UNS 5kA Arrester. Certified Test Report IEC

Similar documents
Understanding New IEC Mechanical Test Requirements of Arresters

Polymer Cutout Testing Recommendations

Polymer Cutout Evaluation NEETRAC

DATA SHEET Metal Element Current Sensing Chip Resistor CLS Series

APEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester

SURGE ARRESTERS kv in silicone shield

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS

MAR 17 Rev B1

TEST REPORT IEC Information technology equipment Safety Part 22: Equipment to be installed outdoors

Technical Specification for LV ABC Fuse Switch Disconnectors

YINGLI SOLAR TWINMAX MODULES Installation and User Manual

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

DATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0

INNOVATIVE LIFE-CYCLE CONCEPTS FOR MEDIUM-VOLTAGE SWITCHGEAR ON BROWN COAL SURFACE MINING DEVICES

SMPM Female Cabled Connectors

ROLINX Laminated Busbar. Design Rules Version 01 (12/2015)

SOT-23 Reliability November 23, 1998

7343M/BAC3-ATVA/C5. Lamp

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application

General Requirements. Technical Specifications for Insulators of Transmission Lines

Scope of Accreditation For Retlif Testing Laboratories

INTERNATIONAL STANDARD

SYGT/S530-E2 LAMP. Features. Description. Applications. Device Selection Guide. Choice of various viewing angles

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

High Quality Porcelain Insulators for Transmission Lines

PART MATERIAL REMARK Metal Case with Pig-tail. Brass (Metal Case) Copper (Pig-tail) Star Contact Copper Silver Plated

General Purpose Chip Resistors MCMR Series

Product Specification JUL 14 Rev. A1

Mar11 Rev D

A Study of Environmental Test Sequences for Electrical Units Jung Ho Yang, Yong Soo Kim

TYPE TEST REPORT OF 11 KV 3 x 240 mm² CU/XLPE/SWA/PVC CABLE. Kinectrics International Inc. Report No.: K RC-0001-R00.

Product or Process Modifications Requiring Limited CBTL Retesting to Maintain Safety Certification

Mar11 Rev B

Friday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems

COMMERCIAL & INDUSTRIAL AMI METER TESTING SUMMARY

Study Committee A3. High Voltage Equipment. Action Plan

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Mar11 Rev C

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

Tantalum Wet Electrolytic Capacitor

Resin impregnated paper bushings. Product information

Surge arrester 3EB4. with polymeric composite housing for operating aboard traction units

Accelerated Testing and Durability. Qualifying your Industrial Anticorrosive Coatings

3.0) TRANSMISSION LINES MINIMUM REQUIRED STANDARDS LINES

Standard of Practice - Campus Electrical Distribution System

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

High Current Thermal Fuse

Transport of IGCT. The transportation of IGCT is classified according to IEC set IE22. Power and productivity for a better world

THE KENYA POWER AND LIGHTING CO. LTD

Factors Affecting Current Ratings for Underground and Air Cables

Fault current interruption in HVDC networks. Tim Schultz

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

Topview 5630 Red SMD LED

Paragraph/ Figure/Table

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -

OSHA s Enforcement and Significant Changes in 2015 NFPA 70E. Presented by Doug Tellin Electrical Safety Specialists LLC.

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS

Anecto Ltd. Ballybrit Business Park, Galway. Testing Laboratory Registration number: 175T

ISO INTERNATIONAL STANDARD. Optics and photonics Environmental requirements Part 6: Test requirements for medical optical instruments

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

High power chip resistors < Wide terminal type > LTR series

INTERNATIONAL STANDARD

Sidelooker Infrared LED IR928-6C-F

Feb12 Rev D

Polymer Suspension Insulators 69kV to 765kV

PowerEnergy MCC. Designed by the specialist for accidental arc fault protection!

Seismic Considerations of Circuit Breakers

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

Hazards. Hazards. Hazards. Effects on the Body. GA Tech Electrical Safety Presentation

Energy Division Insulators

Lightning exposure of Carbon Fiber Composites in wind turbine blades

PHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-P156-60

Investigation of leakage current flow through wooden poles structures on overhead distribution system

SPR-54 Series. Data Sheet. Outline. Features. Viewing angle 2θ 1/2 : 45. Recommended Solder Pattern. Dimensions. Specifications. 1/ Rev.

Electrical Research and Testing Laboratory Nuremberg

2 of 13 pages Directory 1. Outline Drawing 3/13 2. Features 3/13 3. Typical Applications 3/13 4. Specifications 3/13 5. Capacitor series code informat

High Stability Resistor Chips (< 0.25 % at Pn at 70 C during 1000 h) Thick Film Technology

ELECTRICAL BULLETIN

TECHNICAL SPECIFICATION

Gas-insulated medium-voltage switchgear. for wind parks. Answers for energy.

EUROPEAN ETS TELECOMMUNICATION February 1992 STANDARD

Anti-surge chip resistors

Through Hole Lamp Product Data Sheet LTL2P3TBK5 Spec No.: DS Effective Date: 05/11/2012 LITE-ON DCC RELEASE

G M R H T B F A

5mm Round Standard T-1 3/4 Type Full Color Blinking LED Technical Data Sheet. Part No.: LL-F506RGBC2E-F2

LED light engine / OLED LED compact. Umodule STARK SLE GEN2 Mini STARK SLE LES 10 LES 17 Ø10 13,5. PURE (without housing) Ordering data.

3.0x2.0mm SMD LED WITH CERAMIC SUBSTRATE. PRELIMINARY SPEC Part Number: AT3020QB24ZS-RV Blue. Features. Material as follows: Package Dimensions

Through Hole Lamp Product Data Sheet LTL-1BEWJ Spec No.: DS Effective Date: 07/10/2012 LITE-ON DCC RELEASE

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions

Development of 5-MW Downwind Turbine and Floating Substation Facility for Offshore Wind Power

A Proper Design of Wind Turbine Grounding Systems under Lightning

Facility Interconnection Requirements

SOLAR MODULES FOR ROOFTOP SYSTEMS AND SOLAR PARKS ENGLISH

Sulfur tolerant chip resistors

DESIGN VERIFICATION TEST REPORT ERCDA SS-TD-TU. Mated with ERF L-DV-L

Transcription:

CP No.: CP0504 Page 1 of 10 UNS 5kA Arrester Certified Test Report IEC 60099-4 2004 CERTIFICATION Statements made and data shown are, to the best of our knowledge and belief, correct and within the usual limits of commercial testing practice. Michael M Ramarge Chief Engineer Jonathan J Woodworth Arrester Engineering Manager DATE: May 2006 Supercedes June 2005 Cooper Power Systems, Inc.

CP No.: CP0504 Page 2 of 10 INTRODUCTION This test report certifies that the UltraSIL VariSTAR arresters UNS Class 1 5kA were successfully tested to IEC 60099-4:2004 Metal-Oxide surge arresters without gaps for a.c. systems. TEST PROGRAM OBJECT To demonstrate that the UltraSIL VariSTAR Arresters Class 1 5kA meet all performance requirements. PROCEDURE The following design tests were performed on a sufficient number of samples to demonstrate all performance requirements are met. TYPE TESTS A. Insulation Withstand Test a) Lightning Impulse Voltage Test Per IEC 60099-4 Section 8.2.6 b) Power Frequency Voltage Test.. Per IEC 60099-4 Section 8.2.8 B. Residual Voltage Test a) Steep Current Impulse Residual Voltage Test.. Per IEC 60099-4 Section 8.3.1 b) Lightning Impulse Residual Voltage Test. Per IEC 60099-4 Section 8.3.2 C. Long Duration Current Impulse Withstand Test Per IEC 60099-4 Section 8.4.3 D. High Current Impulse Operating Duty Test. Per IEC 60099-4 Section 8.5.4 E. Power Frequency Voltage vs. Time. Per IEC 60099-4 Section 6.10, Annex D F. Characteristics of an Arrester Short Circuit Tests.. Per IEC 60099-4 Section 6.11 G. Internal Partial Discharge Tests Per IEC 60099-4 Section 8.8 H. Moisture Ingress Test a) Terminal Torque Pre-conditioning. Per IEC 60099-4 Section 10.8.13.2.1 b) Thermo Mechanical Pre-conditioning.... Per IEC 60099-4 Section 10.8.13.2.2 c) Water Immersion Test. Per IEC 60099-4 Section 10.8.13.3 d) Verification Tests Per IEC 60099-4 Section 10.8.13.4 I. Weather Aging Tests a) Test Series A: 1000 hr. Per IEC 60099-4 Section 10.8.14.2.1 b) Test Series B: 5000 hr. Per IEC 60099-4 Section 10.8.14.2.2 J. Mechanical Tests a) Test of the Bending Moment.. Per IEC 60099-4 Section 8.9 b) Sulphur Dioxide Test. Per IEC 60099-4 Section 8.10.3.2 c) Salt Mist Test. Per IEC 60099-4 Section 8.10.3.3 K. Disconnector Operation. Per IEC 60099-4 Section 8.6.3 RESULTS The UltraSIL VariSTAR arresters met all performance requirements of IEC 60099-4:2004.

CP No.: CP0504 Page 3 of 10 TEST A: INSULATION WITHSTAND AT-96023133 To demonstrate the voltage withstand capability of the external insulation of the arrester housing. Lightning Impulse Voltage Test The sample was clean and dry. The sample was subject to fifteen positive and negative 1.2 X 50 μs impulses. The sample passed with less than two discharges at the positive and negative voltage values. No internal discharges occurred. Power Frequency Voltage Test The sample was clean and tested under wet conditions. The sample was subject to a power frequency voltage of 0.88 times the lightning impulse protection level for a period of 1 minute. The sample passed with no discharges during the one-minute period. TEST B: RESIDUAL VOLTAGE TESTS AT-96007051 To determine the maximum discharge voltage for each discharge current. Steep Current Impulse Residual Voltage Test One steep current impulse was applied to each sample with a peak value equal to the nominal discharge current of the arrester. The current impulse had a front time between 0.9μs to 1.1μs and the virtual time to half-value on the tail was not longer than 20μs. Lightning Impulse Residual Voltage Test A lightning current impulse was applied to each sample for approximately 0.5, 1, and 2 times the nominal discharge current. The current impulse had a front time between 7μs to 9μs and the virtual time to half-value on the tail was between 18μs to 22μs.

CP No.: CP0504 Page 4 of 10 Result: U R Arrester Rating (kv, rms) U C COV (kv, rms) Steep Current Residual Voltage (kv, crest) Lightning Impulse Residual Voltage (kv, crest) 8/20 μs Current Wave 1.5 ka 3 ka 5kA 10kA 20kA 40kA 3 2.55 10.9 9.0 9.7 10.4 11.4 13.0 15.1 6 5.10 21.8 17.9 19.4 20.8 22.7 26.0 30.2 9 7.65 31.4 25.8 28.0 30.0 32.8 37.4 43.5 10 8.40 32.7 26.9 29.1 31.2 34.1 38.9 45.3 12 10.2 41.1 33.8 36.5 39.2 42.9 48.9 56.9 15 12.7 51.3 42.2 45.7 49.0 53.6 61.1 71.1 18 15.3 61.6 50.8 54.8 58.8 64.3 73.4 85.3 21 17.0 65.4 53.7 58.2 62.4 68.2 77.9 90.6 24 19.5 76.3 62.7 67.8 72.8 79.6 90.8 106.0 27 22.0 86.3 71.0 76.8 82.4 90.1 103.0 120.0 30 24.4 96.2 79.1 85.6 91.8 100.0 115.0 133.0 33 27.0 107.0 87.8 95.1 102.0 112.0 127.0 148.0 36 29.0 115.0 94.7 103.0 110.0 120.0 137.0 160.0 TEST C: LONG DURATION CURRENT IMPULSE WITHSTAND TEST AT-96004925 To demonstrate the ability of the arrester to meet the long duration current impulse withstand test requirements. The sample was subject to eighteen impulses, divided into six groups of three operations, with 50-60 seconds between impulses. The samples cooled to ambient temperature between impulses. The samples met test requirements with less than 5% change in residual voltage and no physical damage.

CP No.: CP0504 Page 5 of 10 TEST D: HIGH CURRENT IMPULSE OPERATING DUTY TEST AT-96004039 To demonstrate the ability of the arrester to meet the high current impulse operating duty test requirements. The sample was subject to twenty 8/20 lighting current impulses with a peak value equal to the nominal discharge current of the arrester with the sample at U C. The impulses were divided into four groups of five impulses, with 50-60 s between impulses and 25-30 minutes between groups. The sample was then subject to two 65Ka + 10kA high current impulses. Within 100ms of the second impulse, the sample shall be energized at U R for 10 s and U C for 30 minutes. The samples met test requirements with less than 5% change in residual voltage, achieving thermal stability, and no physical damage.

CP No.: CP0504 Page 6 of 10 TEST E: POWER FREQUENCY VOLTAGE VS. TIME AT-96004044 To determine the over voltage values and time durations for the arrester design. The sample was subject to one high current impulse, 4 X10 μs, at the elevated temperature 60 o +3 o C. The sample was then subject to each over voltage at each specified time range. The recovery voltage of U C was applied to the sample for thirty minutes. 1.600 1.500 1.511 Voltage (per unit COV) 1.400 1.300 1.200 1.430 1.353 1.280 1.212 1.146 1.100 1.000 0.1 1 10 100 1000 10000 Time (sec)

CP No.: CP0504 Page 7 of 10 TEST F: CHARACTERISTICS OF AN ARRESTER: SHORT CIRCUIT TEST S2-03135-A KEMA To verify arrester with internal fault is not likely to create an explosive event. Samples were pre-killed using an over voltage applied for 5+3 minutes. Two 36kV arresters were then tested at full voltage and two 36kV arrester was tested at a reduced voltage. The 36kV arresters tested at full voltage met high current test requirements of 20kA The 60kV arresters tested at reduced voltage met low current test requirements of 600A. TEST G: INTERNAL PARTIAL DISCHARGE TESTS A4-003924 To verify the arrester design does not generate excessive partial discharge. The sample was energized to the rated voltage for 2 seconds. The voltage was then lowered to 1.05 * U C and the partial discharge level was recorded. The samples met test requirements with partial discharge < 10pC.

CP No.: CP0504 Page 8 of 10 TEST H: MOISTURE INGRESS TEST A4-003910 To verify the arrester design will not decrease in performance under thermo-mechanical and moisture conditions. The samples were subjected to a series of preconditioning tests including power loss, internal partial discharge, residual voltage, terminal torque, and thermo-mechanical preconditioning. The samples were then immersed in boiling de-ionized water with 1kg/m 3 of NaCl for a period of 42 hours. The samples remained in the water until the temperature cooled to 50 o C. After the samples reached ambient temperature they were tested for changes in power loss, internal partial discharge and residual voltage. All samples showed no signs of physical damage, demonstrated less than a 20% change in power loss, the internal partial discharge did not exceed 10pC, and there was a less than 5% deviation in residual voltage with no signs of breakdown seen in the voltage and current oscillograms. TEST SERIES A: 1000 HR TEST I: WEATHER AGING TESTS T04-1373 STRI To verify the ability of the arrester to withstand continuous salt fog conditions and endure surface arcing and heating. The samples were placed in an enclosure filled with a salt fog mist. The samples were energized at U C for a period of 1000 hours. The samples underwent pre and post testing consisting of partial discharge and reference voltage. All samples met the test requirements of: no housing punctures or housing erosion, no internal breakdowns, no surface tracking was evidenced by physical examination, the arrester reference voltage did not decrease by more than 5%, and the partial discharge level did not exceed 10 pc.

CP No.: CP0504 Page 9 of 10 TEST SERIES B: 5000 HR TESTING IN PROGRESS STRI To verify the ability of the arrester to withstand continuous salt fog conditions and endure surface arcing and heating. One 60kV surge arrester was placed under various environmental stresses in a cyclic manner while energized at U C for a period of 5000 hours. These stresses included solar radiation simulation, artificial rain, dry heat, damp heat, high dampness at room temperature, and salt fog at low concentration. The sample underwent pre and post testing consisting of partial discharge and reference voltage. TEST J: MECHANICAL TESTS TEST OF BENDING MOMENT: A4-003917 To verify the arrester could withstand cantilever and environmental stresses. The maximum permissible static load (180 Nm) was applied to the upright arrester for a period of 60 90 seconds. The sample was then immersed in a vessel, boiled in de-ionized water with 1 kg/m 3 of NaCl for 42 hours. At the end of the boiling, the sample remained in the vessel until the water cooled to 50 C. The sample underwent pre and post testing consisting of power loss, partial discharge and residual voltage. The sample showed no physical damage, the power loss did not increase by more than 20 % of the initial measurement, the partial discharge did not exceed 10 pc at 1.05*Uc, and the residual voltage at the same discharge current did not deviate by more than 5%.

CP No.: CP0504 Page 10 of 10 SULPHUR DIOXIDE AND SALT MIST TESTS: 13-7351-20-04-3A-rev2 Thomas A. Edison Technical Center To verify the arrester could withstand cantilever and environmental stresses. The arrester was placed in an airtight box with sulphur dioxide gas for a period of 21 days. The sample was then placed in a chamber with a salt mist atmosphere for a period of 96 hours. The sample underwent pre and post testing of partial discharge. The sample showed no physical damage and the partial discharge did not exceed 10 pc at 1.05*Uc. TEST K: DISCONNECTOR OPERATION A4-000660 To verify the disconnector was effective and permanently disconnected from arrester. Five disconnectors were tested without the surge arrester at 20A, 200A, and 800 A. The applied voltage was approximately 2700 V. In each test, the samples disconnected and the separation was permanent. Disconnect Curve 1 Disconnect Time (sec) 0.1 0.01 0.001 1 10 100 1000 Current (Amps)

Certificate of Compliance Certified Test Report Summary CP0504 is compliant with IEC 60099-4:2004. All tests were completed per IEC 60099-4:1991 and IEC 60099-4:2001 at independent third party testing laboratories. All testing results meet the test requirements stated in the latest revision of the standard IEC 60099-4:2004. Type Tests IEC 60099-4 Revision 1991 2001 2004 Insulation Withstand Test X Residual Voltage Test X Long Duration Current Impulse X High Current Impulse Operating Duty Test X Power Frequency Voltage vs. Time X Characteristics of an Arrester Short Circuit Tests INFO INFO Internal Partial Discharge Tests X Moisture Ingress Test X Weather Aging Tests X Mechanical Tests X Disconnector Operation X Definitions: "X" = Test revision required " " = Same test required as previous revision "INFO" = Informative optional test Michael M Ramarge Chief Engineer Jonathan J Woodworth Arrester Engineering Manager