ET Epoxy-Tie Anchoring Adhesive

Similar documents
The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 17.

Easy to Use A7 Saves You Time and Money

CIA-GEL 7000 EPOXY. One Product For All Applications ADHESIVE ANCHORING SYSTEMS FOR CONCRETE AND MASONRY

High Strength Epoxy Tested in Accordance with ICC-ES AC308

High Strength Epoxy Tested in Accordance with ICC-ES AC308

TITEN HD Heavy Duty Screw Anchor for Concrete & Masonry

High Strength Epoxy tested in accordance to ICC-ES AC308

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

ESR ICC Evaluation Service, Inc. Reissued January 1, 2008 This report is subject to re-examination in one year.

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA TOWSON, MARYLAND EVALUATION SUBJECT:

Adhesive Anchoring Selection Guide Solid Concrete Applications

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

Trusted ICC ES HILTI, INC. SYSTEM E ANCHOR. Conformity! Look. Evaluation. ICC-ES Evaluation

High Strength Epoxy tested in accordance to ICC-ES AC308

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: ITW RED HEAD 700 HIGH GROVE BOULEVARD GLENDALE HEIGHTS, ILLINOIS 60139

C6+ High Strength Epoxy for All. conditions. One product for most environmental conditions and weather conditions. Curing Times

AC50 Silver Adhesive Anchoring System

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

AC100+ GOLD Vinylester Injection Adhesive Anchoring System

Allowable Tension Loads for Drop-In (Stainless Steel) and Coil-Thread Drop-In (Carbon Steel) Anchors in Normal-Weight Concrete

Submittal Information

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INTALLED CONCRETE ANCHORS

FIVE STAR PRODUCTS, INC. (800)

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

SIMPLE CERTAINTY MAXIMUM VERSATILITY INCREASES ANCHOR RELIABILITY AND JOBSITE PRODUCTIVITY

AC200+ Acrylic Injection Adhesive Anchoring System

CONCRETE ANCHORING SYSTEMS

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code.

LOW VISCOSITY STRUCTURAL EPOXY. Table of Contents. Made in the U.S.A. AF35LVE TECHNICAL DATA SHEET

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

ESR-2269 Reissued November 1, 2008 This report is subject to re-examination in one year.

Table of Contents ANCHORING SOLUTIONS. CIA-GEL 7000-C Concrete Epoxy CIA-GEL 7000 Masonry Epoxy... 4

AC100+Gold. Vinylester Injection Adhesive Anchoring System PRODUCT DESCRIPTION FEATURES AND BENEFITS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

CHEMICAL /4" 3/8" to 5/8" /8" 3/4" to 1-1/4" 1 10

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

High-performance anchoring adhesive. n Styrene-free n Low odour n Low wastage n No transportation restrictions

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: POWERS FASTENERS, INC. 701 EAST JOPPA ROAD TOWSON, MARYLAND 21286

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS

APPENDIX A: Strength Design Performance Values

System Components. Grades. General Information Installation Information

Trutek TCM380 PRO. Trutek Fasteners Polska Al. Krakowska 55 Sekocin nowy Rasxyn Poland T:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS SECTION: PRECAST STRUCTURAL CONCRETE SECTION: SITE CAST CONCRETE

February 1, 2018 PARTIES INTERESTED IN ADHESIVE ANCHORS IN MASONRY ELEMENTS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

PE1000+ High Strength Epoxy Anchoring System

weber.anc 405 BFX formerly Conrep.405 BFX

Submittal / Substitution Request

ALLOWABLE STRESS DESIGN OF CONCRETE MASONRY LINTELS. TEK 17-1C Structural (2009) Related TEK: Uniform load. Triangular load. Concentrated loads

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Originally Issued: 11/14/2012 Revised: 11/29/2017 Valid Through: 11/30/2018

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

Injection Adhesive VM-PY

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

1 True Epoxy. Product Submittal/Substitution Request TO: PROJECT: PROJECT LOCATION: SPECIFIED ITEM: Section Page Paragraph Description

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DDI + (DECK INSERT) Threaded Insert for Metal Deck

FROM: PROPOSED SUBSTITUTION: Use HILTI X-U instead of fillet weld or arc spot puddle weld

Construction. Universal anchoring adhesive. Product Description. Tests. Product Data Sheet Edition _1. 1 Sika AnchorFix S 1/6

Masonry Wall Bracing. A Simplified Approach To Bracing Masonry Walls Under Construction. Masonry Bracing Task Force.

May 15, 2012 PARTIES INTERESTED IN ADHESIVE ANCHORS IN MASONRY ELEMENTS

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

REPORT HOLDER: JAACO CORPORATION NE 68 TH STREET, SUITE C 130 REDMOND, WASHINGTON EVALUATION SUBJECT:

Chem-Stud CHEMICAL SPIN TYPE CAPSULE ADHESIVE PRODUCT DESCRIPTION CHEM-STUD ADHESIVE PROPERTIES

ADHESIVE ANCHORS SIMPLE CERTAINTY WITH RED HEAD ADHESIVE ANCHOR SYSTEMS VERSATILE ADHESIVE ANCHORS FOR CONCRETE AND MASONRY APPLICATIONS

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses

SECTION MASONRY ACCESSORIES

April 2, 2012 PARTIES INTERESTED IN EXPANSION ANCHORS IN MASONRY ELEMENTS

Code Compliance Research Report CCRR-0194

Sormat ITH-Pe PRODUCT DATA SHEET. ITH-Pe - POLYESTER BASED RESIN STYRENE FREE. Polyester based injection resin, styrene free. ITH 165 Pe art.

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

CONCRETE STEPS, HANDRAILS, AND SAFETY RAIL

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.

EPCON C8. Chemical Anchoring - Reinforcing Bar Anchorage 16.1 CHEMICAL INJECTION ANCHORING

ChemSet Reo 502. Chemical Anchoring - Reinforcing Bar Anchorage 15.1 CHEMICAL INJECTION ANCHORING 15.1 GENERAL INFORMATION.

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER

Advancements in Adhesive Anchor Technology

HVAC Ductwork and Strut Channels Suspended Ceilings

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER PREFACE

1.02 STANDARD REFERENCES: The following standard specifications shall apply to the Work of this Section as indicated:

Chemical Anchoring Reinforcing Bar Anchorage

FROM: SUBJECT: HILTI X-ENP-19, X-HSN 24 or X-U POWDER-ACTUATED FASTENER SUBSTITUTION REQUEST

EPCON C6 Series. Chemical Anchoring - Reinforcing Bar Anchorage 17.1 CHEMICAL INJECTION ANCHORING 17.1 GENERAL INFORMATION

DIVISION: MASONRY SECTION: CONCRETE UNIT MASONRY REPORT HOLDER: 3B CONSTRUCTION SOLUTIONS, INC.

Transcription:

ET Epoxy-Tie is a two-component, high solids, epoxy-based system for use as a high-strength, non-shrink anchor grouting material. Resin and hardener are dispensed and mixed simultaneously through the mixing nozzle. ET meets the ASTM C-88 specifi cations for Type I, II, IV and V, Grade 3, Classes B and C, except gel time. USES: Threaded rod anchoring Rebar doweling Bonding hardened concrete to hardened concrete Pick-proof sealant around doors, windows and fi xtures Paste-over for crack injection CODES: ICC-ES ER-44 (URM); City of L.A. RR28, RR220; Florida FL 06.2; Multiple DOT Listings. The load tables list values based upon results from the most recent testing and may not refl ect those in current code reports. Where code jurisdictions apply, consult the current reports for applicable load values. APPLICATION: Surfaces to receive epoxy must be clean. For installations in or through standing water, see page for details. The base material temperature must be 40 F or above at the time of installation. For best results, material should be 70 F - 80 F at the time of application. Cartridges should not be immersed in water to facilitate warming. To warm cold material, the cartridges should be stored in a warm, uniformly heated area or storage container for a suffi cient time to allow epoxy to warm completely. Mixed material in nozzle can harden in 7 minutes at a temperature of 40 F or above. INSTALLATION: See pages 3 32 SHELF LIFE: 24 months from date of manufacture in unopened container STORAGE CONDITIONS: For best results store between 4 F - 0 F. To store partially used cartridges, leave hardened nozzle in place. To re-use, attach new nozzle. COLOR: Resin white, hardener black When properly mixed, ET adhesive will be a uniform medium gray color. CLEAN UP: Uncured material Wipe up with cotton cloths. If desired scrub area with abrasive, waterbased cleaner and fl ush with water. If approved, solvents such as ketones (MEK, acetone, etc.), lacquer thinner, or adhesive remover can be used. DO NOT USE SOLVENTS TO CLEAN ADHESIVE FROM SKIN. Take appropriate precautions when handling fl ammable solvents. Solvents may damage surfaces to which they are applied. Cured Material: Chip or grind off surface. TEST CRITERIA: Anchors installed with ET Epoxy-Tie adhesive have been tested in accordance with ICC-ES's Acceptance Criteria for Adhesive Anchors (AC8) for the following: ET22 EDT22B EMN22i 4 Seismic and wind Loading Long-term creep at elevated-temperature Static loading at elevated-temperature Damp holes Freeze-thaw conditions and minimum edge distance and spacing In addition, anchors installed with ET adhesive have been tested in accordance with ICC-ES's Acceptance Criteria for Unreinforced Masonry Anchors (AC60). PROPERTY TEST METHOD RESULTS Consistency (77 F) ASTM C 88 Non-sag/thixotropic paste Heat defl ection ASTM D 648 68 F (76 C) Bond strength (moist cure) ASTM C 882 2,030 psi (2 days) 4,240 psi (4 days) Water absorption ASTM D 70 0.% (24 hours) Compressive yield strength ASTM D 6,74 psi (24 hours) 3,30 psi (7 days) Compressive modulus ASTM D 6 68,200 psi (7 days) Gel time (77 F) ASTM C 88 0 m 60 gram mass 30 min Thin fi lm CHEMICAL RESISTANCE Very good to excellent against distilled water, inorganic acids and alkalis. Fair to good against organic acids and alkalis, and many organic solvents. Poor against ketones. For more detailed information visit our website or contact Simpson Strong-Tie and request Technical Bulletin T-SAS-CHEMRES08. Model No. ET6 ET Cartridge Systems Capacity ounces (cubic inches) Cartridge Type - IMPORTANT - SEE Pages 3 32 FOR INSTALLATION INSTRUCTIONS Carton Quantity ET22 Dispensing Tool(s) Mixing 4 Nozzle 22 EDT22B, EDT22AP, ET22 side-by-side 0 EMN22i (3.7) or EDT22CKT 6 ET6 (0.) side-by-side 6 EDT6AP EMN22i or EMN0. Bulk containers also available, call Simpson Strong-Tie for details. 2. Cartridge and bulk estimation guides are available on pages 63 66. 3. Detailed information on dispensing tools, mixing nozzles and other adhesive accessories is available on pages 87 2. 4. Use only appropriate Simpson Strong-Tie mixing nozzle in accordance with Simpson Strong-Tie instructions. Modification or improper use of mixing nozzle may impair epoxy performance. SUGGESTED SPECIFICATIONS: Anchoring adhesive shall be a twocomponent high solids epoxy based system supplied in manufacturer's standard side-by-side cartridge and dispensed through a static-mixing nozzle supplied by the manufacturer. Epoxy shall meet the minimum requirements of ASTM C-88 specification for Type I, II, IV, and V, Grade 3, Class B and C, except gel time, and must develop a minimum 3,30 psi compressive yield strength after 7 day cure. Epoxy must have a heat deflection temperature of a minimum 68 F (76 C). Adhesive shall be ET Epoxy-Tie adhesive from Simpson Strong-Tie, Pleasanton, CA. Anchors shall be installed per Simpson Strong-Tie instructions for ET Epoxy-Tie adhesive. ACCESSORIES: See pages 87 2 for information on dispensing tools, mixing nozzles and other accessories.

Cure Schedule Base Material Temperature Cure Time F C 40 4 72 hrs. 60 6 24 hrs. 80 27 24 hrs. 00 38 2 hrs. In-Service Temperature Sensitivity Base Material Temperature Percent Load F C 40 4 00% 70 2 00% 0 43 00% 3 7 8% 0 66 6% 80 82 8%. Refer to temperature-sensitivity chart for allowable bond strength reduction for temperature. See page for more information. 2. Percent allowable load may be linearly interpolated for intermediate base material temperatures. 3. C = ( F-32) /.8 Tension Loads for Threaded Anchors in Normal-Weight Concrete ³ ₈ (.) (2.7) (.) (.) (2.4) ¹ ₈ (28.6) ¹ ₄ (3.8) ¹ ₈ ¹ ₄ ³ ₈ 3 (8) 4¹ ₄ (08) (27) 6 (7) 7 (7) 0¹ ₈ (27) ¹ ₄ ¹ ₄ (33) (62) 7 () 0¹ ₈ (27) (2) 3 ¹ ₄ (387) 6 4 (36) 7 (432) 20 (08) 27 (686) 3 (787) 36 (4) 40 (02) 4 (43) Tension Load Based on Bond Strength f'c 2000 psi (3.8 MPa) Concrete Std. Dev. 8,777 324 2, (3.0) (.4) (.8),368 60 3,840 (68.4) (2.7) (7.) 22,877 78,720 (0.8) (3.2) (2.4) 3,4 4,40 8,86 (7.7) (22.0) (3.4) 43,6,30 0,00 (3.) (.0) (48.) 47,333,243,83 (20.) (.) (2.6) 6,840,460 (27.) (68.8) 78,748 (30.3) 4,738 (2.),68 (87.6). load must the lesser of the bond or steel strength. 2. The allowable loads listed under allowable bond are based on a safety factor of 4.0. 3. loads may be increased by 33¹ ₃ percent for short-term loading due to wind or seismic forces where permitted by code. 4. Refer to allowable load-adjustment factors for spacing and edge distance on pages 60 and 6.. Refer to in-service temperature sensitivity chart for allowable load adjustment for temperature. 6. Anchors are permitted to be used within fire-resistive construction, provided the anchors resist wind or seismic loads only. For use in fire-resistive construction, the anchors can also be permitted to be used to resist gravity loads, provided special consideration has been given to fire-exposure conditions. 7. Anchors are not permitted to resist tension forces in overhead or wall installations unless proper consideration is given to fire-exposure and elevated-temperature conditions. A307 (SAE 08) 2,0 (.4) 3,70 (6.7),87 (26.) 8,460 (37.6),00 (.2),02 (66.8),02 (84.6) 23,40 (04.) Tension Load Based on Steel Strength A3 GR B7 (SAE 440) 4,3 (20.2) 8,080 (3.) 2,660 (6.3) 8,230 (8.) 24,78 (0.2) 32,380 (44.0) 4,000 (82.4) 0,620 F3 (A304SS) 3,630 (6.) 6,470 (28.8) 0,20 (4.0) 2,400 (.2) 6,860 (7.0) 22,020 (7.) 27,880 (24.0) 34,420 (3.) See page 0 for an

Shear Loads for Threaded Anchors in Normal-Weight Concrete ³ ₈ (.) (2.7) (.) (.) (2.4) ¹ ₈ (28.6) ¹ ₄ (3.8) ¹ ₈ ¹ ₄ ³ ₈ 3 (8) 4¹ ₄ (08) (27) 6 (7) 7 (7) 0¹ ₈ (27) ¹ ₄ ¹ ₄ (33) (62) 7 () 0¹ ₈ (27) (2) 3 ¹ ₄ (387) 6 ¹ ₄ (33) (62) 7 () 0¹ ₈ (27) (2) 3 ¹ ₄ (387) 6 Shear Load Based on Concrete Distance f'c 2000 psi (3.8 MPa) Concrete Std. Dev. 7,6,0 (33.) (2.6) (8.),273,02 2,820 (0.) (6.7) (2.),,28 4,80 (87.0) (.7) (2.8) 27,66 (23.2) 2,263 (0.) 3,60 (240.0),280 (263.7) 64,72 (287.2) 3,82 (7.0) 3,03 (.6) 6,2 (30.8) 6,2 (30.8) 3,40 (60.0) 4,820 (6.) 6,4 (7.8). load must be the lesser of the load based on concrete edge distance or steel strength. 2. The allowable loads based on concrete edge distance are based on a safety factor of 4.0. 3. loads may be increased by 33¹ ₃ percent for short-term loading due to wind or seismic forces where permitted by code. 4. Refer to allowable load-adjustment factors for spacing and edge distance on pages 60 and 6.. Refer to in-service temperature sensitivity chart for allowable load adjustment for temperature. 6. Anchors are permitted to be used within fire-resistive construction, provided the anchors resist wind or seismic loads only. For use in fire-resistive construction, the anchors can also be permitted to be used to resist gravity loads, provided special consideration has been given to fire-exposure conditions. A307 (SAE 08),08 (4.8),30 (8.6) 3,02 (3.) 4,360 (.4),2 (26.4) 7,740 (34.4),800 (43.6) 2,00 (3.8) Shear Load Based on Steel Strength A3 GR B7 (SAE 440) 2,340 (0.4) 4,60 (8.) 6,20 (2.0),30 (4.8) 2,770 (6.8) 6,680 (74.2) 2,2 (4.0) 26,07 (6.0) F3 (A304SS),870 (8.3) 3,330 (4.8),220 (23.2) 6,38 (28.4) 8,68 (38.6),34 (0.) 4,36 (63.) 7,730 (78.) See page 0 for an Tension Loads for Threaded Anchors in Normal-Weight Concrete Stemwall (.) (.) (24.3) 2 (304.8) 2 (37.) (33.7) Stemwall Width 6 (2.4) 6 (2.4) 8 (203.2) 8 (203.2) M (44.) (44.) (44.) (44.) M End (27.0) (27.0) (27.0) (27.0) Tension Load Based on Bond Strength f'c 2000 psi (3.8 MPa) Concrete Std. Dev. 0,720, 2,680 (47.7) (6.) (.) 6,0 260 4,040 (7.8) (.2) (8.0) 7,000 303 4,20 (7.6) (.3) (8.) 23,340 (03.8) 762 (3.4). load must be the lesser of the bond or steel strength. 2. The allowable loads listed under allowable bond are based on a safety factor of 4.0. 3. loads may be increased by 33¹ ₃ percent for short-term loading due to wind or seismic forces where permitted by code. 4. Refer to in-service temperature sensitivity chart for allowable load adjustment for temperature.. Anchors are permitted to be used within fire-resistive construction, provided the anchors resist wind or seismic loads only. For use in fire-resistive construction, the anchors can also be permitted to be used to resist gravity loads, provided special consideration has been given to fire-exposure conditions.,83 (26.0) Tension Load Based on Steel Strength A307 (SAE 08),87 (26.),87 (26.),00 (.2),00 (.2) See page 0 for an End W= 6"or 8" and end distances for threaded rod in concrete foundation stemwall corner installation 6

Tension Loads for Rebar Dowels in Normal-Weight Concrete Rebar Size No. #4 (2.7) # (.) #6 (.) #7 #8 (2.4) # (28.6) #0 (3.8) # (34.) #4 (44.) ¹ ₈ ¹ ₄ 2 4¹ ₄ (08) 6 (2) (27) ³ ₈ (238) 6 (7) ¹ ₄ 7 (7) 3¹ ₈ (333) 2 (30) (38) 3 (330) 6 ¹ ₄ (38) 8 (476) 2³ ₈ (34) 6 (4) 20 (24) (400) (62) 7 () 4¹ ₈ (3) 0¹ ₈ (27) 6 (2) (02) 3 8 (47) 22 (72) 3 (4) 2³ ₈ (64) 6 22 (72) 28¹ ₈ (74) 8 (473) 24 (62) 3 (787) 23 (600) 7 (432) 24 (60) 20 (08) 37 (3) 27 (686) 4 (43) 3 (787) 2 (334) 36 (4) 48 (2) 60 (24) 36 (4) 2 (32) 67 (7) 4 (43) 60 (24) 7 (0) 4 (27) 66 (676) 82 (206) 63 (600). load must be the lesser of the bond or steel strength. 2. The allowable loads listed under allowable bond are based on a safety factor of 4.0. 3. loads may be increased by 33¹ ₃ percent for short-term loading due to wind or seismic forces for only the shallowest embedment depths listed where permitted by code. 4. Refer to allowable load-adjustment factors for spacing and edge distance on pages 60 and 6.. Refer to in-service temperature sensitivity chart for allowable load adjustment for temperature. 6. Anchors are permitted to be used within fire-resistive construction, provided the anchors resist wind or seismic loads only. For use in fire-resistive construction, the anchors can also be permitted to be used to resist gravity loads, provided special consideration has been given to fire-exposure conditions. 7. Anchors are not permitted to resist tension forces in overhead or wall installations unless proper consideration is given to fire-exposure and elevated-temperature conditions. Tension Load Based on Bond Strength Tension Load Based on Steel Strength f'c 2000 psi (3.8 MPa) Concrete f'c 4000 psi (27.6 MPa) Concrete ASTM A6 Grade 60 Rebar Std. Dev. Std. Dev. 7,6 33 4,400 4,400 (78.3) (2.4) (.6) (.6) 4,800 20,20 263,060 (2.4) (0.) (.2) (22.) 2,427,8 6,3 6,3 (3.) (8.4) (28.3) (28.3) 7,440 2,0 2,270 7,37 (33.) (3.3) (0.) (32.8) 4,82 0,4 0,4 (86.0) (2.6) (46.) (46.) 0,60 44,20,227,00 (47.0) (6.7) (.) (4.2) 0,24 2, 2,60 2,60 (223.) (3.3) (.) (.) 4,400,32 3,444 4,830 (64.) (263.) (.3) (66.0) 60,4,43,03,03 (267.) (24.4) (66.) (66.) 8,260 8,60 (8.2) (84.3) 8,70 7,6 2,40 (382.4) (7.) (.6),03,03 (66.) (66.) 2,30 24,000 (4.8) (06.8) 0,370 4,768 27,0 (4.0) (2.2) (22.7) 70,68,2 7,670 7,670 (34.4) (4.) (78.6) (78.6) 23,60 30,480 (06.6) (3.6) 20,76 6,706 30,24 (38.) (2.8) (34.) 78,422 4,603,60,60 (348.8) (20.) (87.2) (87.2) 28,60 37,440 (27.2) (66.) 0,4 8,287 37,60 (66.) (36.) (67.3),8 3,77 22,880 22,880 4,000 (407.) (6.) (0.8) (0.8) (240.2) See page 0 for an explanation of the 7

Shear Loads for Rebar Dowels in Normal-Weight Concrete Rebar Size No. #4 (2.7) # (.) #6 (.) #7 #8 (2.4) ¹ ₈ # (28.7) ¹ ₄ #0 (32.3) # (3.8) #4 (43.0) 2 4¹ ₄ (08) (27) 6 (7) 7 (7) 0¹ ₈ (27) ¹ ₄ 2³ ₈ (34) 2³ ₈ (34) 8 (203) 0 (24) 2 (30) 4 (36) 6 (406) 8 (47) 20 (08) 22 () 22 () (62) 7 () 0¹ ₈ (27) (2) 3 ¹ ₄ (387) 6 8 (473) 8 (473) Shear Load Based on Concrete Distance f'c 200 psi (7.2 MPa) Concrete Std. Dev. Allow. 3,64 7 3,30 (60.3) (4.3) (.) 20,4 3,034,230 (3.0) (3.) (23.3) 30,48,322 7,3 (34.) (.) (33.) 3,838,84,60 (77.2) (8.2) (44.3) 3,00 3,62 3,270 (236.2) (.8) (.0) 63,88 3,67, (48.7) (6.3) (7.0) 82,782 2,24 20,6 (368.2) (0.0) (2.) 6,06 (427.3) 3,67 (6.3) 24,0 (06.8) 24,0 (06.8) Shear Load Based on Steel Strength ASTM A6 Grade 60 Rebar 3,060 (3.6) 4,740 (2.) 6,730 (2.),80 (40.8) 2,08 (3.8),300 (68.),430 (86.4) 23,86 (06.2) 34,42 (3.) See page 0 for an. load must be the lesser of the load based on concrete edge distance or steel strength. 2. The allowable loads based on concrete edge distance are based on a safety factor of 4.0. 3. loads must be decreased by 2 percent for short-term loading due to wind or seismic forces. 4. Refer to allowable load-adjustment factors for spacing and edge distance on pages 60 and 6.. Refer to in-service temperature sensitivity chart for allowable load adjustment for temperature. 6. Anchors are permitted to be used within fire-resistive construction, provided the anchors resist wind or seismic loads only. For use in fire-resistive construction, the anchors can also be permitted to be used to resist gravity loads, provided special consideration has been given to fire-exposure conditions. 8 Tension and Shear Loads for Threaded Anchors in 6 and 8-inch Normal-Weight Grout-Filled CMU ³ ₈ (.) (2.7) (.) (.) ³ ₈ (.) (2.7) (.) (.) (.) (.) ⁷ ₁₆ ⁹ ₁₆ ⁷ ₁₆ ⁹ ₁₆ 8 M M End M 6 and 8-inch Grout-Filled CMU Loads Based on CMU Strength Tension Shear Anchor Installed in Face Shell (See Figure ) 2 4 4 6,48,300,23,04 3 (30) (02) (36) (28.) (.8) (23.3) (4.6) (8) 2 2 4 7,247,40 6,738,30 (30) (30) (36) (32.2) (6.4) (30.0) (6.0) 2 4 7 8,646,730,70,40 4¹ ₄ (30) (02) (432) (38.) (7.7) (2.4) (.) (08) 2 2 7 8,7,7 0,87 2,7 (30) (30) (432) (3.) (8.0) (48.4) (.7) 2 4 0,23 2,04,73, 4 (30) (02) (483) (4.4) (.) (26.6) (.3) (2) 2 2,20 2,260 3,027 2,60 (30) (30) (483) (0.2) (0.) (7.) (.6) 6 4 4 24 4,0 80 4,766 (2) (02) (7) (60) (2.8) (4.4) (2.2) (4.2) 2 4 27,76 2,3 6 (30) (02) (686) (3.3) (0.7) (7) 2 2 27,4 3,830 (30) (30) (686) (8.) (7.0) Anchor Installed in Mortar T Joint (See Figure 2) 3 8 8 4 7,646,30,07,00 (8) (203) (203) (36) (34.0) (6.8) (24.) (4.) 4¹ ₄ 8 8 7,2,0 8,003,600 (08) (203) (203) (432) (42.4) (8.) (3.6) (7.) 4 8 8,,0,2,0 (2) (203) (203) (483) (44.3) (8.) (42.4) (8.) 6 6 8 27 7,238,40 (7) (406) (203) (686) (32.2) (6.4) Anchor Installed in Cell Opening (Top of Wall) (See Figure 3) 6 4 4 24 6,72,34 4,833 6 (2) (02) (7) (60) (2.) (6.0) (2.) (4.3) 6 4 4 24,34 6 (2) (02) (7) (60) (6.0) (4.3) End Figure 2 anchor placement in grouted CMU face shell Anchor placement in grouted CMU mortar T joint Figure 3 Figure Anchor installed in cell opening (top of wall). Threaded rods must comply with ASTM A 307 minimum. 2. Values for 6 and 8-inch wide CMU Grade N, Type IIconcrete masonry units conforming to UBC Standard 2-4 or ASTM C0. The masonry units must be fully grouted with grout complying with UBC Section 203.4, or IBC Section 203.2. Mortar is prepared in accordance with Section 203.3 of the UBC and UBC Standard 2-, or IBC Section 203.8. The minimum specified compressive strength of masonry, f'm, at 28 days is,00 psi. 3. Embedment depth is measured from the outside face of the concrete masonry unit for installations through a face shell. 4. loads may not be increased for shortterm loading due to wind or seismic forces.. Refer to in-service temperature sensitivity chart for allowable load adjustment for temperature. 6. The tabulated allowable loads are based on a safety factor of.0 for installations under the IBC and IRC. For installations under the UBC use a safety factor of 4.0 (multiply the tabulated allowable loads by.2). 7. Anchors must be spaced a minimum distance of four times the anchor embedment. 8. For embedment depths of 6", 8-inch-wide normalweight grout-filled CMU block must be used.

Tension and Shear Loads for Threaded Anchors in Lightweight, Medium-Weight and Normal-Weight Hollow CMU (2.7) (.) M M End 6 and 8-inch Hollow CMU Loads Based on CMU Strength Tension Shear Anchor Installed in Face Shell w/ets Screen Tube (See Figure ) 3 4 4,400 280,326 (76.2) (0.6) (7.) (6.2) (.2) (.) 3 4 4 280 (76.2) (0.6) (7.) (.2) 26 (.2) 26 (.2). Threaded rods must comply with ASTM A 307 minimum. See page 0 for explanation 2. Values for 6 and 8-inch wide CMU Grade N, Type II concrete masonry units of the conforming to UBC Standard 2-4 or ASTM C0. Mortar is prepared in accordance with Section 203.3 of theubc and UBC Standard 2-, or IBC Section 203.8. The minimumspecified compressive strength of masonry, f'm, at 28 days is,00 psi. 3. Embedment depth is measured from the outside face of the concrete masonry unit for installations through a face shell. 4. loads may not be increased for short-term loading due to wind or seismic forces.. Refer to in-service temperature sensitivity chart for allowable load adjustment for temperature. 6. The tabulated allowable loads are based on a safety factor of.0 for installations under the IBC and IRC. For installations under the UBC use a safety factor of 4.0 (multiply the tabulated allowable loads by.2). 7. Anchors must be spaced a minimum distance of four times the anchor embedment. 8. Set drill to rotation-only mode when drilling into hollow CMU. 4" Placement in Hollow CMU Figure 4" Confi guration A (Shear) Tension and Shear Loads for Installations in Unreinforced Brick Masonry Walls Minimum URM Wall Thickness is 3" (3 wythes thick) Confi guration B (Tension & Shear) (.) (.) (.) M /End M Vertical M Horiz. Tension Load Based on URM Strength Minimum Net Mortar Strength = 0 psi Configuration A (Simpson ETS or ETSP Screen Tube Required) 8 24 8 8 (203) (60) (47) (47) Configuration B (Simpson ETS or ETSP Screen Tube Required) 3 6 8 24,200 (330) (406) (47) (60) (.3) Configuration C (Simpson ETS Screen Tube and AST Steel Sleeve Required) 24 8 8,200 (60) (47) (47) (.3) Shear Load Based on URM Strength Minimum Net Mortar Strength = 0 psi,000 (4.4),000 (4.4) 70 (3.3). Threaded rods must comply with ASTM A 307 minimum. See page 0 for explanation 2. All holes are drilled with a " diameter carbide-tipped drill bit of the with the drill set in the rotation-only mode. 3. The unreinforced brick walls must have a minimum thickness of 3 inches (three wythes of brick). 4. The allowable load is applicable only where in-place shear tests indicate minimum net mortar strength of 0 psi.. The allowable load for Configuration B and C anchors subjected to a combined tension and shear load is determined by assuming a straight-line relationship between allowable tension and shear. 6. The anchors installed in unreinforced brick walls are limited to resisting seismic or wind forces only. 7. Configuration A has a straight threaded rod or rebar embedded 8 inches into the wall with a ³¹ ₃₂" diameter by 8-inch long screen tube (part # ETS78 or ETS78P). This configuration is designed to resist shear loads only. 8. Configuration B has a " threaded rod bent and installed at a 22.-degree angle and installed 3 inches into the wall, to within -inch (maximum) of the exterior wall surface. This configuration is designed to resist tension and shear loads. The pre-bent threaded rod is installed with a ³¹ ₃₂" diameter by 3-inch long screen tube (part # ETS73 or ETS73P).. Configuration C is designed to resist tension and shear forces. It consists of a " diameter, ASTM A 307 threaded rod and an 8" long sleeve (part # AST800) and a ³¹ ₃₂" diameter by 8-inch long screen tube (part # ETS78). The steel sleeve has a plastic plug in one end. A 6" by 6" by ³ ₈" thick ASTM A 36 steel plate is located on the back face of the wall. 0. Special inspection requirements are determined by local jurisdiction and must be confirmed by the local building official.. Refer to in-service temperature sensitivity chart for allowable load adjustment for temperature. Confi guration C (Tension & Shear) Installation Instructions for Confi guration C:. hole perpendicular to the wall to a depth of 8" with a " diameter carbidetipped drill bit (rotation only mode). 2. Clean hole with oil-free compressed air and a nylon brush. 3. Fill 8" steel screen tube with mixed adhesive and insert into hole. 4. Insert steel sleeve slowly into screen tube (adhesive will displace).. Allow adhesive to cure (see cure schedule). 6. through plastic plug in (inside) end of steel sleeve with " bit. 7. completely through the wall with " carbide tipped concrete drill bit (rotation mode only). 8. Insert " rod through hole and attach metal plate and nut.

ET Technical Information Load-Adjustment Factors for ET Epoxy-Tie Adhesive in Normal-Weight Concrete: Distance, Tension and Shear Loads How to use these charts:. The following tables are for reduced edge distance. 2. Locate the anchor size to be used for either a tension and/or shear load application. 3. Locate the embedment (E) at which the anchor is to be installed. 4. Locate the edge distance (C act ) at which the anchor is to be installed.. The load-adjustment factor (f c ) is the intersection of the row and column. 6. Multiply the allowable load by the applicable load-adjustment factor. 7. Reduction factors for multiple edges are multiplied together. 8. Adjustment factors do not apply to allowable steel strength values.. Adjustment factors are to be applied to allowable Tension Load Based on Bond Strength values or allowable Shear Load Based on Concrete Distance values only. Distance Tension (f c ) C act () ³ ₈ ¹ ₈ ¹ ₄ Rebar #4 # #6 #7 #8 # #0 # #4 E 3 4¹ ₄ 6 ³ ₈ 6 ¹ ₄ 7 3¹ ₈ 6 0¹ ₈ ¹ ₄ 8 2³ ₈ 20 C cr ¹ ₄ 7 4¹ ₈ 0¹ ₈ 6 3 22 3 2³ ₈ ¹ ₄ 6 28¹ ₈ 8 3 23 C min 2 2 2 2 2 2 2 2 f cmin 0.0 0.0 0. 0.0 0.64 0.0 0.7 0.0 0.2 0.0 0.47 0.0 0.47 0.8 0.8 0. 0.8 0. 0.8 0.0 0.0 0. 0.0 0.64 0.0 0.7 0.0 0.2 0.0 0.47 2 0.64 0.6 0.6 0. 0.67 0.6 0.60 0. 0. 0.4 0.0 0.0 0.47 0.8 0.8 0. 0.8 0. 0.8 3 0.68 0.64 0.66 0.6 0.68 0.7 0.6 0.6 0. 0. 0.0 0. 0.48 0. 0. 0. 0. 0. 0. 4 0.82 0.74 0.72 0.70 0.7 0.63 0.63 0.6 0.8 0.60 0.3 0.6 0.0 0.62 0.62 0.3 0.6 0.3 0.6 0.6 0.8 0.77 0.78 0.73 0.6 0.66 0.66 0.6 0.64 0. 0.60 0.2 0.66 0.6 0. 0.64 0. 0.63 6.00 0.6 0.83 0.87 0.76 0.7 0.6 0.72 0.63 0.68 0.8 0.6 0. 0.6 0.68 0.7 0.67 0.7 0.6 7.00 0.8 0.6 0.7 0.8 0.72 0.77 0.66 0.72 0.60 0.70 0.7 0.72 0.7 0. 0.6 0.8 0.67 8 0.4.00 0.82 0.87 0.7 0.82 0.6 0.77 0.63 0.74 0. 0.76 0.74 0.6 0.72 0.60 0.6.00 0.8 0.3 0.78 0.87 0.7 0.8 0.66 0.7 0.62 0.7 0.77 0.63 0.7 0.62 0.7 0 0.88 0. 0.80 0.2 0.74 0.8 0.68 0.84 0.64 0.82 0.80 0.6 0.77 0.64 0.73 2 0.4.00 0.86.00 0.7 0.4 0.73 0.3 0.6 0.8 0.86 0.6 0.82 0.67 0.77 4.00 0.2 0.8.00 0.78.00 0.73 0.6 0. 0.73 0.88 0.7 0.8 6 0.8 0.0 0.83 0.78.00 0.7 0.77 0.3 0.74 0.8 8.00 0. 0.8 0.83.00 0.80 0.8 0.77 0.8 20.00 0.4 0.87 0.84.00 0.8 0.3 22 0. 0.2 0.88 0.84 0.7 24.00 0.7 0.2 0.88.00 26.00 0.6 0. 28.00 0. 30 0.8 32.00 See notes below. Distance Shear (f c ) C act () ³ ₈ ¹ ₈ ¹ ₄ Rebar #4 # #6 #7 #8 # #0 # #4 E 3 4¹ ₄ 4¹ ₄ 6 6 7 7 0¹ ₈ 0¹ ₈ ¹ ₄ ¹ ₄ 2³ ₈ 2³ ₈ C cr ¹ ₄ 8 7 0 0¹ ₈ 2 4 3 6 8 ¹ ₄ 6 20 22 22 C min 2 2 2 2 2 2 f cmin 0.2 0.20 0.6 0.3 0.0 0.3 0.0 0.3 0.0 0.08 0.08 0.08 0.4 0.4 0.4 0.4 0.4 0.2 0.20 0.6 0.3 0.0 0.3 0.0 0.3 0.0 0.08 0.08 2 0.4 0.37 0.2 0.28 0.2 0.23 0. 0.22 0.6 0.6 0.4 0.08 0.4 0.4 0.4 0.4 0.4 3 0.4 0.42 0.33 0.32 0.24 0.26 0.2 0.24 0.8 0.8 0.6 0.0 0.6 0.6 0. 0. 0. 4 0.7 0. 0.46 0.47 0.3 0.36 0.30 0.33 0.26 0.26 0.23 0.6 0.23 0.22 0.20 0.20 0.20 0. 0.76 0.60 0.62 0.4 0.47 0.3 0.42 0.33 0.33 0.2 0.22 0.2 0.28 0.2 0.24 0.24 6.00 0.4 0.73 0.77 0.6 0.7 0.47 0.0 0.4 0.4 0.3 0.28 0.36 0.34 0.30 0.2 0.2 7.00 0.87 0.2 0.67 0.68 0.6 0. 0.48 0.4 0.42 0.34 0.43 0.40 0.3 0.33 0.33 8.00.00 0.78 0.78 0.6 0.68 0. 0.7 0.48 0.40 0.0 0.46 0.40 0.37 0.37 0.8 0.88 0.74 0.77 0.63 0.6 0. 0.46 0.7 0.2 0.4 0.42 0.42 0.00 0. 0.82 0.86 0.70 0.73 0.6 0.2 0.64 0.8 0.0 0.46 0.46.00 0. 0.4 0.78 0.80 0.68 0.8 0.7 0.64 0. 0. 0. 2.00.00 0.8 0.88 0.74 0.64 0.78 0.70 0.60 0. 0. 3 0.3 0.6 0.8 0.70 0.8 0.76 0.6 0.60 0.60 4.00.00 0.87 0.76 0. 0.82 0.70 0.64 0.64 0.4 0.82 0.8 0.8 0.7 0.6 0.6 6.00 0.88.00 0. 0.80 0.73 0.73 8.00.00 0.0 0.82 0.82 20.00 0. 0. 22.00.00 See page 0 for an explanation of the 60. E = Embedment depth (inches). 2. C act = actual edge distance at which anchor is installed (inches). 3. C cr = critical edge distance for 00% load (inches). 4. C min = minimum edge distance for reduced load (inches).. f c = adjustment factor for allowable load at actual edge distance. 6. f ccr = adjustment factor for allowable load at critical edge distance. f ccr is always =.00. 7. f cmin = adjustment factor for allowable load at minimum edge distance. 8. f c = f cmin + [( - f cmin) (C act - C min) / (C cr - C min)].

ET Technical Information Load-Adjustment Factors for ET Epoxy-Tie Adhesive in Normal-Weight Concrete:, Tension and Shear Loads How to use these charts:. The following tables are for reduced spacing. 2. Locate the anchor size to be used for either a tension and/or shear load application. 3. Locate the embedment (E) at which the anchor is to be installed. 4. Locate the spacing (S act ) at which the anchor is to be installed.. The load-adjustment factor (f s ) is the intersection of the row and column. 6. Multiply the allowable load by the applicable load-adjustment factor. 7. Reduction factors for multiple spacings are multiplied together. 8. Adjustment factors do not apply to allowable steel strength values.. Adjustment factors are to be applied to allowable Tension Load Based on Bond Strength values or allowable Shear Load Based on Concrete Distance values only. Tension (f s ) S act () ³ ₈ ¹ ₈ ¹ ₄ Rebar #4 # #6 #7 #8 # #0 # #4 E 3 4¹ ₄ 6 ³ ₈ 6 ¹ ₄ 7 3¹ ₈ 6 0¹ ₈ ¹ ₄ 8 2³ ₈ 20 S cr 4 7 24 20 37 27 4 3 2 36 60 36 67 40 4 7 4 82 63 S min 2¹ ₈ 3 2 4 3³ ₈ 3 6 4 7 4 8 ¹ ₈ ³ ₈ 6¹ ₄ 0³ ₈ 7 f smin 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 2 0.8 4 0. 0.0 0.0 0.0 0.8 0.8 6 0.3 0.2 0. 0. 0.8 0.0 0.8 0.0 0.0 0.0 0.8 0.8 8 0. 0.3 0.2 0.2 0.0 0. 0.0 0. 0.8 0.0 0.8 0.0 0.0 0.0 0.8 0.8 0 0.6 0. 0.3 0.4 0. 0.2 0.0 0. 0.0 0. 0.0 0. 0.8 0. 0.0 0.8 0.0 0.8 2 0.8 0.6 0.4 0. 0. 0.3 0. 0.2 0.0 0.2 0.0 0.2 0.0 0. 0. 0.8 0.0 0.8 0.0 4.00 0.8 0. 0.6 0.2 0.4 0. 0.3 0. 0.2 0.0 0.2 0.0 0.2 0. 0.0 0. 0.0 0.0 6 0. 0.6 0.7 0.3 0. 0.2 0.4 0. 0.3 0. 0.3 0.0 0.2 0.2 0.0 0. 0.0 0. 8.00 0.7 0. 0.3 0.6 0.2 0. 0.2 0.4 0. 0.4 0. 0.3 0.2 0.0 0.2 0.0 0. 20 0.8.00 0.4 0.7 0.3 0.6 0.2 0.4 0.2 0.4 0. 0.4 0.3 0. 0.2 0.0 0. 24.00 0. 0. 0.4 0.7 0.3 0.6 0.2 0.6 0.2 0. 0.4 0. 0.4 0. 0.2 28 0.7.00 0. 0. 0.4 0.7 0.3 0.7 0.3 0.6 0. 0.2 0. 0.2 0.3 32 0.8 0.6.00 0. 0. 0.4 0. 0.3 0.7 0.6 0.3 0.6 0.2 0.4 36 0. 0.7 0.6.00 0..00 0.4 0. 0.7 0.3 0.7 0.3 0. 40.00 0. 0.7 0.6 0..00 0. 0.4 0.8 0.4 0. 4.00 0.8 0.7 0.6.00 0. 0. 0.4 0.6 0 0. 0.8 0.7 0.6.00 0. 0.7.00 0. 0.8 0.7 0.6 0.8 60.00 0. 0.7 0.7 0. 6.00 0.8 0.7.00 70 0. 0.8 7.00 0. 82.00 See Notes Below Shear (f s ) S act () ³ ₈ ¹ ₈ ¹ ₄ Rebar #4 # #6 #7 #8 # #0 # #4 E 3 4¹ ₄ 6 7 0¹ ₈ ¹ ₄ 2³ ₈ 2³ ₈ S cr ¹ ₄ 7 0¹ ₈ 3 ¹ ₄ 6 8 8 S min 2¹ ₈ 2 3³ ₈ 3 4 ¹ ₈ 6¹ ₄ 6¹ ₄ f smin 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 2 0.84 3 0.8 0.87 0.8 4 0.4 0. 0.88 0.8 0.83 0. 0. 0.2 0.87 0.8 0.84 6.00 0. 0. 0.0 0.88 0.86 0.84 0.84 7.00 0.8 0.2 0.0 0.88 0.86 0.8 0.84 0.84 8.00 0. 0.2 0.0 0.88 0.87 0.8 0.8 0.7 0.4 0.2 0.0 0.88 0.87 0.87 0.00 0.6 0.3 0. 0.0 0.88 0.88 2.00 0.7 0. 0.3 0. 0. 4.00 0.8 0.6 0.4 0.4 6.00 0. 0.6 0.6 8.00 0. 0. 20.00.00 See page 0 for an. E = Embedment depth (inches). 2. S act = actual spacing distance at which anchors are installed (inches). 3. S cr = critical spacing distance for 00% load (inches). 4. S min = minimum spacing distance for reduced load (inches).. f s = adjustment factor for allowable load at actual spacing distance. 6. f scr = adjustment factor for allowable load at critical spacing distance. f scr is always =.00. 7. f smin = adjustment factor for allowable load at minimum spacing distance. 8. f s = f smin + [( - f smin) (S act - S min) / (S cr - S min)]. See page 0 for an 6