MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

Similar documents
MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

P.V.C. INSULATED UNARMOURED COPPER CABLES

Cables for Railway Signalling Applications General Requirements

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

MTSP MANUFACTURE AND SUPPLY OF INSULATED RAIL JOINTS

Electrical Networks Principles and Performance

INTERNATIONAL STANDARD

Technical Specification for Single Core 38/66kV TR-XLPE Insulated Underground Cable

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

NPS/001/007 Technical Specification for Overhead Line Conductors

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

PHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-BIPV-SM-P125-36

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR

PHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-P156-60

Single core conductor BETAtherm 145

XLPE CABLE (11KV - Aluminium)

Technical Specification for LV ABC Fuse Switch Disconnectors

Factors Affecting Current Ratings for Underground and Air Cables

U.V resistance UL Sunlight Resistance. Flame retardant IEC

INTERNATIONAL STANDARD

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

Construction guideline

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

TECHNICAL SPECIFICATION FOR CONDUCTORS

Electricity Safety (Electric Line Clearance) Regulations 2010

15 kv EPR Insulated, Jacketed, URD Cable

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

TESTING PTE EARTHING

DOMESTIC ELECTRICAL INSTALLATION PERIODIC INSPECTION REPORT (FOR A SINGLE DWELLING) B ADDRESS AND DETAILS OF THE INSTALLATION Address: SPECIMEN

*** Supercedes: BECO E and COM , , & ***

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

CHAPTER 5 METERING REQUIREMENTS

BILLION POWER. Your one stop Supplier for all kinds of Solar Modules and BOS. Scan this quickmark,to visit our website.

MTM REQUIREMENTS METROPOLITAN TRAIN MAINTENANCE DEPOT

Engineering Recommendation G81 Part 7 Issue

Distribution System Design General Requirements

Specification Technical Requirements for Revenue Electricity Meters

TECHNICAL SPECIFICATIONS FOR AERIAL BUNCHED CABLES FOR OVERHEAD DISTRIBUTION

Standard of Practice - Campus Electrical Distribution System

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH THE ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS

Product Application. Prestige Power Post in White Epoxy Coated Aluminium Finish

TECHNICAL SPECIFICATION A.B. CABLE

DATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0

NPS/002/001 Technical Specification for Earthing Materials

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION

Specifications: Ice point resistance: Fundamental interval (0 C to 100 C): 38.5Ω (nominal)

ELECTRICAL CODE TRADE REFERENCE

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

ENGLISH Datasheet Platinum Resistance Pt100 & Pt1000 Thin Film Detectors Platinum Sensing Resistors Thin Film (Pt100 & Pt1000 Ohm)

Installation Address. Postcode. Purpose of the report This form to be used only for reporting on the condition of an existing installation.

OSHA Subpart V: Power Transmission and Distribution. Cleveland State University Work Zone Safety and Efficiency Transportation Center

MANUFACTURER'S RESPONSIBILITIES AND REQUIREMENTS FOR FACTORY TESTS

ENGLISH. 1metre 7/.02mm Teflon insulated twin twisted lead

Engineering Data for Copper and Aluminum Conductor Electrical Cables

Ceramic Ceramic No. of Lead/Wire Lead Allied RS order Dia Ø Length Wires Type Length Code code

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MTST TRACK DESIGN AND CONSTRUCTION

RIS RIS-1800-ENE. Rail Industry Standard for Network and Depot Interface Management Isolation Documentation. Rail Industry Standard

3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series

COMPILED BY APPROVED BY FUNCTIONAL RESP AUTHORISED BY V SINGH. Date: 16/03/2009. Date: 16/03/2009. Date: 19/03/2009 Date: 26/03/2009

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.

MCST METROPOLITAN RAILWAY STATIONS

AS/NZS 3010:2005 AS/NZS

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS

SPECIFICATIONS FOR A QUALITY LABEL FOR DECORATION OF COATED ALUMINIUM USED IN ARCHITECTURAL APPLICATIONS Edition

TYPE TEST REPORT OF 11 KV 3 x 240 mm² CU/XLPE/SWA/PVC CABLE. Kinectrics International Inc. Report No.: K RC-0001-R00.

METROPOLITAN RAILWAY NETWORK TRACK OCCUPATION PROTOCOL

Datasheet Platinum Resistance Pt100 Dual Element Industrial Sensor Probe 6mm diameter x 150mm or 250mm probe lengths

WALL LINER PRODUCT DATA SHEET FAÇADE & ROOF SYSTEMS

Document No Amendment No Approved By Approval Date Review Date NS122 POLE MOUNTED SUBSTATION CONSTRUCTION

SECTION WIRES AND CABLES

PT. KABELINDO MURNI Tbk SHIPBOARD CABLE WIRE AND CABLE MANUFACTURER. No. EMS No. OSH No. QCS 00152

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

Tehnical Data Sheet Astro HS FM Compound. UIC of product-type: HSFMC CPR-JA5013 ETA-14/0047. ETAG 026-Part 1 ETAG 026-Part 2

Technical Specification for Live Line Tap Connectors

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Lightning Protection Practice for Large-Extended Photovoltaic Installations

Small Wind Turbine Electrical System Considerations

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

MR 120/2015. SUPPLY OF 2 X 2MVA 415V/11kV 3 PHASE TRANSFORMERS

METERING GUIDE PART 1 METERING GENERAL

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS

ELECTRO-FENCE. Fence Protection System. System Manual. EF_System_V1.1

Technical Data. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE

NR/L2/SIG/11107 Issue: 4 Date: 03/03/2012 Compliance date: 03/03/2012. Ref:

FREQUENTLY ASKED QUESTIONS

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072.

Serv. Low-Voltage Cable Insulated Conductors for Overhead and Underground Distribution

SECTION BASIC ELECTRICAL REQUIREMENTS

Mineral Insulated Platinum Resistance Thermometer PT100 Sensor - Available in 3mm or 6mm diameter x 150mm or 250mm probe lengths

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

«CABLE T 92» WORKSHOP BALI, INDONESIA JUNE, 1992 POWER CABLES IN TROPICAL ENVIRONMENTS : SYNTHESIS. By L. DESCHAMPS SEE / EDF (France)

Thermocouples. Operating and Maintenance Manual English. Thermocouples

Armoured Instrumentation Cables to BS7917

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION

Transcription:

Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED Version: 1 Issued: March 2014 Owner: Electrical Networks Asset Manager Approved By: George Marulli Electrical Networks Asset Manager PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION

Approval Amendment Record Approval Date Version Description 18/03/2014 1 Initial issue under MTM. Supersedes MainCo document MESP 0003 PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 2 of 8

Table of Contents 1. Purpose... 4 2. Abbreviations... 4 3. Definitions... 4 4. References & Legislation... 4 4.1 Standards... 4 4.2 Latest Issues and Amendments... 4 5. Service Conditions... 4 6. Cable Details and Ratings... 5 7. Testing... 5 7.1 Type Test... 5 7.2 Factory Tests... 5 7.3 Test Certificates... 6 7.4 Tests after Delivery... 6 8. Warranty... 6 9. Information to be Supplied by Tenderer... 6 10. Appendix Technical Data Schedule Form... 7 PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 3 of 8

1. Purpose This document is the MTM technical specification for a single core, 400mm 2 Aluminium, stranded Conductor, 1.9kV XLPE Insulated PVC/HDPE Sheathed Electric Cable with a Metallic Screen. This is the standard Cable for 1500V DC use on the MTM Traction System. 2. Abbreviations MTM - Metro Trains Melbourne 3. Definitions For all technical terms refer to AS/NZS 1429.1. Shall Should Is used as the descriptive word to express a requirement that is mandatory to achieve conformance to the standard. Is used as the descriptive word to express a requirement that is recommended in order to achieve compliance to the standard. should can also be used if a requirement is a design goal but not a mandatory requirement. 4. References & Legislation 4.1 Standards The cable shall comply with AS/NZS 1429.1 2006 Electric Cables Polymeric Insulated, Part 1: for working voltages 1/9/3.3 (3.6) kv up to and including 19/33 (36) Kv, with the exception that a Conductor Screen and an Insulation Screen is not required. Note: All materials and components shall comply with the relevant Australian Standard or, where these do not exist, with the relevant IEC or EN Standard. 4.2 Latest Issues and Amendments Reference to all standards shall be read as a reference to the latest edition of that standard and amendments available at the time of tendering. 5. Service Conditions The Cable is to be used on the Melbourne Railway 1500 Volt DC Electric Traction System. This System consists mainly of an overhead catenary wiring construction. It is susceptible to lightning, switching surges and short-circuits. The Cable shall be suitable for use when installed directly in the ground, installed in ducting, on cable racks or trays protected and exposed to the weather and ultra-violet radiation. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 4 of 8

6. Cable Details and Ratings Rated Voltage 1.9 / 3.3 (3.6) kv Cores Single-core, Category A Conductor Material Aluminium Conductor Cross Sectional Area 400mm2 Conductor Stranding Stranded circular compacted Conductor Screen Not Required Insulation Material XLPE Insulation Colour Neutral Insulation Screen Not Required Metallic Screen Material Copper Metallic Screen Nominal Area 50mm 2 Oversheath Material PVC/HDPE, UV Stabilised Sheath Colour Black Metre Markings Required Cable Marking RAILWAY ELECTRIC CABLE 1500V DC Cable Drum Type Wooden Nominal Length of Cable on Drum 400m (±50m) The cable shall be supplied on drums clearly marked with full particulars of the cable, including length. The Cable will be delivered to a location Melbourne, Victoria, which will be nominated at or after the cable is ordered. The length of cable on the drums will be specified separately. 7. Testing 7.1 Type Test 7.1.1 Type Test Certificates shall be supplied on request. 7.2 Factory Tests 7.2.1 The cable shall be subjected to Routine Tests at the Manufacturer s Works as described in AS 1429.1. 7.2.2 MTM reserves the right to appoint a representative to witness these tests. Seven working days notification shall be given to MTM of intention to carry out factory testing. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 5 of 8

7.3 Test Certificates 7.3.1 The results of all tests shall be recorded on test certificates. The test certificates shall clearly show the performance of the equipment and shall be accompanied by tables showing the actually measured values and all calculations. 7.3.2 The test certificates shall be forwarded to MTM and the results approved by MTM prior to delivery. 7.4 Tests after Delivery 7.4.1 After delivery, the cable will be inspected and subjected to such tests as may be considered necessary to determine compliance with this Specification. 8. Warranty The Cable shall be warranted by the Supplier against faulty design, materials, processing and workmanship for a minimum of two years after delivery 9. Information to be Supplied by Tenderer The Tenderer shall inset where provided for all of the information required in the Appendix - Technical Data Schedule Form. Failure to do so may render the offer liable to rejection. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 6 of 8

10. Appendix Technical Data Schedule Form The Tenderer shall supply the following information and guaranteed performance. Compliance Does the cable fully comply with this Specification? YES / NO Manufacturer Name Address Outside Diameter Of Cable (mm) Of Conductor (mm) Of Conductor and insulation (mm) Operating Voltage Rated Operating Voltage (kv) Conductor Nominal Area (mm 2 ) Stranding (mm) Material Form Insulation Material Colour Thickness (mm) Curing Method Metallic Screen Material Nominal Area (mm 2 ) Stranding (mm) Maximum space between Strands (mm) Sheath Material and Type Colour Thickness (mm) Carbon Content (%) Ultra-Violet Stabilised YES / NO PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 7 of 8

Current Rating of Cable (for installation conditions of: 2 single core cables in a single way underground duct, ground temperature 25 C, ground thermal resistivity 1.2 C m/w, depth of laying 0.8m) Continuous Current rating (A) Two Hour Current Rating (A) One Minute Current Rating (A) Short Circuit Current Rating (20 ms) Conductor (ka) Metallic Screen (ka) Maximum Conductor Temperature At Continuous Current Rating ( C) At Short Circuit Current Rating ( C) Maximum Metallic Screen Temperature Screen Transient Maximum Temperature ( C) Weights Weight of Cable (kg/m) Weight of Drum (kg) Dimensions of Drum Outside Diameter (m) Width (m) Diameter of Barrel (m) Nominal Length of Cable on Drum (m) PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 8 of 8