SECTION PLUMBING SUPPORTS AND ANCHORS. A. Furnish sleeves and hanger inserts to General Contractor for placement into formwork.

Similar documents
SECTION HANGERS AND SUPPORTS FOR PLUMBING

DIVISION 15-MECHANICAL SECTION SUPPORTS AND ANCHORS PN PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Pipe and equipment support systems.

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping

HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

A. Pipe Supports: ANSI B 31.1, Power Piping. B. Automatic Sprinkler Pipe Supports: Refer to Section

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION SUPPORTS AND ANCHORS

Daytona Beach Pier Building Renovation Jun 2010

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS PART 1 - GENERAL. A. Drawings and Division 1 Specification Sections, apply to this Section.

1.2 ACTION AND INFORMATIONAL SUBMITTALS.1 Provide submittals in accordance with Section Submittal Procedures.

E. Manufacturers Standardization Society of the Valve and Fittings Industry:

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

E. Manufacturers Standardization Society of the Valve and Fittings Industry:

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

University of Delaware

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION NON-PENETRATING PORTABLE ROOFTOP SUPPORTS AND WALKWAYS. For best results, display hidden notes to specifier.

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS. 1. Hangers and supports for electrical equipment and systems.

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

City of Winnipeg BASES, HANGERS AND SUPPORTS Section NEWPCC - Pump Well Isolation Page 1 of 6 Tender No June 2003

SECTION VIBRATION ISOLATION FOR PLUMBING PIPING AND EQUIPMENT

Materials Carbon Steel and Malleable Iron are used in the manufacture of concrete inserts. Stainless Steel and other materials are available.

SECTION PLATE CONNECTED WOOD TRUSSES

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

SECTION CHAIN LINK FENCES AND GATES (GALVANIZED) A. Fence framework, fabric, gates, and accessories.

Fig. 1 - Standard Clevis Hanger

SECTION CHAIN-LINK FENCES AND GATES 02821/1

DARTMOUTH COLLEGE DESIGN September 15, 2004 &CONSTRUCTION GUIDELINES

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.

SECTION SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS REVISED PART 1 GENERAL 1.1 DESCRIPTION:

SECTION GYPSUM BOARD ASSEMBLIES

American Metal Specialties, Inc.

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Diffused Aeration Piping Equipment

SECTION FACILITY STORM DRAINAGE

Division 11 - Equipment Section 11401

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

SECTION ALUMINUM GATES

Anvil CSI 3 Part MasterFormat Specifications:

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

1.02 STANDARD REFERENCES: The following standard specifications shall apply to the Work of this Section as indicated:

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

SECTION MASONRY ACCESSORIES

A. Access doors and frames are part of an access door and frame allowance.

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

SECTION ACOUSTICAL PANEL CEILINGS

PIPE AND TUBE RAILINGS

A. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect.

SECTION 07530CP EPDM MEMBRANE ROOFING

B-LINE SERIES. DURA-BLOK rooftop supports BRTS-17 DURA-BLOK. A complete rooftop support solution

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700

SECTION I -- IRONWORK

Design & Construction Standards, Revised January

TOLCO Fire Protection Support Systems. Pipe Hangers Supports Seismic Bracing. UL Listed FM Approved for Fire Sprinkler Installations

Materials Carbon Steel is used in the manufacturing of riser and pipe clamps. Stainless Steel and other materials are available.

Fig Beam Clamp Retaining Strap (B-Line B3367)

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

SECTION PLUMBING PIPING SYSTEMS

SECTION TURBINE VENTILATORS

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.

B. Polyethylene samples shall be submitted for Owner approval of color and quality.

HIGH MAST CAMERA POLE ASSEMBLY GENERAL

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

SECTION COLD-FORMED METAL FRAMING

CONSULTANT PROCEDURES & DESIGN GUIDELINES Electrical Manholes and Handholes UNIVERSITY OF MISSOURI

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM

Daytona Beach Pier Building Renovation Jun 2010

SECTION HVAC INSULATION

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.

Specifications for FL-100 Soffit Panel

BEARING METAL STUD FRAMING

PRE-ENGINEERED METAL BUILDING SYSTEM

SECTION METAL FLOOR PLATE STAIRS

A. The extent of extruded aluminum walkway covers is shown on the Drawings and as specified herein.

Smarter. Safer. Leaner.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION 1043 FENCE MATERIAL

MASTERSPEC - SHORT FORM. B. See Division 5 Section "Metal Stairs" for steel tube railings associated with metal stairs.

A. Types of lightgauge metal framing units include the following: 1. C-shaped structural steel studs Uniform Building Code.

Transcription:

SECTION 22 05 29 PLUMBING SUPPORTS AND ANCHORS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Hangers, Supports, and Associated Anchors. B. Equipment Bases and Supports. C. Sleeves and Seals. D. Flashing and Sealing of Equipment and Pipe Stacks. E. Cutting of Openings. F. Escutcheon Plates and Trim. 1.2 WORK FURNISHED BUT INSTALLED UNDER OTHER SECTIONS A. Furnish sleeves and hanger inserts to General Contractor for placement into formwork. 1.3 REFERENCES A. MSS SP-58 - Pipe Hangers and Supports - Materials, Design, and Manufacture. B. MSS SP-69 - Pipe Hangers and Supports - Selection and Application. C. MSS SP-89 - Pipe Hangers and Supports - Fabrication and Installation Practices. 1.4 SUBMITTALS A. Submit shop drawings and product data under provisions of Section 22 05 00. PART 2 - PRODUCTS 2.1 SEISMIC RESTRAINTS A. Refer to specification Section 22 05 50 for additional requirements for seismic restraints. 2.2 HANGER RODS A. Hanger rods for single rod hangers shall conform to the following: Pipe Size Hanger Rod Diameter Column #1 Column #2 2" and smaller 3/8" 3/8" 2-1/2"through 3-1/2" 1/2" 1/2" 4" and 5" 5/8" 1/2" 6" 3/4" 5/8" 8" through 12" 7/8" 3/4" Column #1: Cast iron. Column #2: Copper and plastic pipe. B. Rods for double rod hangers may be reduced one size. Minimum rod diameter is 3/8 inches. C. Hanger rods and accessories shall be black steel. Prime rusted areas after installation. KJWW #08.0482.00 22 05 29-1

2.3 PIPE HANGERS AND SUPPORTS A. All pipe hangers, clamps, and supports shall conform to Manufacturers Standardization Society MSS-SP-69. B. Oversize all hangers, clamps, and supports on insulated piping to allow insulation and jacket to pass through unbroken. This applies to both hot and cold pipes. C. Ferrous hot piping 2-1/2 inches and larger shall have steel saddles tack welded to the pipe at each support at a depth not less than the specified insulation. Factory fabricated inserts may be used. Anvil - Fig. 160, 161, 162, 163, 164, 165 Cooper/B-Line - Fig. 3160, 3161, 3162, 3163, 3164, 3165 Erico - Model 630, 631, 632, 633, 634, 635 Nibco/Tolco - Fig. 260-1, 261-1 1/2, 262-2, 263-2 1/2, 264-3, 265-4 D. On all insulated piping, provide a semi-cylindrical metallic shield and fire resistant vapor barrier jacket. E. As an alternative to separate pipe insulation insert and saddle, properly sized integral rigid insulation sections may be used for this application. Cooper/B-Line - Fig. B3380 through B3384 Pipe Shields - A1000, A2000 Erico - Model 124, 127 F. Support and laterally brace vertical pipes at every floor level in multi-story structures, but never at intervals over 15 feet. Support vertical pipes with riser clamps installed below hubs, couplings or lugs welded to the pipe. Anvil - Fig. CT121 Cooper/B-Line - Fig. B3373CT Erico - Model 510 Nibco/Tolco - Fig. 82 G. Place restrained neoprene mounts beneath vertical pipe riser clamps to prevent sweating of cold pipes. Insulate over mounts. Mason RBA, RCA, or BR. H. Hangers in direct contact with copper pipe shall be coated with plastic with appropriate temperature range. HYDRA-ZORB clamps are permitted for this application for bare pipes within their temperature limits of - 65 F to + 275 F. KJWW #08.0482.00 22 05 29-2

I. Unless otherwise indicated, hangers shall be as follows: 1. Clevis Type: Service: Bare Metal Pipe Rigid Plastic Pipe Insulated Cold Pipe Insulated Hot Pipe - 3 inches & Smaller Bare Steel, Plastic Bare Copper Pipe or Insulated Pipe Anvil Fig. 260 Fig. CT65 Cooper/B-Line Fig. 3100 Fig. B3104CT Erico Model 400 Model 402 Nibco/Tolco Fig. 1 Fig. 81 2. Roller Type: Service: Insulated Hot Pipe - 4 inches and Larger 4" through 6" 8" and Above Anvil Fig. 181, 271 Fig. 171, 271 Cooper/B-Line Fig. 3110, 3117 Fig. 3114, 3117 Erico Model 610 Model 605 Nibco/Tolco Fig. 324, 327 Fig. 322, 327 3. Adjustable Swivel Ring Type: Service: Bare Metal Pipe - 4 inches and Smaller Bare Steel Pipe Bare Copper Pipe Anvil Fig. 69 Fig. CT69 Cooper/B-Line Fig. B3170NF Fig. B170CT Erico Model FCN Nibco/Tolco Fig. 200 Fig. 202 J. Support may be fabricated from U-Channel strut or similar shapes. Piping less than 4 in diameter shall be secured to strut with clamps of proper design and capacity as required to maintain spacing and alignment. Strut shall be independently supported from hanger drops or building structure. Size and support shall be per manufacturer s installation requirements for structural support of piping. Clamps shall not interrupt piping insulation. 1. Strut used in mechanical spaces or otherwise dry areas shall have ASTM B633 electro-plated zinc finish. 2. Strut used in damp areas listed in hanger rods shall have ASTM A123 hot-dip galvanized finish applied after fabrication. K. Unless otherwise indicated, pipe supports for use with struts shall be as follows: 1. Clamp Type: Service: Bare Metal Pipe Rigid Plastic Pipe Insulated Cold Pipe Insulated Hot Pipe - 3 inches and smaller a. Clamps in direct contact with copper pipe shall be plastic coated. KJWW #08.0482.00 22 05 29-3

b. Pipes subject to expansion and contraction shall have clamps slightly oversized to allow limited pipe movement. Bare Steel, Plastic Bare Copper Pipe or Insulated Pipe Unistrut Fig. P1100 or P2500 Cooper/B-Line Fig. B2000 or B2400 Fig. BVT Nibco/Tolco Fig. A-14 or 2STR 2. Roller Type: Service: Insulated Hot Pipe - 4 inches and larger. 4" through 6" 8" and Above Unistrut Fig. P2474 Fig. P2474-1 Cooper/B-Line Fig. B218 Fig. B219 Nibco/Tolco Fig. ROL-12 Fig. ROL-13 L. Unless otherwise shown, upper attachments for hanger rods or support struts shall be as follows: 1. Beam Clamps: Anvil Fig. 228, 292 Cooper/B-Line Fig. B3054 Erico Model 360 Nibco/Tolco Fig. 329 2. Concrete Inserts, Single Rod Galvanized: Anvil Fig. 282 Cooper/B-Line Fig. B3014 Erico Model 355 Nibco/Tolco Fig. 310 3. Concrete Inserts, Continuous Strip Galvanized: Unistrut Corp Cooper/B-Line Erico P3200 Series Fig. B22-J CONCT 4. Concrete Anchors: Fasten to concrete or masonry with inserts, expansion shields or self-tapping masonry screws. Toggle bolts may be used in concrete block. Do not fasten in masonry joints. Do not use explosive devices, wooden plugs or plastic inserts. Do not install fasteners to carry the load in tension unless absolutely necessary. M. Copper piping located in an exposed area including indirect waste piping in a kitchen and janitors closet shall utilize split ring stand off hangers for copper tubing. Support shall have copper electroplating for corrosion resistance. Utilize corrosion resistant expansion anchors with corrosion resistant threaded rod for floor applications. Utilize anchor applicable to the wall type with corrosion resistant threaded rod for wall applications. KJWW #08.0482.00 22 05 29-4

Erico/M-Co Model #456 B-Line Fig. 3198H Anvil Fig. CT138R Nibco/Tolco Fig. 301CT N. Wall supports shall be used where vertical height of structure exceeds minimum spacing requirements. Install wall supports at same spacing as hangers or strut supports along vertical length of pipe runs. O. Welding: 1. Unless otherwise noted, hangers, clips, and auxiliary support steel may be welded in lieu of bolting, clamping, or riveting to the building structural frame. Take adequate precautions during all welding operations for fire prevention and for protecting walls and ceilings from being damaged by smoke. 2.4 FOUNDATIONS, BASES, AND SUPPORTS A. Basic Requirements: 1. Furnish and install foundations, bases, and supports (not specifically indicated on the Drawings or in the Specifications of either the General Construction or Mechanical work as provided by another Contractor) for mechanical equipment. 2. All concrete foundations, bases and supports, shall be reinforced. All steel bases and supports shall receive a prime coat of zinc chromate or red metal primer. After completion of work, give steel supports a final coat of gray enamel. B. Concrete Bases (Housekeeping Pads): 1. Unless shown otherwise on the drawings, concrete bases shall be nominal 4 inches thick and shall extend 3 inches on all sides of the equipment (6 inches larger than factory base). 2. Where a base is less than 12 inches from a wall, extend the base to the wall to prevent a dirt-trap. 3. Concrete materials and workmanship required for the Contractor's work shall be provided by him. Materials and workmanship shall conform to the applicable standards of the Portland Cement Association. Reinforce with 6 x 6, W1.4-W1.4 welded wire fabric. Concrete shall withstand 3,000 pounds compression per square inch at twenty-eight days. 4. Equipment requiring bases is as follows: C. Supports: a. Pump b. Water Heater c. Water Softeners d. Booster Pumps and Tanks e. Filters and RO System 1. Provide sufficient clips, inserts, hangers, racks, rods, and auxiliary steel to securely support all suspended material, equipment and conduit without sag. KJWW #08.0482.00 22 05 29-5

D. Grout: 2. Hang heavy equipment from concrete floors or ceilings with Architect-approved concrete inserts, furnished and installed by the Contractor whose work requires them, except where indicated otherwise. 1. Grout shall be non-shrinking premixed (Master Builders Company "Embecco"), unless otherwise indicated on the drawings or approved by the Architect/Engineer. 2. Use Mix No. 1 for clearances of 1" or less, and Mix No. 2 for all larger clearances. 3. Grout under equipment bases, around pipes, at pipe sleeves, etc., and where shown on the drawings. 2.5 OPENINGS IN FLOORS, WALLS AND CEILINGS A. Exact locations of all openings for the installation of materials shall be determined by the Contractor and given to the General Contractor for installation or construction as the structure is built. B. Coordinate all openings with other Contractors. C. Hire the proper tradesman and furnish all labor, material and equipment to cut openings in or through existing structures, or openings in new structures that were not installed, or additional openings. Repair all spalling and damage to the satisfaction of the Architect/Engineer. Make saw cuts before breaking out concrete to ensure even and uniform opening edges. D. Said cutting shall be at the complete expense of each Contractor. Failure to coordinate openings with other Contractors shall not exempt the Contractor from providing openings at his expense. E. Do not cut structural members without written approval of the Architect or Structural Engineer. 2.6 ROOF PENETRATIONS A. Seal pipes with surface temperature below 150ºF penetrating single-ply roofs with conical stepped pipe flashings and stainless steel clamps equal to Portals Plus Pipe Boots. Material shall match roofing membrane. B. Break insulation only at the clamp for pipes between 60ºF and 150ºF. Seal outdoor insulation edges watertight. 2.7 PIPE SLEEVES AND LINTELS A. Each Contractor shall provide pipe sleeves and lintels for all openings required for the Contractor s work in masonry walls and floors, unless specifically shown as being by others. B. Fabricate all sleeves from standard weight black steel pipe or as indicated on the drawings. Provide continuous sleeve. Cut or split sleeves are not acceptable. KJWW #08.0482.00 22 05 29-6

C. Fabricate all lintels from structural steel shapes or as indicated on the drawings. Have all lintels approved by the Architect or Structural Engineer. D. Sleeves through the floors on exposed risers shall be flush with the ceiling, with planed squared ends extending 1" above the floor in unfinished areas, and flush with the floor in finished areas, to accept spring closing floor plates. E. Sleeves shall not penetrate structural members without approval from the Structural Engineer. Sleeves shall then comply with the Engineer s design. F. Openings through unexcavated floors and/or foundation walls below the floor shall have a smooth finish with sufficient annular space around material passing through opening so slight settling will not place stress on the material or building structure. G. Install all sleeves concentric with pipes. Secure sleeves in concrete to wood forms. This Contractor is responsible for sleeves dislodged or moved when pouring concrete. H. Where pipes rise through concrete floors that are on earthen grade, provide 3/4" resilient expansion joint material (asphalt and cork) wrapped around the pipe, the full depth of concrete, at the point of penetration. Secure to prevent shifting during concrete placement and finishing. I. Size sleeves large enough to allow expansion and contraction movement. Provide continuous insulation wrapping. J. Wall Seals ("Link-Seals"): 1. Where shown on the drawings, pipes passing through walls, ceilings, or floors shall have their annular space (sleeve or drilled hole - not tapered hole made with knockout plug) sealed by properly sized sealing elements consisting of a synthetic rubber material compounded to resist aging, ozone, sunlight, water and chemical action. 2. Sleeves, if used, shall be standard weight steel with primed finish and waterstop/anchor continuously welded to sleeve. If piping carries only fluids below 120ºF, sleeves may be thermoplastic with integral water seal and textured surface. 3. Sleeves shall be at least 2 pipe sizes larger than the pipes. 4. Pressure shall be maintained by stainless steel bolts and other parts. Pressure plates may be of composite material for Models S and OS. 5. Sealing element shall be as follows: Model Service Element Material Temperature Range S Standard (Stainless) EPDM -40ºF to 250ºF T High/Low Temperature Silicone -67ºF to 400ºF T Fire Seals (1 hour) Silicone -67ºF to 400ºF FS Fire Seals (3 hours) Silicone -67ºF to 400ºF 6. Acceptable Manufacturers: Thunderline Corporation "Link-Seals", O-Z/Gedney Company, Calpico, Inc., Innerlynx, or Metraflex Company (cold service only). KJWW #08.0482.00 22 05 29-7

2.8 ESCUTCHEON PLATES AND TRIM A. Fit escutcheons to all insulated or uninsulated exposed pipes passing through walls, floors, or ceilings of finished rooms. B. Escutcheons shall be heavy gauge, cold rolled steel, copper coated under a chromium plated finish, heavy spring clip, rigid hinge and latch. C. Install galvanized steel (unless otherwise indicated) trim strip to cover vacant space and raw construction edges of all rectangular openings in finished rooms. This includes duct and pipe openings. 2.9 PIPE PENETRATIONS A. Seal all pipe penetrations. Seal non-rated walls and floor penetrations with grout or caulk. Backing material may be used. B. Seal fire rated wall and floor penetrations with fire seal system as specified. 2.10 PIPE ANCHORS 2.11 FINISH A. Provide all items needed to allow adequate expansion and contraction of all piping. All piping shall be supported, guided, aligned, and anchored as required. B. Repair all piping leaks and associated damage. Pipes shall not rub on any part of the building. A. Prime coat exposed steel hangers and supports. Hangers and supports in crawl spaces, pipe shafts, and suspended ceiling spaces are not considered exposed. PART 3 - EXECUTION 3.1 PIPE HANGERS AND SUPPORTS A. Install all items per manufacturer's instructions. B. Support all piping and equipment, including valves, strainers, traps and other specialties and accessories to avoid objectionable or excessive stress, deflection, swaying, sagging or vibration in the piping or building structure during erection, cleaning, testing and normal operation of the systems. C. Do not, however, restrain piping to cause it to snake or buckle between supports or to prevent proper movement due to expansion and contraction. D. Support piping at equipment and valves so they can be disconnected and removed without further supporting the piping. E. Piping shall not introduce strains or distortion to connected equipment. F. Where building structural steel is fireproofed, all hangers, clamps, auxiliary steel, etc., which attach to it shall be installed prior to application of fireproofing. Repair all fireproofing damaged during pipe installation. KJWW #08.0482.00 22 05 29-8

G. Set all concrete inserts in place before pouring concrete. H. Furnish, install and prime all auxiliary structural steel for support of piping systems that are not shown on the Drawings as being by others. I. Install hangers and supports complete with lock nuts, clamps, rods, bolts, couplings, swivels, inserts and required accessories. J. Hangers for horizontal piping shall have adequate means of vertical adjustment for alignment. K. Parallel horizontal pipes may be supported on trapeze hangers made of structural shapes and hanger rods; otherwise, pipes shall be supported with individual hangers. L. Trapeze hangers may be used where ducts interfere with normal pipe hanging. M. Coordinate the location and method of support of piping systems with all installations under other Divisions and Sections of the Specifications. N. Avoid eccentric loading of structural members. Load trusses and bar joists from top chord at panel points only. O. Do not exceed the manufacturer's recommended maximum load for any hanger or support. P. Provide additional supports where pipe changes direction, adjacent to flanged valves and strainers, at equipment connections and heavy fittings. Q. Provide at least one hanger adjacent to each joint in cast iron soil pipe, grooved end steel pipe with mechanical couplings, and glass pipe. R. Where pipe support members are welded to structural building framing, scrape, brush clean, and apply one coat of zinc rich primer to welding. S. Spacing of Hangers shall not exceed the compressive strength of the insulation inserts, and in no case shall exceed the following: Pipe Material Maximum Spacing 1. Steel (Std. Weight or Heavier Liquid Service): 1-1/4" & under 7'-0" 1-1/2" 9'-0" 2" 10'-0" 2-1/2" 11'-0" 3" 12'-0" 4" & larger 12'-0" 2. Steel (Std. Weight or Heavier Vapor Service): 1-1/4" and under 9'-0" 1-1/2" 12'-0" 2" & larger 12'-0" 3. Hard Drawn Copper & Brass (Liquid Service): 3/4" and under 5'-0" 1" 6'-0" 1-1/4" 7'-0" 1-1/2" 8'-0" KJWW #08.0482.00 22 05 29-9

Pipe Material Maximum Spacing 2" 8'-0" 2-1/2" 9'-0" 3" 10'-0" 4" 12'-0" 6" 12'-0" 4. Hard Drawn Copper & Brass (Vapor Service): 3/4" & under 7'-0" 1" 8'-0" 1-1/4" 9'-0" 1-1/2" 10'-0" 2" 11'-0" 2-1/2" & larger 12'-0" 5. Cast Iron Soil Pipe - All Sizes: Over 5' pipe lengths Less than 5' pipe lengths Support all direction changes and branch connections. 10'-0" 5'-0" 6. Rigid Plastic Pipe: a. Space hangers at 4-0 maximum centers. 7. Installation of hangers shall conform to MSS SP-69, MSS SP-89 and the applicable Plumbing Code. END OF SECTION KJWW #08.0482.00 22 05 29-10