SECTION HVAC INSTRUMENTATION AND CONTROLS INSTALLATION. (Applicable to IUPUI Only)

Similar documents
SECTION HVAC INSTRUMENTATION AND CONTROLS INSTALLATION

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less)

Technical Services Information Bureau

SECTION SEISMIC CONTROL OSHPD

SECTION HANGERS AND SUPPORTS FOR PLUMBING

Suspension Systems for Acoustical Lay-in Ceilings Seismic Design Categories D, E & F

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

PIP PCEPA003 Process Analyzer System Field Installation Guidelines

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION SUPPORTS AND ANCHORS

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES...

8.1.2 Under no circumstances shall a service entrance be left unmetered. Notify the Company if an unmetered service is encountered.

SECTION VIBRATION ISOLATION FOR PLUMBING PIPING AND EQUIPMENT

TYPICAL INSTALLATION INSTRUCTIONS

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

KINETICS Pipe & Duct Seismic Application Manual

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS. 1. Hangers and supports for electrical equipment and systems.

B. Shop Drawings: For air terminal units. Include plans, elevations, sections, details, and attachments to other work.

SECTION BASIC ELECTRICAL REQUIREMENTS

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

A. Product Data shall be provided for each type of product indicated.

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

A. Pipe Supports: ANSI B 31.1, Power Piping. B. Automatic Sprinkler Pipe Supports: Refer to Section

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

Suspension System Data Center Ceiling Solutions

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

B. System Design and Performance Requirements

SECTION SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS REVISED PART 1 GENERAL 1.1 DESCRIPTION:

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

Revision 1 RAM ELEVATORS. Elevator Electrical Planning Guide. RAM Manufacturing Ltd

Installation of CSST Gas Piping Systems

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Robert E. McMains Date Robert E. McMains Date

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study

CONDUITS AND FITTINGS

ECONOMIZER ECM. Turnkey Price Installed: $115,295

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700

Permitting and Inspecting PV Systems. PV Codes and Standards 101. Photovoltaic System Basics

SECTION I -- IRONWORK

SERVICE LINES, METERS AND APPURTENANCES

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

SECTION CHAIN-LINK FENCES AND GATES 02821/1

NEC 2014 Code Changes

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

SECTION INSULATED WIRE AND CABLE

Communications Page 1 of 9

Details of technical leaflets/write-up on various pieces of equipment.

THOMAS JEFFERSON UNIVERSITY HOSPITAL STANDARD OPERATING PROCEDURE FOR THE BUILD OUT OF TELECOMMUNICATIONS ROOMS AND ASSOCIATED SPACES

SECTION DRAINAGE AND VENT SYSTEMS CONSTRUCTION STANDARD

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal.

Price Single Duct Terminal Units

Element Z General Design Requirements Existing Facilities Information

2012 IPC Sections

FORM HEADWALL. FORM HEADWALL (floating) (floating) Installation Manual

HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION GYPSUM BOARD ASSEMBLIES

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILLION SECTION LABORATORY ELECTRICAL REQUIREMENTS PART 1 - GENERAL REQUIREMENTS

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

PATHWAYS FOR COMMUNICATIONS SYSTEMS

REV. 9/08. Mounting Structure PRE-INSTALLATION GUIDE for Ergon Skybooms

SECTION ACTIVE VEHICLE BARRIERS

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

FORM HEADWALL. FORM HEADWALL (floor mount) (floor mount) Installation Manual

WIRING METHODS CHAPTER 38

CHAPTER 11 CONDUITS AND FITTINGS

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

FEDERAL EMERGENCY MANAGEMENT AGENCY FEMA 414/January 2004 INSTALLING SEISMIC RESTRAINTS FOR DUCT AND PIPE


SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

Introduction. Disclaimer. Table of contents

A. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect.

Element D Services Heating, Ventilating, and Air Conditioning

Electric Service Standards

University of Central Florida Main Campus. Chilled Water. Service and Meter Installations Requirements. Issued January 26 th, 2017.

Douglas County Traffic Signal Installation Guidelines (January 2013)

ROOFTOP EQUIPMENT Guide

Telecommunication Spaces

SECTION HORIZONTAL CABLING

SECTION ACOUSTICAL PANEL CEILINGS

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

A/E Design Deliverable Checklist

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.

Transcription:

SECTION 15957 (Applicable to IUPUI Only) I. GENERAL A. NOTES 1. The University has a pre-purchase agreement (PPA) with Johnson Controls (JCI) and Siemens Building Technologies (SBT). The University will directly purchase all of the required control components as described in the PPA contractor bid documents, and control system engineering, to accomplish the design intent of the designer of record. 2. Installation of controls shall be performed by the Controls Installation Contractor (CIC) as part of this section, and not by the PPA contractor (JCI or SBT) as described in the project construction documents. Installation shall be subject to all applicable federal, state, and local codes as well as the installation standards specified here within. Contact Indiana University / IUPUI Engineering Services with questions and for further details. Contract issues should be referred to the designer of record. B. SYSTEMS 1. Controls Installation Contractor (CIC) shall be responsible for installing all temperature control system components as described in the bid documents, to include all temperature control contractor documents. CIC is responsible for providing and installing all conduits, junction boxes, wire, pneumatic tubing, and any other installation component not specifically called out on the PPA contractor s documents but required for complete installation and operation of the temperature controls to achieve standards and design intent. 2. Installed systems shall be subject to continuous assessment by the PPA contractor and the University to ensure all installation standards are being met. All verifiable and documented discrepancies to the described installation standards, performed by the CIC, shall be promptly corrected at CIC s expense, and subject to all contract provisions. 3. CIC shall install all components according to manufacturers recommended installation specifications and specifications spelled Page 1 of 11 REVISED: February 2007

out herein. CIC shall co-ordinate with all trades to ensure that the installation standards can be and are achieved. 4. PPA Contractor shall be available to answer any questions about temperature controls installation from any trade. C. DOCUMENTATION 1. CIC shall provide a complete marked up as-build set of temperature control drawings to the PPA contractor and the A/E. As-build set shall include and document all wiring, wiring interlocks, pneumatic paths, field changes, additions, omissions, address sequencing, power trunk sequence, and cabling paths. II. INSTALLATION GUIDELINES A. CODES AND STANDARDS 1. Latest edition of NFPA 70 (NEC) 2. Current local codes 3. University standards 4. All project documents B. VENDOR DEVICES 1. REFERENCE MANUALS a) Johnson Controls (1) Johnson Controls Installation Manual b) Siemens Building Technologies (1) Powers Field Installation Manual c) All manufacturer provided installation guidelines and procedures. 2. FLEXIBLE TEMPERATURE SENSORS a) All flexible sensors shall be attached by wire ties to a suspended wire or insulated cable to prevent sensor contact with metal or other unit components. b) Install flexible sensors across all coils at a maximum of 6 from the bottom of the bottom coil and a minimum of 7 radius to turn the sensor. c) Staggered coils shall utilize multiple sensors; each sensor shall cover one section of the staggered coil. Page 2 of 11 REVISED: February 2007

d) All flexible sensors shall be protected at point of penetration of unit via a section of poly tubing to prevent contact of the sensor and the unit. e) Install flexible sensor so as then entire length of the sensor, less the wiring connection point, shall be in contact with the air stream being monitored. Excessive lengths of sensor outside the air stream or located in areas without air movement is not acceptable. 3. LOW TEMPERATURE DETECTOR SWITCH a) All low temperature detectors shall be attached by wire ties to a suspended wire or insulated cable to prevent detector contact with metal or other unit components. b) Install low temperature detectors across all coils at a maximum of 6 from the bottom of the bottom coil and a minimum of 7 radius to turn the detector. c) Staggered coils shall utilize multiple detectors; each detector shall cover one section of the staggered coil. d) All low temperature detectors shall be protected at point of penetration of unit via a section of poly tubing to prevent contact of the sensor and the unit. e) Install the detector in a slight downward incline with a maximum free distance of 12 between each pass. f) Install flexible sensor so as then entire length of the sensor, less the wiring connection point, shall be in contact with the air stream being monitored. Excessive lengths of sensor outside the air stream or located in areas without air movement is not acceptable. g) Install location (1) If unit has heating water preheat (a) Mount low temperature detector downstream of the preheat coil and upstream of chilled water coil. (2) If unit has steam preheat (a) Mount low temperature detector downstream of the chilled water coil and upstream of any device producing a heat load, such as heating coils, humidifiers, fans, etc. (3) If the unit is without preheat (a) 4. HIGH STATIC SWITCH Mount low temperature detector downstream of the first coil containing liquid. a) Install all static switches on the air-handling unit at a maximum height of 6 5 to the center of the switch. Utilize Page 3 of 11 REVISED: February 2007

hard or soft copper for pressure sampling tubes. Install sample tubes in a craftsman like manner and terminate in the sampled air with an appropriate pressure terminal. Bending the end of the copper tubing in the airstreams is not acceptable. 5. LOW STATIC SWITCH a) Install all static switches on the air-handling unit at a maximum height of 6 5 to the center of the switch. Utilize hard or soft copper for pressure sampling tubes. Install sample tubes in a craftsman like manner and terminate in the sampled air with an appropriate pressure terminal. Bending the end of the copper tubing in the airstreams is not acceptable. b) If unit contains a return fan, static switch shall be piped to sample the low-pressure side of the return fan. 6. FLUID DIFFERENTIAL PRESSURE SENSOR a) Fluid differential pressure sensors shall be mounted a minimum of 8 from the top of a wall or column, or as high as possible without interfering with other trades, manifold shall be on top. Utilize hard copper tubing for connection from pipe to manifold. 7. DAMPERS a) All dampers provided by PPA vendor(s) shall be installed with the dampers blades in a horizontal configuration and must be level, plumb, and square. b) All damper(s) shall be properly supported via mechanical methods in a manner that will maintain the damper(s) in a horizontal, level, plumb, and square configuration for the anticipated lifespan of the building. 8. VARIABLE FREQUENCY DRIVES a) Mount all VFD s on u-channel. VFD may be mounted on a stand constructed from u-channel and properly secured to the floor, if wall space is not available or if shown as such on construction drawings. b) The maximum mounting height is such that the user interface/display is no higher than 6 above the finished floor surface directly under the drive. Page 4 of 11 REVISED: February 2007

c) VFD shall be installed in accord with manufacturer s instructions and the National Electric Code. If a remote disconnect is required by code, confirm whether the drive requires an auxiliary contact to disable the drive. Line and load cabling shall be in separate conduits. Coordinate start up with other contractors. 9. STEAM VALVES a) All electronic actuated steam valves must be mounted with the actuator at an angle of 15 to 45 degrees from the vertical. 10. CONTROL PANELS C. MATERIALS a) All control panels shall be mounted to u-channel. Panel may be mounted on a stand constructed from u-channel and properly secured to the floor, if wall space is not available or if shown as such on construction drawings. b) The maximum mounting height is such that the user interface/display is no higher than 6 above the finished floor surface directly under the control readout. c) All penetrations shall be made on the top of the control panel. d) 120VAC and low voltage must utilize separate penetrations. e) All pneumatic penetrations shall be made on the opposite end of the 120VAC penetration. 1. PNEUMATIC TUBING a) Adhere to current NEC and Local Codes b) Main 80# air line shall be run in hard copper, minimum ½ diameter, supported every 6 feet to the building structure. (1) Main 80# air line shall have an air gage and tee tap with a ball valve capped off for future, located between the compressor tank and the refrigerated air dryer. (2) Main 80# air riser shall have a ball valve at each floor prior to an adjacent pressure-reducing valve. c) Main 25# air line shall be run in black polyethylene tubing, minimum 3/8 diameter, supported every 6 feet to the building structure. (1) All poly tubing conduit is EMT, ¾ minimum size, and shall be installed in a craftsman like manner. All Page 5 of 11 REVISED: February 2007

(d) (e) (f) (g) connections, fittings, supports, etc. shall be tight and secure. (a) Mechanical areas: All poly tubing in conduit EMT (b) Space sensors: All poly tubing in conduit in wall construction EMT (c) Accessible ceilings: Bundled neatly, run, and mechanically attached to and parallel with the building structure. Use of existing cable tray is not acceptable. (d) Non Accessible ceilings: All poly tubing in conduit EMT (e) Shaft spaces: All poly tubing in conduit EMT, 1 minimum size (2) Conduits for pneumatic tubing shall be sized by the following standard: (a) ¾ conduit (1) Not to exceed three ¼ poly tubes (b) 1 conduit (1) Not to exceed six ¼ poly tubes Main 25# air line for ELSAM shall be run in black polyethylene tubing, minimum 3/8 diameter. (1) ELSAM main air lines must be run completely in EMT conduit. The conduit must be labeled ELSAM MAIN AIR with a minimum of ½ lettering. Labels shall be placed on every box cover, every 20 on center and within 6 on each side of each wall or structural penetration. Polyethylene connections to steam valve actuators shall utilize a minimum of 12 of coiled copper between the poly tubing and the valve actuator. Polyethylene tubing inside equipment, such as air handling units, shall be run in conduit with a maximum of 12 of exposed tubing at the controlled device. All finished air handling unit penetrations shall be sealed air tight inside and out. Polyethylene tubing shall be manufactured from virgin stock and shall meet the following specifications: (1) Density: 0.92 grams/cc (2) Melt Index: 0.30 decigrams/min. (3) Stress check resistance: 2000 hrs. Minimum per ASTM-D 1693 (4) Tensile strength: 2200 psi (5) Fire resistance: FR type 2. METAL CONDUIT Page 6 of 11 REVISED: February 2007

a. Adhere to current NEC and Local Codes b. Control conduits will be considered secondary to other trades and must heed right of way when there are conflicts. c. All control wiring conduit is EMT, ¾ minimum size, and shall be installed in a craftsman like manner, parallel to the building structure. All connections, fittings, supports, etc. shall be tight and secure. (1) Mechanical areas: All wiring in conduit EMT (2) Space sensors: All wiring in conduit in wall construction EMT (3) Accessible ceilings: Plenum rated cable bundled neatly, run, and mechanically attached to and parallel with the building structure. Use of existing cable tray is acceptable with prior approval. (4) Non Accessible ceilings: All wiring in conduit EMT (5) Shaft spaces: All wiring in conduit EMT, 1 minimum size (6) Pass through building structure walls above plenum ceiling spaces shall utilize a sleeve of EMT conduit, 12 in length, with end steel compression box end fittings or plastic/rubber grommets and fire stopped if the wall is fire rated. (7) Flexible metal conduit (FMC) may be utilized when approved in instances where sensors are to be located in existing walls. (d) All EMT connections shall utilize steel compression fittings up to 1 ½ conduit. Above 1 ½ may utilize steel set screw fittings. (1) All non-terminated, non-connected, open ends of conduit must utilize either a plastic/rubber grommet or box connector. (e) All conduits shall be supported directly from or to structural members. Additional support shall be provided at junction and pull boxes. (1) Conduits shall be supported by trapeze hangers or pipe straps and shall have their support spaced not to exceed 10 on center, or a minimum of one support per piece of conduit. With approval, it is acceptable to use other electrical trapeze. (2) All junction boxes must have a minimum of two anchors per box. Boxes larger than 8 X 8, shall have a minimum of four anchors per box. (3) All conduits shall be run as close to the ceiling if possible. Make all conduit drops at point of connection. Do not run conduit across walls below 8 in mechanical spaces. Page 7 of 11 REVISED: February 2007

(f) (g) (h) (i) (j) (k) (l) (m) (n) Conduits serving air handler units shall be run either along the top of the unit along unit structural members or above the unit supported by u-channel. Drops for devices shall be run on the structural members of each unit, and shall not cross or attach to the panels. Conduit must be seismically isolated from the structure via FMC/LFMC. All boxes shall utilize all normally provided mechanical fasteners to secure their covers. All conduits and junction box covers shall be labeled Temperature Controls with a minimum of ½ lettering. Labels shall be placed on every box cover, every 20 on center and within 6 on each side of each wall or structural penetration. A maximum of 20 of FMC may be used to connect any control device to a junction box. Use FMC to isolate all components that have the potential for vibration. FMC must be secured with an appropriate sized FMC one hole clamp if used inside equipment, such as air handling units. Liquid tight FMC must be utilized on all final connections in moist/damp locations and in all locations exposed to the weather. Power and low voltage wiring shall not be run in the same conduit. Electrical wiring shall not be run in the same conduit with poly tubing. Where more than one panel is mounted together, utilize square duct wire way, 4 X 4 minimum, to connect all panels. Provide one extra 1 EMT conduit from each panel to square duct wire way for future expansion. 3. LOW VOLTAGE CABLE (a) Adhere to current NEC and Local Codes (b) Splicing of cables is not permitted. All connections shall be point to point. (1) If splicing is completely unavoidable, utilize an appropriate sized junction box with terminal blocks to make the connections. Wire nuts are not acceptable. (c) Johnson Controls (1) The following wiring will be utilized on all projects: Metasys Application Cable Sensor Wiring 2C #18 Twisted/Shielded Plenum Terminal Unit 3C #18 Twisted/Shielded Plenum valves & actuators Communication 3C #18 Twisted/Shielded Plenum 24v power trunk 2C #14 Twisted/Shielded Plenum Page 8 of 11 REVISED: February 2007

(d) Siemens Building Technologies (1) The following wiring will be utilized on all projects: Apogee Application Sensor Wiring TEC valves & actuators Communication TEC 24v power trunk Cable 2C #20 (STR) Plenum 3C #20 (STR) Plenum 1P #24 (STR) OAS Plenum 2C #14 (STR) Plenum 4. LINE VOLTAGE CABLE (a) All 120VAC wiring shall be minimum solid copper, 12 THHN, 600-volt insulation. (b) Panel 120VAC power circuit shall be dedicated for building automation system components only. Power shall be run from emergency circuit panels, if emergency power is available in the building. Confirm responsibility for panel 120VAC. (c) External control devices powered via 120VAC from the control panel shall utilize a knife switch, or fuse switch to isolate those devices from the power to the controller. The switch shall be installed in the control panel in such a way as to allow power to be easily disconnected from each control device individually without removing power to the panel completely. 5. GAUGES (a) THERMOMETERS (1) Thermometers shall be well type solar-powered digital thermometers similar to TREND brand. Range 30 Deg. F. to 200 Deg. F. (2) Install at all locations shown on the contract documents. Adjust unit so that the numeric display may be seen from the floor and that the solar power cells obtain as much light as possible. (b) PRESSURE (1) Pressure gauges shall be installed with an isolation valve and snubber to damper pulsations, ease of maintenance and replacement. Scale of gauge shall be of a reasonable nature to allow for accurate reading of operating pressures. Use the following guidelines for gauge ranges. (a) Piping (i) Water Lines: 0-150 psig (ii) 150 psig steam 0-200 psig (iii) 40 psig steam 0-100 psig (iv) 15 psig steam 0-30 psig Page 9 of 11 REVISED: February 2007

(b) Compressed control air (i) Compressor/receiver 0-200 psig (ii) Field devices (a) 1 ½ gauge with ¼ OD poly tubing barbed fitting. (i) Johnson Controls (ii) Siemens Building Technologies 6. RELAYS a) Install in accordance to (NEC) NFPA 70-2005 Article 725.55 7. THERMOSTAT DETAIL a) See sheet MD1 following END OF SECTION Page 10 of 11 REVISED: February 2007

Page 11 of 11 REVISED: February 2007