Effect of Torsion Consideration in Analysis of Multi Storey frame

Similar documents
PUSHOVER ANALYSIS FOR THE RC STRUCTURES WITH DIFFERENT ECCENTRICITY

SEISMIC ANALYSIS OF SIX STOREYED RC FRAMED BUILDING WITH BRACING SYSTEMS

Seismic Performance Evaluation of Torsionally Asymmetric Buildings

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):

EARTHQUAKE ANALYSIS OF A G+12 STOREY BUILDING WITH AND WITHOUT INFILL FOR BHUJ AND KOYNA EARTHQUAKE FUNCTIONS

Analytical Study on Seismic Performance of Hybrid (DUAL) Structural System Subjected To Earthquake

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

PERFORMANCE- BASED SEISMIC DESIGN OF A BUILDING

Seismic Analysis and Design of Vertically Irregular RC Building Frames

Seismic Analysis of Steel Frames with Different Bracings using ETSBS Software.

PUSHOVER ANALYSIS OF BUILDING WITH INFILL WALL

Comparative Study of R.C.C and Steel Concrete Composite Structures

Assessment of P-Delta Effect on High Rise Buildings

ANALYSIS OF MULTISTORIED BUILDING WITH AND WITHOUT FLOATING COLUMN USING ETABS

[Mohammed* et al., 5(8): August, 2016] ISSN: IC Value: 3.00 Impact Factor: 4.116

Earthquakes Analysis of High Rise Buildings with Shear Walls at the Center Core and Center of Each Side of the External Perimeter with Opening

Dr. K. R. C. Reddy 1, Sandip A. Tupat 2 1,2

SEISMIC EVALUATION OF HIGH RISE STEEL STRUCTURES WITH AND WITHOUT BRACING

Effect of Column Discontinuity on Base Shear and Displacement of Structure

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 10, 2016 ISSN (online):

Base Isolation In Seismic Structural Design

SEISMIC BEHAVIOUR OF RC BUILDING RESTING ON PLAIN AND SLOPING GROUND WITH BRACINGS AND SHEAR WALL

INTERACTION OF TORSION AND P-DELTA EFFECTS IN TALL BUILDINGS

Pushover analysis of RC frame structure using ETABS 9.7.1

NONLINEAR STATIC ANALYSIS OF R.C.C. FRAMES (Software Implementation ETABS 9.7)

OPTIMUM POSITION OF OUTRIGGER SYSTEM FOR HIGH RAISED RC BUILDINGS USING ETABS (PUSH OVER ANALYSIS)

Study of P-Delta Effect on Tall Steel Structure

Performance Based Seismic Design of Reinforced Concrete Building

Effect of Edge Beam and Shear Wall on the Structural Behavior of Flat Plate Multistoried Building: A Computing Modeling for lateral load Analysis

Available at ISSN

Seismic performance assessment of reinforced concrete buildings using pushover analysis

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online):

Shaking Table Model Test of a HWS Tall Building

SEISMIC BEHAVIOR OF RC BUILDING FRAME WITH STEEL BRACING SYSTEM USING VARIOUS ARRANGEMENTS

ON DRIFT LIMITS ASSOCIATED WITH DIFFERENT DAMAGE LEVELS. Ahmed GHOBARAH 1 ABSTRACT

Seismic Behavior of High Rise Building for Soft Soil in All Seismic Zones Shaik Fayaz 1 Mrs. B.Ajitha 2

Seismic Analysis of Truss Bridges with Tall Piers

PERFORMANCE BASED SEISMIC EVALUATION OF MULTI-STOREYED REINFORCED CONCRETE BUILDINGS USING PUSHOVER ANALYSIS

SEISMIC PERFORMANCE OF CONCRETE TILT-UP BUILDINGS: CURRENT WALL-TO-SLAB CONNECTIONS

Structural Dynamics and Earthquake Engineering

Analysis of Various Steel Bracing Systems using Steel Sections for High Rise Structures

THE EFFECTS OF P-DELTA AND CONSTRUCTION SEQUENTIAL ANALYSIS OF RCC AND STEEL BUILDING WITH RESPECT TO LINEAR STATIC ANALYSIS

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 11, 2016 ISSN (online):

Sabah Shawkat Cabinet of Structural Engineering 2017

Section A A: Slab & Beam Elevation

Council on Tall Buildings

Parametric Study of Dual Structural System using NLTH Analysis Ismaeel Mohammed 1 S. M. Hashmi 2

Application of Pushover Analysis for Evaluating Seismic Performance of RC Building

Evaluation of Earthquake Risk Buildings with Masonry Infill Panels

REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS

Analysis of Reinforced Concrete Building with Different Arrangement of Concrete and Steel Bracing system

STUDY ON TIME HISTORY ANALYSIS METHOD USING STAAD PRO FOR MULTISTORYED BUILDING

NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS

Modelling of RC moment resisting frames with precast-prestressed flooring system

Comparative study of Performance of RCC Multi-Storey Building for Koyna and Bhuj Earthquakes

PERFORMANCE OF LATERAL SYSTEMS ON TALL BUILDINGS

Earthquake Analysis of High Rise Building with and Without In filled Walls

EFFECT OF PLACEMENT AND OPENINGS IN SHEAR WALL ON THE DISPLACEMENT AT VARIOUS LEVELS IN A BUILDING SUBJECTED TO EARTHQUAKE LOADS

THE STUDY ON BEHAVIOUR OF OUTRIGGERS FOR TALL BUILDINGS SUBJECTED TO LATERAL LOAD

Simplified Finite Element Modelling of Multi-storey Buildings: The Use of Equivalent Cubes

Flat Slabs. d 2. A typical flat slab (without drop and column head)

COMPARATIVE STUDY ON REGULAR & IRREGULAR STRUCTURES USING EQUIVALENT STATIC AND RESPONSE SPECTRUM METHODS

Evaluation of Seismic Behavior for Low-Rise RC Moment Resisting Frame with Masonry Infill Walls

Seismic Assessment of an RC Building Using Pushover Analysis

Stability Analysis of Rigid Steel Frames With and Without Bracing Systems under the Effect of Seismic and Wind Loads

Seismic Base Isolation of RC Frame Structures With and Without Infill

Comparative Study of Different Codes in Seismic Assessment

Performance of Buildings During the January 26, 2001 Bhuj Earthquake. Abstract

Nonlinear Static Pushover Analysis of a Shear Wall Building in Madinah

Evaluation of Progressive Collapse Resistance of Multi-Storey RC Building by Linear Static Analysis Method

International Journal of Advance Engineering and Research Development DYNAMICS ANALYSIS OF STRUCTURES SUBJECTED TO EARTHQUAKE LOAD

EARTHQUAKE DESIGN CONSIDERATIONS OF BUILDINGS. By Ir. Heng Tang Hai

Analysis and Design of Multi-Storey Building Subjected to Lateral Forces

Comparative Study of Elastic Analysis and P-Δ Effect in Elevated Water Tank for Seismic Loads

Seismic Analysis of High-Rise Building using Response Spectrum Method Pratik Bawankar 1

Displacement Based Damage Estimation of RC Bare Frame Subjected to Earthquake Loads: A Case Study on 4 Storey Building

COMPARATIVE STUDY ON DESIGN RESULTS OF A MULTI-STORIED BUILDING USING STAAD PRO AND ETABS FOR REGULAR AND IRREGULAR PLAN CONFIGURATION

ANALYSIS AND DESIGN OF COMMERCIAL BUILDING USING ETABS

USE OF FLAT SLABS IN MULTI-STOREY COMMERCIAL BUILDING SITUATED IN HIGH SEISMIC ZONE

Council on Tall Buildings. and Urban Habitat

4. МЕЂУНАРОДНА КОНФЕРЕНЦИЈА Савремена достигнућа у грађевинарству 22. април Суботица, СРБИЈА

Seismic Retrofitting of Building with Soft Storey and Floating Column

Floor Response Spectra Generation for Seismic Design of Buildings

Ground + 4 floor RCC frame structure in Goa Floor to floor height is 3.0m Plan dimension, 24.0 m x 13.5 m SBC = 20 t/sqm, hard Strata is consider for

Application of Buckling Restrained Braces in a 50-Storey Building

Non-Linear Static Analysis of RCC Frames

Shake-table test on a four-storey structure with reinforced concrete and unreinforced masonry walls

Seismic Model Test of a Hybrid High-rise Building in Shanghai

Concept of Earthquake Resistant Design

Comparative Study of the Static and Dynamic Analysis of Multi-Storey Irregular Building

Investigation on Behaviour of Reinforced Concrete Beam Column Joints Retrofitted with FRP Wrapping

Seismic Performance Evaluation of Eccentrically Braced Frame Using PBPD Method

DESIGN AND COMPARISON OF A RESIDENTIAL BUILDING (G+10) FOR SEISMIC FORCES USING THE CODES: IS1893, EURO CODE8, ASCE 7-10 AND BRITISH CODE

PERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140)

Inelastic Versus Elastic Displacement-Based Intensity Measures for Seismic Analysis

DESIGN FOR PROGRESSIVE COLLAPSE 1

DIAGRID STRUCTURAL SYSTEM: STRATEGIES TO REDUCE LATERAL FORCES ON HIGH-RISE BUILDINGS

[Jagadeesh B N* et al., 5(9): September, 2016] ISSN: IC Value: 3.00 Impact Factor: 4.116

This point intends to acquaint the reader with some of the basic concepts of the earthquake engineer:

Transcription:

Effect of Consideration in Analysis of Multi Storey frame Prof. Wakchaure M. R 1, Nagare Y U 2 1, 2 (Department of Civil Engineering, Pune University, India ABSTRACT At present scenario many buildings are asymmetric in plan and/or in elevation based on the distribution of mass and stiffness along each storey throughout the height of the building. Most recent earthquakes have shown that the irregular distribution of mass, stiffness and strengths may cause serious damage in structural systems.al behavior of asymmetric building is one of the most frequent cause of structural damage and failure during strong ground motions. In this work a study on the influence of the effects on the behavior of structure is done. In building two cases are considered, case one is considering and case two is considering. The Indian standard code of practice IS- 1893 (Part I: 2) guidelines and methodology are used to analyzed and designed building. Results are compared in terms of % Ast in columns. Keywords: Asymmetric plan, Earthquake, Eccentricity,. I. INTRODUCTION Most recent earthquakes have shown that the irregular distribution of mass, stiffness and strengths maycause serious damage in structural systems. However an accurate evaluation of the seismic behaviorof irregular buildings is quite difficult and a complicated problem [1].Due to the variety of parameters andthe choice of possible models for ally unbalanced systems, there is as yet no common agreementnor any accurate procedure advised by researchers on common practice in order to evaluate the aleffects. Seismic damage surveys and analyses conducted on modes of failure of building structures during past severe earthquakes concluded that most vulnerable building structures are those, which are asymmetric in nature. Asymmetric building structures are almost unavoidable in modern construction due to various types of functional and architectural requirements. in buildings during earthquake shaking may be caused from a variety of reasons, the most common of which are non-symmetric distributions of mass and stiffness [4,6]. Modern codes deal by placing restrictions on the design of buildings irregular layouts and also through the introduction of an accidental eccentricity that must be considered in design. The lateral-al coupling due to eccentricity between centre of mass (CM) and centre of rigidity (CR) in asymmetric building structure generates al vibration even under purely translational ground shaking [2,3]. During seismic shaking of the structural systems, inertia force acts through the centre of mass while the resistive force acts through the centre of rigidity as shown in Fig. 1. Fig1- Generation of al moment in asymmetric structures during seismic excitation. II. BUILDING DETAILS al behavior of asymmetric building is one of the most frequent sources of structural damage and failure during strong ground motions. In this work a study on the influence of the effects on the behavior of structure is done. In building two cases are considered, i) considering ii) considering. The Indian standard code of practice IS- 1893 (Part I: 2) guidelines and methodologyare used to analyzed and designed building. Results and is compared in terms of Ast required.each case includes 9 beams of same orientation from first to last floor. The structural analysis and design of nine storey reinforced concrete asymmetrical frame building has been done the help of Staad.pro software. The building is assumed as residential building. Linear static analysis has been done. Regular grid plan of the structure is shown in fig 2. The structure is assumed to be located in seismic zone III on a site medium soil. Building contains different irregularity like plan irregularity and Re-Entrant corner irregularity [3]. 1828 P a g e

Fig 2- Building plan Structural data: Table1: Structural data, No of storey = 9 Ground storey height = 2m Intermediate storey height = 3m Total no of columns = 41 Slab thickness = 140mm Outer wall = 230mm Inner wall = 150mm Parapet (1m height) = 230mm Beam size = B1= 150 x 450 mm = B2= 230 x mm = B3= 230 x 450 mm Column size = A1 = x 450 mm = A2= x mm = A3= x 750 mm Grade of concrete = M25 Grade of = Fe Density of concrete = 25kN/m3 Density of brick = 20 kn /m3 Live load = 2 kn /m2 Roof Live load = 1.5 kn /m2 Floor finish = 1.5 kn /m2.. III. ANALYSIS AND DESIGN The asymmetric building is analyzed by modeling two models Case 1: With considering Case 2: Without considering. Case 1 building is modeled in Staad.pro software. Supports are assigned as fixed supports neglecting soil structure interaction. Case 1 is design for 13 load combinations. Case 2 building is same as case1, from output data from Staad.pro the design area of required is calculated by considering one beam at ground floor up to top floor of same orientation. Considering 4 numbers of cases of beams at critical stage to define the effect. Each case includes 9 beams of same orientation from first to last floor. Taking on X-axis and (Ast) in 1829 P a g e

Required ( ) Required ( ) Required ( ) Required ( ) Prof. Wakchaure M. R, Nagare Y U / International Journal of Engineering Research and Floor on Y-axis in both considering and considering effect. IV. RESULT AND DISCUSSION Table 1.Comparison of area of (Ast) in for beam - B6 Beam Gr. fl. 757 337.55 268.9 333.08 269.41 1 925 703.78 523.93 674.16 521.53 2 1093 705.83 525.06 679.59 522.85 3 1261 678.38 507.54 664.32 503.96 4 1429 651.13 476.92 635.61 467.04 5 1597 626.42 429.58 612.25 423.9 6 1765 578.82 398.35 562.86 392.38 7 1933 516.52 351.29 497.29 338.81 8 2101 458.07 278.95 437.87 267.86 9 2269 520.32 317.69 497.40 297.55 650 450 250 ) Graph 1.1 Astvs floor. 650 450 250 out ) Graph 1.2Astvs floor. Beam B6 is an exterior beam span 3.6m. From the above graphs it can be concluded that area of decreases from ground floor to top floor. The trend of this curve declining towards end because the al moment deceases from ground floor to top floor. & isvaries by 2% to 5%. & is varies by 3% to 6%. Here the variation of moment is not significant becausestiffness of beam is less. Stiffness is varying according to span of beam. Displacement increases due to seismic force increases towards top floor. Table 2 Comparison of area of (Ast) in for beam-b40. Floo r Bea m Gr.fl. 759 415.74 320.95 412.17 323.76 1 927 640.28 509.03 636.83 513.16 2 1095 640.52 519.44 639.07 521.43 3 1263 609.86 496.27 610.67 495.96 4 1431 549.53 442.35 553.25 439.21 5 1599 493.72 385.38 493.4 379.56 6 1767 435.21 329.92 430.89 321.42 7 1935 373.1 255.23 363.9 243.76 8 2103 309.81 184.77 295.62 169.67 9 2271 253.35 148.95 241.71 140.71 top Graph 2.1Astvs floor. top Graph 2.2Astvs floor. Beam B40 is an interior beam span 3.5m. Above graphs shows that area of for decreases towards top floor. This trend shows that moment & stresses decrease towards top floor. & is varies by 2% to 4%. & is varies by 2% to 8%. The seismic load is varying according to floor that is increases 1830 P a g e

Steel Required ( ) Ast Required ( ) Prof. Wakchaure M. R, Nagare Y U / International Journal of Engineering Research and Floor towards top floor. Displacement increases due to seismic force increases towards top floor. Table 3.Comparison of area of (Ast) in Beam 0 800 0 0 1 2 3 4 5 6 7 8 9 10 11 Gr.fl 755 553.37 164.22 477.75 163.83 1 923 772.96 203.36 635.85 163.83 2 1091 798.9 205.01 658.34 163.83 3 1259 789.96 190.64 649.4 163.83 4 1427 763 170.2 622.41 163.83 5 1595 736.8 164.22 594.25 163.83 6 1763 698.3 164.22 549.07 163.83 7 1931 614.16 164.22 492.15 163.83 8 2099 538.36 164.22 409.02 163.83 9 2267 320.06 159.82 315.36 156.60 for beam B7. ) out ) 1 963 493.67 196.23 429.98 163.83 2 1131 548.31 197.89 488.97 163.83 3 1299 545.77 190.08 494.29 163.83 4 1437 904.61 226.99 764.92 163.83 5 1635 538.99 164.22 466.9 163.83 6 1803 502.6 164.22 425.14 163.83 7 1971 444.41 164.22 373.61 163.83 8 2139 407.04 164.22 324.91 163.83 9 2298 236.97 105.57 234.61 105.57 0 0 1 2 3 4 5 6 7 8 9 10 11 ) out ) Graph 4.1: Astvs floor for top & bottom & Beam B-60 is an interior beam span 1.7m. It can be concluded from above graph that top & is varies by 10% to 20 %. & is varies by 15% to 30%. Here moment is more significant. The load from secondary beam comes on it. The effect of seismic force is observed at end of beam. There is no effect on mid span moment & hence on midspan. Graph 3.1: Astvs floor for top & bottom & Beam B-7 is an interior beam span 1.2m. Here the span of beam is less. Due to this stiffness is more. Hence more moment will be attracted. Above graph shows that top & is varies by 15% to 25 %. & is varies by 2% to 20%. Here moment is more significant. The load from secondary beam comes on it. The effect of seismic force is observed at end of beam but there is no effect on mid span moment & hence on mid span. Table 4 Comparison of area of (Ast) in for beam B60. V. CONCLUSION Thus, it can be said that the effect must be taken into account in design practice for asymmetrichigh-rise structures to understand the actual safety margins. After analyzing the building following concluding points are drawn, i) In the asymmetric building case 2, that is considering, it was observed that the area of in the beams at critical stage are much smaller than those obtained in the case 1, that is considering. The bottom bars should be more critical, because they seem to be subjected to more tension than the top bars therefore al behavior of asymmetric building is one of the most frequent source of structural damage and failure during strong ground motions. ii) The variation of Ast is much higher for Beam small span beams. Most of the designer adopts approximate methods for the al analysis of building. However this may be an inaccurate assessment. Several studies of Gr.fl 795 355.72 163.83 306.52 163.83 structural damage during the past earthquake reveal 1831 P a g e

that is the most critical factor leading to major damage or complete collapse of building. It is, therefore, necessary that irregular buildings should be analyzed for. REFERENCES [1] Dr. Naresh Kumar B.G. and Gornale Avinash. Seismic Performance Evaluation of ally Asymmetric Buildings. International Journal of Science and Engineering Research, Volume 3, Issue 6, June 2012. [2] Edoardocosenza, Gaetano manfredi and Roberto realfonzo. Earthquake damages at the perimeter of buildings are often the result of excessive deformations caused by during the earthquake. [3] MaskeSachin G., Dr. Pajgade P. S. al Behavior of Asymmetrical Buildings. International Journal of Modern Engineering Research (IJMER) Vol.3, March-April. 2013. [4] Stathopoulos K.G. and Anagnostopoulos S. A. Earthquake Induced Inelastic in Asymmetric Multistory Buildings. 13th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 4. [5] Francisco crisafulli, AgustínReboredo and Gonzalo Torrisi. Consideration of Effects in the Displacement Control of ductile Building. 13th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 4. [6] V.I. Fernandez-Davila and E.F. Cruz. Estimating inelastic Bi-directional Seismic Response of Multi- Storey asymmetric Buildings Using a Set of Combination Rules. The 14th World Conference on Earthquake Engineering October 12-17, 8, Beijing, China. [7] Wensheng LU and Xilin LU. Seismic model Test And Analysis Multi-Tower High Rise Buildings. [8] Amarnath Roy Chowdhury and Siddhartha Ghosh. Inclusion of P-Delta Effect in the Estimation of Hysteratic Energy Demand Based on Modal Pushover Analysis. [9] KohjuIkago. Dynamic Instability in the High Rise Steel structures Subjected to Strong Ground motions. GraduateSchool of Engineering, TohokuUniversity, Sendai, Japan. [10] S. M. Wilkinsoni and R. A. Hileyii. Collapse Behavior High Rise Buildings. 13th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 4. [11] Mario de Stefano, RaffaeleNudo, StefaniaViti. Evaluation of Second Order Effect On The Seismic Performance RC Frame Structure. 13th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 4. 1832 P a g e