atomizing air at one point through the center opening of air nozzle and results in pattern shown. This pattern can also be caused by a loose air nozzle. Remove air nozzle and wipe off fluid tip using rag wet with thinner. Tighten air nozzle. A split spray or one that is heavy on each end of a fan pattern and weak in the middle is usually caused by: (1) Too high an atomization air pressure (2) Attempting to get too wide a spray pattern with thin material. Reducing air pressure will correct cause (1). To correct cause (2), open material control to full position by turning to left. At the same time, turn spray width adjustment to right. This will reduce width of spray, but will correct split spray pattern. 5. Mask off adjacent areas of the panel to protect from overspray. Hold the gun approximately 15-18 in (38-46 cm) from the wall to achieve a fan of 20 in - 24 in (50 cm - 60 cm). Hold the gun perpendicular to the wall and make steady passes parallel to the wall moving approximately 1.5-2.0 ft/sec (0.5-0.6 m/sec) horizontally across the panel with 50 % overlap. Passes should be approximately 5 in (13 cm) apart. Follow with similar passes in a vertical direction. This is considered one cross hatch pattern and is the first coat of Reflectit. 6. Allow the first coat of Reflectit to dry for a minimum of 30 minutes or until dry to the touch. Spray a second coat using the same procedure as the first. Remove masking tape while the Reflectit is still wet. When dry, the panel should have a uniform, shiny appearance. Protect from rain for a minimum of 24 hours, or until dry. II. Roller Application Instructions A. Mock-up 1. It is strongly recommended that a minimum 8 ft x 8 ft (2.4 m x 2.4 m) area of actual project or mock-up wall be roller applied with Reflectit for the approval of the color and overall appearance by the owner/architect. This area should include individual panels of a minimum 2 ft x 2 ft (0.61 m x 0.61 m) to a maximum 5 ft x 5 ft (1.5 m x 1.5 m) [or 25 sq ft (2.3 m 2 ) with the vertical height not being more than 5 ft (1.5 m)]. The mock-up serves as the basis for approval for the project done under actual project conditions using the tools and materials that will be used on the job. In addition, it allows the applicator to refine the necessary techniques specific to the project. B. General 1. Roller application is only effective on more highly textured finishes, such as Sandblast or coarser. 2. Two coats of Reflectit are required to achieve optimum performance. 3. A maximum 1 in (25 mm) nap polyester or polyester blend with nylon or lamb s wool and with beveled ends and a phenolic core is recommended. 4. An 18 in (460 mm) wide, double pressure roller frame with 2 1/4 in (57 mm) inside diameter is recommended. 5. Make sure that proper staging is provided to maintain a wet edge. 6. Panel sizes shall be limited to a minimum 2 ft x 2 ft (0.61 m x 0.61 m) to a maximum 5 ft x 5 ft (1.5 m x 1.5 m) [or 25 sq ft (2.3 m 2 ) with the vertical height not being more than 5 ft (1.5 m)] NOTE: As with all highly reflective coatings, under critical light conditions, a certain degree of roller marks and other variations may be visible. 5

C. Material Preparation 1. Reflectit a. Just prior to application, mix Reflectit for 1 minute to ensure uniformity using a Wind-lock B-M1 mixing paddle or equivalent driven by a high-torque 1/2 in (12.7 mm) variable speed drill, at maximum 400-500 RPM, just enough to maintain a vortex. DO NOT OVERMIX. D. Surface Preparation 1. The surface to be coated shall be free of dust, dirt, efflorescence, grease, oil, or other materials that may interfere with adhesion of Reflectit. E. Application 1. Apply Reflectit in one continuous coat, maintaining a wet edge as the application proceeds to a natural break. 2. The roller cover must be kept fully loaded as the application proceeds. 3. Do not stretch out the application by rolling with a dry roller. The last leveling roller strokes should always be in the same direction to minimize lap marks and avoid directionality of the reflective pigments. 4. Do not cut in around openings prior to overall application, but rather, do the cut in work as the application proceeds. A 4 in (100 mm) wide roller is recommended for cut in work. NOTE: Where cutting in, Reflectit may be thinned down with water to prevent excessive build-up. Brush application is ONLY recommended on very small areas when use of a roller or spray gun is not practical. 5. Allow first coat of Reflectit to completely dry prior to applying the second coat. Second coat of Reflectit shall be applied in the same manner as the first coat. Troubleshooting Assistance Contact your Field Service Manager for additional information and / or recommendations. DISCLAIMER Information contained in these application instructions conforms to standard detail and product recommendations for the installation of the Reflectit as of the date of publication of this document and is presented in good faith. Dryvit Systems, Inc. assumes no liability, expressed or implied, as to the architecture, engineering or workmanship of any project. To insure that you are using the latest, most complete information, contact Dryvit Systems, Inc., at: One Energy Way West Warwick, RI 02893 (401) 822-4100 Dryvit Systems, Inc One Energy Way West Warwick, RI 02893 (800) 556-7752 www.dryvit.com For more information on Dryvit Systems or Continuous Insulation, visit these links. Printed in USA. Issued 10-04-16 6 Dryvit Systems, Inc. 2008