Displacement Based Assessment and Improvement of a Typical New Zealand Building by an Average Engineer

Similar documents
Modelling of RC moment resisting frames with precast-prestressed flooring system

Types Of Roofs - Vault

Introduction to Earthquake Engineering Behaviour of structures under earthquakes

3.5 Tier 1 Analysis Overview Seismic Shear Forces

Structural Glossary. ARCH 631 Structural Glossary F2014abn

Tech Tips SidePlate Connections FAQ 09/30/2017

Interpretation of SECTION 12 DESIGN AND DETAILING FOR EARTHQUAKE LOADS IS

Introduction to Structural Analysis TYPES OF STRUCTURES LOADS AND

ECCENTRICALLY BRACED FRAME DESIGN FOR MODERATE SEISMIC REGIONS

Technical Notes 39A - Testing for Engineered Brick Masonry - Determination of Allowable Design Stresses [July/Aug. 1981] (Reissued December 1987)

Fagà, Bianco, Bolognini, and Nascimbene 3rd fib International Congress

ctbuh.org/papers CTBUH Recommendations for the Seismic Design of High-Rise Buildings

Supplemental Structural Correction Sheet Steel Brace Frame Design (2017 LABC)

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

Scotia Place 12 Story Apartment Building A Case Study of High-Rise Construction Using Wood and Steel WCTE2000

Sabah Shawkat Cabinet of Structural Engineering 2017

DEVELOPMENT OF THE STRUCTURAL DESIGN AND CONSTRUCTION GUIDELINE FOR HIGH-RISE PC BUILDINGS - JAPANESE PC PROJECT

SEISMIC VULNERABILITY ASSESSMENT OF STEEL PIPE SUPPORT STRUCTURES

SEISMIC EVALUATION OF HIGH RISE STEEL STRUCTURES WITH AND WITHOUT BRACING

Behaviour and design of innovative hybrid coupled shear walls for steel buildings in seismic areas

PORTAL FRAMES 1.0 INTRODUCTION

> 0. 1 f, they are treated as beam-columns.

Seismic design of braced frame gusset plate connections

Analysis of Various Steel Bracing Systems using Steel Sections for High Rise Structures

4.2 Tier 2 Analysis General Analysis Procedures for LSP & LDP

22. DESIGN OF STEEL BRACED FRAMES Eccentrically Braced Steel Frames

DUCTILITY REQUIREMENTS FOR BUILDINGS

5.4 Analysis for Torsion

one structural behavior, systems and design Course Description Course Description Syllabus & Student Understandings statics mechanics of materials

Performance Based Seismic Design of Reinforced Concrete Building

Council on Tall Buildings

Overview of Presentation. SCBFs are Conceptually Truss Structures

COST C26. Urban Habitat Constructions under Catastrophic Events EARTHQUAKE RESISTANCE WG 2 Session, March 30th

COMPARATIVE REPORT CYPECAD VS. ETABS

SEISMIC PERFORMANCE OF CONCRETE TILT-UP BUILDINGS: CURRENT WALL-TO-SLAB CONNECTIONS

This point intends to acquaint the reader with some of the basic concepts of the earthquake engineer:

CVEN 483. Structural System Overview

PEER Tall Building Seismic Design Guidelines

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):

THE BRACE CONNECTION THE BOLTED OPTION FIGURE 1 MODEL SHOWING THE BOILER AND THE STRUCTURAL SUPPORT SYSTEM (BOILER BUILDING)

In-plane testing of precast concrete wall panels with grouted sleeve

Torsional Considerations in Building Seismic Design

DESIGN OF GRAVITY-LOAD RESISTING FRAMES FOR SEISMIC DISPLACEMENT DEMANDS

REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS

Comparative Study of R.C.C and Steel Concrete Composite Structures

Design Example 2 Reinforced Concrete Wall with Coupling Beams

Nonlinear Analysis And Performance Assessment for 3D Structure

Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar

LATERAL LOAD BEHAVIOR OF UNBONDED POST-TENSIONED HYBRID COUPLED WALLS. Qiang SHEN Graduate Research Assistant. Yahya C. KURAMA Assistant Professor

SEISMIC ANALYSIS OF SIX STOREYED RC FRAMED BUILDING WITH BRACING SYSTEMS

Evaluation of Earthquake Risk Buildings with Masonry Infill Panels

HYBRID MOMENT RESISTING STEEL FRAMES

Seismic Rehabilitation of Selby Condominium Complex, Montreal (Quebec), Canada

PERFORMANCE OF ECCENTRICALLY BRACED FRAMES UNDER THE ACTION OF LATERAL LOAD

ON DRIFT LIMITS ASSOCIATED WITH DIFFERENT DAMAGE LEVELS. Ahmed GHOBARAH 1 ABSTRACT

Stability Analysis of Rigid Steel Frames With and Without Bracing Systems under the Effect of Seismic and Wind Loads

Steel Seismic Force Resisting Systems

Analytical Study on Seismic Performance of Hybrid (DUAL) Structural System Subjected To Earthquake

ASSESSMENT OF HOLLOW-CORE FLOORS FOR SEISMIC PERFORMANCE. Richard Fenwick, Des Bull and Debra Gardiner

ADVANCES IN DESIGN OF ECCENTRICALLY BRACED FRAMES Egor P. Popov, Kazuhiko Kasai and Michael D. Engelhardt*

optimal design of frp retrofitting for seismic resistant rc frames C. Chisari 1, C. Bedon 2 1

Displacement-based Seismic Assessment: Practical Considerations

Seismic isolation for three buildings in Nicosia

Pile to Slab Bridge Connections

Feasibility and Detailing of Post-tensioned Timber Buildings for Seismic Areas

THE EXTENDED N2 METHOD IN SEISMIC DESIGN OF STEEL FRAMES CONSIDERING SEMI-RIGID JOINTS

SEAU 5 th Annual Education Conference 1. ASCE Concrete Provisions. Concrete Provisions. Concrete Strengths. Robert Pekelnicky, PE, SE

Effect of Concentric Braces on the Behaviour of Steel Structure by Pushover Analysis

Evaluation of Seismic Behavior for Low-Rise RC Moment Resisting Frame with Masonry Infill Walls

PERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140)

SEISMIC SHEAR FORCE MAGNIFICATION IN RC COUPLED WALL SYSTEMS, DESIGNED ACCORDING TO EUROCODE 8

CHAPTER 8 THE DESIGN AND ANALYSIS OF MULTI-STORY BUILDINGS WITH LARGE MOMENT END-PLATE CONNECTIONS 8.1 INTRODUCTION

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)

International Journal of Advanced Structural Engineering, Vol. 3, No. 1, Pages , July 2011

Gravity Load Collapse of Reinforced Concrete Columns with Brittle Failure Modes

Jurnal Teknologi STEEL WEIGHT SAVING DEVELOPED FROM SEMI- CONTINUOUS CONSTRUCTION IN MULTI-STOREY BRACED STEEL FRAME BASED ON EURO-CODE 3.

A Guide for the Interpretation of Structural Design Options for Residential Concrete Structures

Application of Buckling Restrained Braces in a 50-Storey Building

EVALUATION OF THE NEED FOR WEAK BEAM-STRONG COLUMN DESIGN IN DUAL FRAME-WALL STRUCTURES

The cracking behaviour of reinforced concrete beams under static and dynamic loading

SEISMIC BEHAVIOUR OF RC BUILDING RESTING ON PLAIN AND SLOPING GROUND WITH BRACINGS AND SHEAR WALL

MITRE 3 Building McLean VA

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

CONNECTION PERFORMANCE OF BUCKLING RESTRAINED BRACED FRAMES

Development of a Frame for Wide Openings in Residential Construction

Deformation Capacity of RC Structural Walls without Special Boundary Element Detailing

Strength Design of Reinforced Concrete Structures

Diaphragms 2. Design Process. Design Process. Diaphragms are the roofs and floors of the upper stories

Section A A: Slab & Beam Elevation

Special Reinforced Concrete Structural Walls

for Hamilton City Council

OPTIMUM POSITION OF OUTRIGGER SYSTEM FOR HIGH RAISED RC BUILDINGS USING ETABS (PUSH OVER ANALYSIS)

Seismic Analysis and Design of Vertically Irregular RC Building Frames

DESIGN OF WALLS FOR SHEAR

A SIMPLIFIED METHOD FOR THE ESTIMATION OF THE SEISMIC RESISTANCE OF RC FRAMES WITH WEAK INFILL PANELS

EARTHQUAKE DESIGN CONSIDERATIONS OF BUILDINGS. By Ir. Heng Tang Hai

Marina Bay Sands Hotel Arch 631 Kayla Brittany Maria Michelle

NON-LINEAR STRUCTURAL INTEGRITY ANALYSIS

Seismic Detailing of RC Structures (IS: )

Transcription:

Displacement Based Assessment and Improvement of a Typical New Zealand Building by an Average Engineer M.L. Grant LGE Consulting, Masterton 2016 NZSEE Conference ABSTRACT: The Radiohouse building is a two storey steel frame structure. The analysis and design of the strengthening of the building was completed by an average practicing Engineer using a displacement based method. A push-over process was completed using Microstran, and models of post-yield behaviour were developed. Interventions were designed, and the resultant building capacity determined using a displacement based process. A discussion on the inappropriateness of using an adopt a ductility approach for the building follows. 1 THE BUILDING 1.1 Main Structure The Radiohouse building is a two storey steel frame structure in the town centre of Masterton. Masterton is a typical small town in New Zealand, located in the highly seismic Wairarapa region. The Radiohouse building was designed in 1959 by a structural engineer. Its overall plan dimensions are 33.3 metres x 12.8 metres. The eight steel frames form 7 bays of 15 10, or approximately 4.8 metres, with intermediate supporting columns through the centre of the building. Figure 1 Existing floor plan Figure 2 Typical Frame

The two end walls of the building are formed by two wythes of 4½ brickwork separated by a 2 cavity. The internal wythe is set into the line of the steel frame and is secured at first floor and eaves level by concrete bands. The outer wythe is secured to the internal face by connection to these concrete bands at first floor and eaves level. The internal stairway is formed with cast in place concrete. This staircase is secured to the main frame with reinforcing bars welded to the main steel beams. There is no separation between the levels. The stair well is surrounded with 9 thick unreinforced masonry walls spanning from the ground floor to the underside of the first floor. Figure 3a Column Details Figure 3b Beam Column Joint detail The steel columns are back-to-back 9 battened taper flange channel (TFC) columns. The primary beams (16 x6 x50 lb RSJs) span in both directions along the main grid lines. The beams and columns are joined together by a complicated arrangement of welded plates. The suspended first floor is formed with steel tray deck which is welded to supporting RSJs and filled with a light-weight unreinforced pumice concrete topping. 1.2 Lateral Force Resisting System In the Longitudinal direction, the battened columns and primary RSJ beams attempt to form frames. The orientation of the battened columns meant the TFCs bend in their weak direction, while simultaneously forming a large tension/compression couple. In the transverse direction, the two TFC column members start acting as frames in conjunction with the primary RSJ beams. The frames appear to have been primarily designed as a gravity structure. As such, detailing at beamcolumn joints accommodates little horizontal joint shear. This explains the lack of web doubler plates in the joint region, similar to a lack of joint reinforcing characteristic of a reinforced concrete moment frame of the same period. 2 THE ASSESSMENT PROCESS 2.1 Available Tools The firm completing this assessment is a typical small consultancy with limited software tools. The analysis package available is Microstran. This appears to be typical of most design offices in regional New Zealand, who would not routinely complete more sophisticated analysis such as Inelastic Time History Methods. 2

2.2 Document / Structure Review In depth site inspections were completed to confirm that the structure was constructed in accordance with the available plans. Due to the atypical system, some research was completed on the behaviour of battened columns under seismic cyclic loads. Limited information on post-yield behaviour was available, however a useful reference was found in documented laboratory testing completed on battened parallel flanged channel columns (Sahoo 2004). 2.3 Review of Existing Structural System Conventional assessment of existing buildings usually focuses on force based assessments. A force based approach generally requires the designer to judge the available ductility of the building. The configuration of this building made this difficult for the following reasons; Longitudinal direction Modelling the longitudinal system showed that the battened columns would form a large tension / compression couple, combined with weak axis bending of the TFC. The existing 410UB beams provide more capacity than the battened TFC columns. Evaluating the available ductility from this non-traditional system was difficult. Adopting a ductility required an assumption that each component forming the column could accommodate the post-elastic mechanism. Transverse direction The performance in the transverse direction is dependent on the capacity of the beam-column joint. The beam-column joint required a detailed review in both the longitudinal and transverse direction. In the transverse direction alone, this included the connection between the beam top flange and the TFC, the beam bottom flange and the TFC, the beam web to the TFC and the TFC web panel through the joint. Preliminary analysis showed that the central beam-column joint would fail in web panel shear (highlighted in the joint elevation below) at a reasonably low level of applied force. This mechanism could potentially lead to loss of gravity support, hence a ductility of 1 was adopted when analysing the existing structure. Allowing for improving the web panel, the joint was reviewed further. One of the joint connections reviewed is illustrated below, namely the top flange of the beam to the TFC column in the transverse direction. Each individual component was checked for its capacity, with the critical element of this specific joint being the weld between the two perpendicular plates. Critical weld Web panel Figure 4a Schematic of top of beam/column joint in transverse direction Figure 4b Elevation of beam/column joint in transverse direction 3

Initial attempts to review the building using a force based approach kept circling back to the question of what ductility is appropriate?. Seeking further guidance, a question was asked which helped focus the assessment, which was 2.4 Capacity of Sub-Assemblages If you push it, what will break first? To answer the above question and progress the analysis, the structure was reduced to its components, and the capacity of each component was calculated. Some of the components analysed were; Longitudinal Weld securing the batten plates to the TFC columns Batten plate in shear and bending TFC in weak axis bending combined with axial loads RSJ primary beam bending capacity Base fixity at foundations Beam/column joint capacity Transverse TFC strong axis bending combined with axial loads RSJ primary beam bending capacity Weld length and size at beam-column joint Plate length and size at beam-column joint Web shear capacity at beam-column joint The building was then modelled in Microstran. An initial model was completed with the battened TFC columns modelled as one single element. The model was then developed to include individual elements forming the columns. Modelling the battened column elements required a judgement as to the appropriate configuration. Modelling was initially completed in three-dimensions, however this was further simplified to twodimensions for the analysis. Calibrating and reviewing the appropriateness of the model at the initial stages was important. Figure 5 Longitudinal Model Figure 6 Transverse Model 4

2.5 Capacity of System (completing a push-over analysis) In each orthogonal direction, a push-over analysis was completed. The basic steps to this were as follows; 1. Calculate the seismic weight and lateral force distribution, and model the system in Microstran. 2. In Microstran, set up a load case for the permanent loads (G) and a 1g lateral force (E). Also create a combination case for G+E. Apply a percentage of the 1g load for the push-over. Vary this percentage to suit the analysis. 3. Apply the lateral load in increments. Start with a force low enough to ensure none of the subassemblages have reached yield. Review the analysis results. Does the displacement pattern make sense? Are the forces approximately what you would expect? 4. Increase the force in small increments. After each analysis, stop and review the results. Note down the displacements. Continue checking that no failure has occurred. 5. Continue increasing the applied force until the first sub-assemblage yields. In the longitudinal direction, this was yielding of the TFC in the weak direction as the combined axial force and out-of-plane bending moment increased. In the transverse direction, this was web shear failure of the central beam-column joint. Note the displacement at this point. 6. At the point of yield, the failure needs to be modelled. In the transverse direction, the analysis was halted at this point, as the failure mechanism was considered to have been reached. In the longitudinal direction, post-yield displacements were needed. In Microstran, an additional load case was created titled yield forces. At the point of yield, a pin was introduced into the member, modelling the yield and ensuring the member could not accept more moment. In the yield forces load case, a moment is then applied equal to the moment that was present in the member at yield. Where this occurs in the length of a member, provide equal and opposite moments either side of the pin of equivalent magnitude to the yielding moment. Note that this assumes that flexural capacity of the element is maintained without strength degradation. 7. Increase the seismic forces and continue with the push-over. Note that the deflections will now be non-linear. Slightly increase the forces, run the analysis and note the displacements at each analysis. At any point of yield, continue amending the model to accommodate the yield. 8. Continue as above until a collapse mechanism is determined to have formed. Check that rotation demand is met as required at remaining joints. In the longitudinal direction, the final displacement of the system occurs at the culmination of many hinges forming in the TFC columns. 9. Using the above information, plot the force vs displacement. Note the equivalent linear ductility can be determined from this plot, if desired. In the graphs below, Force has been plotted as a ratio of the total weight, ie G. Displacement is the displacement of the effective mass. 10. Using the provided equations, determine the displacement spectra for the site and calculate the displacement demand. This requires an estimate of the equivalent viscous damping. 11. Determine %NBS %NBS 30% %NBS 25% Figure 7 Longitudinal Force vs Displacement. Figure 8 Transverse Force vs Displacement 5

2.6 Design of the Interventions Once the above assessment of existing is complete, the interventions can then be designed. For each intervention, repeat the above steps and determine the force vs displacement. Choosing the type of intervention, and then calibrating the response of the interventions is an important and sometimes time consuming step in the design process. The interventions selected for the Radiohouse building were as follows; Longitudinal Three new eccentrically braced K frames with new ground beams. These were chosen to introduce ductility into the building. K-frames are initially very stiff, and their yield mechanism can be calibrated to protect the existing structural system. The new K-frames have been designed to yield at small levels of displacement. The existing frames are still elastic at this point, with a first yield not expected until displacement reaches approximately three times the displacement when the K-frame yielded. The final design was achieved through an iterative process, calibrating the stiffness of the K-frames. Transverse Remediate the central and outside beam column joints by installing new web-doubler plates to the TFC. This changes the joint failure from web-panel shear, to forcing a failure in the top plate weld connection. While this in itself is not a ductile yield, it allows the central TFCs to act as a propped cantilever from the ground floor, supporting the first floor and roof. In addition, a check was completed to ensure the gravity support mechanism for the first floor was maintained after this weld fails. As the joint racks side-to-side, the top beam flange will no longer be connected to the PFC. The bottom flange has additional connections to the TFC columns through gusset plates around the joint. These plates and their welds are sufficiently robust to ensure gravity support is maintained. At six of the eight frames, a single new 530UB82 column, with a moment joint to the existing 410UB primary beams. This turns the frames into a four-leg system, with the column size attracting a reasonable proportion of the load. The architect specified five internal inter-tenancy walls. These walls were designed and detailed as ductile plywood shear walls. 2.6.1 Transverse Direction Push-over Process For each of the above lateral load resisting systems, a push-over analysis was completed. In the transverse direction, this meant there were three models to consider, shown below. Weld failure Step 1 Apply loads until yield - central joints weld fails TFC acts as propped cantilever from ground floor. Introduce pins at this location. = 27mm, V=0.065g Step 2 Increase force. Two columns then yield as moment re-distributes. = 46mm, V=0.065g 6

Step 3 Pin yield and apply moment, then continue increasing force. Central column yields at base. = 47mm,V=0.066g Figure 9 Transverse Direction Push-Over with new web doubler plates only Step 4 Pin yield and apply moment, then continue increasing force. Top of central column yields. = 50mm, V=0.067g Weld failure Step 1 Apply loads until yield - central joints weld fails. Introduce pins at this location, apply yield moments as a force. = 26mm, V=0.096g Step 2 Continue increasing force. Outside compression columns yields at base. = 32mm, V=0.097g Step 3 Pin yield point and apply moment, continue increasing force. of two columns. = 33mm, V=0.10g Figure 10 Transverse Direction Push-Over with new 530UB82 Step 4 Pin yield points and apply moment, then continue increasing force. Top of new 530UB82 yields. = 52mm, V=0.123g Force vs displacement information for the new plywood shear walls was obtained using equations from NZS3603 clause 5.2.5. The displacement at points of average and maximum nail slip were back calculated using the forces noted in NZS3606 clause 4.2.2.3. 2.6.2 Longitudinal Direction Push-over Process A Microstran model was prepared with an equivalent static load distribution. A load case of G+E was introduced, with the seismic coefficient being incrementally increased. 7

Step 1 Apply load until yield TFC columns yield with combined out-of-plane moment plus axial compression. Pin yield point and apply moment, continue increasing force. =13mm, V=0.095g Step 2 Pin yield and apply moment, then continue increasing force. TFC column members yield in multiple locations. = 22mm, V=0.135g Figure 11 - Longitudinal Direction Push-Over Existing Frames The above steps were then repeated modelling the new eccentrically braced K-frames. Step 1 Apply incremental loads until active link yields. = 4.8mm, Force=0.0845g Step 2 Model post-yield behaviour. We applied the yield forces in the link as loads, and amended the model as shown. Step 3 Using NZS3404, calculate deflections at link maximum rotation. Using the model, determine force at this displacement. =27mm, V=0.0927g Figure 12 - Longitudinal Direction Push-Over K-Frames 2.7 Determine the System Capacity (ie %NBS once strengthened ) To determine what the %NBS is once the interventions are completed, we need to plot a System force vs displacement. To complete this, we need to sum the force required for each intervention to move a certain displacement. This is relatively simple, however it does mean each intervention must have a matching displacement. 8

System With new UB (6no.) Existing (2no.) Ply walls (5no.) Figure 13 - Transverse Direction Force vs Displacement System K-frames (3no.) Existing (3no.) Figure 14 Longitudinal Direction Force vs Displacement Using the equations provided in the NZSEE Recommendations, determine the displacement spectra for the site and calculate the displacement demand. From this determine the %NBS. The above requires the adoption of a value for Equivalent Viscous Damping, and a Structural 9

Performance Factor. The Structural performance factor was calculated using Clause 4.4.2 in NZS1170.5. The actual system displacement was used when determining this factor. However a conservative approach was adopted by the author to limit Sp to no less than 0.85. Equivalent viscous damping of 8% was adopted for the system. However a sensitivity analysis was also completed to review the system results at a damping value of 5%. 3 DISCUSSION 3.1 Complications / Barriers to use Summing the forces at a displacement requires that the force at a common displacement is known for all interventions. This is relatively easy to interpolate if in the linear range, but can require some trial and error in Microstran if in the non-linear. Most practicing engineers are not used to displacement based procedures, having more experience and familiarity with the force based equations. This is simplified by a force based spectra being provided in the code. Determining the displacement spectra and using the displacement based equations requires practice and developing an understanding of a new process. 3.2 Benefits The displacement process gives a much more accurate feel for the response of a building. Any assessment process requires particular attention to the details of the structure. The displacement process gives the actual ductility available, as opposed to using an adopt a ductility approach. All elements of a structure, from primary beams down to the smallest beam/column joint must be reviewed for their failure mechanism. The displacement approach gives an exact force that the intervention has to be designed for. This is critical to make sure that a design is economical. Design can be completed knowing the forces that the intervention must accommodate, which means efficient sizes of foundations and connections is possible. The displacement process maximises the existing structure load resistance. 3.3 Secondary Elements By focusing on displacement, the displacement demands placed on other structural elements becomes obvious. For this building, the two end walls of the building are brickwork, secured to the primary steel beams. In addition, the internal stairway is formed with cast in place concrete, and the stair well is surrounded with 9 thick unreinforced masonry walls. If these stiffer elements remain connected to the main frames, they will attract loads. These elements need to be altered to accommodate the drift demands, either by being separated from the main frames and independently secured, or removed. The final design involved removal of the brickwork, with a light timber framed replacement, and seismic separation of the stairs. 3.4 Lower Bound Checks The modelling of such a structure requires assumptions and judgement. A lower bound check on the model was completed in each direction. This lower bound check reviewed the %NBS achieved assuming no ductility was available in the existing structural systems, ie that the System reaches capacity as soon as the existing structure has a yield point. This check confirmed that with the interventions proposed, a compliance level of above 67% was achieved in both directions. This means that there is no strong reliance on post-yield mechanisms of the existing structural system. Mindful of the uncertainties in modelling such a structure, the author also adopted conservative values for structural performance factors and damping. No allowance was made for stiffening provided by concrete encasement to the ground floor columns. 10

4 SUMMARY The displacement based assessment and design of interventions requires a different approach than the usual force based methods. For the design of new structures, adopting a ductility (µ) is an acceptable premise. The designer adopts a µ, then details the structure in accordance with the code to ensure that the chosen ductility can, in theory, be achieved. For assessing existing structures however, using the displacement based approach provides the available ductility, and removes an assumption of ductility, which may or may not be available. The displacement process allows the designer to maximise the use of existing structural systems, and design interventions for a measurable demand. For the displacement process to be adopted by more practicing engineers, it would be beneficial to have available some fully worked examples for typical low-rise New Zealand buildings. REFERENCES: NZSEE 2006. Assessment and Improvement of the Structural Performance of Buildings in Earthquakes. Recommendations for a NZSEE Study Group on Earthquake Risk Buildings. NZS3404:1997 Steel Structures Standards. NZS3603:1993 Timber Structures Standards. NZS1170.5:2004 Structural Design Actions Part 5 Earthquake Actions New Zealand Sahoo (D.R.) et al. 2004. Built up battened columns under lateral cyclic loading. Paper 67 at 13 th World Conference on Earthquake Engineering. ACKNOLWLEDGEMENTS: The author wishes to thank the Land Trust Masterton for allowing the technical content to be published. Many thanks to Gareth Alley from Dunning Thornton Consultants and Stefan Lanser from LGE Consulting for reviewing and providing comment on the paper. 11