ESTIMATION OF RADON CONCENTRATION IN HOUSE USING A SIMPLE VENTILATION MODEL

Similar documents
AIRFLOW PATTERNS AND STACK PRESSURE SIMULATION IN A HIGH RISE RESIDENTIAL BUILDING LOCATED IN SEOUL

SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT

ASTATT1 Prepare to carry out air tightness testing

Live Transportation Research and Improvement Initiatives

COMPLEX SYSTEM OF RADON DIAGNOSIS METHODS AND SPECIFIC EXPERIMENTAL AND THEORETICAL PROCEDURES APPLIED IN THE INDOOR BUILDING ENVIRONMENT ABSTRACT

E/V Shaft Cooling Method as a Stack Effect Countermeasure in Tall Buildings

New Models to Support Vapor Intrusion Mitigation Design

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA

P. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract

HEAT RECUPERATION IN VENTILATION SYSTEM OF BASEMENT LABORATORY

VISQUEEN RADON MEMBRANE SYSTEM

Feasibility study of a roof top Solar room heater

Assessment of the natural air ventilation of buildings in urban area with the CFD tool UrbaWind. Dr Stéphane SANQUER Meteodyn

Moisture and temperature conditions in cold lofts and risk of mould growth

Corridor Pressurization System Performance in Multi-Unit Residential Buildings

SHELTER-IN-PLACE STRATEGY: CONFINE, AN AIRTIGHTNESS LEVEL CALCULATION TOOL TO PROTECT PEOPLE AGAINST ACCIDENTAL TOXIC RELEASES

ASHRAE 62.2: What s New in 2016

Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms

Validation of Numerical Modeling of Air Infiltration through Building Entrance Doors

CONFINE: an airtightness level calculation tool for people s protection in case of accidental toxic releases

Gas Protection System Components

Leak Tightness of Jointing. 1. Basic Principles

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

Insulating Basements: Part 1 Fundamentals

Definition and Validation of a Simplified Multizone Dynamic Building Model Connected to Heating System and HVAC Unit

TEST REPORT No. RS CONCERNING THE FIRE RESISTANCE OF A BUILDING ELEMENT

RADON MITIGATION IN BLOCKS OF FLATS

SIMULATION OF A TYPICAL HOUSE IN THE REGION OF ANTANANARIVO, MADAGASCAR DETERMINATION OF PASSIVE SOLUTIONS USING LOCAL MATERIALS

Balancing the Control of Heat, Air, Moisture, and Competing Interests

INTEGRATING WHOLE BUILDING AIR LEAKAGE TEST DATA INTO ENERGYPLUS INFILTRATION MODELS

Accuracy of simplified indoor humidity simulation

A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS

Airtightness: When it s not as airtight as it s cracked up to be!

AIR BARRIER DESIGN PRINCIPLES AN OVERVIEW.

INDOOR AIR QUALITY IN CLASSROOMS: FIELD CAMPAIGN BY QUESTIONNAIRES AND MEASUREMENTS S. P. Corgnati and S. Viazzo

ENERGY SAVING IN BUILDING USING PCM IN WINDOWS

Radon in civil engineering building code, building standards, guidelines for building professionals

RADON PREVENTIVE MEASURES FOR NEW BUILDINGS

Airtightness of Dwellings in Ireland: Design, Workmanship and Control

Architectural Testing, Inc. 849 Western Avenue North Saint Paul, Minnesota Dan Johnson, Director - Regional Operations

40-Ton Articulated Truck Cooling System Modelling Using STAR-CCM+

Advances in building energy simulation tools and integration of microclimate issues

This presentation. Basements: New & Retrofit. Basements Part of the Enclosure. Basements are Changing. Basement functions Basement Performance

DURABILITY OF LIME STABILIZED EARTH BLOCKS

Influence of compressibility of domestic waste on fluid conductivity

Web-Based Energy Savings Calculator for Building Envelope Air Tightness

ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES OF INTEGRATED METHODOLOGY FOR EVALUATION OF ENERGY EQUIVALENT R-VALUE FOR BUILDING ENCLOSURES;

Comparative analysis of control strategies for passive cooling

EFFECT OF HEAT DISCHARGE BY NATURAL VENTILATION ON INDOOR ENVIRONMENT AND HEAT REMOVAL STRUCTURE

AIRFLOW WINDOW: NUMERICAL STUDY AND SENSIBILITY ANALYSIS OF THERMAL PERFORMANCES. *Corresponding author:

URSA AIR ALU ALU P5858

Hygrothermal Performance Study. (Experimental & Modeling)

The potential of earth-air heat exchangers for low energy cooling of buildings in South Algeria

SRM UNIVERSITY FACULTY OF ENGINEERING AND TECHNOLOGY SCHOOL OF ARCHITECTURE AND INTERIOR DESIGN

Observation of Liquid-filled Window without Presence of Liquid in Test Chamber

ENERGY AND THERMAL COMFORT EVALUATION FOR DIFFERENT PASSIVE SOLUTIONS IN A KINDERGARTEN IN SUMMER CONDITIONS.

External Environment and Indoor Microclimate

TITLE: POLICY ON INDOOR AIR QUALITY IN BUILDINGS. July 14, 2017 Material Resources Department Material Resources Department ROADMAP

Enhancement of Gravity Ventilation in Buildings

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort

Radon Demonstration: Application of Building Code Changes in Winnipeg New Home Construction. April 2014

BACK TO BASICS: DUCT DESIGN. Matthew Low, M.AIRAH, CPEng 15 MAY 2013

MEASUREMENTS AND BENCHMARK OF PV-T COLLECTORS ACCORDING TO EN12975 AND DEVELOPMENT OF A STANDARDIZED MEASUREMENT PROCEDURE

PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT

Passive Houses in South West Europe

Distribution Restriction Statement

MODELLING THE ENERGY PERFORMANCE OF NIGHT-TIME VENTILATION USING THE QUASI-STEADY STATE CALCULATION METHOD

Asset Energy Calculator Guidance

Ventilation and Airtightness, different relationship for different quality of buildings

1 Exam Prep 2014 Florida Building Code -Energy Conservation Questions and Answers

Hygrothermal properties applied in numerical simulation: Interstitial condensation analysis Received (in revised form): 24th July 2009

Modelling of the off-gas exit temperature and slag foam depth. of an Electric Arc Furnace

Hourly Analysis Program v.4.1 Page 1 of 1

An all-in-one system that combines the advantages of Kingspan KoolDuct with the durability of Techna-Duc, and is suitable for indoor and outdoor

Using Experimental Measurements of the Concentrations of Carbon Dioxide for Determining the Intensity of Ventilation in the Rooms

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28

Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers

OFSETTING THE NATURE

A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings

DISPLACEMENT VENTILATION

ENERGY EFFICIENCY OF RESIDENTIAL BUILDINGS IN SERBIA

Effect of Rotation Speed of a Rotary Thermal Wheel on Ventilation Supply Rates of Wind Tower System

Air-tightness, Carbon Emissions & Health The case for a balanced approach

ARCHIVES OF CIVIL ENGINEERING, LX, 1, 2014 NUMERICAL INVESTIGATIONS OF EFFECT OF INDOOR AIR QUALITY ON THERMAL COMFORT IN RESIDENTIAL BUILDINGS

Efficient cooling in a natural and energy-saving way. Large volume flows of outside air provide cooling. Intelligent control

When R-Value Doesn t Measure Up

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation

Protocols for measuring the airtightness of multi-dwelling units in Southern Europe

Of Building Science: From Control Layers to High Performance Enclosures

CONCEPTUAL IMPLEMENTATION OF NATURAL VENTILATION STRATEGY

VENTILATION REQUIREMENTS TO PREVENT PIT AIR UP-DRAFTING IN

Optimal orientation for housing with low energy profile in a semi arid climate.

Protan Exposed Membrane Roof. Your design - Our solution

PS Modeling airflow in outdoor grain pile aeration systems. Introduction

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Numerical Modelling of Air Distribution in the Natatorium Supported by the Experiment

The Centre for Sustainable Building (ZUB) * A Case Study

Ventilative Cooling potential tool

Transcription:

Radon in the Living Environment, 105 ESTIMATION OF RADON CONCENTRATION IN HOUSE USING A SIMPLE VENTILATION MODEL B. Collignan - J.R. Millet C.S.T.B. - Centre Scientifique et Technique du Bâtiment BP 02 F-77421 MARNE LA VALLE CEDEX 2 - France e-mail : collignan@cstb.fr - millet@cstb.fr Fax n : 33 164 68 83 50 The aim of this study is to evaluate the efficiency of different ventilation strategies for a house and for a subfloor void to reduce the radon concentration level of the indoor air. A steady-state analytical ventilation model is derived to estimate the indoor air radon concentration in houses on ground floor or with subfloor voids. It enables to analyse the influence of different environmental and construction parameters on this concentration, in a way to better define and dimension technical solutions to reduce radon concentration in indoor air. First main results obtained with this model are presented in this article. The model developped could also be a help to dimension natural ventilation of a void equiped with specific duct to use stack effects. INTRODUCTION The soil is recognised to be the main source of radon in indoor air of buildings. Its entry into buildings is mainly due to pressure difference between the soil beneath the house and the house. It depends on many environmental parameters such as radon concentration in the soil, permeability, humidity and cracks of the soil. It depends also on characteristics of the building considered (type of construction and basement, cracks on floors in contact with soil or a void, ventilation system ). In this context and in order to improve the efficiency of different ventilation strategies to reduce the indoor air radon concentration, we have developped a steady-state analytical ventilation model. After a description of our model, we present in this article the main results obtained with this model. DESCRIPTION OF THE MODEL On the basis of the ventilation code developped at C.S.T.B. called SIREN95 (Simulation of air RENewal), and taking into account previous work like Woolliscroft (1994), a steady-state analytical ventilation model is derived to estimate the indoor air radon concentration in houses on ground floor or with subfloor voids. This code enables to analyse the influence of different environmental and construction parameters on this concentration. The house can be ventilated by natural ventilation or by mechanical ventilation. Stack effect The stack effect describes an air flux resulting from the pressure difference between the columns of warm and cold air inside and outside the house. In our model, hydrostatic fields for internal and external pressures are assumed and calculated to take into account the stack effect. This means that we consider an homogeneous field for the pressure with the air density which is variing as a function of temperature. The equation of ideal gas leads to : 889

105 Radon in the Living Environment, ρ 1 T 1 = ρ 2 T 2 and permits to calculate the density for the associated temperature. So, for a considered height H, we have : P H_ext = P 0_ext ρ ext.g.h P H_int = P 0_int ρ int.g.h Wind effect The wind effect induces a dynamic air pressure acting on building walls. This dynamic pressure is added to the static pressure to determine the external pressure field. The dynamic pressure term is calculated as follows : P dyn = 1/2.C p. ρ.v² ρ is the density of external air and v its velocity. C p is the pressure coefficient in the range 1 to +1 which describes the distribution of wind induced pressure over building house. Positive values of C p relate to the winward side of the building and describe air compression. Negative values relate to the rear side of the building. In our calculation, we consider conventionnal values of C p of (+ 0.6) and (- 0.35) for the winward and rear sides of the building respectively. Ventilation Once we know the hydrostatic fields for internal and external pressure, we can determine the air fluxes incoming and outcoming the building. For the house, air leakage, air inlets and cracks, are characterised by their flow rate curves as a function of pressure difference (power lows) : Air flow throught air leakage Q p = k p.( P) 2/3 With Q p : air flow rate circulating throught air leakages (m 3 /h), k p : coefficient function of level of permeability of the enveloppe, P : pressure difference between inside and outside at the level of the considered air leakage. Air flow throught air inlets Q ai = k ai.( P) 1/2 With Q ai : air flow rate circulating throught air inlets (m 3 /h), k ai : coefficient function of size of air inlet, P : pressure difference between inside and outside at the level of the considered air inlet. Air flow throught cracks The considered cracks are those on the floor between the house and the soil (house on ground floor) or the subfloor void. 890

Radon in the Living Environment, 105 Q c = k c.( P) 0.8 With Q c : air flow rate circulating throught cracks (m 3 /h), k c : coefficient function of size and type of cracks, P : pressure difference between inside the house and the ground or the void. Air flow throught the ground In the case of subfloor void, air is incoming in the void throught the ground due to pressure difference between the ground and the void with the following law : Q g = k g. P With Q g : air flow rate coming from the ground (m 3 /h), k g : porosity coefficient of the ground, P : pressure difference between the void and the ground. Under equilibrium condition, the total amount of air entering the building should be equal to the total amount of air leaving the building. This condition leads to an equation which enables to determine the pressure at the soil of the building (P 0_int ), and so all the different incoming and outcoming air flow rates, when we know external pressure on the ground, internal and external temperatures. A constant air flow rate due to a mechanical exhaust or supply can be easily added to this equation. Model for house constructed on ground floor For house on ground floor, we consider a single volume. We suppose that radon only penetrates from the ground into the house through cracks in the floor by convection, due to pressure difference between the ground and the house. We assume a constant radon concentration in the soil beneath the house. Model for house with subfloor void For a house with subfloor void, we consider two volumes, one for the house and the other for the subfloor void. We suppose that radon penetrates from the ground into the void by convection, due to pressure difference between the ground and the void and by diffusion, and penetrates from the void into the house through cracks in the floor by convection. We assume a constant radon concentration in the soil beneath void and a constant radon diffusion source into the void (figure 1). Due to strong hypotheses (steady state, constant radon concentration in soil and constant flux in the void, porosity of the soil and level of cracks in floor), results obtained with this model can only give tendancies. However they can point out the influence of different environmental and construction aspects. This model enables to make sensitivity studies on different parameters : exterior temperature, wind velocity, characteristic of the house such as type of basement, permeability, level of mechanical air change rate for the house and for subfloor void. It can also be an help to test and dimension technical solutions for existing and new buildings. 891

105 Radon in the Living Environment, RESULTS Increase of air renewal Increasing the air change rate of the house is not very effective, and can resonnably be done only if the initial air change rate is too low, until a level of about 0.5 a.c.h. As mentionned in previous work like Bonnefous (1992), this measure will not generally be sufficient to reduce radon concentration until an acceptable level. Figure 2 shows the evolution of indoor radon concentration when mechanical exhaust of the house is accentuated until 2 a.c.h., for an airtight and a permeable house. Use of supply mechanical ventilation for the house The use of supply mechanical ventilation for the house to reduce its depressurisation can be effective to prevent the entrance of radon but depends on the air permeability of the house (figure 3). Depressurisation of subfloor void The most effective way to reduce radon concentration level of a house with subfloor void is to depressurise mechanically the void in order to have pressure in the void lower than pressure in the house. This is possible with not too high air change rate of the void only if it is sufficiently airtight (figure 4). Ventilation of subfloor void When the house is constructed with a subfloor void, a natural ventilation of this void will be generally insufficient to reduce radon concentration in it and so in the house, and one can't rely on wind effect because wind velocity is generally low at ground level (figure 5). So, when the subfloor void is too permable, the most efficient way is to use supply or extract mechanical ventilation of the void (figure 6). At low level of ventilation of the void, supply ventilation is less efficient because it accentuates the air flow rate between the void and the house. CONCLUSION A steady-state analytical ventilation model is derived to estimate the indoor air radon concentration in houses on ground floor or with subfloor voids. It enables to analyse the influence of different environmental and construction parameters on this concentration. First main results are presented in this article. When it is possible, the most effective way to reduce radon concentration level of a house is to depressurise mechanically the ground beneath the floor or the subfloor void. This work has been done to improve the efficiency of different ventilation strategies to reduce the indoor air radon concentration. The model we have developped could also be a help to dimension natural ventilation of a void equiped with specific duct to use stack effects. ACKNOWLEGMENT This study was supported by the P.U.C.A. (Plan Urbanisme, Construction et Architecture), the research department of Ministère du Logement. 892

Radon in the Living Environment, 105 REFERENCES [1] Bonnefous Y. Etude Numérique des Systèmes de Ventilation du Sol pour Diminuer la Concentration en Radon dans l Habitat. Thèse de Doctorat de l Institut National des Sciences Appliquées de Lyon. 1992. [2] Woolliscroft M. The Mechanical Ventilation of Suspended Timber Floors for Radon Remediation - A simple Analysis. 15 th AIVC Conference, Buxton Great Britain, p 193-202, 27-30 September 1994. 893

105 Radon in the Living Environment, Figure 1: Example of model for a house with subfloor void. 894

Radon in the Living Environment, 105 Bq/m 3 1200 1000 800 600 (-1.5) (-3.5) (-2.2) airtight house permeable house ( ) : relative pressure on the floor of the house (-6.9) (-11.5) (-16.9) 400 (-3.1) (-4.0) (-5.0) 200 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 a.c.h. Figure 2: Radon concentration function of a.c.h. (mechanical exhaust for airtight and permeable house). 895

105 Radon in the Living Environment, Bq/m 3 1000 5 Pa 800 600 400 200 0 Cr (airtight house) Cr (permeable house) Pint (airtight house) Pint (permeable house) 0 0.5 1 1.5 2 a.c.h. 4 3 2 1 0-1 -2-3 Figure 3: Radon concentration and relative pressure on the floor, function of a.c.h. with mechanical air supply (airtight and permeable house). 896

Radon in the Living Environment, 105 Bq/m 3 2000 1600 1200 Cradon_house DP (int-void) Pa 2 1 0 800-1 400-2 0 0 0.5 1 1.5 2 2.5-3 Extract airflow in the subfloor void (m 3 h -1 m -2 ) Figure 4: Radon concentration and difference pressure between the floor and the void, function of a.c.h. with mechanical extract air from the void. 897

105 Radon in the Living Environment, Bq/m 3 1500 1300 1100 900 700 500 Vext = 0 m/s Vext = 1 m/s Vext = 2 m/s Vext = 3 m/s Vext = 4 m/s Vext = 5 m/s 300 100 100 300 500 700 900 Opening of subfloor void (cm²) Figure 5: Radon concentration in a house as function of sizes of openings for the void, and different wind velocity. 898

Radon in the Living Environment, 105 Bq/m 3 1400 1200 1000 800 600 Mec. Exhaust Mec. Supply 400 200 0 0 1 2 3 4 5 Mechanical ventilation of the void (m 3 h -1 m -2 ) Figure 6: Radon concentration in house function of extract or supply mechanical ventilation of the void. 899

105 Radon in the Living Environment, 900