CONCEPTION OF A HIGH PRECISION MEASUREMENT ROOM

Similar documents
HEAT RECUPERATION IN VENTILATION SYSTEM OF BASEMENT LABORATORY

Computational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study

Clean-room technology for the pharmaceutical industry and for the industrial sector. Overall solutions. And the required products.

MEASURING THE DYNAMIC TWISTING BEHAVIOUR OF SAW BLADES IN THE KERF DURING THE SAWING PROCESS

The Centre for Sustainable Building (ZUB) * A Case Study

Numerical Modelling of Air Distribution in the Natatorium Supported by the Experiment

Detail catalogue for multistory timber buildings

TABLE OF CONTENT. Equipment kit Description of the technology Installation of equipment Start of construction...

Earth, Wind & Fire Natural Airconditioning [1] Research objectives and Methods

A Solar Wall System Utilized in Rural Houses of Northeast China

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

P. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract

KNX-based Energy Efficient Heating and Lighting in Educational Buildings

Structural assessment of the integrated steel fly-overs widening the historic multiple-arch concrete viaduct over the Pede valley

DISPLACEMENT VENTILATION

POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Bruck an der Mur. Project summary. Energy concept: Background for the renovation reasons

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

Feasibility study of a roof top Solar room heater

STAGNATION BEHAVIOR OF THERMAL SOLAR SYSTEMS

Flexible Vapor Control Solves Moisture Problems of Building Assemblies - Smart Retarder to Replace the Conventional PE-Film

COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS

LOW-ENERGY HOUSING ESTATE SUNDAYS

Conveyor System Technology. krones AirCo. Air Conveyor

STRATEGIES AND PRINCIPLES TO DESIGN ROBUST PRODUCTS

PARTICLE-FOAM COMPOSITE INJECTION MOLDING

Observation of Liquid-filled Window without Presence of Liquid in Test Chamber

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

CHAPTER 6 : GAS SAMPLING SYSTEMS

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

Observation and numerical simulation of melt pool dynamic and beam powder interaction during selective electron beam melting

ARPAN JOHARI. Architect. 13/08/10 AW Design. Ahmedabad

An experimental investigation of a passive chilled beam system in subtropical

EVALUATION OF THE THERMAL PERFORMANCE OF FIVE REFRIGERATED VANS

Model FD 115 Drying and heating chambers Avantgarde.Line with forced convection

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

MEP's Letter of Assurance

CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION

Quality from the Depth of the Mold

Analyzing & Testing. Guarded Hot Plate - GHP. Method, Instrumentation, Applications. GHP 456 Titan. Leading Thermal Analysis

Development of Energy-Saving High-Performance Continuous Carburizing Furnace

Thermal Energy Storage in Office Buildings Foundations

FLUXUS F601. Portable, quick and reliable. Clamp-on ultrasonic flow meter. Measure from outside what's flowing inside

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

NEC Acostix. Sound Attenuation Calculations and Design Software. General Information

Hourly Analysis Program v.4.1 Page 1 of 1

MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

Equipment for Engineering Education

Understanding Extrusion

Solar Passive Techniques: Earth Air Tunnel

ECO-THERM. MOBILE FACTORY Technical information on innovative construction methods

Sustainable Renovation and Redevelopment. Khuong Nguyen - Kirill Volskii - Mariia Smirnova - Paz Gonzalez Group 10

Local Temperature Measurements on Full-Size Systems in the Laboratory: Insight into the Extent of Thermal Bridges in Building Envelope Components

Great Ocean Rd Ice Creamery

Save with Business Programs and Services

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA

Attached Solar Greenhouse Plans for a solar heated greenhouse attached to your home

Standard Test Method of Measuring Shrinkage from Mold Dimensions of Thermoplastics 1

WHITE PAPER. HVLS Industrial Fans Evaluation Guide: 7 Defining Application Design Factors That Will Add Up to a Smart Investment

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

Design guidelines for direct ground cooling systems in different climates

Flow investigations for fish pass Lauffen/Neckar in field and laboratory

Technical Information

Hourly Analysis Program v.4.1 Page 1 of 1

THERMAL PERFORMANCE OF MASONRY

Energy Efficient Buildings in Germany An Introduction

A Case Study of the Design Calculation for a Logical Biogas Plant

Advanced simulation methods for heat pump systems

General European OMCL Network (GEON) QUALITY MANAGEMENT DOCUMENT

HOLISTIC QUALIFICATION IN MANUFACTURING METROLOGY BY ENHANCING KNOWLEDGE EXCHANGE AMONG DIFFERENT USER GROUPS

ENERGY EFFICIENCY IN BUILDINGS AND COMMUNITIES

100 % SOLAR HEATED MONOLITHIC CLAY BLOCK HOUSE

Effect of Rotation Speed of a Rotary Thermal Wheel on Ventilation Supply Rates of Wind Tower System

Underf loor For Schools

Energy Efficiency. best in class

Attic Insulation. Student Guide

Modelling Approaches for Displacement Ventilation in Offices

These systems are offered an alternative to overhead, mixing ventilation (MV), systems. Due to their potential advantages which are [1]:

QINEO PULSE. The versatile welding machine for industry

EXPERIMENTAL INVESTIGATION ON COOLING RATE FOR CENTRIFUGAL CASTING Kirti Kanaujiya, Yugesh Mani Tiwari Department of Mechanical Engineering

Steam Power Station (Thermal Station)

DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS

A Comparative Study of Medium Deep Borehole Thermal Energy Storage Systems Using Numerical Modelling

Parameters of the Atmospheric Air in the Dimensioning of Industrial Cooling Tower

Controls and Software CHORE-TRONICS 2 Controls

PRODUCT BROCHURE. Fixed Helical Swirl Diffuser HSC-FD HSC-FD : smartemp.com

Real-time X-ray radioscopy on metallic foams using a compact micro-focus source

KEYNOTE LECTURES REGULAR SESSIONS. Special Sessions AND mini-symposia. SESSION index

Designing Air-Distribution Systems To Maximize Comfort

EFFECTIVE THRUST TRANSFORMATION INSIDE TUNNELS WITH JET FANS (BANANA JET)

Performance Efficiency Standard for Evaporative Cooling Equipment

Controls and Software CHORE-TRONICS 2 Controls

Electromagnetic Shielding of the Powerful Turbogenerator Stator End Zone

Work environment. Microclimate - definition. Main microclimate elements. Core temperature. Microclimate

Transcription:

CONCEPTION OF A HIGH PRECISION MEASUREMENT ROOM A. Weckenmann and W. Scharf Chair Quality Management and Manufacturing Metrology University Erlangen-Nuremberg, D-91054 Erlangen, Germany Abstract: The aim of a high precision measurement room is to minimize most of the disturbing influences on the measuring devices installed in the measurement room by structural organization. The goal of scientific research in the field of manufacturing metrology is in particular the improvement of the measurement accuracy in the micro- and sub-micrometer range with simultaneously desired automation of the measurement procedures. In each case, reliable results must be obtained according to the internationally defined units for the success of the research work and for the acknowledgement of the results in the professional world. This is only possible under most extensive exclusion of the disturbing environmental influences in a measurement room of highest grade, which is particularly shielded and kept at constant temperature. Keywords: measurement room, precision dimensional measurement, air conditioning 1 INTRODUCTION Each measurement result is joined by deviations. Both the result s value and the uncertainty of measurement depend on a huge number of influences. Substantially, these influences are caused by the measuring instrument, the workpiece, the operator and the environment. The ratio between deviations caused by environment and measuring instrument is approximately 10:1 [1]. Therefore, highest requirements regarding the minimization of environmental influences are necessary to fulfill research tasks in the field of manufacturing metrology or precise measurements. Scientific realizations or precise measurements will only be accepted by experts if the predications are reliable or the measurement results are restorable [2]. This is given if the environmental conditions are documented during the moment of measuring. In consequence, the main task of a measurement room is to minimize influences by the environment and to keep them on a well-known, constant level. Figure 1. The new measurement room building of the University Erlangen-Nuremberg, Chair Quality Management and Manufacturing Metrology

The most important environmental measurement influences are: temperature (thermal conduction, convection and radiation) vibrations humidity pollution The structural organization of a measurement room ensures that most of these disturbing influences will be reduced and kept constant. Some recommendations relating to the conception of measurement rooms are given in VDI/VDE 2627 [3], but only partially fit the requirements of a high precision measurement room. The new high precision measurement room of the University Erlangen- Nuremberg demonstrates the demands for such a building and features of technical realization. 2 CONCEPTION OF A HIGH PRECISION MEASUREMENT ROOM The aim for planning a high precision measurement room is to minimize by structural organization most of the disturbing influences on the measuring instruments installed in the measurement room and the measuring process. The Chair Quality Management and Manufacturing Metrology as the user of the building describes the requirements regarding the environmental conditions in consideration of the accuracy of the instruments and the future measuring tasks as a base for all further planning. Table 1. Requirements regarding the environmental conditions of the new measurement room of the University Erlangen-Nuremberg Characteristic Requirements Dimensions length 13,2 m width 8,0 m height 5,9 m area 110 m 2 Volume 623,0 m 3 Air circulation ratio per hour 17 Percentage of fresh air 5% - 10% Base Temperature 20 C ± 0,1 C Operating temperature range 18-25 C Allowable temporal temperature deviations DT during 1h 24h Allowable spatial temperature difference DT per 1m totally 0,1 K 0,3 K 0,1 K 0,5 K First step towards the conception of a measurement room is the search and selection of an optimal location for the building which is oriented to aspired uncertainty of future measuring tasks. With extensive investigations and ground-analysis on vibrations, the suitability of the planned location was acknowledged. In addition, the loose sandy soil at the location makes a flexibly stored foundation of the measurement building redundant. The reinforced concrete base plate of the actual measurement room with a thickness of 1 meter is isolated from the ground only by a mineral material insulating layer for the avoidance of thermal conduction. A seam around the base plate prevents direct contact to the remaining foundation of the measurement room building and in such a manner it also prevents a transfer of building oscillations through the base plate on the installed measurement devices [4]. The function of the air conditioning system is to keep the measurement room at a basic temperature within the given limits spatially and temporally during operation. For later operation, the air conditioning system must be qualified to compensate thermal interference and minimize spatial temperature gradients. The basis for planning and dimensioning the air conditioning system results from an exact analysis of all expected interferences. From the beginning, suitably choices of constructional measures might reduce or weaken those influences. The measurement room is protected against thermal interference with state of the art technology. Electrical heating conductors in the neutral fiber of the base plate let the temperature of the floor remain accurately at the given base temperature. The thermal input due to the lights is minimized by

an additional air exhaust in the light-system of the dome lamps. Inside the measurement room, the walls are covered with hollow section metal elements, which are equipped with rectangular openings towards the inside of the measurement room. The air will be fed back to the air conditioning through these openings. The exhausted air warms up the wall panels up to the basic temperature and isolates them from the colder main construction walls. The external walls are thermally isolated by mineral material insulating layers. To remove a local, intermittent heat load the measurement room is divided into four quadrants, and the middle temperature in each of these quadrants will be recorded by Pt-100 double sensors. The air conditioning system is concepted that each quadrant can be regulated independently. With a room height of 5.90 meters a considerable space volume of 623 m 3 is available, which additionally absorbs temporary thermal interferences. The large room height enables a good mixture of the turbulent injected air. 21,40 m Rooter Air Condition I 5.45 m 2 60,68 m 2 Measurement Room 108,03 m 2 14,30 m Stairhall I 18,70 m 2 Sluice 8,00 m 2 PC Preparation 35,14 m 2 PreSluice 11,88 m 2 Archive 13,20 m 2, Entrance 4,95 m 2 Figure 2. Basement of the measurement room building of the University Erlangen-Nuremberg Because of temporally different temperature levels which may occur within the four-quadrant conception, a strict temperature plausibility check is necessary. The application of Pt-100 double sensors permits a mutual alignment and avoids an unwanted automatic controller action of the climatic-technical system with malfunctions of the temperature entry. With an uncertainty of ± 1 mk and a resolution of 0.1 mk the assigned resistance of the temperature measuring bridge enables an uncertainty of the entire temperature measuring chain less than 0,01 K and thereby fulfills all requests regarding the spatial and temporary temperature stability. 3 DESCRIPTION OF THE AIR-CONDITIONING SYSTEM To obtain reliable measurement results a climate with defined values for temperature, humidity, air pressure, air speed and particles is necessary. It is task of a air conditioning system to heat, cool, humidify, dry, filter and circulate the air [5]. A lot of factors are to be taken into account while laying out an air conditioning system. Figure 3 shows a rough order of these factors. Some examples for these factors for the measurement room are displayed here: the average total thermal output of the installed instruments including the operators was estimated with 10 kw (to minimize thermal fluctuations all thermal loads will be kept running); the external climate for summer time was defined with an average temperature of 32 C and a relative humidity of 40%, for winter time is was defined with an average temperature of -12 C and a relative humidity of 80%.

1000 m 3 /h 300 m 3 /h Lights Meassurement R oom Ceiling Preparation 960 m 3 /h Pre-Sluice Sluice Archive 5400 m 3 /h 10800 m 3 /h 11300 m 3 /h 2820 m 3 /h 600 m 3 /h 1400 m 3 /h 7650 m 3 /h 11300 m 3 /h 2820 m 3 /h 2000 m 3 /h 2000 m 3 /h Figure 3. Structure of the air conditioning system ISO 1 defines the reference temperature to be 20 C [6]. Normally, the air conditioning system of a measurement room is planned for a fix operating point which is equal to the reference temperature. The air conditioning system of the considered measurement room can work at any operating point in the range between 18 C and 25 C. In the future, this enables the investigation of different ways for economizing the energy and running costs and protecting the investment against changes in standards which were fundamental when planning the air conditioning system. For this purpose, a lot of parameters of the air conditioning system i.e. heating and cooling capacity, airflow rate, cross section of outlets must be variable. The system must be capable of ensuring the required characteristics both in the cooling and in the heating mode. For this reason, the chosen operating point will always be reached from the same direction. The ingoing air as a mixture of fresh air from outside and circulated air from the measurement room will first be cooled down to a temperature of 5 C and then heated up in two steps to the demanded temperature of the operating point. To ensure an ideal mixture of the air in the entire measurement room in the heating mode, the ingoing air will be blown in by radial fans and the outgoing air exhausted also by radial fans. The quantity of the ingoing air is more than the quantity of outgoing air. This causes a slight overpressure of about 10 Pa in the measurement room, which prevents the irruption of unfiltered and unconditioned air when doors are opened. The aim of the already mentioned monitoring in 4 zones is to compensate local dispersions of cool load (e.g. caused by a group of people) as well as to generate well defined temperature gradients in the space. Based on these generated temperature gradients, the behaviour of measuring instruments can be analysed. Manipulating variables are the volume flow of the ingoing and outgoing air. The air flow volumes can be controlled separately in each quadrant of the measurement room. The desired air quantities can be set up either dynamically by changing the number of revolutions of the radial fans or statically by changing the cross section of the ingoing and outgoing air feeder. With respect to the comfortable feeling of the operators in the measurement room, the mean air velocity should not exceed 0,2 m/s. Accordingly, the air changing rate has a value of 17 per hour. To achieve an optimal intermixture of the room air for these low level values, the ingoing air is blown in through twisted inlets. In other comparable measurement rooms the air is blown in laminar through the ceiling and the floor. 4 BENEFITS FOR RESEARCH WORK Normally, air conditioning systems in measurement rooms are calculated for a fixed, given operating point. Apart from the described four-zone regulation a further remarkable property of the air conditioning system is to be pointed out. As a special feature, the system guarantees the required temperature characteristic values at a basic temperature freely eligible in the interval from 18 C to 25 C. Future research work in the measurement room will thus lead to a reduction of measurement uncertainty by including investigations of the temperature influences on measurement devices and results of measurement.

REFERENCES [1] A. Weckenmann, B. Gawande, Koordinatenmeßtechnik, Carl Hanser Verlag, München, 1999 [2] P.H. Osanna, Die Einhaltung konstanter Meßraumbedingungen, gezeigt am Beispiel des Feinstmeßraumes der Technischen Universität Wien, in ME (1981), Nr.9, p.206-208. [3] Richtlinie VDI/VDE 2627, Blatt 1, August 1998. Meßräume - Klassifizierung und Kenngrößen - Planung und Ausführung. [4] H.-G.. Pressel, Genau messen mit Koordinatenmeßgeräten, expert Verlag, Renningen-Malmsheim, 1997 [5] H.J. Warnecke, W. Dutschke [Hrsg.], Fertigungsmeßtechnik - Handbuch für Industrie und Wissenschaft, Springer Verlag, Berlin, 1984 [6] Norm ISO 1, 1975. Standard reference temperature for industrial length measurements. AUTHORS: Prof. Dr.-Ing. A. WECKENMANN and Dipl.-Ing. W. SCHARF, Chair Quality Management and Manufacturing Metrology, University Erlangen-Nuremberg, D-91052 Erlangen, Germany Phone Int +49 9131 85 26521, Fax Int +49 9131 26524, E-mail: qfm@qfm.uni-erlangen.de URL: http://www.qfm.uni-erlangen.de