Shading effects on the winter thermal performance of the Trombe wall air gap: An experimental study in Dalian

Similar documents
An approach for energy conscious renovation of residential buildings in Istanbul by Trombe wall system

Numerical study on a low energy architecture based upon distributed heat storage system

Thermal Characteristics and Energy Performance of Double Skin. Façade System in the Hot Summer and Cold Winter Zone

Thermal efficiency of a modified thermal storage wall containing phase change material in comparative test periods

Simulation and Energy Analysis of Thermal Environment of Unassisted Passive Solar House

Transient Performance Analysis of a Model Building Integrated with a Trombe-Wall

Observation of Liquid-filled Window without Presence of Liquid in Test Chamber

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Chapter 7. Passive Solar Contents

A Solar Wall System Utilized in Rural Houses of Northeast China

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE

Coupling of thermal mass and natural ventilation in buildings

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Application of Low Cost Active and Passive Energy Saving Technologies in an Ultra-low Energy Consumption Building

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

Effects of external window form on residential building energy consumption

Experimental Study to Evaluate the Performance of Iraqi Passive House in Summer Season

SOLAR ENERGY Utilization

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

Thermal Characteristics of a Vernacular Building Envelope

. ENERGY ANALYSIS OF VENTILATED ROOF WITH EXTENDED TOP IN HOT REGIONS. Ping Wang*, Guoqiang Zhang, Quan Zhang and Mingjing Xie

Thermal performance of concrete wall panel with advanced coating materials: a sustainable design

A Study on the Analysis of Indoor Temperature. According to the PCM Temperature Applied to the. Double Skin Facade System for Saving Cooling

3C.1 Passive Solar Design National Sustainable Building Advisor Program

Lecture 3: Utilization of Passive Solar Technology

EFFECT OF AIR GAP ON PERFORMANCE ENHANCEMENT OF BUILDING ASSISTED WITH PHOTO VOLTAIC SYSTEMS

A calculation model for Trombe walls and its use as a passive cooling technique

The Influence of Operation Modes, Room Temperature Set Point and Curtain Styles on Energy Consumption of Room Air Conditioner

Field investigation on indoor thermal environment of a high-rise condominium in hot-humid climate of Bangkok, Thailand

ENERGY EFFICIENT TECHNIQUES AND SIMULATION OF ENERGY CONSUMPTION FOR THE SHANGHAI ECOLOGICAL BUILDING

Advances in Engineering Research, volume 103 Proceedings of the 3rd International Conference on Material Engineering and Application (ICMEA 2016)

COMPARISON OF THERMAL PERFORMANCE OF DIFFERENT WALL STRUCTURES

Passive Solar Systems

HUMAN-BEHAVIOR ORIENTED CONTROL STRATEGIES FOR NATURAL VENTILATION IN OFFICE BUILDINGS

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang

Evaluation on the Performances of a Ventilated and Non-ventilated Cavity behind a BIPV: Modelling and Experimental Monitoring

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

CAE 331/513 Building Science Fall 2017

171: An urban office designed for the southern Brazilian climate

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Thermal Control in Buildings by John Straube (updated )

SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT

Radiative heat transfer simulation between outdoor and indoor. spaces for predicting the performance of a direct heat gain system

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

10 tips from your Architect

INVESTIGATION OF UNSTEADY THERMAL RESPONSE CHARACTERISTICS OF HOLLOW BRICKS EXPOSED TO SINUSOIDAL SOLAR THERMAL EXCITATION

PASSIVE SOLAR WALL INTEGRATED WITH A LATENT STORAGE LAYER

Thermal Environment of Chinese Residential Buildings with Different Thermal Insulation Materials in Hot-Summer-and-Cold-Winter Zone of China

Optimal design for a dual-airflow window for different climate regions in China

Interventions for Ensuring Thermal Comfort Equality in Apartment Buildings

Assessing the energy performance of modern glass facade systems

What is Sustainable Design?

Modeling Energy Consumption Effects of Glazing

ScienceDirect. Thermal Performance Improvement of Prefab Houses by Covering Retro-reflective Materials

Introduction to basics of energy efficient building design

Solar Flat Plate Thermal Collector

The Study on Thermal Performance and Applicability of Energy-saving. Wall Materials in Hot Summer and Cold Winter Zones

EFFECTS OF TREES ON THE ROOM TEMPERATURE AND HEAT LOAD OF RESIDENTIAL BUILDING. Tokyo, Japan

Field measurements of performance of roof solar collector

*Corresponding authors. Tel.: x415, address: (N. Zhu)

FAST EVALUATION OF SUSTAINABLE HEATING AND COOLING STRATEGIES FOR SOLAR HOMES WITH INTEGRATED ENERGY AND CFD MODELING

ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

FULL YEAR PERFORMANCE SIMULATION OF A DIRECT-COOLED THERMAL STORAGE ROOF (DCTSR) IN THE MIDWEST

Passive cooling effect of building features in traditional Japanese buildings

Solar gains in the glazing systems with sun-shading

Study on the Engineering Simulation of the Electric Hot Air De-icing. Device of the Substation Equipment. Jian Li1,a

Design and retrofitting of a hybrid building in Athens

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS)

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

SOME PRELIMINARY RESULTS OF A BUILDING INTEGRATED PHOTOVOLTAIC (BIPV) SYSTEM INSTALLED AT YASAR UNIVERSITY, IZMIR, TURKEY

Q-Air unique selling propositions in detail

LIGHTWEIGHT WOOD-BASED WALLS WITH VARIOUS THERMAL INSULATIONS: LONG-TIME MEASUREMENT AND SUBSEQUENT COMPARISON WITH HAM SIMULATION

Numerical Investigation of the Air Flow in a Novel PV-Trombe Wall Based on CFD Method

additional cooling energy consumption. Because the thermal resistance of windows has always been a weak point, even with vacuum glass or low-e glass,

SunCatcher Design GroupTM

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

Available online at ScienceDirect. Procedia Technology 23 (2016 )

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES

Effect of insulation ground on anti-condensation in rural residence

546: High Altitude Design, Optimising Residential Architecture in the Alborz Mountains, Iran

THERMAL PERFORMANCE USING RADIANT BARRIER AND PHASE CHANGE MATERIAL IN ROOFS

Nanoparticles Enhanced Phase Change Material (NPCM) as Heat Storage in Solar Still Application for Productivity Enhancement

OPTIMIZATION OF PCM NUMBER IN HOT WATER TANK FOR THE APPLICATION OF SOLAR DRIVEN ADSORPTION CHILLER IN TROPICAL CLIMATE

2006 Building Science Press All rights of reproduction in any form reserved.

Available online at ScienceDirect. Procedia Engineering 146 (2016 )

LIFE CYCLE ASSESSMENT FOR COOLING AND HEATING SOURCES OF BUILDING

GENERALIZED CRITERIA OF ENERGY PERFORMANCE EVALUATION IN EARLY DESIGN STAGES OF NEARLY ZERO-ENERGY BUILDINGS

Energy Consumption Simulation and Analysis of Heat Pump Air Conditioning. System in Wuhan by the BIN Method

Available online at ScienceDirect. Energy Procedia 69 (2015 ) Beiertiao, Zhongguancun, Beijing, P.R.

Open Access The Impact of Cool Roofs on Energy Consumption of Office Buildings in Chongqing of China

362: Indoor climate control effect of AAC panels as determined by house model measurements and simulations

Study on the heat transfer model and the application of the underground pipe system

Thermal Dynamic Model and Analysis of Residential Buildings

Thermal Performance of Solar Heating System with Water Floor

Thermal environment and thermal comfort in a passive residential building in the severe cold area of China

Optimizing the Configuration of a Compact Thermal Facade Module for Solar Renovation Concept in Buildings

Transcription:

Renewable Energy 31 (26) 1961 1971 www.elsevier.com/locate/renene Shading effects on the winter thermal performance of the Trombe wall air gap: An experimental study in Dalian B. Chen, X. Chen, Y.H. Ding, X. Jia Laboratory of Building Environment and New Energy Resources, School of Civil and Hydraulic Engineering, Dalian University of Technology, Dalian, Liaoning 1162, PR China Received 22 October 2; accepted 27 July 25 Available online 19 October 25 Abstract There has been little research on the application of shading devices in the air gap of the Trombe wall in China. Experiments on the thermal performance of an advanced Trombe wall with shading in the air gap was conducted in a passive solar house in Dalian. The thermal performance was investigated with regard to the simultaneous temperatures, heat gain and their acquisition of the Trombe wall. By analyzing experimental data, an investigation was carried out on the heat preservation effect by the shading device on a winter night. The theoretical optimum fixed location of the shading in the air gap for minimizing the heat loss was also discussed. Finally, the influence of shading on improving indoor thermal comfort was discussed using the concept of the building envelope response factor (BER) presented earlier by Lukic [The transient house heating condition the building envelope response factor (BER). Renewable Energy 23;28():523 32]. r 25 Elsevier Ltd. All rights reserved. Keywords: Passive solar house; Trombe wall; Shading device; Night insulation; Energy efficiency 1. Introduction To enhance the thermal storage effect of a Trombe wall, various techniques have been developed and used, such as installing an absorber plate in the air gap and using a black surface of the heat storage wall. For the sake of reducing heat loss of the Trombe wall at Corresponding author. Tel.: +86 11 876371. E-mail address: chenbin8911@yahoo.com.cn (B. Chen). 22-596/$ - see front matter r 25 Elsevier Ltd. All rights reserved. doi:1.116/j.renene.25.7.1

1962 B. Chen et al. / Renewable Energy 31 (26) 1961 1971 Nomenclature l e equivalent thermal conductivity, W/(m 2 1C) l thermal conductivity, W/(m 2 1C) Gr d Grashoff number, Gr d ¼ gl 3 adt=n 2 Pr Prandtl number, Pr ¼ n=a e c dimensionless convective coefficient, which is a function of Gr d Pr, T wo external surface temperature of the Trombe wall, 1C T w core temperature of the Trombe wall, 1C T wi inner surface temperature of the Trombe wall, 1C T a air temperature of the air gap, 1C T s shading temperature, 1C T g inner surface temperature of the glazing, 1C T m characteristic temperature of the air in the gap, 1C T o outdoor temperature, 1C DT wg temperature difference between the inner surface of the glazing and external surface of the massive wall, 1C DT sg temperature difference between the inner surface of the glazing and the shading, 1C SR solar radiation, MJ BER building envelope response factor, kw 1Ch 2 DH degree hour number, 1Ch Subscripts e w east side (no shading) west side (shading) night in a cold climate, insulated layers are installed outside the massive walls. But the outside insulated layer also greatly weakens its heat storage capacity. In order to improve heat accumulation of the massive wall at daytime and reduce its heat loss at nighttime, a shading device is installed in the air gap in a passive solar house in Dalian, China. In winter, the shading device can be opened at daytime to allow the black massive wall to absorb solar heat directly and shut down at night to minimize heat loss of the wall. In summer, the shading device can be closed at daytime to decrease the direct heat gain from solar radiation and prevent overheating. An experiment was carried out in the passive solar house to investigate thermal performance of the Trombe wall with a shading device in the air gap during a winter period at night from February 12 to 16, 2. 2. Experiments 2.1. Test cell One test room and one reference room are included in our experiment (see Fig. 1). The two rooms are partitioned by a 1 mm thick styrofoam panel. The volumes of both rooms

B. Chen et al. / Renewable Energy 31 (26) 1961 1971 1963 Fig. 1. South facade view of the test room (right) and the reference room (left). are 3.9 (long) 3.9 (wide) 2.7 (high) m 3. In our Trombe wall system, a south-facing concrete wall is located behind the double glazing to form a narrow air gap. The massive wall is constructed of 3 mm thick concrete. A shading device with a low emissivity is introduced in the air gap to avoid overheating in summer and improve insulation in winter. Two pairs of rectangular vents, each of size.17 m.15 m, were located at the bottom and top of the massive wall. Except for the south wall of the test room, the other components of both the rooms are constructed to be the same. The external walls are made of 3 mm thick cinder block and 1 mm thick styrofoam panels. The ceiling is made of 8 mm thick concrete and 1 mm thick styrofoam panels. The structure of the Trombe wall and temperature probe locations are shown in Fig. 2. 2.2. Measurement This experiment was carried out from February 12 to 16, 2. Measured parameters include solar radiation SR, outdoor air temperature T o, air temperature in the gap T a, temperature of the massive wall T w, inner surface temperature of glazing T g and inner/ external surface temperatures of the massive wall T wi and T wo, respectively. Data were recorded every 1 min and saved by a computerized data-logger. Climate data (temperature, relative humidity, wind speed and direction) were also recorded every 1 min by a WMR968 cable-free weather station driven by a solar cell, and hourly solar radiation accumulative value was measured by a PC-2 Pyranometer. To study the effect of the shading device on insulation performance of the massive wall, a comparative experiment is designed. The shading device on the east side was opened throughout the day and that on the west side was controlled depending on the weather, which was opened during sunshine periods and closed at cloudy weather or at night. The

196 B. Chen et al. / Renewable Energy 31 (26) 1961 1971 massive wall with bottle-green surface 21mm Á9mm air gap 1 mm T g T a T wo T w tint shading hollow glass inner top vent 17mm Á15mm concrete massive wall 3mm T in 2mm away from inner surface wall T wi inner bottom vent 17mm Á15mm Fig. 2. Schematic diagram of the structure and locations of temperature probes of the Trombe wall. Table 1 Shading operation of the west side and weather conditions Date Weather Ambient temperature (1C) Open/close time of the shading of the west side Highest Lowest Open Close February 12, 2 Fine 1 8:5 17:5 February 13, 2 Cloudy and rainy 8 1 11: 16:3 February 1, 2 Fine 7 8:5 17:22 February 15, 2 Cloudy 9 2 9: 17:1 February 16, 2 Cloudy 2 8:35 17:5 shading operations of the west side and the weather conditions during the experimental period are summarized in Table 1. During the experimental period, the ambient temperature ranged between 2 and 1 1C. 3. Experimental results and discussion 3.1. Preservation effect of the shading Fig. 3 shows the temperature of each probe in the air gap during the experimental period. It is observed that T a and T wo of the east side are both about 2 1C lower than those of the west side at night. On the contrary, T g of the west side is about 1 3 1C higher than that of the east. This result is consistent with the insulation effect of the shading device at night. The use of the shading device makes the wall less influenced by the outdoor environment and the wall temperature is increased by minimizing the heat loss. But the glazing temperature dropped along with a lower heat gain from the wall. So the temperature difference between the two vertical surfaces (the external surface of the massive wall and the inner surface of the glass panel) of the east side (DT wge ) is about 5 1C

B. Chen et al. / Renewable Energy 31 (26) 1961 1971 1965 Tg ( C) (a) Ta ( C) (b) Two ( C) (c) 36 32 28 2 2 16 12 8-36 32 28 2 2 16 12 8-36 32 28 2 2 16 12 8 - Night The east side T o The west side SR 21: 9: 21: 9: 21: 9: 21: 21: 9: 21: 9: 21: 9: 21: 21: 9: 21: 9: 21: 9: 21: 6 5 3 2 1 6 5 3 2 1 6 5 3 2 1 SR (MJ) SR (MJ) SR (MJ) Fig. 3. Hourly temperature variations of probes in the air gap. lower than that of the west side (DT wgw ) and this temperature difference has a direct effect on conductive and radiative heat transfer which is discussed in the following section. Fig. shows the temperature profile of the massive wall. On the west side, both inner and external surface temperatures of the wall are lower than the core temperature of the wall (T wow ot wiw ot ww ) at night. The temperature difference between the core and the external surface is larger than that between the core and inner surface. Thus, the heat loss to the air gap is more than the heat loss to the room on the west side [1]. It should meliorate the shading design (material or fixed location) to improve its insulation performance. But on the east side, T wie is sometimes higher than T we at night. It means that the indoor environment loses more heat to the outdoor without shading than with shading.

1966 B. Chen et al. / Renewable Energy 31 (26) 1961 1971 Night Two Tw Twi Temperature ( C) (a) 32 3 28 26 2 22 2 18 16 1 12 1 8 21: 9: 21: 9: 21: 9: 21: The east side Temperature ( C) (b) 32 3 28 26 2 22 2 18 16 1 12 1 8 21: 9: 21: 9: 21: 9: 21: The west side 3.2. Analysis of heat transmission Fig.. Hourly temperature variations of probes in the Trombe wall. When investigating the thermal performance of a traditional wall in winter, its heat transfer process can be approximately regarded as a steady state because mean temperature difference between indoor and outdoor is much larger than the oscillating value of the outdoor temperature [2]. But for the special structure of the Trombe wall, the heat transfer process becomes rather complex. Due to the fact that the periodic solar radiation and ambient temperature have a large integrative influence on the air temperature in the air gap, the wall heat transfer process becomes unsteady according to the studies in [3,]. The mathematical model for the narrow air gap should thereby be the unsteady state. In order to evaluate the performance of the conduction and convection in the overall heat transfer process of the air gap, an equivalent conductivity l e [] is introduced, which represents the proportion of conduction and convection in the heat transfer process: e c ¼ l e =l. (1) For 1. 1 3 ogr Pro1. 1 9 in the present study, the following equation is used to evaluate e c : e c :18ðGr d PrÞ 1= m. (2)

B. Chen et al. / Renewable Energy 31 (26) 1961 1971 1967 When e c ¼ 1:, it means only conduction exists in the air gap. If the e c value is much larger than 1., natural convection dominates in the whole process and the conductive heat transfer can be neglected. In this experiment, e c ¼ :1 on the east side and e c ¼ 3:8 on the west side, which are both larger than 1.. But in order to clarify the thermal performance of the shading device more accurately, the conductive, radiative and convective heat transfer processes of the air gap are all considered. 3.2.1. Conductive heat transfer The thickness of the shading is about.2 mm and its thermal conductivity is infinitesimal compared with that of the air in the gap. Thus, only the air conductive thermal resistance is taken into account in calculating conductive heat transfer between the wall and glazing. Fig. 5(a) shows the hourly heat loss of the air gap. It can be observed that conductive heat loss of the air gap with shading (about 297. kj) is slightly larger than that without shading (about 2. kj) at night, since DT wg of the west side is slightly higher than that in the east and it has already been illustrated in Section 3.1. Although the conductive heat loss is increased a little using shading, its insulative performance is positive, because the contribution from heat conduction is the least one to the whole heat transfer process and it will be clarified further in the following section. Conductive heat loss (W) (a) 8 6 2-2 - -6-8 Night The east side 3: 21: 15: 9: 3: Radiative heat loss (W) (b) 8 6 2-2 - -6-8 The west side 3: 21: 15: 9: 3: Conductive heat loss (W) (c) 8 6 2-2 - -6-8 Total heat loss (W) 8 6 2-2 - -6-8 3: 21: 15: 9: 3: (d) 3: 21: 15: 9: 3: Fig. 5. Comparison of hourly heat loss in the air gap.

1968 B. Chen et al. / Renewable Energy 31 (26) 1961 1971 In this experiment, the conductive thermal resistance of the shading is so small that it can be ignored in the calculation. But changing its conductive resistance by way of changing shading material or increasing its thickness, the total thermal resistance of the air gap of the west side is increased and the conductive heat loss is correspondingly decreased. According to our simple estimation, the conductive heat loss in the west side drops less than that in the east side when the shading conductive coefficient is greater than 3. m 2 1C/ W. Normally, the thermal resistance should be as high as possible, but the feasibility of the installment should be also considered in practice. 3.2.2. Radiative heat transfer It is well known that glazing can effectively prevent long-wave radiation to the sky, which is emitted from the external surface of the black green wall at night. Therefore, the radiative heat transfer mainly occurs between the external surface of the massive wall and the inner surface of the glazing, and it is a function of the temperature difference between them. For the west side, T a and T s are almost close to T wo. Thus, the radiative loss between the shading and the massive wall can be ignored and the radiative loss mainly occurs between the shading and glazing. Fig. 5(b) illustrates the hourly radiative loss in the gap of the east and west sides at night. It seems that the mean value of the radiative loss in the gap of the west side (about 53. kj from the shading to the glazing) is a little more than that of the east side (about 51. kj from the wall to the glazing), which is due to the relatively higher temperature difference DT sg. However, the use of shading can prevent radiative loss from the wall to the glazing directly at night. Furthermore, emissivity of the shading is a main factor that influences radiative heat transfer. Shading with a low emissivity and a high radiative resistance can further decrease the heat loss at night. 3.2.3. Convective heat transfer According to the theory of natural convection in a narrow space [1], the thickness of the air gap has a great impact on the air flow pattern. So varying the thickness of the air gap is another way to reduce heat loss. In this experiment, the air gap thickness is 1 mm on the east side, while on the west side, the air gap is divided into two 5 mm spaces and the shading thickness is ignored. Because of the relative larger cross-section size of the air gap (2.7 m.1 m), the relatively lower air temperature and current velocity, the air flow pattern is considered as laminar in the gap. The Nusselt number can be calculated by Eqs. (3) and (): Nu d ¼ :197ðGr d PrÞ 1= d 1=9 6oGr d Prp2: 1 5, (3) h Nu d ¼ :73ðGr d PrÞ 1=3 d 1=9 2: 1 5 ogr d Pro1:1 1 7. () h Fig. 5(c) shows hourly variations of the convective heat loss of both sides. From calculation, the mean value of the convective heat loss of the east side at night is about 12.5 kj, while that of the west side is about 22. kj. It can be known that the convective heat loss is the absolutely major part of the whole heat losses, and using shading can decrease effectively the convective heat loss.

3.2.. Total heat loss Fig. 5(d) represents the total hourly heat loss of the east and west sides. According to the comparison, the total heat loss is reduced by 2 % because of using shading at night. In summary, although the rise of DT sg and DT wg and, ignoring the conductive coefficient of shading leads to an increase in radiative and conductive heat loss of the air gap, the shading can effectively decrease the convective heat loss and prevent the radiative heat loss from the wall to the glazing directly. Thus, installing shading results in an insulation effect which improves thermal performance of the massive wall.. Effect of the shading location There are two important factors for determining the conductive and convective heat losses in the air gap, i.e. the shading material and fixed location, because different shading materials can lead to different thermal resistances and different fixed locations means different structures of the air gap which dominate the air flow pattern. But when the air gap thickness is greater than 6 mm, the thermal resistance of the channel will tend to be stable with the gradual enhancement of convection [3]. From Fig. 5, it can be seen that the convective heat loss is dominant in the total heat loss. From this point of view, the key to the improvement of insulation performance of the Trombe wall is to decrease the convective heat transfer. If the size of the air gap is confirmed, changing the fixed location of the shading can alter the air flow pattern and decrease the convection heat loss in the air gap. At the same time, varying the thickness of the air gap can also affect the conductive heat loss. So there must be a reasonable location of the shading that results in the least convective and conductive heat loss. It is assumed that the optimum distance between the shading and glazing is d. According to [5,6], d can be calculated using the following equation: d ¼ 2 2:93 Pr 1=2 ð:952 þ PrÞ 1= Gr 1= h: (5) In this experiment, the optimum distance between the shading and glazing d as confirmed by Eq. (5) is 23 mm and the convective heat loss is reduced by about 2%. In the present experimental study, the facility has already been completed and the shading is hermetic in the gap. Thus it is not possible to validate the optimum location. The location of the shading is an important factor for improving the thermal performance of the Trombe wall and raise the indoor temperature in winter, so it will be further investigated in our subsequent study. 5. Analysis of indoor thermal comfort B. Chen et al. / Renewable Energy 31 (26) 1961 1971 1969 Installing shading in the air gap of the Trombe wall can raise indoor temperature and improve thermal comfort owing to its insulative performance in winter. The influence of walls on thermal comfort is presented by the analysis of the building envelope response factor (BER) which was introduced by Lukic [7]. The greater the BER, the more the heat needed to reach the indoor comfort zone. In other words, the higher the value of BER, the greater the indoor air temperature deviated from the comfort zone. BER is defined in Eq. (6) as BER ¼ DH X ðq n hcdtþ, (6)

197 B. Chen et al. / Renewable Energy 31 (26) 1961 1971 where BER is the building envelope response factor, kw 1Ch 2 ; P ðq n hcdtþ is the total heating load during one heating day, W; and DH is the degree hour number, 1Ch. DH ¼ X ðt tc T n inþdt, (7) where T tc is defined as the thermal comfort temperature and it is 18 1C in this experiment; T n in is the indoor air temperature of the moment of calculation time, 2 mm from the wall, 1C; and Dt is the time interval which is 1 min. It should be noted that the P ðq n hcdtþ value for calculating BER of the two experimental walls is identical because both walls are installed in the same passive solar room. Thus, the relationship between BER and DH becomes linear and thermal comfort can be analyzed by comparing DH values of the two massive walls only. Moreover, the indoor air temperature is influenced simultaneously by the two compared Trombe walls (the east and west sides) and the direct gain in this experiment. Thus, T n in is represented by the air temperature 2 mm far from the massive wall for more objective analysis of the shading s insulative contribution. The result is shown in Fig. 6. The DH difference between the two walls is not significant at daytime, but DH value of the east side is 1 1C h higher than that of the west at night. This illustrates that more heat should be consumed to meet thermal comfort requirements without shading at night. In this case, the installation of the shading device makes a positive effect on raising indoor temperature, thermal comfort and saving energy. 1. 12. The west side (day) The east side (day) The west side (night) 1. The east side (night) DH ( Ch) 8. 6.. 2.. 2-12 2-13 2-1 2-15 Date (day) Fig. 6. Daily DH values of the Trombe wall.

B. Chen et al. / Renewable Energy 31 (26) 1961 1971 1971 6. Conclusions The use of shading in the air gap is an effective way to improve thermal performance of the Trombe wall. The experimental data show that shading plays a significant role in optimizing the passive solar house design. Using shading can decrease convective heat loss of the air gap and prevent radiative heat transfer from the Trombe wall to the outside. Based on the calculation, it is found that the insulation can reduce about 2 % heat loss in the air gap on a winter night and increase the external surface temperature of the Trombe wall. From analysis of the heat transfer process, convective heat loss is found to dominate in the total heat loss. Therefore, reducing convective heat loss is the key to improve thermal performance of the Trombe wall. Different shading fixed locations can change the thickness of the air gap, which has an important effect on the air flow pattern variation to decrease the convective heat loss. The relative optimized location of the shading in the gap calculated by Eq. (5) can reduce about 2% of the total convective heat loss. Referring to the thermal comfort, DH of the east side of the gap is about 1 1Ch higher than that of the west side, so the shading has an obvious effect on improving indoor thermal comfort. References [1] Min ZX, Ren XP, Mei FM. Heat transmission, 3rd ed. Beijing: Architecture Publishing Company of China; 2. [2] Jin ZF, Zhu YX. Architecture environment. Beijing: Architecture Publishing Company of China; 21. [3] Jiang H, Hu HB, Wang ZQ, Sun ML. Influence of air-gap design on the preservative and energy saving wall thermal performance. Wall Innovat Build Energy Conserv 22;1:35 8. [] Wang BX. Theory of heat and mass transfer in the project. Beijing: Beijing Science publishing Company; 1998. [5] Hoffman JP. Heat transmission. People s Education Publishing Company; 1979. [6] Shi YY, Liu H, Zhang JP. Optimized thermal design of passive solar house and massive wall. Ningxia Technol Inst J 1996;8(1):52 9. [7] Lukic N. The transient house heating condition the building envelope response factor (BER). Renew Energy 23;28():523 32.