Jabfloor 70, 100, 150, 200, 250

Similar documents
Floors Walls Roofs. Jabfloor Premium board Jablite Premium board Jabfloor board Jablite board. APPLICATION: Basements PRODUCTS: Vencel Resil Limited

TECHNICAL DATA SHEET CIVILS & INFRASTRUCTURE CLAY HEAVE PROTECTION

JABLITE JABFLOOR BOARDS JABFLOOR PREMIUM 70 AND 100

Garage Conversion - Between and Under Joist Applications

Floors Walls Roofs. Jablite Premium board Jablite board. APPLICATION: Internally Lined Pitched Roof PRODUCTS: Vencel Resil Limited

Floors Walls Roofs. Jablite Premium board Jablite board. APPLICATION: Internal Wall PRODUCTS: Vencel Resil Limited

Floors Walls Roofs. Jabroll. APPLICATION: Flat and Curved Roofs PRODUCTS: Vencel Resil Limited

Platinum. I n s u l a t i o n INSULATION FOR FLOORS. Low Energy Low Carbon Buildings

June Residential Refurbishment Exposed soffit floors

Xtratherm Thin-R Thermal Liner (XT/TL Grade)

SPRINGVALE FLOORING INSULATION FOR CONCRETE GROUND FLOORS

The Celotex Handy Guide

V1/0715/AI/TDO1. KORE Loft. Insulated Flooring System Design Guide

Thermal Laminate Board.

PRODUCT SHEET 1 KINGSPAN KOOLTHERM K3 FLOORBOARD

OS Thermal System Installation Guide

Dow Building Solutions. Insulating floors with STYROFOAM Solutions: basic principles

Flooring System. I n s u l a t i o n NEXT GENERATION INSULATION SOLUTION FOR FLOORS. Low Energy Low Carbon Buildings

EUROTHANE GP. Date of Second issue: 17 October 2013 John Albon Head of Approvals Claire Curtis-Thomas

KINGSPAN THERMAFLOOR TF73 Isolation en polystyrène pour planchers en béton Wärmedämmung aus Polystyrol für Betonfußboden

Specification Guide INSULATION EXCELLENCE

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade)

PowerDeck F. PIR insulation for Warm Flat Roofs. Product Guide

September Saddle Flooring Systems

K12 Framing Board. Insulation INSULATION FOR USE BEHIND WALL LINING AND FRAMED WALLS

ALL-IN-ONE THERMAL FLOOR SYSTEM NON STRUCTURAL TOPPING (NST)

URSA MINERAL WOOL URSA Cavity Batts

Your reference for Recticel PIR insulation.


Acoustic Cradle Levelling System

Uspan Ufloors Uchoices

Thermablok Aerogel Insulation Blanket Thermablok Aerogel Blanket

HP Partial Fill. Robust, long-lasting protection

Thermablok Aerogel Isolation Strips Thermablok Aerogel Isolation Strips

June Non - Residential Refurbishment Internal lining walls

EcoHome-Insulation.com. Aluminium Foil Bubble Insulation. General Purpose Insulation. Dry Lining. Cavity Wall. Insulation System.

GypLyner UNIVERSAL Metal framed wall lining system

Insulated Ground Floors

JABLITE FULL FILL CAVITY WALL INSULATION JABFILL PREMIUM

Specification Guide INSULATION EXCELLENCE

Thermal Laminate Board.

Agrément Certificate 2000/276

TILING SPECIFICATIONS

JABLITE EPS BLOCKS JABLITE QUICKFLOOR EPS INFILL BLOCKS

TR26 LPC/FM / TR27 LPC/FM

BEAM & BLOCK SYSTEM. 108mm. 175mm Deep (160mm) Wide Beam. 160mm

CI/SfB (2-) Rn7 (M2) Cavity Wall Specification Guide

FIRE PROTECTION AND PERFORMANCE DRY LINING BOARD THE ULTIMATE IN FIRE PROTECTION! 91 mins fire integrity and 86 mins fire insulation on 9mm board

K8 Cavity Board. Insulation CAVITY WALL INSULATION

K8 Cavity Board. Insulation PARTIAL FILL CAVITY WALL INSULATION P E R F O R M A N C E BBA BRITISH

Gas barrier and damp proofing accessories

RAINSCREEN DUO SLAB. Non-combustible thermal insulation

K5 External Wall Board

Multi-layer Insulation Blanket for Walls

August 2008: Issue 1. Non - Residential New Build Pitched Roofs - Ceiling Level

June Residential New Build Render and cladding walls

26 Visqueen 100% Recycled Ecomembrane 28 Visqueen DPM To Pifa Standard PROOF. membranes

Installation Engineered Flooring

Multi-layer Insulation Blanket for Walls

K10 FM Soffit Board. Insulation

a new liquid screed solution from

Kingspan Insulation. Flat Roofing User Guide. Building for the Future. For more information on Kingspan Insulation visit

K5 External Wall Board

Section II Subfloor Guidelines & Specifications Page Chapter 4 Wood Subfloor Guidelines 23 Chapter 5 Concrete Subfloor Guidelines 26 Chapter 6

Engineered Timber Systems AN INTRODUCTION. Low Energy Low Carbon Buildings. CI/SfB (2-) Rj7 - Thirteenth Issue September 2017

CABERDEK. Date of First issue: 28 November 2008 Simon Wroe Greg Cooper

DELTA MEMBRANE SYSTEMS DELTA-MS500

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

HOW TO: BOARD ROOMS WITH HIGH HUMIDITY AND CONDENSATION GTEC MOISTURE AND VAPOUR BOARD WITH PLASTERBOARD

CI/Sfb (2 ) Rn7 M2 Fourth Issue June Product Selector INSULATION FOR ROOFS, WALLS & FLOORS. Low Energy Low Carbon Buildings

EasylationWall. External Wall Insulation System. bringing european innovation

CORDEK VENTILATION VOID FORMERS VENTFORM PANELS

K12 Framing Board INSULATION FOR TIMBER AND STEEL FRAMING SYSTEMS. P E R F O R M A N C E Manufactured to BS EN ISO 9002: 1994 Certificate No.

Multi-layer Insulation Blanket for Walls

TW50. I n s u l a t i o n. Low Energy Low Carbon Buildings

KINGSPAN THERMAROOF TR21

XTRATHERM THIN-R INSULATION XTRATHERM XT/TL THERMAL LINER DRY LINING SYSTEM

SUITABILITY: SMARTPLY OSB3 - ZERO ADDED FORMALDEHYDE

Brick Veneer Walls. Insulation

SINTEF Building and Infrastructure confirms that. Separating floors with Hunton Silencio 36 / Hunton Silencio Thermo

TR27 LPC/FM. Insulation

K12 Framing Board INSULATION FOR TIMBER AND STEEL FRAMING SYSTEMS P E R F O R M A N C E

Insulation. Second Issue November Quick Guide. Building a better Kingdom together. Low Energy Low Carbon Buildings

Installation instructions Thin, flexible multi-foil insulation

Real Stone Cladding mm sandstone ashlar. Thin Sandstone Ashlar Catalogue

DURABASE CI 1/5. Underlay mats for decoupling and waterproofing tiled flooring APPLICATIONS AND FUNCTION.

RADBAR DAMP-PROOF COURSES RADBAR HIGH PERFORMANCE DAMP-PROOF COURSE

Regupol CONSTRUCTION. Regupol BA. Heavy duty screed isolation. Regupol BA. Excellent impact performance.

JABLITE FLAT ROOF INSULATION ROOF BOARDS JABLITE INVERTED ROOF INSULATION HIGH PERFORMANCE (HP)

Kingspan Insulation. Flat Roofing User Guide. Building for the Future. Technical Advice

URSA 20 Plus and URSA 20

Concrete Faced Insulated Perimeter Wall Panels. Durability. Sustainability. Energy Efficiency. Durable Finish & Superior Insulation in One Easy Step

DURABASE CI. Underlay mats for decoupling and sealing tiled flooring 1/5 A P P L I C A T I ONS AND FUNCTION.

RECTICEL INSULATION RECTICEL EUROWALL +

April Section 2.3. Flat Roofs

System Overview. Beam & Block components. BIM Objects for Beam & Block available to download Forterra.co.uk/bim

Your One Stop Shop Insulation Provider

CI/SfB. November Design Guide Concrete block masonry

RIW SHEETSEAL GR BENEFITS APPLICATIONS APPLIED TO

Protech Regular 870 Radon Resisting Membrane

Transcription:

Jabfloor 70, 100, 150, 200, 250 Floor insulation over slab with chipboard finish Jabfloor is a closed cell expanded polystyrene (EPS) insulation board for use in all floor constructions. A range of compressive strengths are available to suit all building types from domestic to industrial. Jabfloor insulation has been tested and approved by the British Board of Agrément (BBA) covering Grades 70, 100 and 150. Certificate number 87/1796. For domestic applications 18mm thick Type P5 chipboard to BS EN 312 may be used. Further details and information for non-domestic floors are given in our installation information. Jabfloor can be used in temperatures up to 80 C. It is therefore suitable for use with underfloor heating systems. Jabfloor does not degrade when placed in high moisture areas and is resistant to the effects of freeze thaw. Jabfloor will remain an effective insulation for the life of the building Jabfloor is lightweight and easy to install. There are no requirements for special PPE when installing or cutting Jabfloor. (full installation details are shown later) Dimensions Standard Size Standard Thickness 2400 x1200mm 25, 30, 40, 50, 60, 75, 100, 120, 150 and 200mm (Other thicknesses available to order) Properties : Grade Thermal Conductivity (Lambda) (W/mK) Design load at 1% nominal compression (kpa) Design load at 10% nominal compression (kpa) Jabfloor 70 0.038 20 70 Jabfloor 100 0.036 45 100 Jabfloor 150 0.035 70 150 Jabfloor 200 0.034 90 200 Jabfloor 250 0.034 100 250 More detailed physical properties are shown on our EPS Datasheet.

Application : This information is provided as guidance only, please refer to the Jabfloor compressive strengths table. Grade Jabfloor 70 Jabfloor 100 Jabfloor 150 Jabfloor 200 Jabfloor 250 Application Domestic Offices, Special Occupancy Residential (e.g. Care Home) Public, Government and Educational Buildings Industrial and Commercial Industrial, Cold Store, Heavy Commercial Accreditation : BBA Jabfloor Insulation has been assessed and approved by the British Board of Agrément as Jablite Floor Insulation for use over slab with a chipboard finish in ground bearing floors. Certificate number 87/1796. This Certificate covers Grades 70, 100 and 150. NHBC Approved NHBC accepts the use of Jablite Floor Insulation, provided it is installed, used and maintained in accordance with the BBA Certificate, in relation to NHBC Standards, Chapters 5.1 Substructure and ground bearing floors and 5.2 Suspended ground floors CE marking Jablite have taken the responsibility of CE marking the product in accordance with harmonised European Standard BS EN 13163 : 2012. Declaration of Performance is available on Request. Quality All Jablite products are manufactured in production facilities which are certified to ISO 9001 Quality Management Environmental Responsibility All Jablite manufacturing facilities are ISO 14001 certified. We operate an Environmental Management System which includes our supply chain (see BREEAM section for more information) Compliance Jabfloor conforms to the required properties as defined in BS EN 13163:2012 Thermal insulation products for buildings Factory made expanded polystyrene (EPS) products Specification. This includes compliance with BS 3837 Part 1 Fire Solid ground floors are not required to provide fire resistance. When properly installed Jabfloor is fully protected by the chipboard floor finish and will have no adverse effect on the fire performance of the building into which it is installed. Jabfloor is supplied as non-flame retardant material as standard.

Environment and Sustainability : A+ Jabfloor insulation is manufactured from EPS (expanded polystyrene) which achieves an A+ rating in the BRE Green Guide to Specification. Climate Change Jabfloor insulation has an ozone depletion potential (ODP) of zero and a global warming potential (GWP) of less than 5. EPS does not create any known risk to the environment 100% Jabfloor insulation is 100% recyclable. BREEAM Responsible Sourcing. Jablite insulation products are manufactured in factories which are ISO 14001 and ISO 9001 certified Jablite purchases raw material from suppliers who are ISO 14001 certified. The ISO certificate are in the Technical Resource Centre on the Jablite website www.jablite.co.uk Key Process (Insulation Manufacture) ISO 14001: Certificate Number EMS 559414 Supply Chain Processes (supply of materials for end products) ISO 14001: Certificate Number NL 015213-1 Embodied Impact Jablite EPS is manufactured using low energy processes. The calculation of embodied impact relative to thermal performance is a function of the material volume (for each build), its BRE Green Guide Rating and its thermal conductivity. The thermal conductivity of our products is available on both the product packaging and this datasheet Biological Properties Jabfloor EPS insulation is non-toxic and non-biodegradable. Jabfloor will not sustain mould growth and has no nutrient value to insects or vermin.

INSTALLATION Concrete slab The concrete floor should have a level even surface. A tamped finish is suitable for laying Jabfloor. Damp-proof membrane A suitable DPM such as 250 (1000 gauge) polythene must be installed in the floor either above or below the concrete slab, (See diagrams) If a liquid DPM is used, care should be taken that it is compatible with Jabfloor*, and that it is completely dry before the insulation is laid. Jabfloor Jabfloor should be loose-laid over the prepared surface with board joints tightly butted. Jabfloor HP is easily cut with a sharp knife or fine toothed saw to fit on site Thermal Bridges Jabfloor edge strip is placed vertically around the external perimeter of the insulation. The edge strip should finish at the top of the screed thickness, isolating the screed from the external masonry wall. The cavity wall insulation must overlap the floor insulation by at least 150mm (as indicated below) *Note: Jablite EPS products are compatible with all common building materials. Direct contact with hydrocarbons and strong solvents should be avoided. A suitable membrane such as polythene sheet may be used to separate Jablite EPS from these substances.

INSTALLATION Chipboard finish For normal domestic floors the chipboard should be Type P5 minimum 18mm thick, with tongued and grooved edges, as described in BS EN 312. It is important that the recommendations given in BS EN 312 are followed regarding protection of the chipboard from water spillage in bathrooms, kitchens and utility areas. Laying should proceed from one corner of the room ensuring that a 10-12mm gap is provided at the perimeter to allow for expansion of the chipboard. Temporary wedges should be placed in expansion gaps during laying to allow the chipboard joints to be tightened; the wedges must be removed after the adhesive has dried. The boards should be laid with staggered joints, and all edges should be glued as laying proceeds using a PVA-based woodworking adhesive. In corridors, or wherever there are long uninterrupted runs of flooring, the inclusion of a 20mm expansion gap at 10m centres is required in addition to the 10-12mm perimeter gap. A suitable solid timber batten should be installed beneath the expansion joint to provide support. Services It is permissible to accommodate the services within the thickness of the insulation providing the pipes etc are securely fixed to the slab. Jabfloor should not be allowed to come into direct contact with PVC-sheathed cable, nor closer than 12mm to hot-water pipes. Pipes should be haunched with a sand/cement mix or lagged using a proprietary material intended for this purpose. Jabfloor may be used in direct contact with underfloor heating pipes. These pipes do not exceed the maximum working temperature of Jabfloor. Where access is required to the services, a removable board should be provided by cutting out an area of chipboard flooring and supporting it on battens (see diagram above). The battens should be of preservative-treated timber, securely attached to the concrete slab using masonry nails or screws and plugs, and the chipboard screwed to the batten.

INSTALLATION Doorways The chipboard should be supported at external doorways by the use of a solid batten spanning at least the width of the door. The batten should be of preservativetreated timber, securely attached to the concrete slab using masonry nails or screws and plugs. At internal doorways, if the tongued-andgrooved joint of the chipboard is lost, a batten should be used to provide support as described above for external doorways. Partitions etc Where masonry partitions or other heavy structures are to be built directly onto the chipboard floor, the insulation should be interrupted and a solid batten provided along the line of the partition, beneath the chipboard, to provide support. The batten should be of preservative-treated timber, securely attached to the concrete slab using masonry nails or screws and plugs. Other timber floor finishes Timber boards such as plywood or OSB may be used over Jabfloor. Any timber floor board used must have tongued and grooved edges glued together. The specification for thickness and type of timber finish will vary dependent on the type building and its use. Please refer to BS EN 312 for specification of chipboards, BS EN 636 for plywood and BS EN 300 for OSB (Oriented Strand Board). Wood strip flooring and timber laminate floors, even where they have a tongued and grooved edges or click together detail must be placed over a solid board such as chipboard, plywood or OSB. You should seek the advice of the flooring manufacturer regarding any specific requirements, otherwise it may be treated as a normal decorative finish when placed over a standard timber board floor as detailed above.

U VALUES The calculation of heat loss or U value through a floor is based on the ratio of the external perimeter to the area of the floor (P/A Ratio). Example of how to calculate the P/A ratio is shown below. The perimeter and area are measured to the internal wall finishes as shown on the diagram. Example Detached House Perimeter (P) = 8 + 5 + 3 + 4 + 5 + 9 = 34 Area (A) = (5 x 4) + (8 x 5) = 60 P/A Ratio = 34 60 = 0.57 Note: The exposed perimeter includes any edges where heat loss may occur. i.e. external walls and those into an unheated space such as a porch or garage. Tables showing the thickness of Jabfloor to achieve U values based on P/A ratios are provided on the following pages.

U VALUES The tables below show the required thicknesses of Jabfloor 70, 100, 150, 200 and 250 to meet U-values of 0.25, 0.22, 0.20, 0.18, 0.15 and 0.10W/m²K. The calculations have been based on a standard dense concrete floor slab 100mm thick with Jabfloor 70 over slab and an 18mm chipboard finish and carried out in accordance with BS EN ISO 13370. Table 6.1: Thickness (mm) to achieve U-value 0.25 W/m 2 K 1.00 105 100 95 95 0.90 105 100 95 95 0.80 100 95 90 90 0.70 95 90 90 85 0.60 90 85 85 80 0.50 85 80 75 75 0.40 75 70 70 65 0.30 60 55 55 55 0.25 50 50 50 40 0.20 30 30 25 25 0.15 25 25 25 25 Table 6.2: Thickness (mm) to achieve U-value 0.22 W/m 2 K 1.00 130 120 120 115 0.90 125 115 115 115 0.80 120 115 115 110 0.70 120 110 110 105 0.60 110 105 105 100 0.50 105 100 95 95 0.40 95 90 85 85 0.30 80 75 75 70 0.25 65 65 60 60 0.20 50 50 50 50 0.15 25 25 25 25 NB: Thickness indicated may be obtained using one or two layers of standard thickness product

Table 6.3: Thickness (mm) to achieve U-value 0.20 W/m 2 K 1.00 150 135 135 130 0.90 140 135 130 125 0.80 140 130 125 125 0.70 135 125 120 120 0.60 130 120 115 115 0.50 120 115 110 110 0.40 110 105 100 100 0.30 95 90 90 85 0.25 85 80 75 75 0.20 65 60 60 60 0.15 40 40 40 40 Table 6.4: Thickness (mm) to achieve U-value 0.18 W/m 2 K 1.00 170 160 150 145 0.90 160 160 150 145 0.80 160 150 145 140 0.70 160 145 140 140 0.60 150 140 135 135 0.50 140 135 130 125 0.40 130 125 120 115 0.30 115 110 105 100 0.25 100 100 95 90 0.20 85 80 75 75 0.15 55 55 50 50

Table 6.5: Thickness (mm) to achieve U-value 0.15 W/m 2 K 1.00 210 195 190 190 0.90 200 190 190 180 0.80 200 190 190 180 0.70 195 190 180 175 0.60 190 180 175 170 0.50 180 170 170 160 0.40 170 160 160 150 0.30 150 140 140 135 0.25 140 130 130 125 0.20 120 115 110 110 0.15 90 85 80 80 Table 6.6: Thickness (mm) to achieve U-value 0.10 W/m 2 K 1.00 320 320 300 300 0.90 320 300 300 300 0.80 320 300 300 300 0.70 320 300 300 300 0.60 320 300 300 275 0.50 300 300 275 270 0.40 300 275 270 270 0.30 270 260 250 240 0.25 250 240 230 225 0.20 230 220 210 210 0.15 200 190 190 180