Sika Galvashield CC Embedded Galvanic Anodes for Corrosion Control in Contaminated but Sound Concrete

Similar documents
Section Fluid Applied Waterproofing

PRODUCT DATA SHEET Sika Galvashield XP

INNOVATIVE SOLUTIONS FOR REINFORCEMENT CORROSION

TECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS. Financial Project ID , &

STANDARD SPECIFICATION FOR CRIBLOCK CONCRETE CRIBWALL

SPECIAL SPECIFICATION 4900 Sacrificial Cathodic Protection Pile Jacket

MS-2A LINER SPECIFICATIONS: for STRUCTURAL REPAIR and SEALING of MANHOLES

Construction. SikaTop 111 Plus. Application Instructions. Sika Corporation

CELCORE CELLULAR INSULATING CONCRETE SPECIFICATION FOR RETROFIT PLACEMENT OVER EXISTING ROOF MEMBRANES

A. Drawings and general provisions of the contract, including General and Supplementary Conditions, apply to this section.

***************************************************************************************************************

FIVE STAR PRODUCTS, INC. (800)

SECTION CAST-IN-PLACE CONCRETE

Construction. Sika Armatec 110. Application Instructions. Sika Corporation

Construction. Sika Armatec 110. Application Instructions. Sika Corporation

TABLE OF CONTENT

SECTION EXPANSION CONTROL

September 1, 2003 CONCRETE MANUAL SPECIAL TYPES OF CONCRETE

SECTION MOISTURE RESISTANT/WATER-PROOF FLOORING ADHESIVE FOR CONCRETE SLABS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

Proudly Made in the U.S.A.

Ductile Iron Piles Corrosion Resistance

GUIDE SPECIFICATIONS For STRUCTURAL PRECAST HOLLOW CORE SLABS SECTION 03410

A. Submittal Procedures: See Article 13 of the General Conditions.

By CTS Cement Manufacturing Corp.

KOSTER AMERICAN CORPORATION

SECTION XXXX POLYMER CONCRETE PUMP STATIONS

Strong-Seal Sealant Specification, a permanent method of sealing the interior of the chimney and casting in manholes and catch basins.

SECTION CHAIN LINK FENCES AND GATES (GALVANIZED) A. Fence framework, fabric, gates, and accessories.

Minimum Guidelines for the Design and Use of Underpins When Performing Foundation Stabilization and/or Supplementation UP-08

CTP STITCH-TIE AGAIN! Quick and easy way to re-anchor existing veneers to back-up structures.

European Standard En 1504


STRUCTURAL MASONRY SPECIAL INSPECTOR. Study Guide

SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL

FIVE STAR PRODUCTS, INC.

STANDARD SPECIFICATIONS SECTION JACKED CASING

Section 2: Underground

SECTION MASONRY ACCESSORIES

DIVISION 9 FINISHES Section Floor Finishes

STANDARD INSPECTION OF GUY ANCHORS IN DIRECT CONTACT WITH SOIL. Rev: 4/06

SPECIFICATION GUIDELINE

ESR ICC Evaluation Service, Inc. Reissued January 1, 2008 This report is subject to re-examination in one year.

American Metal Specialties, Inc.

CSI SECTION MAINTENANCE OF CONCRETE Repair & Resurfacing with Rapid Hardening, High Strength, Low-Shrink, Non-Metallic Cementitious Materials

Florock Seamless Flooring Systems

1.3 Work shall include all reinforcement and accessories necessary to complete installation.

SUGGESTED MANHOLE FRAME SEALING SPECIFICATION (Rehabilitation)

SECTION ARCHITECTURAL CAST STONE

Best Management Standards / Specifications. For Concrete Slab Raising. Prepared in conjunction with the Concrete Repair Association

San Antonio Water System Standard Specifications for Construction ITEM NO. 850 SANITARY SEWER STRUCTURES

Specification Lightning Protection Systems

SECTION COMMON WORK RESULTS FOR CONCRETE SSPECIALTY COATINGS

HANDHOLES, PULLING VAULTS AND JUNCTION BOXES

May 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building

SECTION RIGID PAVEMENT. 1. Portland Cement Concrete (PCC) pavement. 2. Section Aggregate Base Course.

SECTION mil thickness COLD FLUID-APPLIED WATERPROOFING

Standard Specifications for Road and Bridge Construction. Adopted January 1, 2012

DIVISION 3 HEAVY DUTY CONCRETE FLOOR TOPPING SECTION 03340

SAMPLE SPECIFICATION for CROSSHOLE SONIC LOGGING (CSL) September 2015

METAL HANDRAILS AND RAILINGS. A. Properly identified manufacturer's literature, including shop and erection drawings before starting work.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Fence & Guardrail Block Reference Manual ReCon Series 50

A. Drawings and general provisions of the contract, including General and Supplementary Conditions, apply to this section.

BAYFILTER SPECIFICATIONS

Single Post Anchor Part Number Spectrum Lane ~ Missoula MT ~

WORK REPORT FOUNDATION REPAIR AND REGROUT NUOVO-PIGNONE 6HE COMPRESSOR ENAGÁS BARCELONA PORT. REPORT NO: V-011 DATE: 6 August 2001 PAGE NO: 1

Author: M Shaw, Sika Limited. Construction. A Guide to the Concrete Repair European Standards BS EN 1504 Series

PARKING FACILITIES REPAIR SOLUTIONS

CONDUITS AND FITTINGS

DBI-SALA Uni 8 Overhead Horizontal Lifeline Cable System SECTION HORIZONTAL FALL PROTECTION - OVERHEAD CABLE

Protective Coatings for Underground Utility Concrete Structures. By: John E. Davis Inside Sales & Marketing Specialist: Sauereisen, Inc.

1.02 STANDARD REFERENCES: The following standard specifications shall apply to the Work of this Section as indicated:

Broadcast Parking Garage System

Section 2 Supplemental Specification 2.11 High Tension Cable Barrier

Chevy Chase Club June 30, 2008 Bowie Gridley Architects SECTION GYPSUM BOARD SHAFT WALL ASSEMBLIES

PRECAST CONCRETE ON-SITE WASTEWATER TANKS

TILE TILE

MANHOLES, VAULTS AND CATCH BASINS SECTION A. Section Soil and Aggregate Materials. C. Section Storm Drainage Systems

Vertical and Overhead Spall Repair by Hand Application

CHAPTER 11 CONDUITS AND FITTINGS

SECTION GROUNDING AND BONDING

Flygt Advanced Low Pressure Sewer System Package

PROJECT: TULSA COMMUNITY COLLEGE BOOKSTORE RENOVATION PROJECT NUMBER: ISSUE: CONSULTANT: SEAL: SHEET NUMBER: GENERAL NOTES

High performance shrinkage compensated cementitious grout

1.2 Reference Standard: NOFMA - National Oak Flooring Manufacturers Association Grading Standards.

TYPICAL INSTALLATION INSTRUCTIONS

CONCRETE STEPS, HANDRAILS, AND SAFETY RAIL

SECTION SITE CONCRETE

Section Storm Sewers STORM SEWERS PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Storm Sewers. B. Abandonment of Storm Sewers

CAST IN PLACE TACTILE / DETECTABLE WARNING SURFACE TILES

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards

NGWA s Water Well Construction Standard: ANSI/NGWA 01-14

ITEM D-701 PIPE FOR STORM DRAINS AND CULVERTS

A. Section includes hydraulic-cement-based, polymer-modified, self-leveling underlayment for application below interior floor coverings.

MASTER GUIDE SPECIFICATION

SECTION RESILIENT SHEET FLOORING

RETAINING WALL LEVEL BACKFILL

8245 Remmet Ave Canoga Park, CA (888) Installation Instructions - AVM System 700 Under Tile Waterproofing and Anti-Fracture Membrane

Surface Repair Using Form-and- Pour Techniques

Transcription:

Sika Galvashield CC Embedded Galvanic Anodes for Corrosion Control in Contaminated but Sound Concrete Note To Specifier: This document is intended to provide assistance in developing a specification for the installation of embedded zinc anodes and should be modified as appropriate to accommodate project-specific conditions and applications. Refer to the Galvashield CC product data sheet for anode selection and spacing guidelines. For additional information, contact Sika Corporation. PART 1 GENERAL 1.01 Related Documents A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.02 Summary A. This Section includes furnishing all labor, tools, materials, equipment and services necessary to properly install embedded galvanic anodes. B. Embedded galvanic anodes are designed to provide corrosion control in chloridecontaminated or carbonated concrete. When placed in drilled holes at the appropriate spacing, the anodes will extend the service life of the concrete structure. 1.03 References A. ACI/ICRI 2003 Concrete Repair Manual B. ACI 222R Corrosion of Metals in Concrete C. ASTM C 309 Curing Compounds for Concrete D. ASTM B418-95a Standard Specification for Cast and Wrought Galvanic Zinc Anodes E. ASTM A82-97a Specification for Plain Steel Wire for Concrete Reinforcement 1.04 Installation Contractor A. The embedded galvanic anodes shall be installed by an experienced concrete repair contractor as determined by the owner [owner s representative]. 3200US-2010AUG3-1

PART 2 PRODUCTS 2.01 Materials A. Embedded galvanic anodes shall be cylindrical in shape, approximately 1 ¾ inches in diameter by 2 ½ inches high (44 mm x 64 mm), pre-manufactured, and consist of electrolytic high-grade zinc in compliance with ASTM B418-95a Type I cast around a steel electric lead wire in compliance with bright annealed ASTM A82-97a and encased in a highly alkaline cementitious shell with a ph of 14 or greater. The cementitious shell shall contain no chlorides or other corrosive constituents as per ACI 222R. Embedded galvanic anodes shall be Sika Galvashield CC [Specify type of anode i.e. CC65, see note below] from Sika Corporation, or approved equal. Note to Specifier: Galvashield CC s are available in 3 standard configurations (CC65, CC100, and CC135). Custom sizes are also available for specific projects. Anode selection should be based on factors such as steel density and concrete thickness. Refer to Galvashield CC product data sheet for selection and spacing guidelines. Specify the required CC product in 2.01 A. B. Grouting material shall be Galvashield Embedding Mortar available from Sika Corporation or approved equal. C. Rebar connections shall be made using Galvashield CC Rebar Connection Kit and Galvashield CC Setting Tool from Sika Corporation or approved equal. D. Anode connections shall be made using Galvashield CC Anode Connection Kit from Sika Corporation or approved equal. E. Application for approved equals shall be requested in writing two weeks before submission of project bids. Application for anode equals shall include: 1. A highly alkaline cementitious shell with a ph of 14 or greater. 2. Provide a minimum of 10 years service life in similar environment. 3. Contain no corrosive constituents detrimental to reinforcing steel, e.g. chloride, etc. 4. Proven track record showing a minimum of three years satisfactory field performance. 5. A minimum of three projects of similar size and application. 6. Anodes shall be supplied with integral steel lead wire for making connection with the reinforcing steel. F. Deliver, store, and handle all materials in accordance with manufacturer s instructions. 3200US-2010AUG3-2

PART 3 EXECUTION 3.01 Anode Layout A. Using a suitable rebar locator, the location of the reinforcing grid should be determined and marked out in areas where anodes are to be installed. B. Mark out locations for anode installation. The anodes shall be installed in a grid pattern with a maximum spacing of [enter maximum grid dimension] on center, in each direction. When possible, anodes shall be installed a minimum 4 inches (100 mm) away from reinforcing grid. Note to Specifier: Refer to Galvashield CC product data sheet for product selection and spacing guidelines. Specify maximum grid dimensions in 3.01 B. C. Mark out location of rebar connections. If the anodes are to be individually connected, one rebar connection per anode is required. If the anodes are to be installed in series, two rebar connections per string of anodes are required with a maximum of 10 anodes per string. 3.02 Drill Holes A. Rebar Connection Electrical connection shall be established using a Galvashield CC Rebar Connection Kit. At the location of the rebar connections, drill ½ inch (12 mm) diameter holes from the concrete surface until contact is established with the top surface of the rebar. B. Anode Location - Drill a hole 2 inches (50 mm) in diameter by a minimum of 3 ¾ inches (95 mm) deep in close proximity to marked out location to accommodate the anode. Do not damage rebar when drilling holes. Note to Specifier: Maximum anode spacing guidelines can be found on the Sika Galvashield CC data sheet. Anode spacing should be adjusted for aggressive source conditions or for an extended anode service life. If Galvashield CC100 or Galvashield CC135 anodes are to be installed, modify hole dimensionsin 3.02B appropriate for the selected anode. For additional information, refer to the Galvashield CC data sheet. C. Saw cuts All saw cuts into the concrete surface between the anode installation holes and the rebar connection holes shall be approximately ¼ inch (6 mm) wide by ½ inch deep. 1. If anodes are to be individually connected, saw cut grooves between the anode installation hole and the rebar connection hole for each anode location. 2. If anodes are to be installed in series, saw cut a single continuous groove between the anode installation holes and the rebar connection holes. D. All holes and saw cuts shall be cleaned of debris and concrete dust. 3200US-2010AUG3-3

3.03 Rebar Connections A. Using one Galvashield CC Rebar Connector per rebar connection hole, place the weighted end of the connector into the drilled hole until the steel coil contacts the top of the rebar. B. Feed the steel connector wire through the Galvashield CC Setting Tool and set into place by striking with a hammer. C. Proper connection and rebar continuity shall be verified between two rebar connections using a multi-meter. Maximum resistance between the two locations shall be less than 1 ohm. 3.04 Anode Installation A. Holes shall be in a saturated-surface dry condition prior to anode placement. B. Presoak anodes in a small volume of water for 10 to 30 minutes. Remove from water bath immediately prior to installation. C. Complete wiring between the anodes and the rebar conections. 1. If anodes are to be installed in series: a. Trim the cable supplied in the Anode Connection Kit leaving enough length to interconnect the anodes and rebar locations along a single string. Trim the steel anode connection wire on each anode to a length of approximately ½ in. (12 mm) b. Insert the interconnecting cable though the open side of the button-type wire connectors supplied in the Galvashield CC Anode Connection Kit and the steel anode wire into the terminated side. With the anode along side of the installation hole, crimp the button connector until it is flush with its casing. c. Connect the bare ends of the interconnecting cable and reinforcing steel connector wires using the same procedures as outlined above in 3.04.C.1.b. d. After all anodes along the string are connected to the interconnecting cable, verify continuity between anodes and rebar connections with a multi-meter. Resitivity of 1 ohm or less is acceptable. 2. If anodes are to be connected individually: a. Trim the steel anode connection wire on each anode to a length of approximately ½ in. (12 mm). b. Insert the end of the rebar connection wire though the open side of the button-type wire connectors supplied in the Galvashield CC Anode Connection Kit and the steel anode wire into the 3200US-2010AUG3-4

terminated side. Crimp the button connector until it is flush with its casing. c. Verify continuity between steel anode wire and rebar connection wire with a multi-meter. Resitivity of 1 ohm or less is acceptable. D. Mix the embedding mortar per the manufacturer s instructions. After removing excess water from the presoaked holes, fill each anode installation hole approximately 2/3 full with mixed embedding mortar. E. Insert an anode into each hole, forcing the embedding mortar to fill the annular space from the bottom up. Top off the hole with embedding mortar and strike off excess flush with the concrete surface. Minimum cover over the top of the anode shall be 1 in. (25 mm). F. After burying all wiring into the saw cut and drilled holes, backfill saw cut and rebar connection holes with embedding mortar or other material approved by the owner [owner s representative] and strike off flush with the concrete surface. Note to Specifier: While it is important that the Sika Galvashield CC anodes be grouted into place with the specially formulated Galvashield Embedding Mortar, saw cuts and rebar connection holes can be backfilled with the Galvashield Embedding Mortar or other cementitious or polymer-based materials. G. Wet cure cement-based mortar(s) or cure with two coats of a membrane-forming concrete curing compound meeting the requirements of ASTM C309. H. Protect area from traffic for 24 hours. END OF SECTION The preceding specifications are provided by Sika Corporation as a guide for informational purposes only and are not intended to replace sound engineering practice and judgment and should not be relied upon for that purpose. SIKA CORPORATION MAKES NO WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED, AS TO THE ACCURACY, COMPLETENESS OR THE CONTENTS OF THESE GUIDE SPECIFICATIONS. Sika Corporation assumes no liability with respect to the provision or use of these guide specifications, nor shall any legal relationship be created by, or arise from, the provision of such specifications SIKA SHALL NOT BE RESPONSIBLE UNDER ANY LEGAL THEORY TO ANY THIRD PARTY FOR ANY DIRECT OR CONSEQUENTIAL DAMAGES OF ANY KIND ARISING FROM THE USE OF THESE GUIDE SPECIFICATIONS. The specifier, architect, engineer or design professional or contractor for a particular project bears the sole responsibility for the preparation and approval of the specifications and determining their suitability for a particular project or application. Prior to each use of any Sika product, the user must always read and follow the warnings and instructions on the product's most current Technical Data Sheet, product label and Material Safety Data Sheet which are available at www.sikaconstruction.com or by calling (201) 933-7452. Nothing contained in any Sika materials relieves the user of the obligation to read and follow the warnings and instructions for each Sika product as set forth in the current Technical Data Sheet, product label and Material Safety Data Sheet prior to product use. 3200US-2010AUG3-5