Water Distribution Systems

Similar documents
Environmental Engineering-I

Unit 2. Water Distribution System Design Criteria and Planning

Water supply components

Piping layout for fire sprinkler system: An overview

The purpose of distribution system is to deliver water to consumer with appropriate quality, quantity and pressure. Distribution system is used to

Learning objectives. Upon successful completion of this lecture, the participants will be able to:

STUDY OF WATER DISTRIBUTION NETWORK USING EPANET

Types of Water Resource Systems. Types of Water Resource Systems. Design of Water Resource Systems. Design for Public Water-Supply

Fluid Mechanics. The Energy Equation [7] Dr. Mohammad N. Almasri

Introduction to Water Supply System OUTLINE

Section 7 Hydraulic Model Development and Evaluation Criteria

SAWEA Workshop 2010 Innovative Water and Wastewater Networks Presented by Greg Welch, AECOM

RELIABILITY BASED OPTIMAL DESIGN OF A WATER DISTRIBUTION NETWORK FOR MUNICIPAL WATER SUPPLY

Earthquake damage detection in Tehran s water distribution system

Analysis of Continuous Water Distribution in Surat City using EPANET: A Case Study

APPENDIX G HYDRAULIC GRADE LINE

Session 2 Pump Selection. Mark Markham, P.E. Gresham, Smith and Partners September 14, 2017

Section V WATER DISTRIBUTION SYSTEM DESIGN GUIDELINES

Ivins City Standard Specifications for Design and Construction Part 2 Engineering and Design Standards

SEMESTER LESSON PLANS (RPS)

SECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES

UNIFORM DESIGN AND CONSTRUCTION STANDARDS FOR EXTENDING WATER DISTRIBUTION SYSTEMS SECTION 2 DESIGN STANDARDS

Facilities Development Manual

4A General Information A. Concept... 1 B. Conditions... 1

The Islamic University of Gaza- Civil Engineering Department Sanitary Engineering- ECIV 4325 L5. Storm water Management

Outlines for Water Saving Practices in Kuwait

NZQA registered unit standard version 4 Page 1 of 5

Section 5 - Planning Criteria. Section 5

Overview. We will not study pipe systems in detail as these are always solved with software. Wednesday, September 01, :21 PM.

Utilities are constantly striving to

Water Pipeline Design Guidelines

EVALUATION OF A WATER TREATMENT PLANT PERFORMANCE CASE STUDY

Planning of Water Distribution Network to Desapatrunipalem (55 th ward, Visakhapatnam) by using EPANET& GIS

December Illinois American Water Cross Connection Control Program

Guidelines for Construction of Pipe Distribution Network (PDN) for Irrigation

Index. Page numbers followed by f indicate figures.

Assignment I Design of a Marine Outfall

Module 7: Hydraulic Design of Sewers and Storm Water Drains. Lecture 7: Hydraulic Design of Sewers and Storm Water Drains

Hydraulic Transient: Lift Irrigation Scheme

ANALYSIS OF WATER LOSS IN SEMARANG MUNICIPAL WATERWORKS

CHAPTER 4 HYDRAULIC ANALYSIS

HYDRAULIC PERFORMANCE OF PALESTINIAN WATER DISTRIBUTION SYSTEMS (JENIN WATER SUPPLY NETWORK AS A CASE STUDY) Shaher Hussni Abdul Razaq Zyoud

UNESCO EOLSS. The various methods available for the treating and disposing of treated sewerage in natural receiving water bodies are outlined.

Clean energy saving: applied research into Etna s water supply systems in Catania, Italy

SEWER SYSTEM DESIGN GUIDELINES

PipelineNet: A GIS Based Water Quality Model for Distribution Systems

Sag Pipe (depressed sewers, or Inverted siphons) Dr. Sataa A. Al-Bayati(10-11)

Screening, Definition: The unit involved is called a screen.

Optimizing the Design of Water Distribution Networks Using Mathematical Optimization

Hydrant Flow Testing Purpose, Process & Experiences. James P. Cooper - Prof. Engineer, Cert. Operator

MOMENT REDISTRIBUTION IN CONTINUOUS BEAMS OF EARTHQUAKE RESISTANT MULTISTOREY REINFORCED CONCRETE FRAMES

Application of Variable Frequency Drives for Energy Savings

REQUEST FOR PROPOSALS (RFP) Design Services for District Heat Distribution System

Outlet Flow Velocity in Circular Culvert

CURRENT NORTH LAS VEGAS ADDENDA

Design of Sewerage System for Jaffarpur area in Southwest New Delhi

DUBAI ELECTRICITY AND WATER AUTHORITY GUIDELINES FOR NEW DEVELOPMENT PROJECTS UPDATE

Storm Sewer Design. Bob Pitt University of Alabama and Shirley Clark Penn State Harrisburg

The effect of future water demand reduction on WDS rehabilitation planning

CHAPTER 4 MINIMUM DESIGN CRITERIA

DESIGN OF SEWER SYSTEMS

Irrigation System. BWCDD Zanjero Training 2/13/2008

A Multi-Faceted Approach to Odor Control for a 28.5-Mile Long Force Main

CROSS-CONNECTION CONTROL/BACKFLOW PREVENTION

CONSERVATION PLAN April 2009

Irrigation Rehabilitation Program Design and Construction Standards

SECTION 4 RECOMMENDED DISTRIBUTION SYSTEM IMPROVEMENTS

NEW MAINS DESIGN WORKSHOP

Efficient Control of Potable Water Distribution

Unit 1: Introduction and basic hydraulics of water transport

Pump selection: a real example

Rehabilitation of a water distribution system with diffused water losses

Hancor, Inc. Drainage Handbook Hydraulics 3-1

Section 12 Hydraulic Design and Analysis

La modellazione per la gestione efficiente della rete idrica Pedro Pina

Regional District of Okanagan-Similkameen 101 Martin Street Penticton, BC V2A 5J9. November 2008 Project No

Design and Development of Pico-hydro Generation System for Energy Storage Using Consuming Water Distributed to Houses

Your recycled water guide

SSC-JE STUDY MATERIAL ENVIRONMENTAL ENGINEERING [PA ENVIRONMENTAL ENGINEERINGG PART-A

Model Lift Irrigation Scheme

Dual Water Systems in Northern Colorado. Wayne E. Eckas, P.E. Aqua Engineering, Inc., Fort Collins, Colorado

CHAPTER 6 COLLECTION SYSTEM HYDRAULIC MODEL

DESIGNING PRESSURE SEWER SYSTEMS FOR TOPOGRAPHICALLY CHALLENGING CATCHMENTS: AN ACCOUNT OF THE OPUA PRESSURE SEWER SCHEME

HYDRAULICS OF CULVERTS

Water Loss Management In Distribution Pipe Basic Knowledge

Feasibility of Pipe Distribution Network (PDN) over Canal Distribution Network (CDN) For Irrigation

Analysis of Spring Development and Gravity Flow System to Capture Water for Local Communities

PRESSURIZED IRRIGATION SYSTEM MASTER PLAN

POROSITY, SPECIFIC YIELD & SPECIFIC RETENTION. Physical properties of

Basic Irrigation Design

TABLE OF CONTENTS PREFACE...V CONTRIBUTORS... VI I. MICROIRRIGATION THEORY AND DESIGN PRINCIPLES CHAPTER 1. INTRODUCTION...1

Waterhammer Analysis Essential and Easy and Efficient

SGM Engineering, Inc.

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below)

ATS WMK AGA. Installation and Operating Instructions ASI25 ISSUE D 15/02/2016

Calculate the Costs of Piping System Elements

Pinellas County Utilities provides drinking

B. Brunone University of Perugia C. Chiesa Metropolitana Milanese M. Ferrante - University of Perugia

Energetic Efficiency Analysis of Water Pumping Installations

Transcription:

The Islamic University of Gaza Faculty of Engineering Civil Engineering Department Hydraulics - ECIV 3322 Chapter 4 Water Distribution Systems 1

Introduction To deliver water to individual consumers with appropriate quality, quantity, and pressure in a community setting requires an extensive system of: Pipes. Storage reservoirs. Pumps. Other related accessories. Distribution system: is used to describe collectively the facilities used to supply water from its source to the point of usage. 2

Methods of Supplying Water Depending on the topography relationship between the source of supply and the consumer, water can be transported by: Canals. Tunnels. Pipelines. The most common methods are: Gravity supply Pumped supply Combined supply 3

Gravity Supply The source of supply is at a sufficient elevation above the distribution area (consumers). so that the desired pressure can be maintained HGL or EGL Source (Reservoir) (Consumers) Gravity-Supply System 4

Advantages of Gravity supply Source HGL or EGL No energy costs. Simple operation (fewer mechanical parts, independence of power supply,.) Low maintenance costs. No sudden pressure changes 5

Used whenever: Pumped Supply The source of water is lower than the area to which we need to distribute water to (consumers) The source cannot maintain minimum pressure required. pumps are used to develop the necessary head (pressure) to distribute water to the consumer and storage reservoirs. HGL or EGL Source (Consumers) (River/Reservoir) Pumped-Supply System 6

Disadvantages of pumped supply Complicated operation and maintenance. Dependent on reliable power supply. Precautions have to be taken in order to enable permanent supply: Stock with spare parts Alternative source of power supply. HGL or EGL Source (Consumers) (River/Reservoir) 7

Combined Supply (pumped-storage supply) Both pumps and storage reservoirs are used. This system is usually used in the following cases: 1) When two sources of water are used to supply water: Pumping HGL Gravity HGL Source (1) Pumping station City Source (2) 8

Combined Supply (Continue) 2) In the pumped system sometimes a storage (elevated) tank is connected to the system. When the water consumption is low, the residual water is pumped to the tank. When the consumption is high the water flows back to the consumer area by gravity. High consumption Low consumption Elevated tank Pumping station City Pipeline Source 9

Combined Supply (Continue) 3) When the source is lower than the consumer area A tank is constructed above the highest point in the area, Then the water is pumped from the source to the storage tank (reservoir). And the hence the water is distributed from the reservoir by gravity. Pumping HGL Gravity Pumping Station Reservoir HGL Source City 10

Distribution Systems (Network Configurations ) In laying the pipes through the distribution area, the following configuration can be distinguished: 1. Branching system (Tree) 2. Grid system (Looped) 3. Combined system 11

Branching System (tree system) Submain Dead End Main pipe Source Branching System Advantages: Simple to design and build. Less expensive than other systems. 12

Disadvantages: Dead End Source The large number of dead ends which results in sedimentation and bacterial growths. When repairs must be made to an individual line, service connections beyond the point of repair will be without water until the repairs are made. The pressure at the end of the line may become undesirably low as additional extensions are made. 13

Grid System (Looped system) Grid System Advantages: The grid system overcomes all of the difficulties of the branching system discussed before. No dead ends. (All of the pipes are interconnected). Water can reach a given point of withdrawal from several directions. 14

Disadvantages: Hydraulically far more complicated than branching system (Determination of the pipe sizes is somewhat more complicated). Expensive (consists of a large number of loops). But, it is the most reliable and used system. 15

Combined System Combined System It is a combination of both Grid and Branching systems This type is widely used all over the world. 16

Design of Water Distribution Systems A properly designed water distribution system should fulfill the following requirements: Main requirements : Satisfied quality and quantity standards Additional requirements : To enable reliable operation during irregular situations (power failure, fires..) To be economically and financially viable, ensuring income for operation, maintenance and extension. To be flexible with respect to the future extensions. 17

The design of water distribution systems must undergo through different studies and steps: Design Phases Preliminary Studies Network Layout Hydraulic Analysis 18

Preliminary Studies: Must be performed before starting the actual design: 4.3.A.1 Topographical Studies: 1. Contour lines (or controlling elevations). 2. Digital maps showing present (and future) houses, streets, lots, and so on.. 3. Location of water sources so to help locating distribution reservoirs. 19

Water Demand Studies: Water consumption is ordinarily divided into the following categories: Domestic demand. Industrial and Commercial demand. Agricultural demand. Fire demand. Leakage and Losses. 20

Domestic demand It is the amount of water used for Drinking, Cocking, Gardening, Car Washing, Bathing, Laundry, Dish Washing, and Toilet Flushing. The average water consumption is different from one population to another. In Gaza strip the average consumption is 70 L/capita/day which is very low compared with other countries. For example, it is 250 L/c/day in United States, and it is 180 L/c/day for population live in Cairo (Egypt). The average consumption may increase with the increase in standard of living. The water consumption varies hourly, daily, and monthly 21

The total amount of water for domestic use is a function of: Population increase How to predict the increase of population? Use Geometric-increase model P P ( r ) n P 0 = recent population 0 1 r = rate of population growth n = design period in years P = population at the end of the design period. The total domestic demand can be estimated using: Q domestic = Q avg * P 22

Industrial and Commercial demand It is the amount of water needed for factories, offices, and stores. Varies from one city to another and from one country to another Hence should be studied for each case separately. However, it is sometimes taken as a percentage of the domestic demand. 23

Agricultural demand It depends on the type of crops, soil, climate Fire demand To resist fire, the network should save a certain amount of water. Many formulas can be used to estimate the amount of water needed for fire. 24

Fire demand Formulas Q F 65 P(1 0.01 P) Q F = fire demand l/s P = population in thousands QF 53 P Q F = fire demand l/s P = population in thousands QF 320* Q C A F = fire demand flow m 3 /d A = areas of all stories of the building under consideration (m 2 ) C = constant depending on the type of construction; The above formulas can be replaced with local ones (Amounts of water needed for fire in these formulas are high). 25

Leakage and Losses This is unaccounted for water (UFW) It is attributable to: Errors in meter readings Unauthorized connections Leaks in the distribution system 26

Design Criteria Are the design limitations required to get the most efficient and economical water-distribution network Pressure Velocity Average Water Consumption 27

Velocity Not be lower than 0.6 m/s to prevent sedimentation Not be more than 3 m/s to prevent erosion and high head losses. Commonly used values are 1-1.5 m/sec. 28

Pressure Pressure in municipal distribution systems ranges from 150-300 kpa in residential districts with structures of four stories or less and 400-500 kpa in commercial districts. Also, for fire hydrants the pressure should not be less than 150 kpa (15 m of water). In general for any node in the network the pressure should not be less than 25 m of water. Moreover, the maximum pressure should be limited to 70 m of water 29

Pipe sizes Lines which provide only domestic flow may be as small as 100 mm (4 in) but should not exceed 400 m in length (if dead-ended) or 600 m if connected to the system at both ends. Lines as small as 50-75 mm (2-3 in) are sometimes used in small communities with length not to exceed 100 m (if dead-ended) or 200 m if connected at both ends. The size of the small distribution mains is seldom less than 150 mm (6 in) with cross mains located at intervals not more than 180 m. In high-value districts the minimum size is 200 mm (8 in) with crossmains at the same maximum spacing. Major streets are provided with lines not less than 305 mm (12 in) in diameter. 30

Head Losses Optimum range is 1-4 m/km. Maximum head loss should not exceed 10 m/km. 31

Design Period for Water supply Components The economic design period of the components of a distribution system depends on Their life. First cost. And the ease of expandability. 32

Average Water Consumption From the water demand (preliminary) studies, estimate the average and peak water consumption for the area. 33

Network Layout Next step is to estimate pipe sizes on the basis of water demand and local code requirements. The pipes are then drawn on a digital map (using AutoCAD, for example) starting from the water source. All the components (pipes, valves, fire hydrants) of the water network should be shown on the lines. 34

Pipe Networks A hydraulic model is useful for examining the impact of design and operation decisions. Simple systems, such as those discussed in last chapters can be solved using a hand calculator. However, more complex systems require more effort even for steady state conditions, but, as in simple systems, the flow and pressure-head distribution through a water distribution system must satisfy the laws of conservation of mass and energy. 35

Pipe Networks The equations to solve Pipe network must satisfy the following condition: The net flow into any junction must be zero Q 0 The net head loss a round any closed loop must be zero. The HGL at each junction must have one and only one elevation All head losses must satisfy the Moody and minor-loss friction correlation 36

Node, Loop, and Pipes Pipe Node Loop 37

Hydraulic Analysis After completing all preliminary studies and layout drawing of the network, one of the methods of hydraulic analysis is used to Size the pipes and Assign the pressures and velocities required. 38

Hydraulic Analysis of Water Networks The solution to the problem is based on the same basic hydraulic principles that govern simple and compound pipes that were discussed previously. The following are the most common methods used to analyze the Grid-system networks: 1. Hardy Cross method. 2. Sections method. 3. Circle method. 4. Computer programs (WaterCAD,Epanet, Loop, Alied...) 39

Hardy Cross Method This method is applicable to closed-loop pipe networks (a complex set of pipes in parallel). It depends on the idea of head balance method Was originally devised by professor Hardy Cross. 40

Assumptions / Steps of this method: 1. Assume that the water is withdrawn from nodes only; not directly from pipes. 2. The discharge, Q, entering the system will have (+) value, and the discharge, Q, leaving the system will have (-) value. 3. Usually neglect minor losses since these will be small with respect to those in long pipes, i.e.; Or could be included as equivalent lengths in each pipe. 4. Assume flows for each individual pipe in the network. 5. At any junction (node), as done for pipes in parallel, Q in Q out or Q 0 41

6. Around any loop in the grid, the sum of head losses must equal to zero: 0 loop h f Conventionally, clockwise flows in a loop are considered (+) and produce positive head losses; counterclockwise flows are then (-) and produce negative head losses. This fact is called the head balance of each loop, and this can be valid only if the assumed Q for each pipe, within the loop, is correct. The probability of initially guessing all flow rates correctly is virtually null. Therefore, to balance the head around each loop, a flow rate correction ( ) for each loop in the network should be computed, and hence some iteration scheme is needed. 42

7. After finding the discharge correction, (one for each loop), the assumed discharges Q 0 are adjusted and another iteration is carried out until all corrections (values of ) become zero or negligible. At this point the condition of : 0. 0 loop h f is satisfied. Notes: The flows in pipes common to two loops are positive in one loop and negative in the other. When calculated corrections are applied, with careful attention to sign, pipes common to two loops receive both corrections. 43

How to find the correction value ( ) h F n 2 kq n (1) Darcy, Manning Q Q o (2) n 1.85 Hazen William h from1& 2 f loop kq n k Q o Neglect terms contains 2 For each loop h F kq loop n kq n kq 0 n o n k Q n o nkq nq h f n1 n1 o kq n 0 n k n 1 2 Q n o Q n2 o nq 2 n1 o... 44

nkq kq n o n1 o n h h Q F F o Note that if Hazen Williams (which is generally used in this method) is used to find the head losses, then h f k Q 185. (n = 1.85), then h 185. If Darcy-Wiesbach is used to find the head losses, then h f k Q 2 (n = 2), then f h f Q 2 h h f f Q 45

Example 11.4 Solve the following pipe network using Hazen William Method C HW =100 63 L/s 1 24 3 2 4 pipe L D 37.8 L/s 1 2 305m 305m 150mm 150mm 5 3 4 610m 457m 200mm 150mm 25.2 L/s 5 153m 200mm 46

h f C 10.7 L 1.852 HW D 4.87 Q 1.852 C HW 100, Q in L/s 1 h f h h f f C 6.0210 K 10.7 L 1.852 HW Q D 1.852 4.87 9 Q 1000 L D 4.87 Q 1.852 1.852 3 2 5 4 0.28 1.85 0.64 F 1 hf n h Q o 0.24 0.45 1.85 0.43 F 2 hf n h Q o 0.57 for pipe2 in loop1 1 for pipe2 in loop 2 2 2 1 47

1 3 2 4 5 hf 0.18 hf 0.07 0.15 hf 1.850.64 hf 1.850.42 1 n Q o 1 n Q o 0.09 for pipe2 in loop1 1 for pipe2 in loop 2 2 2 1 48

Example Solve the following pipe network using Hazen William Method C HW =120 49

Iteration 1 50

for Iteration 1 n kqo Δ n1 nkq o n h h Q f f o Δ Δ Δ Δ 1 2 3 4 185. 185. 101. 3886. 0. 84 79. 41 41. 185. 10171. 153. 185. 154. 75 0. 014 0. 006 0. 022 0. 005 51

Iteration 2 52

Iteration 3 53

Example The figure below represents a simplified pipe network. Flows for the area have been disaggregated to the nodes, and a major fire flow has been added at node G. The water enters the system at node A. Pipe diameters and lengths are shown on the figure. Find the flow rate of water in each pipe using the Hazen- Williams equation with C HW = 100. Carry out calculations until the corrections are less then 0.2 m 3 /min. 54

55

56

57

58

59

60

61

62

63

General Notes Occasionally the assumed direction of flow will be incorrect. In such cases the method will produce corrections larger than the original flow and in subsequent calculations the direction will be reversed. Even when the initial flow assumptions are poor, the convergence will usually be rapid. Only in unusual cases will more than three iterations be necessary. The method is applicable to the design of new system or to evaluate the proposed changes in an existing system. The pressure calculation in the above example assumes points are at equal elevations. If they are not, the elevation difference must be includes in the calculation. The balanced network must then be reviewed to assure that the velocity and pressure criteria are satisfied. If some lines do not meet the suggested criteria, it would be necessary to increase the 64 diameters of these pipes and repeat the calculations.

Summary Assigning clockwise flows and their associated head losses are positive, the procedure is as follows: Assume values of Q to satisfy Q = 0. Calculate H L from Q using h f = K 1 Q 2. If h f = 0, then the solution is correct. If h f 0, then apply a correction factor, Q, to all Q and repeat from step (2). For practical purposes, the calculation is usually terminated when h f < 0.01 m or Q < 1 L/s. A reasonably efficient value of Q for rapid convergence is given by; Q 2 H H L L Q 65

Example The following example contains nodes with different elevations and pressure heads. Neglecting minor loses in the pipes, determine: The flows in the pipes. The pressure heads at the nodes. 66

Assume T= 15 0 C 67

Assume flows magnitude and direction 68

First Iteration Loop (1) Pipe L (m) D (m) Q (m 3 /s) f h f (m) h f /Q (m/m 3 /s) AB 600 0.25 0.12 0.0157 11.48 95.64 BE 200 0.10 0.01 0.0205 3.38 338.06 EF 600 0.15-0.06 0.0171-40.25 670.77 FA 200 0.20-0.10 0.0162-8.34 83.42 S -33.73 1187.89 33.73 3 0.01419 m /s 2(1187.89) 14.20 L/s 69

First Iteration Loop (2) Pipe L (m) D (m) Q (m 3 /s) f h f (m) h f /Q (m/m 3 /s) BC 600 0.15 0.05 0.0173 28.29 565.81 CD 200 0.10 0.01 0.0205 3.38 338.05 DE 600 0.15-0.02 0.0189-4.94 246.78 EB 200 0.10-0.01 0.0205-3.38 338.05 S 23.35 1488.7.35 23 0.00784 m 3 /s 2(1488.7) 7.842 L/s 70

14.20 Second Iteration Loop (1) 14.20 14.20 7.84 Pipe L (m) D (m) Q (m 3 /s) f 14.20 h f (m) h f /Q (m/m 3 /s) AB 600 0.25 0.1342 0.0156 14.27 106.08 BE 200 0.10 0.03204 0.0186 31.48 982.60 EF 600 0.15-0.0458 0.0174-23.89 521.61 FA 200 0.20-0.0858 0.0163-6.21 72.33 S 15.65 1682.62.65 15 0.00465 m 3 /s 4.65 L/s 2(1682.62) 71

7.84 Second Iteration Loop (2) 14.20 7.84 7.84 Pipe L (m) D (m) Q (m 3 /s) f h f (m) h f /Q (m/m 3 /s) BC 600 0.15 0.04216 0.0176 20.37 483.24 CD 200 0.10 0.00216 0.0261 0.20 93.23 DE 600 0.15-0.02784 0.0182-9.22 331.23 EB 200 0.10-0.03204 0.0186-31.48 982.60 7.84 S -20.13 1890.60 20.13 3 0.00532 m /s 2(1890.3) 5.32 L/s 72

Third Iteration Loop (1) Pipe L (m) D (m) Q (m 3 /s) f h f (m) h f /Q (m/m 3 /s) AB 600 0.25 0.1296 0.0156 13.30 102.67 BE 200 0.10 0.02207 0.0190 15.30 693.08 EF 600 0.15-0.05045 0.0173-28.78 570.54 FA 200 0.20-0.09045 0.0163-6.87 75.97 S -7.05 1442.26 7.05 3 0.00244 m /s 2(1442.26) 2.44 L/s 73

Third Iteration Loop (2) Pipe L (m) D (m) Q (m 3 /s) f h f (m) h f /Q (m/m 3 /s) BC 600 0.15 0.04748 0.0174 25.61 539.30 CD 200 0.10 0.00748 0.0212 1.96 262.11 DE 600 0.15-0.02252 0.0186-6.17 274.07 EB 200 0.10-0.02207 0.0190-15.30 693.08 S 6.1 1768.56.1 2(1768.56) 6 3 0.00172 m /s 1.72 L/s 74

After applying Third correction 75

Velocity and Pressure Heads: pipe Q (l/s) V (m/s) h f (m) AB 131.99 2.689 13.79 13.79 23.85 BE 26.23 3.340 21.35 FE 48.01 2.717 26.16 6.52 21.35 1.21 AF 88.01 2.801 6.52 BC 45.76 2.589 23.85 26.16 7.09 CD 5.76 0.733 1.21 ED 24.24 1.372 7.09 76

Velocity and Pressure Heads: p/g+z Z P/g Node (m) (m) (m) A 70 30 40 13.79 23.85 B 56.21 25 31.21 C 32.36 20 12.36 6.52 21.35 1.21 D 31.15 20 11.15 E 37.32 22 15.32 26.16 7.09 F 63.48 25 38.48 77

Example For the square loop shown, find the discharge in all the pipes. All pipes are 1 km long and 300 mm in diameter, with a friction factor of 0.0163. Assume that minor losses can be neglected. 78

Solution: Assume values of Q to satisfy continuity equations all at nodes. The head loss is calculated using; H L = K 1 Q 2 H L = h f + h Lm But minor losses can be neglected: h Lm = 0 Thus H L = h f Head loss can be calculated using the Darcy-Weisbach equation h f L D V 2 2g 79

First trial H H H H H L L L L L h f 2.77 554Q K'Q K' 554 1000 V 0.0163 x x 0.3 2 x 9.81 Q A 2 2 L D 2 2 2 V 2g 2 2 Q 2.77 x x 0.3 4 2 2 Pipe Q (L/s) H L (m) H L /Q AB 60 2.0 0.033 BC 40 0.886 0.0222 CD 0 0 0 AD -40-0.886 0.0222 S 2.00 0.0774 Since H L > 0.01 m, then correction has to be applied. 80

Second trial H Q H 2 L L Q 2 2x0.0774 12.92L / s Pipe Q (L/s) H L (m) H L /Q AB 47.08 1.23 0.0261 BC 27.08 0.407 0.015 CD -12.92-0.092 0.007 AD -52.92-1.555 0.0294 S -0.0107 0.07775 Since H L 0.01 m, then it is OK. Thus, the discharge in each pipe is as follows (to the nearest integer). Pipe Discharge (L/s) AB 47 BC 27 CD -13 AD -53 81